R48-2000e3 eSure Data Sheet

DC Power for
Business-Critical Continuity™
eSure™ Rectifier
R48-2000e3
Key Features
High efficiency, above 96% –
reduces power consumption
for lower operating costs
Full output power (2kW) up to
+65 ° C allows savings on climate
system and operating costs
High power density –
reduced footprint allows
installation in short-depth
racks and cabinets
In addition to reducing power consumption and
lowering operating cost, eSure™ high-efficiency
rectifiers offer superior performance and
uncompromised reliability.
Description
The 2000W high-efficiency eSure™ rectifier ( model R48-2000e3) is designed to convert
standard AC supply voltages into stable nominal -48 V DC voltage that is adjustable to
application needs. The R48-2000e3 is a constant power rectifier designed with the latest
patented switchmode technology, using DSP (Digital Signaling Processor) functionality
for efficient operation.
For a higher load capacity, rectifiers can be connected in parallel, and intelligent
control can be added with the help of a separate controller.
Wide input voltage range to
operate in the most
demanding environments
Hot pluggable – facilitates
future expansions and easy
maintenance
Compliant with global
standards – delivers quality,
performance and reliability no
matter what the application or
location demands
Efficiency
eSure™ Rectifier
Efficiency Curve
98%
96%
94%
eSure™Rectifier
92%
90%
88%
86%
84%
10%
2013.09
20%
30%
40%
50%
60%
70%
80%
90%
100%
Load
1
eSure™ Rectifier R48-2000e3
DC Output
Output Voltage, Adjustment Range
Output Power
Output Power, Derated for Input
Voltage
200 to 250 VAC
85 to 300 VAC
45 to 65 Hz
12 A
>0.99 for 50%-100% load
≤5% for 50%-100% load at 208Vac, 220Vac, 230Vac, 240Vac
176
85
120
300
100
80
60
40
20
0
0
50
100
150
200
250
Output Power vs. Temperature
at Uin > 200VAC
See diagram
Output Current Limit Set Point
Peak Efficiency
Temperature Derating
0 to 42 A
96.2%
Full output power up to +65°C at input voltage range
>200 - 300VAC ( >176 - 200VAC, +55°C)
65 70
120
100
80
60
40
20
0
-40
-20
0
20
40
60
80
100
120
Temperature (°C)
Alarm and status reported via CAN bus to system controller
Green LED:
Normal Operation
Yellow LED:
Alarm
Red LED:
Failure
Output voltage vs. Output current,
max. output power 2000 W
34.5
41.7
-40 to 80°C,-40 to +176°F (See diagram for de-rating)
-40 to +70°C, -40 to +158°F
0 to 95%
Safety
Mechanics
Dimensions (H x W x D)
Weight
41x84.5x252.5mm/1.61x3.33x9.94 inches
1.13kg/2.49lbs
Other Parts
Controller Units
See separate controller datasheet
Output Voltage (V)
60
2000 m, 6560 ft at full power
ETSI EN300 386: 2005, Class B. Other than telecom centers.
FCC CFR 47 Part 15, Class B conducted and radiated
EN55022, Class B conducted and radiated
CISPR22, Class B conducted and radiated
Telcordia GR-1089-CORE issue 6
UL 60950-1;EN 60950-1;IEC 60950
EMC
350
-42 to -58 V DC
2000W Maximum
42A@-48VDC
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
300
Input Voltage (VAC)
Output Current
Control and Monitoring
Rectifier Alarm and Signaling
Visual Indications
Output Power vs. Input Voltage
at Tamb < 55 °C
% of max output power
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD (Total Harmonic Distortion)
Diagrams
% of max output power
Technical Specifications
50
40
30
20
10
0
0
5
10
15
20
25
30
35
40
45
50
Output Current (A)
Ordering Information
Part Number
1R482000e3
Description
High efficiency eSure ™ r ectifier, -48VDC,2000W
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2013.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson
Electric Co. EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
2013.09