Liebert DSE- 165kW, 47 Tons, Downflow, 60Hz- User Manual Supplement (R03/14) (SL-18931)

Liebert® DSE™
User Manual Supplement–165kW, 47 Tons, Downflow, 60Hz
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0
PRE-INSTALLATION GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1
Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1.1
1.1.2
1.1.3
Cooling, Dehumidification and Humidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Humidification Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0
AIR-COOLED SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1
Capacity and Physical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.0
LIEBERT DSE DIMENSIONS AND WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.0
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1
Standard Electrical Field Connections, DA165 Downflow Models . . . . . . . . . . . . . . . . . . . . 12
4.2
Optional Electrical Field Connections, DA165 Downflow Models. . . . . . . . . . . . . . . . . . . . . 12
4.3
Optional Low Voltage Terminal Package Connections, DA165 Downflow Models . . . . . . . 13
5.0
PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.1
Piping Guidelines—Air-Cooled Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.2
Scroll and Digital Scroll—Additional Oil Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3
Dehydration/Leak Test and Charging Procedures for R-410A . . . . . . . . . . . . . . . . . . . . . . . 18
5.3.1
6.0
Air-Cooled Condenser - Premium Efficiency Control (PCB version) . . . . . . . . . . . . . . . . . . . . 18
PIPING SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
COMPLIANCE WITH EUROPEAN UNION DIRECTIVES . . . . . . . . . . . . . . . . . . . . . . INSIDE BACK COVER
i
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Cabinet and floor planning dimensions—downflow, air-cooled, DA165, tandem scroll
compressor models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Floor stand and floor planning dimensions—downflow model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Condenser planning dimensions, MCL165 and MCL220 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Required receiver mounting MCL165, MCL220 units, left-side mounting outlet receiver . . . . . 10
Required receiver mounting MCL165, MCL220 units, right-side mounting outlet receiver . . . . 11
Electrical connection locations for DA165 downflow models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical field connections for DA165 downflow model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Piping schematic—air-cooled DA165 models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Primary connection locations—downflow, air-cooled DA165 scroll compressor models . . . . . . . . 20
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Performance data, air-cooled unit with EC fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Shipping dimensions and weights—domestic and export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Floor stand and floor planning dimensions—downflow, 165kW (47 ton) models . . . . . . . . . . . . . . 8
Cabinet and anchor dimensions, MCL165 and MCL220 with receivers . . . . . . . . . . . . . . . . . . . . . 9
Recommended refrigerant line sizes - OD copper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Indoor unit approximate refrigerant charge for R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Interconnecting piping refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Condenser refrigerant charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Liebert PR125/PR085 module charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Condenser ambient selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Additional oil required per refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ii
Important Safety Instructions
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert DSE, Model DA165. Read this manual thoroughly before attempting
to install or operate this unit. For additional information, refer to the Liebert DSE user manual,
SL-18925.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in
this manual. Follow all operating and user instructions.
! WARNING
Arc flash and electric shock hazard. Open all local and remote electric power disconnect
switches, verify that power is off with a voltmeter and wear appropriate personal protective
equipment per NFPA 70E before working within the electrical control enclosure. Failure to
comply can cause injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “unit off”
mode. Some internal components require and receive power even during the “unit off” mode of
Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch
contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
! WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and gases under high pressure. Relieve pressure before working with
piping.
! WARNING
Risk of refrigerant system rupture or explosion. Can cause equipment damage, injury or
death. Do not install a shutoff valve between the compressor and the field-installed pressure
relief valve.
For systems requiring EU CE compliance (50Hz), the system installer must provide and
install a discharge pressure relief valve rated for a maximum of 650 psig (45bar) in the high
side refrigerant circuit. The pressure relief valve must be CE-certified to the EU Pressure
Equipment Directive by an EU “Notified Body.”
! WARNING
Risk of very heavy 145 lb (65.7kg) fan modules dropping downward suddenly. Can cause
injury or death.
Support fan modules before removing mounting hardware. Use caution to keep body parts out
of the fan modules pathway during repositioning. Only properly trained and qualified
personnel should work on this equipment.
1
Liebert® DSE™ DA165 Supplement
Important Safety Instructions
! WARNING
Risk of improper moving. Can cause equipment damage, injury or death.
Use only lifting equipment that is rated for the unit weight by an OSHA-certified rating
organization. Shipping weights and unit weights are listed in Table 3 and Figure 1. Use the
center of gravity indicators on the unit to determine the position of the slings (refer to the
Liebert DSE user manual, SL-18925). The center of gravity varies depending on the unit size
and selected options. The slings must be equally spaced on either side of the center of gravity
indicator.
! WARNING
Risk of contact with high-speed rotating fan blades. Can cause injury or death.
Disconnect all local and remote electric power supplies and verify that the fan blades have
stopped rotating before working in the unit.
Do not operate unit with any or all cabinet panels removed.
! CAUTION
Risk of sharp edges, splinters, and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should attempt to move the unit, lift it, remove packaging or prepare the
unit for installation.
! CAUTION
Risk of contact with hot surfaces. Can cause injury.
The compressors, fan motors, refrigerant discharge lines, humidifiers and reheats are
extremely hot during unit operation. Allow sufficient time for them to cool before working
within the unit cabinet. Use extreme caution and wear protective gloves and arm protection
when working on or near hot compressors, fan motors, discharge lines, humidifiers and
reheats.
! CAUTION
Risk of improper handling of cabinet panels. Can cause personal injury and equipment
damage.
