Liebert® eXL™ Installation Manual – 625-1200kVA, 1.0PF, 60Hz, Three-Phase, Single-Module and Multi-Module CONTACTING EMERSON NETWORK POWER FOR SUPPORT To contact Emerson Network Power Liebert Services for information or repair service in the United States, call 800-543-2378. Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts. For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Liebert Services, the authorized distributor is responsible for providing qualified, factory-authorized service. For Liebert Services to assist you promptly, please have the following information available: Part numbers: _________________________________________________________________ Serial numbers:________________________________________________________________ Rating: _______________________________________________________________________ Date purchased: _______________________________________________________________ Date installed:_________________________________________________________________ Location: ______________________________________________________________________ Input voltage/frequency: ________________________________________________________ Output voltage/frequency: ______________________________________________________ Battery reserve time:___________________________________________________________ Product Warranty Registration To register for warranty protection, visit the Service and Support section of our Web site at: www.liebert.com Click on Product Registration and fill out the form. TABLE OF CONTENTS CONTACTING EMERSON NETWORK POWER FOR SUPPORT . . . . . . . . . . . . . . . INSIDE FRONT COVER IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.1 1.2 1.3 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.1 1.3.2 1.4 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.1 1.4.2 1.4.3 1.4.4 1.4.5 Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Raised-Floor Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Kick Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6 6 6 7 1.5 1.6 1.7 System Composition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cable routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.0 UPS ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 2.1 2.2 2.3 External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Sizing the Input Breaker Feeding a Liebert eXL UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.3.1 2.4 Control Cable and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.4.1 2.4.2 2.5 2.6 Power Cable Connection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Multi-Module Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Digital LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.6.1 2.6.2 2.6.3 Three-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 High Resistance Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Preferred Grounding Configuration, Battery Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.7 2.8 No CB2 Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Internal Breaker Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.0 OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.1 Single-Module System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.1.1 3.1.2 3.1.3 3.2 Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Matching Liebert eXL Battery Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Remote Alarm Status Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Communication and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.2.1 Alber Monitoring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 i 4.0 5.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 APPENDIX A - SHIPPING SPLITS, KICKPLATES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Cabinet arrangement—Liebert eXL and battery cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Liebert eXL customer connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 UPS MMS/1+N connectivity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 LBS connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 No CB2 option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Typical main components, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Typical main components, 1000-1200kVA Liebert eXL, SMS and 1+N multi-module unit . . . . . 20 Outline Drawing, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . 21 Outline Drawing, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . 22 Base drawing, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . 23 Base drawing, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . 23 Input and battery terminal detail, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Input and battery terminal detail, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Output and bypass terminal detail, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Output and bypass terminal detail, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Input, output and bypass terminal spacing details, 625-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Low-voltage cable routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Cabling for single input configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Optional Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Control wiring, Programmable Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Inverter overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Rectifier overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Bypass overload data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Shipping split, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit . . . . . . . . . . . . 42 Shipping split, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit, continued . . . 43 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 1. . . . 45 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 2. . . . 46 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 3. . . . 47 Kickplate installation—625-800kVA units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Kickplate installation—1000-1200kVA, single module units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Kickplate installation—1000-1200kVA, 1+N multi-module units . . . . . . . . . . . . . . . . . . . . . . . . . 50 ii TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 UPS Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS control contacts to Battery Interface Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS control contacts to Remote Status Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Contact Isolator Board pre-assigned values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Contact Isolator Board control wiring connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Relay Board pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liebert eXL UPS specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—rectifier input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current ratings—DC source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended conduit and cable sizes for use with 100% rated breakers . . . . . . . . . . . . . . . . . . Recommended breakers, upstream and downstream . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended lug sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections associated with top down view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section J-J connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections associated with sections in “View” column. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii 13 13 14 14 31 31 32 33 35 35 35 35 39 40 41 41 43 43 44 iv Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert eXL UPS. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel. ! WARNING Risk of electrical shock. Can cause personal injury or death. This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires. Extreme caution is required when performing installation and maintenance. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and Maintenance Manual, SL-26030, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Ce système ASC comporte plusieurs circuits à haute tension c.a et c.c. Vérifiez les tensions au moyen de voltmètres c.a. et c.c. avant d’utiliser le système ASC. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d’établir tout contact. Seuls des employés qualifiés et dûment formés portant un casque, des gants, des chaussures et des lunettes de sécurité adéquats doivent se charger d’installer le système ASC ou de le préparer pour l’installation.Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. En cas d’incendie associé à du matériel électrique, n’utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d’origine électrique. Les opérations d’installation et d’entretien requièrent une extrême prudence. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien du système ASC. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer le système ASC. Observez également toutes les précautions décrites dans le manuel d’utilisation et d’entretien, SL-26030, avant et pendant toutes les procédures d’entretien. Observez toutes les précautions de sécurité appropriées lorsque vous travaillez sur à proximité d’une source c.c. de sécurité appropriées dès que vous vous trouvez à proximité d’une source c.c. 1 Liebert® eXL™ Important Safety Instructions ! WARNING Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight is up to 8095 lb. (3672 kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the module cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit. Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or prepare unit for installation. ! AVERTISSEMENT Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention peut entraîner des dommages matériels, des blessures et même la mort. Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviter de les endommager ou de blesser le personnel. Le module ASC pèse jusqu’à 3 672 kg (8 095 lb). Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler chaque armoire. Testez le levage et l’équilibre des armoires avant de transporter l’appareil. Maintenez en tout temps l'inclinaison verticale minimale. Les fentes situées à la base des armoires du module sont conçues pour utiliser le chariot élévateur. Les fentes situées à la base peuvent soutenir le système seulement si les fourches se trouvent complètement sous le système. Lisez toutes les instructions ci-dessous avant de tenter de déplacer, lever, déballer ou préparer le système en vue de son installation. ! WARNING Risk of electrical shock and fire. Can cause equipment damage, personal injury or death. Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections. All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes. One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident. Liebert® eXL™ 2 Important Safety Instructions ! AVERTISSEMENT Risque de décharge électrique et d’incendie. pouvant entraîner des dommages matériels, des blessures et même la mort. Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d’eau, d’humidité excessive et de débris. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours un voltmètre c.a. et c.c. pour vérifier les tensions avant d’établir un contact ou d’utiliser des appareils. Des tensions dangereusement élevées peuvent demeurer dans les batteries de condensateurs et au niveau des raccords c.c., même une fois l’alimentation coupée. Tous les raccords doivent être effectués par un électricien dûment formé et qualifié. Tous les câbles d’alimentation et de commande doivent être conformes aux codes nationaux et locaux en vigueur. Une personne ne devrait jamais travailler seule, même si toute l’alimentation d’entrée est coupée. Une deuxième personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident. NOTE Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions. NOTICE If optional filtering is installed, this unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. 3 Liebert® eXL™ Mechanical Installation 1.0 MECHANICAL INSTALLATION 1.1 Introduction This section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert eXL uninterruptible power supply and related equipment. This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures. ! WARNING Risk of electrical shock. Can cause injury or death. Special care must be taken when working with the batteries associated with this equipment. When they are connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Des précautions particulières doivent être prises lors de travaux touchant les batteries associées à cet équipement. Lorsque les batteries sont branchées ensemble, la tension à la borne d’une batterie dépasse 400 V c.c. et est potentiellement mortelle. NOTE All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation. NOTICE Three-phase input supply required. The standard Liebert eXL UPS is suitable for connection to three-phase, three-wire (+ Earth) TN-C and TN-S. NOTICE Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer. 1.2 Preliminary Checks Before installing the UPS, please carry out the following preliminary checks: • Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper immediately. • Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the interior doors reporting the type, size and main calibration parameters of the UPS. • Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system. Liebert® eXL™ 4 Mechanical Installation 1.3 Environmental Considerations 1.3.1 UPS Room The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Environmental Parameters in Table 8). The Liebert eXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings. The Liebert eXL UPS is equipped with air filters located behind the front doors. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions. When bottom entry is used, the conduit plate must be installed. NOTE The UPS is suitable for mounting on concrete or other non-combustible surface only. 1.3.2 Storage Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and/or heat sources (see Environmental Parameters in Table 8). 1.4 Positioning The cabinet is structurally designed to handle lifting from the base. Access to the power terminals, auxiliary terminal blocks and power switches is from the front. The door can be opened to give access to the power connection bars, auxiliary terminal blocks and power isolators. Front door can be opened to 90 degrees, and interior doors can be removed for more flexibility in installations. NOTE The UPS must be placed on a non-combustible surface suitable to support the weight of the unit. 5 Liebert® eXL™ Mechanical Installation 1.4.1 Moving the Cabinets The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors). Ensure that the UPS weight is within the designated surface weight loading (lb/in2) of any handling equipment. For weight details, see Table 8. The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit. Handling with straps is not authorized. ! WARNING Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death. Because the weight distribution in the cabinet is uneven, use extreme care while handling and transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weighs up to 8095 lb. (3672 kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. ! AVERTISSEMENT Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention peut entraîner des dommages matériels, des blessures et même la mort. En raison de la distribution inégale du poids de l’armoire, vous devez faire preuve d’extrême prudence lors de sa manipulation et de son transport. Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviter de les endommager ou de blesser le personnel. Le module ASC pèse jusqu’à 3 672 kg (8 095 lb). Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler chaque armoire. Testez le levage et l’équilibre les armoires avant de transporter l’appareil. Maintenez en tout temps l'inclinaison verticale minimale 1.4.2 Clearances The Liebert eXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to permit free passage of personnel with the doors fully opened. It is important to leave a distance of 24in. (610mm) between the top of the UPS and any overhead obstacles to allow the module to be serviced and to permit adequate circulation of air coming out of the unit. 1.4.3 Raised-Floor Installations If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to Figure 10 to design this pedestal. 1.4.4 Kick Plate Installation If the unit is to be installed in a position that does not permit access to rear kick plates, then the kick plates should be installed before the unit is placed in its final position. Liebert® eXL™ 6 Mechanical Installation 1.4.5 Special Considerations for 1+N Parallel Systems Design the grounding configuration of the system before finalizing module placement See 2.6 Grounding. The cabling impedance must be carefully controlled to ensure good load-sharing. Impedance mismatch may cause an overload on one module in a 1+N system, triggering a shutdown and loss of power to the connected load. Mismatched cable impedance is amplified when a 1+N system is operating on bypass because the power on the bypass path is not controlled. The Liebert 1+N UPS module is supplied with a sharing inductor to minimize the impact of cable impedance mismatch. An impedance mismatch may be further minimized by controlling the wiring length of each unit. The design and the layout of the UPS system and associated panels and cabling must be designed to ensure that cable lengths and impedances are closely matched. Contact Emerson Network Power® customer support for further information about matching cable impedances. 1.5 System Composition A UPS system can include a number of equipment cabinets, depending on the system design: (e.g., UPS cabinet, battery cabinet, maintenance bypass cabinet). In general, all the cabinets used in a particular installation are of the same height. Refer to the drawings provided in 4.0 - Installation Drawings for the positioning of the cabinets as shown in Figure 1. 1.6 Cable Entry Cables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) of the unit; see the figures in 4.0 - Installation Drawings. 7 Liebert® eXL™ Mechanical Installation 1.7 Cable routing Per NEC 300.20 (NEC 2014 or equivalent), all phase conductors and ground conductors must be grouped together when they are installed in ferrous enclosures or go through ferrous material. This is to avoid heating from induction currents. Figure 1 Cabinet arrangement—Liebert eXL and battery cabinets Liebert eXL UPS If the cabinets are to be bolted together, the side panels and hangers must be removed before beginning. Additional Battery Cabinet(s) (Matching) Additional Battery Cabinet(s) (Matching) Battery Cabinet (Matching) Battery Cabinet (Matching) Liebert eXL UPS Liebert eXL UPS Battery cabinets can be bolted to the left of the UPS and the cabling routed internally. Possible only with Enersys front terminal batteries or equivalent batteries in a Liebert cabinet. Liebert® eXL™ Liebert eXL UPS Battery Cabinet (Matching) Additional Battery Cabinet(s) (Matching) Battery cabinets can be bolted to the right of the UPS. However, the cabling must be routed externally. 