R400-15000e Rectifier Data Sheet

eSure™ Rectifier
R400-15000e
Key Features
15kW high-efficiency rectifier
designed for 400V DC power
applications
Optimized depth –
reduced footprint allows
installation in short-depth
racks and cabinets
DSP (Digital Signaling
Processor) – means fewer
components, optimized
operation and active load
sharing for increased reliability
In addition to reducing power consumption and
lowering operating cost, eSure™ high-efficiency
rectifiers offer superior performance and
uncompromised reliability.
Description
The 15kW high-efficiency eSure™ rectifier (model R400-15000e) is designed to convert
standard AC supply voltages into stable 400V DC voltage that is adjustable to
application needs. The R400-15000e is a constant power rectifier designed with the latest
patented switchmode technology, using DSP (Digital Signaling Processor) functionality
for efficient operation.
For a higher load capacity, rectifiers can be connected in parallel, and intelligent
control can be added with the help of a separate controller.
Compliant with global
standards – delivers quality,
performance and reliability no
matter what the application or
location demands
High efficiency, peak 97% –
reduces power consumption
for lower operating costs
Hot pluggable – facilitates
future expansions and easy
maintenance
Efficiency
eSure™ Rectifier
Efficiency Curve
98%
Wide input voltage range to
operate in the most
demanding environments
96%
94%
eSure™Rectifier
92%
90%
Wide temperature operating
range to meet the harshest
climatic environments
88%
86%
84%
0%
20%
40%
60%
80%
100%
Load
Load
Load
2013.04
1
eSure™ Rectifier R400-15000e
Output Current
Output Current Limit Set Point
Efficiency
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
260
120
80
60
40
20
0
200
250
300
Alarm and status reported via CAN bus to system controller
Green LED:
Normal Operation
Yellow LED:
Alarm
Red LED:
Failure
Mechanics
Dimensions (H x W x D)
Weight
88 x 218 x 565mm / 3.5 x 8.5 x 22 inches
10 kg / 22 lbs
Other Parts
Controller Units
See separate controller datasheet
400
450
500
550
Output Power vs. Temperature
at Uin>340VAC, Vo >336V DC
120
100
80
60
40
20
0
-5
5
15
25
35
45
55
65
Temperature (C°)
Output voltage vs. Output current,
max. output power 15000 W
-40°C to +65°C,-40°F to+149°F (See diagram for de-rating)
-40°C to +75°C , -40°F to +167°F
0 to 95%
Safety
350
Input Voltage (VAC)
See diagram
44.6 A maximum
0 to 44.6 A
Peak 97%
530
304
100
290V to 400V DC
15000W @ Vout > 336VDC
2000 m, 6560 ft at full power
ETSI EN300 386: 2005, Class B. Other than telecom centers.
FCC CFR 47 Part 15, Class B conducted and radiated
EN55022, Class B conducted and radiated
CISPR22, Class B conducted and radiated
Telcordia GR-1089-CORE issue 6
UL 60950-1(US & Canada);EN 60950-1;IEC 60950
EMC
Output Power vs. Input Voltage
at Tamb <45°C
% of max output power
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power, Derated for Input
Voltage
380V/480V AC
260V to 530V AC
45Hz to 65Hz
30 A
0.99
<5% from 50 to 100% of rated load
44.6
37.5
Output Voltage (V)
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
Diagrams
% of max output power
Technical Specifications
400
350
300
250
200
150
100
50
0
0
5
10
15
20
25
30
35
40
45
50
Output Current (A)
Ordering Information
Product Name
Description
R400-15000e
Rectifier 400V,15kW
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and
trademarks of Emerson Electric Co. EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson
Network Power Energy Systems North America. Any other product, brand, or company names or logos are the property of the respective owner.
2
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. SpecJ»cations subject to
change without notice.
2013.04