Cabinet panels can exceed 5ft. (1.5m) in length and weigh more than 35lb. (15.9kg). Follow
relevant OSHA lifting recommendations and consider using a two-person lift for safe and
comfortable removal and installation of cabinet panels. Only properly trained and qualified
personnel wearing appropriate safety headgear, gloves and shoes should attempt to remove or
install cabinet panels.
NOTE
The Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high
side refrigerant circuit. Consult local building codes to determine whether the Liebert Premium
Efficiency Control (PCB) condensers will require field-provided pressure relief devices.
NOTICE
Risk of clogged or leaking drain lines. Can cause equipment and building damage.
This unit requires a water drain connection. Drain lines must be inspected regularly and
maintenance must be performed to ensure that drain water runs freely through the drain
system and that lines are clear and free of obstructions and in good condition with no visible
sign of damage or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the
unit. Water leakage can result in severe property damage and loss of critical data center
equipment.
Do not locate unit directly above any equipment that could sustain water damage.
Emerson recommends installing monitored leak detection equipment for unit and supply
lines.
Liebert® DSE™ DA165 Supplement
2
Important Safety Instructions
NOTICE
Risk of internal system corrosion and frozen coolant fluid. Can cause equipment damage and
major fluid leaks resulting in serious building damage, expensive repair costs and costly
system down time.
Cooling and heat rejection coils, heat exchangers and piping systems that are connected to
open cooling towers or other open water/glycol systems are at high risk of freezing and
premature corrosion. Fluids in these systems must contain the proper antifreeze and
inhibitors to prevent freezing and premature coil, piping and heat exchanger corrosion. The
water or water/glycol solution must be analyzed by a competent local water treatment
specialist before startup to establish the inhibitor and antifreeze solution requirement and at
regularly scheduled intervals throughout the life of the system to determine the pattern of
inhibitor depletion.
The complexity of water/glycol solution condition problems and the variations of required
treatment programs make it extremely important to obtain the advice of a competent and
experienced water treatment specialist and follow a regularly scheduled coolant fluid system
maintenance program.
Read and follow individual unit installation instructions for precautions regarding fluid
system design, material selection and use of field-provided devices. Liebert systems contain
iron and copper alloys that require appropriate corrosion protection. It is important to have
the system running with flow through exchangers maintained at initial system fill for 24 to 48
hours depending on size and system configuration.
Water chemistry varies greatly by location, as do the required additives, called inhibitors,
that reduce the corrosive effect of the fluids on the piping systems and components. The
chemistry of the water used must be considered, because water from some sources may
contain corrosive elements that reduce the effectiveness of the inhibited formulation.
Sediment deposits prevent the formation of a protective oxide layer on the inside of the
coolant system components and piping. The water/coolant fluid must be treated and
circulating through the system continuously to prevent the buildup of sediment deposits and
or growth of sulfate reducing bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system.
Consult glycol manufacturer for testing and maintenance of inhibitors.
Commercial ethylene glycol (examples are Dow Chemical Dowtherm SR-1 Union Carbide
Ucartherm and Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive
to the common metals of construction than water itself. It will, however, assume the
corrosivity of the water from which it is prepared and may become increasingly corrosive with
use if not properly inhibited.
3
Liebert® DSE™ DA165 Supplement
Pre-Installation Guidelines
1.0
PRE-INSTALLATION GUIDELINES
1.1
Operating Conditions
1.1.1
Cooling, Dehumidification and Humidification
The Liebert DSE must be operated in a conditioned space within the operating envelope ASHRAE
recommends for data centers: Maximum return air temperature of 105°F (40°C) and maximum dew
point of 59°F (15°C).The recommended minimum return air temperature setpoint for the Liebert DSE
is 75°F (24°C).
Operating outside this envelope can decrease equipment reliability.
Refer to ASHRAE’s publication, “Thermal Guidelines for Data Processing Environments.”
NOTE
If running in supply air control, the minimum supply air setpoint is 64°F (18°C).
DA165 Dehumidification Control
The DA165 is designed to maximize sensible cooling not latent cooling loads. With all four
compressors running, no reheat will be available at this dehumidification load point (Stage 4).
The room load must be 94.1kW (74% of unit capacity) to prevent overcooling the room at 85°F (29°C)
return air temperature. If the room load is too low to maintain the setpoint, the compressors will cycle
On and Off. During Stage 3, with three of the four compressors running, 10kW of reheat will be
available to offset cooling. During Stage 1 and 2, with one and two compressors running respectively,
30kW of reheat is available to offset cooling. For rooms with multiple units, Emerson® recommends
performing dehumidification via Teamwork mode to prevent compressor cycling in case of lightly
loaded rooms or having standard Liebert DS units available to perform dehumidification. Liebert
DSE units in dehumidification mode might not hold the temperature setpoint unless there is
sufficient room load. This will allow for better dehumidification of the room. The Liebert DSE will
allow the return air temperature to run down to 68°F (20°C) regardless of the temperature setpoint
during dehumidification mode of operation.
1.1.2
Heating
The Liebert DSE is qualified for heating-only operation at temperatures not exceeding 80°F (27°C).
1.1.3
Humidification Control
To prevent the humidifier from running when not required (especially when return air temperatures
exceed 75°F [24°C]), the default control for humidity and dehumidification is based on dew point
temperature, not relative humidity. If this default control is changed, adjust the relative humidity
setpoint based on return air temperature to prevent from overhumidifying the space.