8 UPS Electrical Installation 2.0 UPS ELECTRICAL INSTALLATION This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed. ! WARNING Risk of electrical shock. Can cause injury or death. The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Le système ASC contient des tensions c.c. et c.a. élevées. Vérifiez les tensions au moyen de voltmètres c.a. et c.c. avant d’utiliser le système ASC. Seuls des employés qualifiés et dûment formés portant un casque, des gants, des chaussures et des lunettes de sécurité adéquats doivent se charger d’installer le système ASC ou de le préparer pour l’installation. 2.1 External Protective Devices For safety, circuit breakers must be installed in the input AC supply and external battery system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed. External overcurrent protection must be provided. See Figures 21, 22 and 23 for overload capacity. 2.2 Power Cables The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run separately from the power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected. The cable design must comply with the voltages and currents in Tables 9 through 12, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media), room temperature and conditions of installation of the cable and system’s overload capacity (see 5.0 - Specifications). ! WARNING Risk of electrical shock. Can cause injury or death. Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the UPS input/bypass supply to the power distribution panel. Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Avant de procéder au câblage du système ASC, assurez-vous que vous êtes au courant de l’emplacement et du fonctionnement des isolateurs externes qui raccordent l’alimentation d’entrée ou de dérivation au panneau de distribution électrique. Vérifiez que ces raccords sont isolés électriquement et installez tous les panneaux d’avertissement nécessaires pour empêcher leur utilisation accidentelle. When sizing battery cables, a maximum voltage drop of 2VDC is permissible at the current ratings given in Table 12. 9 Liebert® eXL™ UPS Electrical Installation The following are guidelines only and are superseded by local regulations and codes of practice where applicable: • The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible. • Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably. • AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields. 2.3 Sizing the Input Breaker Feeding a Liebert eXL UPS Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in the NEC. Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for default current limit of 125%. If a smaller input feed breaker is used, the input current limit can be adjusted; see your Emerson representative for more information. The input current limit should not be set less than 105% of the current needed to support the inverter at full load for normal operation. This results in sufficient power to recharge the battery in a reasonable time and to operate over the published input voltage range. 2.3.1 Power Cable Connection Procedure The rectifier input, bypass, output and battery power cables (all require lug-type terminations) are connected to busbars in the I/O sections (refer to 4.0 - Installation Drawings). Equipment Ground The equipment ground busbars are in the I/O sections (refer to 4.0 - Installation Drawings). The grounding conductor must be connected to the ground busbar and bonded to each cabinet in the system. All cabinets and cabling should be grounded in accordance with local regulations. NOTE Proper grounding reduces problems in systems caused by electromagnetic interference. ! WARNING Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur. All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Emerson Network Power. See the back page of this manual for contact information. ! AVERTISSEMENT Le non-respect des procédures de mise à la terre peut entraîner des risques d’électrocution du personnel, ou des risques d’incendie en cas de défectuosité de la mise à la terre. Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou des techniciens professionnels dûment formés et qualifiés . En cas de difficultés, communiquez avec Emerson Network Power. Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel. Once the equipment has been positioned and secured, connect the power cables as described below (refer to the appropriate cable connection drawing in 4.0 - Installation Drawings): 1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. Liebert® eXL™ 10 UPS Electrical Installation 2. Open exterior and interior panels on the front of the I/O sections. 3. Connect the ground to the equipment ground busbar located in the I/O sections. 4. Make power connections and tighten the connections to the proper torque. Ensure correct phase rotation. ! WARNING Risk of electrical shock. Can cause injury or death. If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their termination. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Si les équipements branchés ne sont pas prêts à être alimentés à l’arrivée de l'ingénieur de mise en service, assurez-vous que les bornes des câbles de sortie du système soient isolées de façon sécuritaire. ! WARNING Risk of electrical shock. Can cause injury or death. When connecting the cables between the battery extremities to the circuit breaker, always connect the circuit breaker end of the cable first. ! AVERTISSEMENT Risque de décharge électrique pouvant causer des blessures graves, voire mortelles. Lors du raccordement de câbles entre des bornes de batterie et un disjoncteur, branchez toujours en premier l’extrémité du câble qui se raccorde au disjoncteur. 5. For control connection details, see 2.4 - Control Cable and Communication. NOTE If any fault bracing brackets were removed during installation, they MUST be replaced. 6. Close and secure the interior and exterior doors. 7. Attach the kick plates to the bottom of the unit. See Figure 29. 2.4 Control Cable and Communication Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker), communicate with a building management system or provide alarm signaling to external devices, or for Remote Emergency Power Off (REPO). The external interface connections, arranged for this purpose, are next to the option box in the Rectifier section (refer to 4.0 - Installation Drawings). 11 Liebert® eXL™ UPS Electrical Installation Figure 2 Liebert eXL customer connections 3 2 1 TB3-SKRU Enable TB2 – Digital Inputs Input 10 Input 9 Input 8 Input 7 Input 6 TB1-Remote Status Panel 10 9 8 7 6 5 4 3 2 1 20 19 18 17 16 15 14 13 12 11 4 3 2 1 4 3 2 1 Input 5 Input 4 Input 3 Input 2 Input 1 TB1154 – DC Communication J1 J2 J3 Reserved for MMS J4 J8 Remote Input Breaker J9 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 Liebert® eXL™ Remote Back Feed Breaker Reserved for Remote Breaker Options J7 Reserved for LBS Remote Output Breaker Liebert eXL Control Drawer J5 J6 12 10 9 8 7 6 5 4 3 2 1 Reserved for Remote Breaker Options 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 Reserved for Remote Breaker Options UPS Electrical Installation 2.4.1 Dry Contacts Table 1 UPS Digital Inputs Item Maintenance Bypass Breaker (MBB) Maintenance Isolation Breaker (MIB) Bypass Isolation Breaker (BIB) Not Used Not Used REPO/EPO (N.O.) REPO/EPO (Form-C or N.C.) REPO/EPO (Form-C) Key Status Not Used Terminal Block Pin TB2 1 MBB Aux Contact, Closed = CB Is Closed TB2 2 MBB Aux Contact Common TB2 3 MIB Aux Contact, Closed = CB is Closed TB2 4 MIB Aux Contact Common TB2 5 BIB Aux Contact, Closed = CB is Closed TB2 6 BIB Aux Contact Common TB2 7 — TB2 8 — Connects to (Description of External Item) TB2 9 TB2 11 REPO Switch, Normally Open Contact — TB2 12 REPO Switch, Normally Open Common TB2 13 REPO Switch, Normally Closed Contact TB2 14 REPO Switch, Normally Closed Common TB2 15 REPO Switch, Normally Open Contact TB2 17 Key Status Switch, Closed = Key Released TB2 18 Key Status Switch, Common TB2 19 — TB2 20 — 1. All contacts have: Maximum voltage: 24VDC Maximum current: 10mA Wire range: #14-22AWG Maximum length: 500' (150m) 2. All external wire furnished by others 3. All wiring must be in accordance with national and local electrical codes. 4. If using REPO/EPO with Form-C contacts, Pins 13-15 must be used. 5. If using REPO/EPO with normally closed (N.C.) contacts only, a jumper must be placed across Pins 13 and 14. Table 2 UPS Output Item SKRU Enable Terminal Block TB3 Pin Connects to (Description of External Item) 1 Maintenance Bypass Cabinet, Common 2 Normally Closed (NC) 3 Normally Open (NO) Maximum Voltage Maximum Current Wire Range Maximum Length 120VAC 1A #14AWG 164ft (50m) 1. To prevent signal interference, low-voltage (<48V) and low-current (5A) cable groups should be run in separate, grounded conduit from high-voltage or high-current cable groups. 2. All external wire furnished by others. 3. All wiring must be in accordance with national and local electrical codes. 13 Liebert® eXL™ UPS Electrical Installation Table 3 UPS control contacts to Battery Interface Boards Terminal Block Item Battery Cabinet Communication TB1154 Pin Connects to (Description of External Item) 1 CAN +24V 2 CAN Common 3 CANbus High 4 CANbus Low Maximum Voltage Maximum Current Wire Range Maximum Length 24VDC 2A 18AWG 1000ft (305m) 1. To prevent signal interference, low voltage (<48V) and low current (5A) cable groups should be run in separate grounded conduit from high voltage or high current cable groups. 2. All external wire furnished by others. 3. All wiring must be in accordance with national and local electrical codes. 4. The maximum length must take into account all battery communications connections in the system. Table 4 UPS control contacts to Remote Status Panel Item Remote Status Panel Terminal Block TB1 Pin Connects To (Description of External Item) 1 CAN +24V 2 CAN Common 3 CANbus High 4 CANbus Low Maximum Voltage Maximum Current Wire Range Maximum Length 24VDC 150mA 18AWG 1000ft (305m) 1. To prevent signal interference, low voltage (<48V) and low current (5A) cable groups should be run in separate grounded conduit from high voltage or high current cable groups. 2. All external wire furnished by others. 3. All wiring must be in accordance with national and local electrical codes. Liebert® eXL™ 14 UPS Electrical Installation 2.4.2 Multi-Module Communication Paralleling cables that connect the module to other modules in the 1+N system are connected via Terminals J1-J6 customer connections on the control drawer. See Figure 3. Figure 3 UPS MMS/1+N connectivity Cat 6 Cable UPS 1 Reserved for MMS/1+N Reserved for LBS UPS 2 UPS n J1 J1 J1 J2 J2 J2 J3 J3 J4 J4 J4 J5 J5 J5 J6 J6 J7 J7 J7 J8 J8 J8 J9 J9 J9 NC NC 15 J3 J6 Liebert® eXL™ UPS Electrical Installation 2.5 Digital LBS The Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or when supplied by unsynchronized input sources. Digital LBS cables that connect the module to the system are connected to Terminals J7-J9 customer connections on the control drawer. See Figure 4. Figure 4 LBS connectivity Cat 6 Cable UPS 1 Reserved for MMS/1+N UPS n J1 J1 J1 J2 J2 J2 J3 J3 J4 J4 J4 J5 J5 J5 J6 J6 NC J6 J7 J7 NC J7 NC J8 J8 NC J8 NC J9 J9 NC J9 NC To next set of modules, UPS1-J7 Cat 6 Cable UPS 2 2.6 Grounding 2.6.1 Three-Wire Input connections NC J3 Reserved for LBS This module must NOT be used when single-phase loads are directly connected to the UPS. Note that whenever the UPS module transfers to or from bypass, two AC sources (UPS output and bypass) are briefly connected together and circulating current must flow. In this configuration, the current flows through the ground path and may trip ground fault interrupters (GFI’s), distorting the output voltage waveform. Proper adjustment of GFI’s is necessary to avoid unwanted tripping. The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation. NOTICE Failure to set the ground fault interrupters properly could cause loss of power to the critical load. 2.6.2 High Resistance Grounding Contact your Emerson® representative or the factory to determine whether the Liebert eXL is compatible with the specific type of HRG system involved. Liebert® eXL™ 16 UPS Electrical Installation 2.6.3 Preferred Grounding Configuration, Battery Systems Open-rack battery systems, depending on local code requirements and customer preference, are normally: • Floating (ungrounded) OR • Center-tapped and floating Battery cabinet systems must be connected as floating (ungrounded) systems. Center-tapped or grounded battery systems are not possible with battery cabinet systems. Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus. 2.7 No CB2 Option Figure 5 No CB2 option Maintenance Bypass 3-Wire + GND FBO FBO UPS Module AC Output 3-Wire + GND Critical Load If a module does not have the inverter output breaker CB2, an overcurrent protection device with a manual disconnect must be supplied by others in a readily accessible location. This overcurrent protection device must be appropriately sized. See Table 11 for rated module output current. For system breaker coordination, see Figures 21 through 23 for the overload capabilities of the modules. NOTE This option does not allow the Liebert eXL module to be isolated from critical load. Emerson recommends installing a wraparound maintenance bypass. If a wraparound bypass is not installed, according to the latest OSHA safety regulations, the output of the module may need to be shut down to maintain the module. 2.8 Internal Breaker Settings All internal breakers—CB1, CB2 and BFB—were installed and set at the factory. NOTICE Risk of incorrect adjustment. Can cause equipment damage. Factory circuit breaker settings must not be altered without contacting Emerson Network Power® customer support. 17 Liebert® eXL™ Optional Equipment 3.0 OPTIONAL EQUIPMENT 3.1 Single-Module System Options 3.1.1 Battery Temperature Sensor The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board. 3.1.2 Matching Liebert eXL Battery Cabinet The optional matching Liebert eXL Battery Cabinet can be used to obtain the desired autonomy time. The battery cabinets are designed to be either attached to the UPS or separate from the UPS (for details, see the Liebert eXL Battery Cabinet installation manual, SL-26035, available at Emerson Network Power’s Liebert Web site: www.liebert.com). 3.1.3 Remote Alarm Status Panel The remote alarm status panel has LED alarm lights. An audible alarm sounds upon any alarm condition. The surface- or flush-mounted NEMA 1 enclosed panel indicates: Load on UPS, Load on Bypass, Battery Discharging, Low Battery Warning, Overload Warning, Ambient Overtemp Warning, UPS Alarm Condition, New Alarm Condition (For a Second UPS Alarm Condition). 3.2 Communication and Monitoring The Liebert eXL has these monitoring options: • Liebert IntelliSlot® Unity-DP (Dual Protocol) Card The Liebert IntelliSlot Unity Card provides Web, embedded Emerson® LIFE™ Technology, Emerson Protocol, SNMP, BACnet IP/MSTP, Modbus TCP/RTU, SMTP, SMS, and telnet communication and control capabilities in one unified communication platform. The platform supports 10/100 Mbit Ethernet, IPv4 and IPv6, HTTP/HTTPS for device Web page access, SMTP interface for e-mail, SMS interface for text messaging, Emerson Protocol for communicating with Trellis™ and Liebert Nform® software applications and LIFE technology for supporting Liebert Remote Service Delivery. SNMP v1/v2c/v3, Modbus TCP/IP, BACnet IP, Modbus RTU, BACnet MSTP and YDN23 thirdparty protocols are also supported for building management and network management applications. The Liebert IntelliSlot Unity card provides ground fault isolated 10/100 baseT Ethernet and RS-485 network connectivity. • Programmable Relay Board • Input Contact Isolator Board 3.2.1 Alber Monitoring System The matching Liebert eXL Battery Cabinet has space for an Alber battery monitoring system. The battery monitoring system can be factory-installed or field-installed later. The Alber Battery Monitor by Emerson continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Capabilities include automatic internal patented DC resistance tests and trend analysis, providing the ability to analyze performance, aid in troubleshooting and detect failing cells before they fail. Liebert® eXL™ 18 Installation Drawings 4.0 INSTALLATION DRAWINGS Figure 6 Typical main components, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit Liebert IntelliSlot Housings Back Feed Circuit Breaker (BFB) HMI Screen (On Exterior Door) Keylock or EMO Button (optional) Module Output Circuit Breaker (CB2) Main Input Circuit Breaker (CB1) Option Box (5 Slots) High Voltage Sense Connectors FRONT DOORS REMOVED Input Core Core Output/Bypass Output Ground Busbar Bypass Busbars DC Input Input Busbars Control Drawer Output Busbars Input Ground U46-8C-2000 Rev. 4 19 Liebert® eXL™ Installation Drawings Figure 7 Typical main components, 1000-1200kVA Liebert eXL, SMS and 1+N multi-module unit Liebert IntelliSlot Housings Back Feed Circuit Breaker (BFB) HMI Screen (On Exterior Door) Module Output Circuit Breaker (CB2) Keylock or EMO Button (Optional) Main Input Circuit Breaker (CB1) FRONT DOORS REMOVED Option Box (5 Slots) High-Voltage Sense Connectors DC Input Input Core Core Core Output/Bypass Bypass Busbars Input Busbars Output Ground Busbar Input Ground Output Busbars Control Drawer DOORS AND INNER SKINS REMOVED Liebert® eXL™ 20 U46-12C-2000 Rev. 3 Installation Drawings Figure 8 Outline Drawing, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit Bypass\Output Cable Exit, Area With Panel Removed 12.5" x 23.2" (318mm x 590mm) Panel to Frame Typical To Frame 1.3" (33mm) Opposite Side Rectifier\DC Cable Entry, Area With Panel Removed 12.5" x 21.9" (318mm x 556mm) Low Voltage Cable Entry \ Exit, Area With Panel Removed 8.8" x 9.8" (224mm x 250mm) To Frame 1.3" (33mm) 4" (101mm) to Frame TOP VIEW 14.3" (363mm) to Frame To Frame 2.4" (60mm) Rectifier\DC Cable Entry, Area With Panel Removed (23.5" x 21.8" (597mm) x 553mm) To Frame 2.6" (65mm) 1.4" (37mm) To Frame Typ Opposite Side 1.6" (40mm) Section A - (Top Looking Down) Low-Voltage Cable Entry\Exit, Area With Panel Removed 4.9" x 21.8" (125mm x 553mm) 33.9" (862mm) 123.6" (3140mm) 51.2" (1300mm) BOTTOM VIEW Bypass\ Output Cable Exit, Area With Panel Removed 10.9" x 28.4" (278mm x 722mm) 38.5" (978mm) 77.5" (1969mm) See Bottom View Input Core Core Output/Bypass FRONT VIEW Notes 1. 24" (610mm) minimum clearance above unit required for air exhaust, and 36" (914mm) front access required for service. 2. Keep cabinet within 15 degrees of vertical while handling. 3. Top and bottom cable entry available through removable access plates. Remove punch to suit conduit size and replace. 4. Unit bottom is structurally adequate for forklift handling. 5. Control wiring and power wiring must be run in separate conduits. 6. All wiring is to be in accordance with national and local electrical codes. 7. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels. 8. See technical information drawing for shipping split weights. 21 33.5" (851mm) 34.4" (874mm) With Accent Strip RIGHT SIDE VIEW U46-8C-2001 Rev. 3 Liebert® eXL™ Installation Drawings Figure 9 Outline Drawing, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit Rectifier/DC Cable Entry, Area With Panel Removed 22.7" x 32.2" (577 x 819mm) 2.4" (60mm) To Frame 2.4" (60mm) To Frame 1.3" (33mm) To Frame Typical Opp. Side Section A (Top Looking Down) BOTTOM VIEW Low-Voltage Cable Entry/Exit, Area With Panel Removed 6.0" x 32.2" (152 x 819mm) 1.3" (33mm) To Frame Rectifier/DC 2" Cable Entry, Area (50mm) With Panel Removed 14.7" x 33.3" (373 x 846mm) Low-Voltage Cable Entry/Exit, Area With Panel Removed 10.6" x 7.9" (269 x 7.9mm) Bypass/Output Cable Exit, Area With Panel Removed 28.7" x 14.3" (730 x 364mm) 1.3" (33mm) To Frame 3" (77mm) To Frame Bypass/Output Cable Exit, Area With Panel Removed 25.4" x 15.7" (645 x 399mm) FRONT TOP 26.7" (679mm) To Frame 170.7" (4335mm) 47" (1193mm) 76.7" (1949mm) 47" (1193mm) 77.5" (1969mm) A A INPUT CORE CORE CORE See Bottom View OUTPUT/BYPASS 33.5" (850mm) 34.4" (874mm) With Accent Strip RIGHT SIDE FRONT NOTES 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit required for air exhaust; 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. All wiring is to be in accordance with national and local electrical codes. 8. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels. 9. See technical information drawing for shipping split weights. Liebert® eXL™ 22 U46-12C-2001 Rev. 2 Installation Drawings Figure 10 Base drawing, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit Input Core Core Output/Bypass Front 20.5 (520) 27.8 (705) 16.4 (416) 20.5 (520) Forklift Openings 12.8 (324) 23.8 (605) Oppo. Side Typ. Forklift Openings FRONT VIEW 26.2 (665) 18.5 (470) Right Side Lift Clearance 14.8 (376) 18.5 (470) 3.9 (99) Oppo. Side Typ 11.2 (284) 30.8 (781) 23.8 (605) Foot Spacing Outside Foot Spacing Inside 25.6 (651) Pillar Spacing Inside 31.3 (795) Pillar Spacing Outside Front 3.5 (90) 7.1 (180) 1. All dimensions are in inches (mm). 2. Unit bottom is structurally adequate for forklift handling. 7.1 7.1 (180) (180) (Top Looking Down) BOTTOM VIEW Footprint Spacing 4.7 (120) Conduit Plate Behind Support Rail 3.5 (90) Front 6.1 (155) Oppo. Side, Typ BOTTOM OUTPUT Right Side Bottom Cable Entry Panels Figure 11 U46-8l-1000 Rev. 0 Base drawing, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit Input Core Output/Bypass Core Core Front 20.5 (520) 20.5 (520) 20.5 (520) 23.8 (605) Opposite Side Typical 18.8 (478) Forklift Openings 18.8 (478) Forklift Openings RIGHT SIDE Lift Clearance 3 (99) Opposite Side Typical FRONT VIEW 40.7 (1035) 18.5 (470) 18.5 (470) 18.5 (470) 18.8 (478) 18.8 (478) 31.3 (795) Pillar Spacing 25.6 (651) Outside Pillar Spacing Inside 30.8 (781) Foot Spacing 23.8 (605) Outside Foot Spacing Inside 2.8 (70) Foot to Pillar 6.3 (160) Front 7.1 7.1 (180) (180) BOTTOM VIEW (Top Looking Down) Footprint Spacing 6.3 (160) 3.1 (80) 2.8 (70) Foot to Pillar NOTES: 1. All dimensions are in inches (mm). 2. Unit bottom is structurally adequate for forklift handling. U46-12L-1000 Rev. 0 23 6.1 (155) Opposite Side BOTTOM OUTPUT Right Side Bottom Cable Entry Panels Liebert® eXL™ Installation Drawings Figure 12 Input and battery terminal detail, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit #1 Input Phase Busbar 20.5 x 4 x .38 Ø.56 (14) Typ. 2.05 (52) Typ. #3 ISOMETRIC VIEW 1.75 (44) #2 #2 DC Pos. / Neg. Busbar 20.1 x 4 x .5 Ø.56 (14) Typ. #1 #1 1.75 (44) #3 #3 Input Ground Busbar 25.4 x 3 x .25 (See Isometric View) #3 Ø.56 (14) Typ. 42.8 (1088) 1.75 (44) 23 (584) LEFT SIDE VIEW INPUT 1.26 (32) Typ. LEFT SIDE VIEW TILTED DOWN TO SHOW BUSBARS Notes 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits. 3. All wiring is to be in accordance with national and local electrical codes. 4. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1" (25mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing are the responsibility of the installing contractor and authority having jurisdiction. Liebert® eXL™ Ø.56 (14) Typ. 1.75 (44) U46-8E-3200B Rev. 3 24 Installation Drawings Figure 13 Input and battery terminal detail, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit 2. Input Aux. Ground Busbar 21.6 x 5 x .25 1. Input Ground Busbar 29.5 x 5 x .25 Ø 0.563 x .875 (14x22) Typical Ø 0.563 x .875 (14x22) Typical 2.2 (56) 1.97 (50) 1.75 (44) 1.75 (44) 2.09 (5.3) 1.97 (50) 2.5 (64) Ø 0.624 x 1 (16 x 25.4) 2 Places 4. DC Pos. / Neg. Busbar 18.7 x 6 x .5 Ø 0.563 (14) Typical 3. Input Phase Busbar 18.6 x 3.5 x .5 Ø 0.563 (14) Typical 1.75 (44) 1.75 (44) 2.06 (52.4) Typical 2.04 (52) Typical 1 4 3 FRONT 2 1 43.7 (1109) SECTION OF LEFT SIDE VIEW Tilted Down to Show Busbars LEFT SIDE VIEW NOTES Input 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits 3. All wiring is to be in accordance with national and local electrical codes. 4. See Page 1, Drawing U46-12E-3200A and Page 3, Drawing U46-12E-3200C. 5. Based on NEC 408.56 minimum spacing, all live parts, including lugs, need to be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction (AHJ). 25 U46-12E-3200B Rev. 0 Liebert® eXL™ Installation Drawings Figure 14 Output and bypass terminal detail, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit 2.36" (60mm) Typ. #4 Bypass Input Busbar 38.2 x 4 x .25 Ø .56" (14mm) Typ. 1.43" (36mm) 2.36" (60mm) Typ. 2.36" (60mm) Typ. 4 6 #5 Phase Output Busbar 17.7 X 4 X .25 Ø .56" (14mm) Typ. 1.44" (37mm) 1.0" (25mm) Typ. 2.36" (60mm) Typ. 5 #6 Output Ground Busbar 25.4 x 3 x .25 1.97" (50mm) Typ. 58.4" (1484mm) Ø .56" (14mm) Typ. 1.75" (44mm) 30.3" (770mm) 18.5" (469mm) Notes: 1. Control wiring and power wiring must be run in separate conduits 2. All wiring is to be in accordance with national and local electrical codes. 3. See Page 1, Drawing U46-8E-3200A and Page 2, Drawing U46-8E-3200B. 4. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1" (25mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction. Liebert® eXL™ 26 RIGHT SIDE VIEW OUTPUT/BYPASS Dual Hole Lug Pad Width (Max.) 1.75" (44mm) U46-8E-3200C Rev. 3 Installation Drawings Figure 15 Output and bypass terminal detail, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit 5. Bypass Input Busbar 44.3" x 3.5" x .5" (1125 x 89 x 13mm) Ø 0.563" (14mm), Typical 1.56" (39.6mm) 1.75" (44mm) Typical Ø 0.563" x 1.375" (14 x 35mm) Typical 6. Output Ground Busbar 28.4" x 5" x .25" (722 x 127 x 7mm) 1.97" (50mm) 5 1.75" (44mm) 6 2.63" (67mm) Ø 0.563" x 1.375" (14 x 35mm) Typical 7 7. Output Phase Busbar 29.5" x 4" x .375" (749 x 102 x 10mm) Ø 0.563" (14mm), Typical 1.56" (39.6mm) 1.75" (44mm) Typical 54.4" (1381mm) Ø 0.563" x 1.375" (14 x 35mm) Typical 23" (585mm) 20.9" (531mm) Dual Hole Lug Pad Width (Max.) 1.75" (44mm) RIGHT SIDE Output/Bypass Notes: 1. All dimensions are in inches (mm). 2. Control wiring and power wiring must be run in separate conduits 3. All wiring is to be in accordance with national and local electrical codes. 4. See Page 1, Drawing U46-12E-3200A and Page 2, Drawing U46-12E-3200B. 5. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method U46-12E-3200C of stacking and required minimum spacing is the responsibility of the Rev. 0 installing contractor and authority having jurisdiction (AHJ). 27 Liebert® eXL™ Installation Drawings Figure 16 Input, output and bypass terminal spacing details, 625-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit #1 #2 SEE BUSBAR DETAIL PAGES 2 & 3 A B C - + #3 A B C A B C 3 [75] Typ. Input (Front) #4 3 (75) Typ. Between Busbars #5 #6 Output/Bypass TOP VIEW 1. All dimensions are in inches [mm]. 2. Control wiring and power wiring must be run in separate conduits. 3. All wiring is to be in accordance with national and local electrical codes. 4. See Page 2, Drawing U46-8E-3200B and Page 3, Drawing U46-8E-3200C. Liebert® eXL™ #1 Input Phase Busbar #2 DC Pos. / Neg. Busbar #3 Input Ground Busbar #4 Bypass Input Busbar #5 Phase Output Busbar #6 Output Ground Busbar 28 U46-8E-3200A Rev. 0 Installation Drawings Figure 17 Low-voltage cable routing Use these entry holes for Liebert IntelliSlot® Unity™ card cables only Low Voltage Control Cable Top Entry Low Voltage Wire Way Service Drawer Provide at least 18" (457mm) of service loop to all control connections to permit opening the service drawer without removing the connections. The extra service loop can either be left hanging or loosely attached to the corner post. Openings to Control Wire Way To Ensure Isolation: All wiring must have insulation rated for 600V or higher. • All cables not rated Class 1 must be kept separated and secured away from high-voltage Class 1 cables. Bottom Entry INPUT Low-Voltage DOORS AND INNER SKINS REMOVED Control Cable Use these entry holes for Liebert IntelliSlot® Unity™ card cables only 29 Liebert® eXL™ Installation Drawings Figure 18 Cabling for single input configuration Note 1 INPUT CORE CORE OUTPUT/BYPASS 625-800kVA unit shown, similar configuration for 1000-1200kVA unit INPUT CORE CORE OUTPUT/BYPASS NOTES 1. 24" (610) minimum clearance above unit required for air exhaust. 2. Top and bottom cable entry available through removable access plates. Remove punch to suit conduit size and replace. 3. All wiring is to be in accordance with national and local electrical codes. 