Liebert® DSE™ DA165 Supplement
4
Air-Cooled Systems
2.0
AIR-COOLED SYSTEMS
2.1
Capacity and Physical Data
Table 1
Performance data, air-cooled unit with EC fans
Model
DA165
Total kW (kBTUH)
Sensible kW (kBTUH)
Net Full-Load SCOP (kW/kW) @ Outdoor Ambient (Compressor Mode
90°F DB, 66.1°F WB, 52.3°F DP (32.2°C DB, 18.9°C WB) 28% RH
Total kW (kBTUH)
Sensible kW (kBTUH)
Net Full-Load SCOP (kW/kW) @ Outdoor Ambient (Compressor Mode
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32% RH
Total kW (kBTUH)
Sensible kW (kBTUH)
Net Full-Load SCOP (kW/kW) @ Outdoor Ambient (Compressor Mode
80°F DB, 62.8°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38% RH
Total kW (kBTUH)
Sensible kW (kBTUH)
Net Full-Load SCOP (kW/kW) @ Outdoor Ambient (Compressor Mode
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 19.8°C WB) 45% RH
Total kW (kBTUH)
Sensible kW (kBTUH)
Net Full-Load SCOP (kW/kW) @ Outdoor Ambient (Compressor Mode
FAN SECTION - DOWNFLOW MODELS WITH EC FANS
181 (53)
181 (53)
3.2
NET CAPACITY DATA, kW (kBTUH)
95°F DB, 67.7°F WB, 52.3°F DP (35°C DB, 19.8°C WB) 24% RH
Standard Air Volume, CFM (CMH) 0.2" external static
Operating Fan kW, Total for All Fans
Number of Fans
PHYSICAL DATA
172 (50)
172 (50)
3.0
163 (48)
162 (48)
2.9
154 (45)
154 (45)
2.7
147 (43)
147 (43)
2.5
20,000 (33980)
8.0
3
Evaporator Coil - A-Frame, Copper Tube/Aluminum Fins
Face Area, ft2 (m2)
Rows of Coil
Face Velocity - FPM (m/s), standard air volume
Reheat Section
56.2 (5.2)
6
354 (1.8)
Electric - Three-State Stainless Steel Fin Tubular (capacity does not include fan motor heat)
Capacity, Standard Selection, kW (kBTUH)
30.0 (102)
Capacity, Optional Selection, kW (kBTUH)
10.0 (34.1)
HUMIDIFIER SECTION
Infrared Humidifier Capacity, lb/hr (kg/hr)
FILTER SECTION - DISPOSABLE TYPE
Nominal Size, inches
Number
22.0 (10.0)
21.5 x 24
10
LINE SIZES
Liquid Line, O.D. Copper (2 per unit), up to 300 eq. ft.
Hot Gas Line, O.D. Copper (2 per unit), up to 300 eq. ft.
Infrared Humidifier, O.D. Copper
Condensate Drain, FPT
Condensate Drain w/Optional Condensate Pump, OD
5
7/8"
1-3/8"
1/4"
1-1/8"
1/2"
Liebert® DSE™ DA165 Supplement
Air-Cooled Systems
Table 2
Voltage
VAC
Electrical data
Reheat and Humidifier
Humidifier Only
Reheat Only
No Reheat; No Humidifier
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
380
130.4
137.0
150
130.4
137.0
150
118.2
128.1
150
118.2
124.8
150
460
105.5
110.7
125
105.5
110.7
125
95.8
106.6
110
93.9
99.1
110
575
86.2
90.3
100
86.2
90.3
100
75.6
84.0
90
74.6
78.7
90
Liebert® DSE™ DA165 Supplement
6
Liebert DSE Dimensions and Weights
3.0
LIEBERT DSE DIMENSIONS AND WEIGHTS
Table 3
Shipping dimensions and weights—domestic and export
Domestic Packaging
Model #
DA165
Figure 1
Export Packaging
Dimensions
L x W x H, in. (mm)
Weight
lb (kg)
Dimensions
L x W x H, in. (mm)
Weight
lb (kg)
153 x 54 x 85
(3886 x 1372 x 2159)
3785
(1717)
153.5 x 54.5 x 83.5
(3899 x 1384 x 2121)
3991
(1810)
Cabinet and floor planning dimensions—downflow, air-cooled, DA165, tandem scroll
compressor models
Filter Plenum
(shipped separately)
Filters are removed
though the front of
the plenum
48"
(1219mm)
Secondary Refrigerant
Piping Entrance
117-11/16"
Opening
(2989mm)
47"
(1194mm)
45"
(1143mm)
42"
(1067mm)
Opening
3/4"
(19mm)
Bezels
Striated area indicates
the recommended
minmum clearance for
component access.
24"
(610mm)
Shaded area indicates the required minimum
clearance below the unit to lower the fans
into the floor. Fans may remain in their shipped position.
144" (3658mm)
45"
(1143mm)
Plenum
18"
(457mm)
94"
(2388mm)
Total Height
76"
(1930mm)
Base Unit
142" (3607mm)
FRONT VIEW
1" TYP
(25mm)
Dry Weight
DA165: 3565 lb. (1617kg)
45"
(1143mm)
47"
(1194mm)
7
DPN002311
Rev. 0
Liebert® DSE™ DA165 Supplement
Liebert DSE Dimensions and Weights
Figure 2
Floor stand and floor planning dimensions—downflow model
C + 1-1/2" (38mm)
(with feet)
C
D
46-1/2"
(1181mm)
With Feet 43-1/2"
Typ (1105mm)
Center Feet
Typ
43"
(1092mm)
59-1/4"
Center Feet
(1505mm)
118-1/2"
Center Feet
(3010mm)
120-3/4" Center Feet
(3067mm)
1" (25mm)
Typical
45"
(1143mm) Typical
3/4" (19mm)
Typical
7/8"
(23mm)
Typical
A*
3"
(76mm)
Typical
47"
(1194mm)
Typical
B
1. This floor stand should be used when EC fans are intended to be lowered into the floor stand.
The standard Liebert floor stand can be used if the fans are to remain in their original raised position.
2. All paneled sides of unit overhang floorstand 1" (25mm).
3. The floor stand used with EC units is not symmetrical and proper orientation required for lowering
the blowers. Unless the floor stand is installed in the correct position, the blowers will not lower into
the floor stand.
4) Jack and jack support are shipped loose and are intended to be placed into position under each fan
and utilized to lower or raise that fan as needed individually.
5) Jack to lower blowers not provided with 18" floor stand.
* Leveling feet are provided with ±1-1/2” (38mm) adjustment from nominal height A.
Table 4
DPN002315
Rev. 1
Floor stand and floor planning dimensions—downflow, 165kW (47 ton) models
Height, in. (mm)
Dimensions, in. (mm)
A*
B*
Coolant Type
24 (610)
—
Air Cooled
30 (762)
—
36 (914)
5 (127)
42 (1067)
11 (279)
48 (1219)
17 (432)
Liebert® DSE™ DA165 Supplement
C
D
142 (3607)
21 (533)
Source: DPN002315, Rev. 1
8
Liebert DSE Dimensions and Weights
Figure 3
Condenser planning dimensions, MCL165 and MCL220
Height to top
of fan guard
Emerson recommends a clearance of
36" (915mm) on each side for proper
operation and component access.
55-5/8"
(1413mm)
Eyebolts for lifting condenser
provided on 3-fan and 4-fan models
13/16"
(21mm)
2-1/2"
(64mm)
3-5/8"
(93mm)
1-7/8" (48mm)
15-1/4"
(387mm)
2-1/2" (64mm)
55-1/2"
(1409mm)
1/2"x1"
3-5/8"
(12.7mm x 25.4mm)
(93mm)
Obround
1-7/8"
(48mm)
TYPICAL FOOTPRINT
For Dual
Circuit Only
15-1/4"
(387mm)
Provided on
3-fan and
4-fan models
One leg supplied
for each Liebert
Lee-Temp Kit
on 2-,3- &
4-fan models
Electric Box End
D
E
48-3/4"
(1239mm)
53-7/8"
(1368mm)
DPN002415
Rev. 3
54-3/8"
(1381mm)
Table 5
Cabinet and anchor dimensions, MCL165 and MCL220 with receivers
Dimensions
Liebert
No.
Model No. Fans A, in. (mm) B, in. (mm) C, in. (mm) D, in. (mm) E, in. (mm)
*
Leg Height
F*
G
H
MCL165
3
180-1/4
(4578)
73-7/16
(1866)
168-1/4
(4274)
110-1/2
(2806)
56-1/8
(1425)
18
(457)
35-7/8
(911)
43-5/8
(1108)
MCL220
4
236-5/16
(6003)
129-9/16
(3291)
224-3/8
(5699)
110-1/2
2806)
112-1/4
(2851)
36
(914)
53-7/8
(1368)
61-5/8
(1565)
48
(1219)
65-7/8
(1673)
73-5/8
(1870)
60
(1524)
77-7/8
(1978)
85-5/8
(2175
Cross-bracing required for legs longer than 18" (457mm); varies per model and options selected.
Source: DPN002415, Rev. 3
9
Liebert® DSE™ DA165 Supplement
Liebert DSE Dimensions and Weights
Figure 4
Required receiver mounting MCL165, MCL220 units, left-side mounting outlet receiver
Receiver Mounting Holes
Single Circuit
DETAIL A
Typ. 4 Places
4, 3, 2
1 16 15
3
1
Trim piping
as needed
A
7
14
13,12 2
8
11.23" (285.3mm)
Notes
1.
Use Items 15 and 16 as needed
for mounting Item 1.
2.
Item 12 to be used on MCL165 units.
Item 13 to be used on MCL220 units.
64.3"
(1383.1mm)
36"
(914.4mm)
Clearance required for
viewing sight glass
3
Cross-Bracing
Not Shown
3. Small receiver shown. Actual receiver
size may vary.
DPN002554
Pg. 1, Rev. 3
Item #
Description
Quantity
1
Receiver and Bracket Assembly
1
2
Cap Screw HXDIN933M8-1.25x25A2
4
3
Fender Washer DIN9021 M8x24 A2
8
4
Lock Nut, Hex Nylon Insert, M8
4
7
90-degree Elbow FTGXC 7/8" Copper
1
8
Copper Formed Tube 1-1/8"
1
12
Coupling, Copper 1-1/8"
1
13
Coupling, Copper 1-1/8" / Reducer, Copper CXC 1-3/8" x 1-1/8"
1
14
Reducer, Copper CXC 1-1/8"x7/8"
1
15
Support Leg
1
16
Fastener assembly: Cap Screw, Lock Washer, Fender Washer
4
Source: DPN002554, Page 1, Rev. 3
Liebert® DSE™ DA165 Supplement
10
Liebert DSE Dimensions and Weights
Figure 5
Required receiver mounting MCL165, MCL220 units, right-side mounting outlet receiver
Receiver Mounting Holes
Single Circuit
Trim piping
as needed
2
DETAIL B
12, 13
Typ. 4 Places
4, 3, 2
8
B
9
1 3
7
15 16 1
14
5,6
11.13" (282.6mm)
3
64.3"
(1383.1mm)
36"
(914.4mm)
Clearance required for
viewing sight glass
Cross-Bracing
Not Shown
DPN002554
Pg. 2, Rev. 3
Item #
Notes
1.
Use Items 15 and 16 as needed
for mounting Item 1.
2.
Item 12 to be used on MCL165 units.