4. See Table 13 for cable sizing 5. Connection between the rectifier and bypass busbars are supplied by others. 6. Based on NEC 408.56 minimum spacing, all live parts, including lugs, must be at least 1 inch (25.4mm) from any other live part from a different phase or the chassis frame. If lug stacking is required, the method of stacking and required minimum spacing is the responsibility of the installing contractor and authority having jurisdiction. See Figures 12- 16 for busbar details. Figure 19 Optional Input Contact Isolator Board P99 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 P66 1. 2. 3. 4. 5. 6. J51 Customer control wiring connection points are terminals 1 through 16 (see Table 6). Customer provided normally open dry contacts for user alarm messages. All control wiring (by others) must be run separate from power wiring. Signal voltage: 100mA @ 12VDC. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. All wiring must be in accordance with national and local electrical codes. Liebert® eXL™ 30 Installation Drawings Table 5 Input Contact Isolator Board pre-assigned values Channel # ICI #1 ICI #2 Pre-Assigned Label Pre-Assigned Label 1 Reduced Rect ILimit * Inhibit Intelligent Paralleling 2 Reduced Batt ILimit None 3 Stop Battery Charge None 4 Inhibit Auto Restart None 5 * EcoMode Suspended None 6 Inhibit BPSS None 7 Manual Xfer to UPS None 8 Manual Xfer to BPSS None * EcoMode and Intelligent Paralleling are currently not supported. Table 6 Input Contact Isolator Board control wiring connections Input Contact 1 2 3 4 5 6 7 8 Pin No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 31 Liebert® eXL™ Installation Drawings Figure 20 Control wiring, Programmable Relay Board J71 P99 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 P66 J72 1. 2. 3. 4. 5. 6. Customer control wiring connection points are terminals 1 through 12. Programmable Relay Board option includes eight signal channels with one Form-C dry contact per channel (see Table 7). All control wiring (by others) must be run separate from power wiring. Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. All wiring must be in accordance with national and local electrical codes. Table 7 Terminal Block J71 J72 Liebert® eXL™ Programmable Relay Board pinout Channel Pin No. Common Normally Closed Normally Open CH1 CH2 CH3 1-3 4-6 7-9 1 4 7 2 5 8 3 6 9 CH4 CH5 CH6 CH7 CH8 10-12 1-3 4-6 7-9 10-12 10 1 4 7 10 11 2 5 8 11 12 3 6 9 12 32 Specifications 5.0 SPECIFICATIONS Table 8 Liebert eXL UPS specifications 625-800kVA 1000-1200kVA Input Voltage to Rectifier, VAC 480V 3-phase, 3-wire 480V 3-phase, 3-wire Input Voltage to Bypass, VAC 480V 3-phase, 3-wire 480V 3-phase, 3-wire +10% to -30% +10% to -30% Model Size Input Parameters Input Voltage Range, VAC 60 60 Permissible Input Frequency Range, Hz Input Frequency, Hz 55 to 65 55 to 65 Reflected Input THDi, Nominal Voltage, Full Load, % <5% <5% 1 to 30 (selectable) in 1 sec. Increments 1 to 30 (selectable) in 1 sec. Increments VRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid) VRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid) Nominal Battery Bus, VDC 480V 480V Battery Float Voltage, VDC 540V 540V 384V (for VRLA / Flooded Lead Acid) 384V (for VRLA / Flooded Lead Acid) <1 (RMS value) < 3,4% Vpp <1 (RMS value) < 3,4% Vpp Optional (with temperature probe) Optional (with temperature probe) IGBT-based Sine Wave PWM Controlled IGBT-based Sine Wave PWM Controlled 625 | 750 | 800 1000 | 1100 | 1200 Power Walk-In, sec Battery & DC Parameters Battery Type Minimum End of Discharge Voltage, VDC DC Ripple Voltage in Float & Const V Ch. Mode, % Temperature Compensated Battery Charging Output Parameters Inverter Type Output Power, kW 480V 3-ph, 3-wire 480V 3-ph, 3-wire Output Voltage Regulation, % Output Voltage, VAC < 1% (3-phase RMS average) < 1% (3-phase RMS average) Output Voltage Regulation (50% Unbalanced Load) < 2% (3-phase RMS average) < 2% (3-phase RMS average) 60 60 Output Frequency, Hz Output Frequency Regulation, % ± 0.1 ± 0.1 Output THDv Linear Load at Nominal Voltage, % <3% <3% Output THDv at Nominal Voltage Including a 100kVA Non-Linear Load per EN 62040-3, % 6% (max) 6% (max) Capacity to Handle High Crest Factor Load 3:1 3:1 0-100 or 100-0 0-100 or 100-0 IEC 62040-3, Section 5.3.1 Figure 1 IEC 62040-3, Section 5.3.1 Figure 1 100% of nominal phase current 100% of nominal phase current 0.7 Leading to 0.7 Lagging 0.7 Leading to 0.7 Lagging 120° ±1° (with 50% unbalanced load) 120° ±1° (with 50% unbalanced load) Capacity to handle Step Load, % Step Load Transient Recovery (linear loads), % Unbalance Loads Current Capacity Load Power Factor Supported (Without Derating) Voltage Displacement, ° (Electrical Degree) Overload Conditions, % FL See Figures 21, 22 and 23 33 Liebert® eXL™ Specifications Table 8 Liebert eXL UPS specifications (continued) 625-800kVA 1000-1200kVA 123.6 (3140) 171.7 (4330) Depth, in (mm) 34.4 (874) 33.5 (850) Model Size Physical Parameters and Standards Width, in (mm), With Static Bypass Height, in (mm) 77.5 (1969) 76.8 (1950) Weight, Unpackaged, lb. (kg) approximate with Static Bypass (1+N) 5687 (2580) 8095 (3672) Maximum Heat Dissipation, Full Load, BTU/hr (kW) 625kVA UPS: 77,348 (22.7) 750kVA UPS: 92,817 (27.2) 800kVA UPS: 101,940 (29.9) 1000kVA UPS: 123,756 (36.3) 1100kVA UPS:136,132 (39.9) 1200kVA UPS:152,909 (44.8) <4,800 <4,800 Black (ZP-7021) Black (ZP-7021) 90° 90° IP 20 (with and without front door open) IP 20 (with and without front door open) Minimum Clearance, Top, in (mm) 24 (610) 24 (610) Minimum Clearance, Back, in (mm) 0 0 Minimum Clearance, Sides, in (mm) 0 0 Cooling Air, CFM Color Front Door Opening (for serviceability) Degree of Protection for UPS Enclosure Location of Cable Entrance Top or Bottom Top or Bottom Standards and Conformities UL 1778, 4th Ed. CSA 22.2 107.3 FCC Part 15, Class A (with optional filters installed) IEC62040-2, Level 4, Criteria A ANSI C62.41, Category A3 &B3 ISTA WEEE UL 1778, 4th Ed. CSA 22.2 107.3 FCC Part 15, Class A (with optional filters installed) IEC62040-2, Level 4, Criteria A ANSI C62.41, Category A3 &B3 ISTA WEEE -13 to 158 (-25 to 70) -13 to 158 (-25 to 70) 32°F to 95°F (0°C to 35°C) at full rated load 1.5% maximum kW / degrees C derating up to 50°C 122°F (50°C) absolute maximum with derating 32°F to 95°F (0°C to 35°C) at full rated load 1.5% maximum kW / degrees C derating up to 50°C 122°F (50°C) absolute maximum with derating 95% or less Non-Condensing (Operating and Non-Operating) 95% or less Non-Condensing (Operating and Non-Operating) 3300 ft.(1000m) (per IEC 62040/3) 1% Maximum kW derating / 1000 ft. rise between 3300 and 10,000 ft.(305m rise between 1000 and 3000m) 3300 ft. (1000m) (per IEC 62040/3) 1% Maximum kW derate / 1000 ft. rise between 3300 and 10,000 ft. (305m rise between 1000 and 3000m) Environmental Parameters Storage Temperature Range, °F (°C) Operating Temperature Range, °F (°C) Relative Humidity Maximum Altitude Above MSL Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels. Depth dimensions include the front door and rear panel. Liebert® eXL™ 34 Specifications Table 9 Current ratings—rectifier input UPS Rating kVA kW Voltage VAC Nominal Current Maximum Current 625 625 480 779 818 750 750 480 935 982 800 800 480 995 1044 1000 1000 480 1244 1308 1100 1100 480 1368 1438 1200 1200 480 1493 1569 Table 10 Current ratings—bypass input UPS Rating kVA kW Voltage VAC Nominal Current 625 625 480 752 750 750 480 902 800 800 480 962 1000 1000 480 1203 1100 1100 480 1323 1200 1200 480 1443 Table 11 Current ratings—output UPS Rating kVA kW Voltage VAC Nominal Current 625 625 480 752 750 750 480 902 800 800 480 962 1000 1000 480 1203 1100 1100 480 1323 1200 1200 480 1443 Table 12 Current ratings—DC source UPS Rating kVA kW Voltage VAC 625 625 480 Maximum Current at EOD 1601 750 750 480 1923 800 800 480 2051 1000 1000 480 2591 1100 1100 480 2850 1200 1200 480 3109 Notes on Tables 9 through 12 1. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered non-continuous). 2. The rectifier overload current is controlled by the input current limit setting, which is adjustable from 25 to 200% (default:125%). 3. For breaker coordination while the module is overloaded, see the current versus time values on the overload curves. 