Item 13 to be used on MCL220 units.
3.
Small receiver shown. Actual receiver
size may vary.
Description
Quantity
1
Receiver and Bracket Assembly
1
2
Cap Screw HXDIN933M8-1.25x25A2
4
3
Fender Washer DIN9021 M8x24 A2
8
4
Lock Nut, Hex, Nylon Insert, M8
4
5
Clamp Omega 1-1/8"
1
6
Screw Self-Drilling HWH YZ 10-16 x 5/8
2
7
90-degree Elbow FTGXFTG 7/8" Copper
1
8
Copper Formed Tube 1-1/8"
1
9
Copper Formed Tube 1-1/8"
1
12
Coupling, Copper 1-1/8"
1
13
Coupling, Copper 1-1/8" / Reducer, Copper CXC 1-3/8" x 1-1/8"
1
14
Reducer, Copper CXC 1-1/8" x 7/8"
1
15
Support Leg
1
16
Fastener assembly: Cap Screw, Lock Washer, Fender Washer
4
Source: DPN002554, Page 2, Rev. 2
11
Liebert® DSE™ DA165 Supplement
Electrical Connections
4.0
ELECTRICAL CONNECTIONS
4.1
Standard Electrical Field Connections, DA165 Downflow Models
Source: DPN002317, Revision 4; refer to Figure 7 for numbered items
1. Primary high voltage entrance—2.5" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts in bottom of box.
2. Primary low voltage entrance—Three knockouts, each 1.375" (35mm) diameter, in bottom of
unit.
3. Three-phase electrical service—Terminals are on top of the disconnect switch. Three-phase
service not by Emerson.
4. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for
Liebert units.
5. Remote unit shutdown—Replace existing jumper between Terminals 37 and 38 with
field-supplied, normally closed switch having a minimum rating of 75VA, 24VAC. Use
field-supplied Class 1 wiring.
6. Customer alarm inputs—Terminals for field-supplied, normally open contacts having a
minimum rating of 75VA, 24VAC, between Terminals 24 and 50, 51, 55, 56. Use field-supplied
Class 1 wiring. Terminal availability varies by unit options.
7. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 and 76
for remote indication. 1 AMP, 24VAC maximum load. Use field-supplied Class 1 wiring.
8. Heat rejection interlock—On any call for compressor operation, normally open dry contact is
closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1 AMP,
24VAC maximum load. Use field-supplied Class 1 wiring.
9. CANbus Connector—Terminal block with 49-1 (CAN-H) and 49-3 (CAN-L). The terminals are
used to connect the CANbus communication cable (provided by others) from the indoor unit to the
Liebert MC Condenser-Premium Model and Optional PRE unit.
10. CANbus Cable—CANbus cable provided by others to connect to the outdoor condenser. Cable
must meet the following specifications:
a. Conductors—22-18AWG stranded, tinned copper
b. Twisted pair (minimum eight twists per foot)
c. Braided shield or foil shield with drain wire
d. Low capacitance—15pf/ft or less
e. UL approved temperature rated to 75°C
f. UL approved voltage rated to 300V
g. UV-resistant and moisture-resistant if not run in conduit.
h. Plenum rated—NEC type CMP, if required by national or local codes
4.2
Optional Electrical Field Connections, DA165 Downflow Models
Source: DPN002317, Revision 4; refer to Figure 7 for numbered items
11. Factory-installed disconnect switch
12. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO
and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor
is not intended to function as or replace any room smoke detection system that may be required
by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
13. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 and 83 for lockout
of reheat and humidifier.
14. Condensate alarm (with condensate pump option)—On pump high water indication,
normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1A, 24VAC
maximum load. Use field-supplied Class 1 wiring.
15. Remote humidifier—On any call for humidification, normally open dry contact is closed across
Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
Liebert® DSE™ DA165 Supplement
12
Electrical Connections
4.3
Optional Low Voltage Terminal Package Connections, DA165 Downflow Models
Source: DPN002317, Revision 4; refer to Figure 7 for numbered items
16. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as
37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a
minimum rating of 75VA, 24VAC. Use field-supplied Class 1 wiring.
17. Common alarm—On any alarm, two additional normally open dry contacts are closed across
Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use Class 1
field-supplied wiring.
18. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is
closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
19. Liebert Liqui-tect® shutdown and dry contact—On Liebert Liqui-tect activation, normally
open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect
sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring
NOTE
Refer to specification sheet for total unit full load amps, wire size amps and maximum
overcurrent protective device size.
Figure 6
Electrical connection locations for DA165 downflow models
Low-Voltage Field
Wiring Pathways
High-Voltage Field
Wiring Pathways
DPN002317
Pg. 1, Rev. 4
13
Liebert® DSE™ DA165 Supplement
Electrical Connections
Figure 7
Electrical field connections for DA165 downflow model
Refer to Section 4.1 through 4.3 for keys to numbered items.
3
Liebert IntelliSlot Housing
P67
P64
OVERCURRENT PROTECTION DEVICES
A
B
F
C
D
4
(60Hz)
4
11
E
G
OVERLOADS
Contactors and Relays
1
6
24
50
51
55
56
A
16
5
7
17
13
14
12
19
8
18
15
75
76
94
95
96
97
B
82
83
88
89
C
80
81
91
92
93
58
59
70
71
230
84
85
11
12
D
37C
38C
37B
38B
37
38
F
9
10
Item 10 Installation Conditions
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or
chase as high voltage wires (120-600V).
3.Separate high volt wires from CAN wires by 12 in. (305mm).
4. Contact factory for runs greater than 350ft (107m).
E
Liebert® DSE™ DA165 Supplement
Low-Voltage Section 2
Notes:
Typical orientation of components shown.
Component location varies by option and unit size.
Refer to DPN002318 for descriptions of numbered callouts
DPN002317
Pg. 2, Rev. 4
14
Piping
5.0
PIPING
Risk of internal system corrosion and frozen coolant fluid. Can cause equipment damage and
major fluid leaks resulting in serious building damage, expensive repair costs, and costly
system down time.
Cooling and heat rejection coils, heat exchangers and piping systems that are connected to
open cooling towers or other open water/glycol systems are at high risk of freezing and
premature corrosion. Fluids in these systems must contain the proper antifreeze and
inhibitors to prevent freezing and premature coil, piping and heat exchanger corrosion. The
water or water/glycol solution must be analyzed by a competent local water treatment
specialist before startup to establish the inhibitor and antifreeze solution requirement and at
regularly scheduled intervals throughout the life of the system to determine the pattern of
inhibitor depletion.
The complexity of water/glycol solution condition problems and the variations of required
treatment programs make it extremely important to obtain the advice of a competent and
experienced water treatment specialist and follow a regularly scheduled coolant fluid system
maintenance program.
Read and follow individual unit installation instructions for precautions regarding fluid
system design, material selection and use of field-provided devices. Liebert systems contain
iron and copper alloys that require appropriate corrosion protection. It is important to have
the system running with flow through exchangers maintained at initial system fill for 24 to 48
hours depending on size and system configuration.
Water chemistry varies greatly by location, as do the required additives, called inhibitors,
that reduce the corrosive effect of the fluids on the piping systems and components. The
chemistry of the water used must be considered, because water from some sources may
contain corrosive elements that reduce the effectiveness of the inhibited formulation.
Sediment deposits prevent the formation of a protective oxide layer on the inside of the
coolant system components and piping. The water/coolant fluid must be treated and
circulating through the system continuously to prevent the buildup of sediment deposits and
or growth of sulfate reducing bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system.
Consult glycol manufacturer for testing and maintenance of inhibitors.
Commercial ethylene glycol (examples are Dow Chemical Dowtherm SR-1 Union Carbide
Ucartherm and Texaco E.G. Heat Transfer Fluid 100), when pure, is generally less corrosive
to the common metals of construction than water itself. It will, however, assume the
corrosivity of the water from which it is prepared and may become increasingly corrosive with
use if not properly inhibited.
15
Liebert® DSE™ DA165 Supplement
Piping
5.1
Piping Guidelines—Air-Cooled Units
• Indoor unit ships with a nitrogen holding charge. Do not vent the evaporator until all refrigerant
piping is in place, ready for connection to the unit and condenser.
• Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as
Sil-Fos. Avoid soft solders, such as 50/50 or 95/5.
• Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide
scale inside the piping. When copper is heated in the presence of air, copper oxide forms. POE oils
will dissolve these oxides from inside the copper pipes and deposit them throughout the system,
clogging filter driers and affecting other system components.
• A pure dry nitrogen flow of 1-3ft3/min (0.5-1.5 l/s) inside the pipe during brazing is sufficient to
displace the air. Control the flow using a suitable measuring device.
• Ensure that the tubing surfaces to be brazed are clean and that all burrs have been removed from
the ends of the tubes.
• Ensure that all loose material has been cleaned from inside the tubing before brazing.
• Protect all refrigerant line components within 18" (460mm) of the brazing site by wrapping them
with a wet cloth or with a suitable heat sink compound.
• Isolate piping from the building using vibration-isolating supports.
• Refer to Table 6 for piping sizes.
• Install traps on hot gas (discharge) lines at the base of vertical risers over 5 feet high. If the rise
exceeds 25 feet (7.5m), then install a trap in 20-foot (6m) increments or evenly divided of vertical
rise.
• Pitch horizontal hot gas piping down at a minimum rate of 1/2" per 10 feet (42mm per 10m) so
that gravity will aid in moving oil in the direction of refrigerant/oil flow.
• Condenser cannot be installed below the evaporator. The maximum height of the condenser above
the evaporator is 60 feet (18.3m).
• Consult factory if piping run exceeds 300 feet (91.4m) actual length, or 450 feet (137.2m)
equivalent length.
• Keep piping clean and dry, especially on units with R-410A refrigerant.
• Avoid piping runs through noise-sensitive areas.
• Do not run piping directly in front of indoor unit discharge airstream.
• Refrigerant oil—Do not mix oil types or viscosities (see refer to the Liebert DSE user manual,
SL-18925).
• Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping. The
Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side
refrigerant circuit. Consult building codes to determine if condensers without receivers will
require field-provided pressure relief devices. A fusible plug kit is available for field installation.
NOTE
All indoor and outdoor field refrigerant piping must have at least 1/2" of insulation. All
outdoor insulation must be UV and ozone resistant.
Table 6
Recommended refrigerant line sizes - OD copper
Equivalent
Length, ft. (m)
Hot Gas
Line, in.
Liquid
Line, in.
50 (15)
1-3/8
7/8
100 (30)
1-3/8
1-1/8
150 (45)
1-3/8
1-1/8
300 (90)
1-3/8
1-1/8
450 (137)
1-3/8
1-1/8
NOTE
Install a 1-3/8" liquid line between the condenser and the Liebert EconoPhase™ unit,
regardless of line sizes indicated in Table 6. See Figure 8.
Liebert® DSE™ DA165 Supplement
16
Piping
Table 7
Indoor unit approximate refrigerant charge for R-410A
R-410A Charge, lb (kg)
System Type
Model
Outer Circuit
Inner Circuit
Air-Cooled
DA165
28 (12.7)
25 (11.3)
Table 8
Interconnecting piping refrigerant charge
R-410A, lb/100 ft. (kg/30m)
Line Size,
O.D., in.