4. Nominal battery voltage is shown at 2.0 volts/cell. 5. DC Source current based at 401VDC. 35 Liebert® eXL™ Liebert® eXL™ 36 100% 0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 Continuous 110% 631.1 106%: 15005 secs 324.8 120% 194.7 120.0 130% 75.9 49.0 140% 32.4 21.8 10.4 % Load 150% 14.9 160% 7.3 5.2 170% 3.8 2.8 180% 2.1 1.5 190% 1.2 0.9 200% 0.2 Specifications Figure 21 Inverter overload data Time (sec) Time (sec) 37 100% 0.0 100.0 200.0 300.0 400.0 500.0 600.0 700.0 Continuous 341.0 694.2 110% 106%: 16506 secs 120% 204.5 126.0 130% 79.6 51.5 140% 34.0 22.9 10.9 % Load 150% 15.6 160% 7.7 5.5 170% 4.0 3.1 180% 2.3 1.7 190% 1.3 1.0 200% 0.2 Specifications Figure 22 Rectifier overload data Liebert® eXL™ Liebert® eXL™ 38 100% 0.0 50.0 100.0 150.0 200.0 250.0 300.0 350.0 400.0 450.0 500.0 110% 324.8 500.0 120% 194.7 120.0 130% 75.9 49.0 140% 32.4 21.8 10.4 % Load 150% 14.9 160% 7.3 5.2 170% 3.8 2.8 180% 2.1 1.5 190% 1.2 0.9 200% 0.2 Specifications Figure 23 Bypass overload data Continuous Time (sec) Specifications Table 13 Recommended conduit and cable sizes for use with 100% rated breakers Rectifier Input UPS Rating kVA kW 625 625 750 800 1000 1100 1200 750 Voltage VAC 480 800 1000 1100 480 1200 Cable Entry (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors Top (3) 2.5"C 3-350kcmil; #2/0AWG (3) 3"C 3-500kcmil; #4/0AWG Bottom (3) 3"C 3-350kcmil; #2/0AWG (3) 3.5"C 3-500kcmil; #4/0AWG Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG Top (4) 2.5"C 3-350kcmil; #3/0AWG (4) 3"C 3-500kcmil; 250kcmil Bottom (4) 3"C 3-350kcmil; #3/0AWG (4) 3.5"C 3-500kcmil; 250kcmil Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil Bypass Input UPS Rating kVA kW 625 625 750 750 800 800 1000 1000 1100 1100 1200 1200 Voltage VAC 480 480 Cable Entry (# of conduits); size of conduits; # - size of phase cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors Top (3) 2.5"C 3-350kcmil; #1/0AWG (3) 3"C 3-500kcmil; #3/0AWG Bottom (3) 3"C 3-350kcmil; #1/0AWG (3) 3.5"C 3-500kcmil; #3/0AWG Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil Output UPS Rating kVA kW 625 625 750 800 1000 1100 1200 750 Voltage VAC 480 800 1000 1100 1200 480 Cable Entry (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors Top (3) 2.5"C 3-350kcmil; #1/0AWG (3) 3"C 3-500kcmil; #3/0AWG Bottom (3) 3"C 3-350kcmil; #1/0AWG (3) 3.5"C 3-500kcmil; #3/0AWG Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG Top (3) 3"C 3-500kcmil; #2/0AWG (3) 3"C 3-600kcmil; #4/0AWG Bottom (3) 3.5"C 3-500kcmil; #2/0AWG (3) 3.5"C 3-600kcmil; #4/0AWG Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil Top (4) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-500kcmil; 350kcmil Bottom (4) 3.5"C 3-500kcmil; #4/0AWG (5) 3.5"C 3-500kcmil; 350kcmil Top (5) 3"C 3-500kcmil; #4/0AWG (5) 3"C 3-600kcmil; 350kcmil Bottom (5) 3.5"C 3-500kcmil; #4/0AWG (5) 4"C 3-600kcmil; 350kcmil 39 Liebert® eXL™ Specifications Table 13 Recommended conduit and cable sizes for use with 100% rated breakers (continued) Battery UPS Rating kVA kW 625 625 750 750 800 1000 1100 1200 1. 2. 3. 4. 5. 6. 7. 8. Voltage VAC 480 800 1000 1100 480 1200 Cable Entry (# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit Copper Conductors Aluminum Conductors Top (5)3"C 2-600kcmil; 250kcmil (6) 3"C 2-600kcmil; 400kcmil Bottom (5)3"C 2-600kcmil; 250kcmil (6) 3.5"C 2-600kcmil; 400kcmil Top (5)3"C 2-600kcmil; 250kcmil (6) 3"C 2-600kcmil; 400kcmil Bottom (5)3"C 2-600kcmil; 250kcmil (6) 3.5"C 2-600kcmil; 400kcmil Top (6)3"C 2-600kcmil; 350kcmil (7) 3"C 2-700kcmil; 600kcmil Bottom (6)3"C 2-600kcmil; 350kcmil (7) 3.5"C 2-700kcmil; 600kcmil Top (8)3"C 2-600kcmil; 500kcmil (8) 3"C 2-700kcmil; 600kcmil Bottom (8) 3.5"C 2-600kcmil; 500kcmil (8) 3.5"C 2-700kcmil; 600kcmil Top (8)3"C 2-600kcmil; 500kcmil (8) 3"C 2-700kcmil; 600kcmil Bottom (8) 3.5"C 2-600kcmil; 500kcmil (8) 3.5"C 2-700kcmil; 600kcmil Top (9)3"C 2-750kcmil; 500kcmil (11) 3"C 2-700kcmil; 750kcmil Bottom (9) 3.5"C 2-750kcmil; 500kcmil (11) 3.5"C 2-700kcmil; 750kcmil Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. Refer to NEC recommendations for 104°F (40°C) ambient rated conductors. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C. Recommended cables and conduits are based on breaker trip setting sized for the maximum continuous rated current for the rectifier input and the nominal current for the bypass and output listed in Tables 9 through 12. Conduit size is based on RNC type conduit for bottom input and EMT-type conduit for top input. Emerson recommends that the site planner choose the appropriate cable type based on the particular installation requirements. These recommendations are for use with 100% rated breakers. For 125% rated breakers, refer to NEC recommended conduit and cable sizes. Upstream and downstream non-standard recommended breaker settings have their trip adjustment behind a suitable cover in accordance with 240.6(c) of the NEC. Table 14 Recommended breakers, upstream and downstream UPS Rating kVA System Input Nominal Current Recommended External Breaker Trip, Amps Upstream Breakers 625 777 900 750 933 1000 800 995 1200 1000 1246 1400 1100 1371 1600 1200 1496 1600 Downstream Breakers 625 752 800 750 902 1000 800 962 1000 1000 1203 1400 1100 1323 1400 1200 1443 1600 Liebert® eXL™ 40 Specifications Table 15 Recommended lug sizes Cable Size T&B Copper One Hole T&B Copper Two Hole T&B Aluminum One Hole T&B Aluminum Two Hole #8AWG 54930BE 54850BE 60104-TB — #6AWG 54905BE 256-30695-868 60109-TB — #4AWG 54906BE 256-30695-733 60114-TB — #2-3AWG 54942BE 54811BE 60120 — #1AWG 54947BE 54857BE 60126 — #1/0AWG 54950BE 256-30695-593 60132 — #2/0AWG 54951BE 54862BE 60138 60238 #3/0AWG 54965BE 54864BE 60144 60244 #4/0AWG 54970BE 54866BE 60150 60250 250kcmil 54913BE 54868BE 60156 60256 300kcmil 54914BE 54870BE 60162 60262 350kcmil 54915BE 54872BE 60165 60267 400kcmil 54916BE 54874BE 60168 60269 500kcmil 54918BE 54876BE 60171 60273 600kcmil 54920BE 54878BE 60176 60275 750kcmil 54922BE 54880BE 60178 60277 (750kcmil) Table 16 Recommended torque values Grade 5 Steel: Unified Thread System Torque, lbf.*in. Fastener Finish Size 1/4 5/16 3/8 7/16 1/2 9/16 Class 8.8 Steel: Metric Thread System Torque, N*m Plain Steel Zinc Plating Fastener Finish Plain Steel Zinc Plating Threads/ Inch, Tpi No Washer/ Flat Washer No Washer/ Flat Washer Size Thread Pitch, Tp No Washer/ Flat Washer No Washer/ Flat Washer 20 101 91 0.8 6.1 5.5 28 116 104 0.5 6.9 6.2 18 209 188 1 10 9 24 231 208 0.75 11 10 16 370 333 1.25 25 23 24 420 378 1 27 24 14 593 534 1.5 50 45 20 662 596 1.25 53 47 13 904 814 1.75 87 78 20 1,020 918 1.25 95 86 12 1305 1,175 2 139 125 18 1456 1310 1.5 151 136 M5 M6 M8 M10 M12 M14 41 Liebert® eXL™ Shipping Splits, Kickplates APPENDIX A - SHIPPING SPLITS, KICKPLATES Figure 24 Shipping split, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit A B See Detail E Shipping Split Core 1 & 2 SHIPPING SPLIT INPUT Shipping Split Bypass & Output G F G F H EMI Plates (3) {PN: 5533579P1} M6 Large Flat Washer (6) {PN: 09-43B00Z-00} M6 Split Lock Washer (6) {PN: 09-36B00Z-00} M6 x 25 Bolt (6) {PN: 09-02BL0Z-11} See Detail C See Detail D ABatt Neg (-) Flex from Input Cabinet B Ph C - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) M8 Large Flat Washer (4) {PN: 09-43E00Z-00} M8 Belleville Washer (8) {PN: 09-39D00Z-A7} M8 x 40 Bolt (4) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) Batt Pos (+) Flex from Input Cabinet M8 Large Flat Washer (4) {PN: 09-43E00Z-00} M8 Belleville Washer (8) {PN: 09-39D00Z-A7} M8 x 40 Bolt (4) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) PH B - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) PH A - Flex from Bypass Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) PH B - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) PH A - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 X 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) DETAIL C PH C - Flex from Input Cabinet M8 Large Flat Washer (2) {PN: 09-43E00Z-00} M8 Belleville Washer (4) {PN: 09-39D00Z-A7} M8 x 40 Bolt (2) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) DETAIL D Install MH From Input Install MH From Core 1 Install MH From Bypass Install MH From Bypass Batt + Install MH From Core 2 Batt Install MH From Input Install MH From Core 1 Output C Output B Input Ph A Install MH From Core 2 Input Ph B Install MH From Input Input Ph C Install MH From Core 1 FRONT Output A Install MH From Bypass SECTION A-A Install MH From Bypass FRONT SECTION B-B Cabinet-to-Cabinet Mounting Hardware M10 Large Flat Washer (1) {PN: 09-43G00Z-00} M10 Split Lock Washer (1) {PN: 09-36G00Z-00} M10 X 30 Bolt (1) {PN: 09-02GL0Z-12} (Typically 12 Places) (Labeled “MH”) Torque 240 in-lb (27 Nm) Liebert® eXL™ 553028P1 Pg. 1, Rev. 6 42 Bend flex to 90° position before pushing the bypass and core together. Monitor flex to avoid pinching between cabinets or busbars. Shipping Splits, Kickplates Figure 25 Shipping split, 625-800kVA Liebert eXL UPS, SMS and 1+N multi-module unit, continued Route harness from input in duct to Core 1 (Connectors - J400, J11) Bypass (Connectors - J13, J100, J200, J300) Core 1 & 2 Prechg (See Section J-J) J Route harness from bypass in duct to input (Connectors - P13, P100, P200, P300) J Connect to input harness (Connectors P400, P11 Rear Wiring Duct Bypass Cabinet Bypass Connector Board From Input FRONT WIRING DUCT Core 2 (Connectors - P1, P2, P3) See Detail E Core 1 (Connectors - P1, P2, P3) See Detail E Bypass (Connectors - P1) See Section G-G P1 Input (Connector HVAB P20) See Section F-F Route harness from input in duct to Core 1 (Connectors - P1, P2, P3, P66) Core 2 (Connectors - P1, P2, P3) Bypass (Connectors - P99A, P1) Route harness from bypass in duct to input (Connector - P20) Bypass (Connector - CB2 I/F BD P99) See Detail H Core 1 (Connectors - P66) See Detail E From Input SECTION G-G From Input From Bypass From Bypass P2 Input Cabinet HVAB P20 P3 P66 P99 P3 From Input P2 P1 P1 Core 1 Connector Board CORE 1 FIB 1 DETAIL E SECTION F-F Core 2 Connector Board Bypass Cabinet CB2 I/F Board From Input Wire Duct Core 1 Prechr PhB (Orange Wire) Core 1 Prechr PhA (Brown Wire) SECTION J-J Core 2 Prechr PhA (Brown Wire) Core 2 Prechr PhB (Orange Wire) See connection details in Tables 17, 18 and 19. Table 17 From Input DETAIL H 553028P1 Pg. 2, Rev. 6 Connections associated with top down view Cabinet Start Connector Label Cabinet Finish Connector Label Duct Input J100 Bypass P100 Rear Input J13 Bypass P13 Rear Input J200 Bypass P200 Rear Input J300 Bypass P300 Rear Input J11 Core 1 P11 Rear Input J400 Core 1 P400 Rear Connected together in the rear duct. Table 18 Section J-J connections Cabinet Start Connector Label Cabinet Finish Cabinet Finish Duct Input Core Prechg Ph A Core 1 Prechg Ph A Core 2 