Table 9
Liquid Line
Hot Gas Line
7/8
19.8 (9.1)
2.3 (1.0)
1-1/8
33.8 (15.5)
3.9 (1.8)
1-3/8
51.5 (23.5)
5.9 (2.7)
Condenser refrigerant charge
Standard
Condenser Models
R410A Charge per Circuit Including Receiver, lb (kg)
MCL220E2
Large Receiver
Small Receiver
27 (12.2)
20 (9.1)
MCL165E1
33 (15)
26 (11.8)
MCL220E1
39 (17.7)
32 (14.5)
Condenser charge includes receivers
Small Receiver: 28" long; Large Receiver: 60" long
Table 10
Liebert PR125/PR085 module charge
System Type
Model
EconoPhase
Pumping Unit
PR125
PR085
Table 11
R410A Charge
per Circuit, lb (kg)
5.4 (2.5)
Condenser ambient selections
Outdoor
Design Ambient
High Efficiency
Condenser Match-Ups
Small Footprint
Condenser Match-Ups
95°F (35°C)
MCL165 (x2)
MCL165 (x2)
100°F (38°C)
MCL220 (x2)
Consult Factory
for Alternate Selections
MCL165 (x2)
105°F (41°C)
MCL220 (x2)
MCL220 (x2)
17
Liebert® DSE™ DA165 Supplement
Piping
5.2
Scroll and Digital Scroll—Additional Oil Requirements
System charges over 75lb (34kg) per circuit require additional oil charge. See Table 12 for the
amount required for various system charge levels.
After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at
the suction side of the system while the system is running.
The amount of oil added by field service must be recorded on the tag marked “Oil Added Field Service
Record,” attached to each compressor. The date of oil addition must be included as well.
Table 12
Additional oil required per refrigerant charge
System Charge Per Circuit - lb (kg) *
40
(18.1)
60
(27.2)
Model
DA165
80
(36.3)
100
(45.5)
120
(54.2)
140
(63.8)
160
(73.0)
180
(82.1)
200
(91.3)
122
(3458.6)
138
(3912.2)
Additional Oil Required Per Circuit - Ounces (Grams)
10
(283.5)
26.0
(737.1)
42
(1190.7)
58
(1644.3)
74
(2097.9)
90
(2551.5)
106
(3005)
* Consult your Emerson representative for system charges over 200 lb. (90.7kg).
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system
damage reduced or loss of cooling capacity and voiding of the compressor warranty.
Use only the oil types, viscosities and quantities recommended by the compressor
manufacturer. See the Liebert DSE user manual, SL-18925, for compressor oil types.
• Do not mix polyolester (POE) and mineral-based oils.
• Do not mix oils of different viscosities.
• Consult Emerson or the compressor manufacturer if questions arise.
5.3
Dehydration/Leak Test and Charging Procedures for R-410A
5.3.1
Air-Cooled Condenser - Premium Efficiency Control (PCB version)
The Liebert Premium Efficiency Control (PCB version) condenser is required for air-cooled Liebert
DSE models. The Electronically Commutative (EC) fan control system utilizes a Premium Efficiency
Control (PCB) board, EC fan motor(s) operating from 0 to 100% rpm based on refrigerant head
pressure, and refrigerant pressure transducer(s). The PCB board determines frequency changes
required to adjust the EC fan speed based on refrigerant head pressure. The PCB board, EC fan(s),
and transducer(s) are factory-wired. Multiple fan dual refrigeration circuit condensers adjust fan
speed independently to match each circuit's head pressure conditions.
NOTE
Liebert EconoPhase™ pumping units cannot be used with the Liebert Lee-Temp™ kit.
Liebert® DSE™ DA165 Supplement
18
Piping Schematic
6.0
PIPING SCHEMATIC
Figure 8
Piping schematic—air-cooled DA165 models
Optional EconoPhase
Unit
Differential
Check Valve
1-3/8" Liquid Line from Condenser
See Note 2.
Check
Valve
Liebert MC Condenser Liebert DSE
Receiver
Ball Valve
Includes Factory Traps
No External Trap Required
Hot Gas
Discharge
DA125 and DA150
Differential
Check Valve
DA125: 7/8"
DA150: 7/8" or 1-1/8"
Liquid to Indoor Unit
Depending on length of line
See Note 2
Solenoid Ball
Valve
Valve
1-3/8" Hot Gas Discharge
from Indoor Unit
See Note 2.
Liquid
Evaporator
Coil
Service
Valve
For rises over 25ft.
(7.6m), trap every
20ft. (6m) or
evenly divided
Suction
Field-installed relief valves
required for 50Hz EU CE
units rated maximum
650 PSIG (45 Bar)
Check
Valve
* Trap at Base
of Risers Over
5ft. (1.5m)
*Full Ported
Ball Valve
See Note 4.
Service
Valve
Check
Valve
Hot Gas Discharge
See Note 2.
Electronic
Expansion Valve
Liquid Return
See Note 2.
Differential
*Full Ported
Check Valve
Ball Valve
(Recommended)
See Note 4.
* Components are not supplied by
Emerson but are recommended for
proper circuit operation and
maintenance.
Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection, No Valve Core
Service/Schrader (Access) Connection, With Valve Core
1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit.
Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit.
3. Schematic representation shown. Do not use for specific connection locations.
4. Port in ball must be the same diameter as the piping I.D.
5. Length of piping between condenser and indoor unit shall be no greater than
300 ft (91.4 m) [Maximum equivalent length of 450 ft (137.2 m)].
6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m).
7. All indoor and outdoor field refrigerant piping must be insulated,
1/2" minimum thickness. All outdoor insulation must be UV- and ozone-resistant
19
DPN002340
Rev. 5
Liebert® DSE™ DA165 Supplement
Piping Schematic
Figure 9
Primary connection locations—downflow, air-cooled DA165 scroll compressor models
A
A
All dimensions from
rear corner of unit
including panels
X
FRONT VIEW
NOTE: Drawing not to scale.
Tolerance on all piping dimensions
is ±1/2" (13mm).
SECTION A-A
O
3-3/8"
(86mm)
L1 L2
G1 G2
R
Y
19"
(483mm)
CD
41"
(1041mm) Typical
AIR DISCHARGE
AREA
29-5/16"
(744mm) Typical
AIR DISCHARGE
AREA
47"
(1193mm)
LV1
LV2
LV3
E1 E2 HUM
B
FRONT EDGE OF UNIT
144" (3657mm)
* Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
DPN002312
Opening for conduit chase, E1 and E2 are openings for conduit for connections to 2-1/2", 1-3/4" and
Pg. 2, Rev. 4
1-3/8" knockouts at electric panel
DX Only
Point
Description
DX with Liebert
EconoPhase™
X
inches (mm)
Y
inches (mm)
Connection Size/
Opening, inches (mm)
19 x 3-3/8 (483 x 86) 19 x 3-3/8 (483 x 86)
R
Refrigerant Access
122-5/16 (3106)
12-1/8 (333)
L1
Liquid Line System 1
140 (3554)
14 (355)
1-1/8 Cu Sweat
1-1/8 Cu Sweat
L2
Liquid Line System 2
136-11/16 (3471)
14 (355)
1-1/8 Cu Sweat
1-1/8 Cu Sweat
G1
Hot Gas Discharge 1
127-7/8 (3248)
13-3/4 (348)
1-3/8 Cu Sweat
1-3/8 Cu Sweat
G2
Hot Gas Discharge 2
124-13/16 (3170)
13-3/4 (348)
1-3/8 Cu Sweat
1-3/8 Cu Sweat
110 (2794)
35-1/16 (891)
1-1/8 FPT
1-1/8 FPT
Condensate Drain *
(infrared humidifier or no humidifier)
CD
Condensate Drain
(steam generating humidifier) *
W/ Optional Pump
HUM Humidifier Supply Line
HS
Consult Factory
110 (2794)
35-1/16 (891)
1/2 Cu Sweat
1/2 Cu Sweat
101-1/4 (2572)
43 (1091)
1/4 Cu Sweat
1/4 Cu Sweat
Hot Water Reheat Supply
Consult Factory
HR
Hot Water Reheat Return
E1
Electrical Connection (High Volt)
113 (2870)
42-1/2 (1080)
Consult Factory
2-1/2
2-1/2
E2
Electrical Connection (High Volt)
110 (2794)
42-1/2 (1080)
2-1/2
2-1/2
LV1 Electrical Connection (Low Volt)
2-1/2 (64)
36 (914)
7/8
7/8
LV2 Electrical Connection (Low Volt)
2-1/2 (64)
37-1/2 (952)
7/8
7/8
LV3 Electrical Connection (Low Volt)
2-1/2 (64)
39 (991)
7/8
7/8
5-1/8 (131)
44 (1117)
93 x 41 (2362 x 1041)
93 x 41 (2362 x 1041)
B
Blower Outlet
Source: DPN002312, Rev. 4, Pg. 2
Liebert® DSE™ DA165 Supplement
20
Piping Schematic
NOTES
21
Liebert® DSE™ DA165 Supplement
Piping Schematic
Liebert® DSE™ DA165 Supplement
22
COMPLIANCE WITH EUROPEAN UNION DIRECTIVES
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
USA
Il Produttore dichiara che, se munito di marchio CE, il prodotto è conforme alle direttive dell'Unione
europea:
The Manufacturer hereby declares that this product, when bearing the CE mark, conforms to the
European Union directives:
Der Hersteller erklärt hiermit, dass das vorliegende Produkt, sollte es die CE-Kennzeichnung tragen, den
folgenden Richtlinien der Europäischen Union entspricht:
Le fabricant déclare par la présente que ce produit, portant la marque CE, est conforme aux directives
de l'Union européenne :
El fabricante declara por la presente que si este producto lleva el marcado CE es conforme con las
directivas de la Unión Europea:
O fabricante declara por este meio que este produto, quando ostenta a marca CE, está em
conformidade com as directivas da União Europeia:
Tillverkaren tillkännager härmed att den här produkten, när den är CE-märkt, överensstämmer med
EU:s direktiv:
De fabrikant verklaart hierbij dat dit product, indien het van de CE-markering is voorzien, conform de
EU-richtlijnen is:
Valmistaja vakuuttaa täten, että mikäli tuotteessa on CE-merkintä, se täyttää seuraavien EU-direktiivien
vaatimukset:
Produsenten erklærer herved at dette produktet, når det er CE-merket, er i samsvar med EU-direktiver:
Producenten erklærer hermed, at dette produkt overholder EU's direktiver, når det bærer CE-mærket:
Ο Κατασκευαστής δηλώνει ότι το προϊόν αυτό, το οποίο φέρει σήμανση CE, είναι σύμμορφο με τις
οδηγίες της Ε.Ε.:
2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2014 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
or registered trademarks of their respective owners.
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
SL-18931_REV1_03-14
Emerson Network Power
Liebert
www.emerson.com
www.EmersonNetworkPower.com