Prechg Ph A Rear Input Core Prechg Ph B Core 1 Prechg Ph A Core 2 Prechg Ph A Rear 43 Liebert® eXL™ Shipping Splits, Kickplates Table 19 Connections associated with sections in “View” column Cabinet Start Connector Label Cabinet Finish Connector Label (Connect This End) Duct View Bypass CT7-CT9 Input P20 HVAB Front Section F-F Input P50 Bypass P1 BypassConnector Board Front Section G-G Input P66A Bypass P99A CB2 I/F BD Front Detail H Input P11 Core 1 P1 Core Connector Board Front Detail E Input P12 Core 1 P2 Core Connector Board Front Detail E Input P1 Core 1 P3 Core Connector Board Front Detail E Input P99 Core 1 P66 FIB 1 Front Detail E Input P21 Core 2 P1 Core Connector Board Front Detail E Input P22 Core 2 P2 Core Connector Board Front Detail E Input P2 Core 2 P3 Core Connector Board Front Detail E Bypass P66 Core 1 P99 FIB 1 Front Detail E Liebert® eXL™ 44 1 45 Install from Core 3 1 Install from Core 3 1 Install from Core 3 1 Input Ph C SECTION B-B SECTION A-A Input Ph B FRONT Install from Core 1 Output Ph A BATT + BATT - Install from Core 1 Install from Core 1 FRONT Install from Core 3 1 Output Ph C Output Ph B Output Ph A Install from Core 3 1 Install from Core 3 1 Install from Input 1 Install from Input 1 Install from Input DC MID CORE 2 Remove hardware, install wires from Core 3 then reuse hardware Torque 180 in-lb (20.0 Nm) A A DETAIL C DC Pos (+) CORE 2 Remove hardware, install wires from Core 3, then reuse hardware Torque 180 in-lb (20.0 Nm) EMI Plates (3) {PN: 553579P1} M6 Large Flat Washer (6) {PN: 09-43B00Z-00} M6 Split Lock Washer (6) {PN: 09-36B00Z-00} M6 x 25 Bolt (6) {PN: 09-02BL0Z-11} Input Cabinet Shipping Split Input HV Attenuator Burden Board (Sheet 3) Core 1 Core 2 Route wires through bushing between cores Core 3 to bypass cabinet mounting hardware; see Section BB Install 6 places 1 Core 3 Shipping Split Core 3 C See cabinet-to-cabinet power connections detail (Sheet 2) Core 2 to Core 3 mounting 1 hardware; install 6 places from Core 2 Shipping Split Core 1 & 2 Input cabinet to Core 1 mounting hardware; see Section A-A 1 Install 6 places 1 Typical Cabinet To Cabinet Mounting Hardware M10 Large Flat Washer (1) {PN: 09-43G00Z-00} M10 Split Lock Washer (1) {PN: 09-36G00Z-00} M10 x 30 Bolt (1) {PN: 09-02GL0Z-12} Torque 240 in-lb (27 Nm) See Detail D (Sheet 3) B B E Bypass Cabinet See Detail E (Sheet 3) Shipping Split Bypass & Output Shipping Splits, Kickplates Figure 26 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 1 Liebert® eXL™ Liebert® eXL™ 46 x8 2 x6 AC Input Flex from Input Cabinet 2 F Core 1 AC Ph-A AC Ph-C AC Ph-B Installed in Factory BATT Neg (-) BATT Pos (+) BATT Neg (-) 3 x8 3 x8 SECTION F-F Core 2 Core 2 Core 3 Core-to-Core Busbars 1 per Phase Installed in Factory Core 2 AC Ph-C AC Ph-B AC Ph-A BATT Neg (-) BATT Pos (+) 4 x6 3 x6 3 Core 3 Core 3 Cabinet Finish Bypass Bypass Bypass Core 1 Core 1 Core 3 2 x6 Cabinet Finish Duct Rear Rear Rear Rear Rear Rear Connector Label Connector Label P100 P200 P300 P11 P400 P12 Core 1 Prechg Ph A Core 2 Prechg Ph A Core 1 Prechg Ph B Core 2 Prechg Ph B Core 3 Prechg Ph A Core 3 Prechg Ph B 4 3 2 Duct Rear Rear Rear Rear Typical Double Core to Core Busbar Hardware M8 Large Flat Washer (1) {PN: 09-43E00Z-00} M8 Belleville Washer (2) {PN: 09-39D00Z-A7} M8 X 40 Bolt (1) {PN: 09-02EL0Z-14} Torque 180 in-lb (20 Nm) Typical Single Core to Core Busbar Hardware M8 Large Flat Washer (1) {PN: 09-43E00Z-00} M8 Belleville Washer (2) {PN: 09-39D00Z-A7} M8 X 35 Bolt (1) {PN: 09-02EL0Z-13} Torque 180 in-lb (20 Nm) Typical Flex to Core Busbar Hardware M8 Large Flat Washer (1) {PN: 09-43E00Z-00} M8 Belleville Washer (2) {PN: 09-39D00Z-A7} M8 X 50 Bolt (1) {PN: 09-02EL0Z-16} Torque 180 in-lb (20 Nm) AC Output Flex from Bypass Cabinet Core 3 Prechr Ph B (Orange Wire) Connector Label Core Prechg Ph A Core Prechg Ph B Core Prechg Ph A Core Prechg Ph B Core-to-Core Busbars 1 per Phase 4 x6 Connector Label J100 J200 J300 J11 J400 J12 Connected together in rear duct. Cabinet Start Input Input Input Input Input Input Core 3 Prechr Ph A (Brown Wire) Cabinet Start Input Input Input Input Front Wiring Duct Rear Wiring Duct Route harness from bypass in duct to input (Connectors P100, P200, P300) AC Ph-C AC Ph-B AC Ph-A x8 Rear Wire Duct Route harness from bypass in duct to input (Connector - P20) Core 2 Prechr Ph B (Orange Wire) F CORETOCOREBUSBAR S (2)SIDEBYSIDEFORBATT NEG(-) (2)SIDE BYSIDEFOR BAT T POS(+) Core 2 Prechr Ph A (Brown Wire) Connect to input harness (Connectors P12) Cabinet-to-Cabinet Power Connections Core 1 Prechr Ph B (Orange Wire) Core 1 Core 1 Connect to input harness (Connectors P400, P11) Installed in Factory Core 1 Prechr Ph A (Brown Wire) Batt Neg (-) & Batt Pos(+) Flex from Input Cabinet From Input Route harness from input in duct to Core 1 (Connectors -P1, P2, P3, P66) Core 2 (Connectors - P1, P2, P3) Core 3 (Connectors - P1, P2, P3) Bypass (Connectors - P99A, P1) Input (Connector HVAB P20) See Sheet 3 Route harness from input in duct to Core 1 (connectors - J400, J11, J12) bypass (connectors - J100, J200, J300) Core 1, 2 & 3 prechg (See Section F-F) Shipping Splits, Kickplates Figure 27 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 2 47 P3 P2 TIB P99 P99 Located in Bypass Cabinet See Detail E for Exact Location TEMPERATURE INTERFACE BOARD CB2 P99A For Units Without CB2 Factory-Installed Jumper (555648G1) Located in Input Cabinet See Sheet 1 for Exact Location HV ATTENUATOR BURDEN BOARD P20 HVAB P20 Core 1 Connector Board P1 Core 1 P3 Located in Bypass Cabinet See Detail E for Exact Location Connectors P1, P2, P3 P1 P2 P3 TB1-1 Core 3 TB1-2 Connectors FIB2 P66, FIB2 P99, P1005 & P1006 Optional CB2 Motor OP Wires TB1-1 & TB1-2 P1005 P99 View Option HV Attenuator Burden Board Bypass Connector Board CB2 CB2 Interface Board No CB2 Temperature Interface Board Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D Detail D CB2 Mtr Op Only Detail D CB2 Mtr Op Only Detail D Located in Bypass Cabinet See Detail E for Exact Location CB2 INTERFACE BOARD CB2 P99A For Units With CB2 Installed DETAIL E CB2 Interface Board Bypass Connector Board Temperature Interface Board Core 2 Connector Board Core 3 FIB 2 Connectors Connect to TB1 from bypass cabinet Incoming: P1, CB2 P99A Only if CB2 is equipped with motor operator (Fan Interface Board) Outgoing: FIB2 P99, P1005 & P1006 (Wire will be in bypass wire duct) Optional CB2 Mtr Op Wires TB1-1 & TB1-2 Duct Duct Front Front Front Front Front Front Front Front Front Front Front Front Front Front Front Front Front Front Front DETAIL D Connector Label (Connect This End) (P20) HVAB (P1) Bypass Connector BD (P99A) CB2 I/F BD (P99A) TIB BD (P66) FIB 1 (P1) Core Connector Bd (P2) Core Connector Bd (P3) Core Connector Bd (P1) Core Connector Bd (P2) Core Connector Bd (P3) Core Connector Bd (P1) Core Connector Bd (P2) Core Connector Bd (P3) Core Connector Bd (P66) FIB 2 (P99) FIB 2 (P1005) FIB 2 (P1006) FIB 2 (TB1‐1) (TB1‐2) Core 2 BYPASS CONNECTOR BOARD Bypass Connector Board - P1 Bypass Core 1 Core 1 Core 1 Core 1 Core 2 Core 2 Core 2 Core 3 Core 3 Core 3 Core 3 Core 3 Core 3 Core 3 Core 3 Core 3 P66A P99 P11 P12 P1 P21 P22 P2 P31 P32 P3 FIB 1 (P99) BFB I/F BD (P66) Fan 13 Fan 14 F70‐1 F69‐1 Input Bypass Cabinet Finish Input Input Input Input Input Input Input Input Input Input Core 1 Bypass Bypass Bypass Bypass Bypass Connector Label (Factory-Connected) CT7-CT9 P50 Core 2 Connector Board P2 Input Cabinet Start Bypass Input Core 1 FIB 1 (Fan Interface Board) P1 Connectors P1, P2, P3 P1 P66 P1006 Connectors P1, P2, P3 Connectors FIB1 P66 FIB1 P99 Shipping Splits, Kickplates Figure 28 Shipping split, 1000-1200kVA Liebert eXL UPS, SMS and 1+N multi-module unit, Page 3 Liebert® eXL™ P66 Shipping Splits, Kickplates Figure 29 Kickplate installation—625-800kVA units LEFT HAND REAR Panel Rear Bottom Panel Rear Bottom RIGHT HAND FRONT Panel Rear Bottom Panel Side Bottom Panel Front Bottom Panel Front Bottom M10 Flat Washer ZP, Typical Panel Front Bottom Panel Side Bottom Screw Cap HH M10‐1.5x25mm ZP Hexagonal Cap Black M10 (17mm) Typical M10 Lock Washer, Split ZP, Typical Liebert® eXL™ 48 553029P1 Pg. 1, Rev. 2 Shipping Splits, Kickplates Figure 30 Kickplate installation—1000-1200kVA, single module units RIGHT HAND FRONT Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Side Bottom LEFT HAND REAR Panel Rear Bottom Panel Rear Bottom Panel Rear Bottom Panel Rear Bottom M10 Flat Washer ZP, Typical Panel Rear Bottom Panel Side Bottom Hexagonal Cap Black M10 (17mm) Typical Screw Cap HH M10‐1.5x25mm ZP M10 Lock Washer, Split ZP, Typical 555130P1 Pg. 1, Rev. 0 49 Liebert® eXL™ Shipping Splits, Kickplates Figure 31 Kickplate installation—1000-1200kVA, 1+N multi-module units RIGHT HAND FRONT Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Front Bottom Panel Rear Bottom LEFT HAND REAR Panel Rear Bottom Panel Rear Bottom Panel Rear Bottom Panel Rear Bottom Panel Rear Bottom Panel Side Bottom M10 Flat Washer ZP, Typical Screw Cap HH M10‐1.5x25mm ZP M10 Lock Washer, Split ZP, Typical Liebert® eXL™ 50 Hexagonal Cap Black M10 (17mm) Typical 555130P1 Pg. 2, Rev. 0 Shipping Splits, Kickplates NOTES 51 Liebert® eXL™ Shipping Splits, Kickplates Liebert® eXL™ 52 Technical Support / Service Web Site www.liebert.com Monitoring [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets [email protected] 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572 SL-26085_REV0_06-15 Emerson Network Power Liebert www.emerson.com www.EmersonNetworkPower.com