Liebert MC User Manual, 60Hz Air-Cooled Microchannel Condensers; (R02/13); (SL-19536)

Liebert® MC™
User Manual—60 Hz Air-cooled Microchannel Condenser – Premium/EC Fan
Table of Content
Important Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Liebert MC Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Product Description and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Control, Fan Types and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2.1 Premium Efficiency Control/EC Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1.1 Anti-Freezing Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1.2 Fan Reversal for Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1.3 Low-Noise Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
6
6
1.3 Liebert Lee-Temp™ Refrigerant Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Surge Protective Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.0 Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Site Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Dimensions and Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2.1 Condenser and Options Net Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.0 Inspection and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.1.1 Packing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2 Handling Unit on the Skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3 Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.4 Unpacking the Condenser—All Unit Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.5 Preparing a Condenser for Moving and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.5.1 Attaching 18" (457mm) Legs, Removing the Skid and Attaching Slings. . . . . . . . . . . . . . 26
3.5.2 Special Considerations for 36-60” (914-1524mm) Legs . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.6 Mounting the Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.6.1 Standard Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.6.2 Seismic-Certified and Wind-Certified Mounting Requirements . . . . . . . . . . . . . . . . . . . . . 32
i
Liebert® MC™ User Manual
4.0 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1 Line Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
4.1.1 Wye- vs. Delta-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1.1.1 Acceptable Power Supplies—208V to 575V Nominal Units. . . . . . . . . . . . . . . . 36
4.1.1.2 Unacceptable Power Supplies—208V to 575V Nominal Units . . . . . . . . . . . . . 36
4.2 Low-voltage Control Wiring—CANbus Communication and Interlock Connections . . . . . 37
4.2.1 Electrical Field Connection Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
4.2.1.1 Key Electrical Details—Typical Connections, Premium Efficiency Control . . . . 44
5.0 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.1 Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.2 Field Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.2.1 Field Piping Guidelines for a Liebert DX System and Liebert MC Condenser . . . . . . . . . 56
5.2.2 Field Piping Guidelines for a Liebert DSE and Liebert Premium MC Condenser . . . . . . . 60
5.3 Refrigerant Planning Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.3.1 Recommended Refrigerant Line Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.4 Equipment Application Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.5 Refrigerant Oil Addition Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.6 System Dehydration/Leak Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.7 System Charging with Liebert MC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.7.1 Liebert MC Charging, Units with Liebert Lee-Temp™ Receivers . . . . . . . . . . . . . . . . . . . 68
5.7.2 Liebert MC Condenser Charging with Liebert DSE™ Receivers. . . . . . . . . . . . . . . . . . . . 68
5.7.3 Liebert MC Charging, Premium Efficiency Control, Units without Receivers . . . . . . . . . . 69
6.0 Checklist for Completed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.1 Moving and Placing Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.2 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.3 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.4 Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.0 Initial Startup Checks and Commissioning . . . . . . . . . . . . . . . . . . . . . . 75
7.1 Startup Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.2 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
8.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Liebert® MC™ User Manual
ii
9.0 Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.1 Premium Efficiency Control Board and Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.1.1 Initial Screen Upon Power-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9.1.2 Main Menu Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9.1.3 Analog Signals Menu Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
9.2 Premium Efficiency Condenser Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.2.1 Active Alarms Menu Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.2.2 History Alarms Menu Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
10.0 Liebert MC Seismic Application—Optional Unit Configuration . . . . . 89
10.1 Seismic Anchoring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
10.2 Seismic piping considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.3 Seismic wiring considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
11.0 System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
11.1 General Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
11.2 Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.2.1 When to Clean the Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.2.2 What to Use to Clean the Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.2.3 How to Clean the Condenser Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.3 Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
11.3.1 Verify the Fan Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
11.4 Premium Efficiency Control Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.4.1 Replacement Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.4.2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
12.0 Preventive Maintenance Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
iii
Liebert® MC™ User Manual
List of Figures
Figure 1-1: Two-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2-1: Condenser planning dimensional data—MCS028, MCM040 and MCL055. . . . . . . . . . . . . . . . . . . . . 12
Figure 2-2: Condenser planning dimensional data—MCS056, MCM080, MCL110. . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 2-3: Condenser planning dimensional data—MCL165 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 2-4: Condenser planning dimensional data—MCM160 and MCL220. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 2-5: Liebert DSE receiver mounting—MCL165 and MCL220,
single-circuit condenser, left-side condenser outlet receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2-6: Liebert DSE receiver mounting—MCL165 and MCL220,
single-circuit condenser, right-side condenser outlet receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 2-7: Liebert DSE receiver mounting—MCL110 and MCL220, dual-circuit condenser . . . . . . . . . . . . . . . . 18
Figure 2-8: Liebert DSE receiver mounting—MCM160 dual circuit condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 3-1: Equipment recommended for handling a Liebert condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 3-2: Forklift position with one-fan or two-fan condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 3-3: Removing protective material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 3-4: Attaching legs to one-fan or two-fan condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 3-5: Securing slings to condensers for lifting off skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 3-6: Remove skid, set condenser on floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 3-7: Lifting condensers with one, two, three or four fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 3-8: Recommended bolt locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 3-9: Remove bolts along the long edge of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 3-10: Lifting the unit for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 4-1: Wye- vs. delta-connected power supply connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 4-2: CANbus communication and interlock connections
between a Liebert DSE, one premium Liebert MC and a Liebert EconoPhase . . . . . . . . . . . . . . 38
Figure 4-3: CANbus communications and interlock connections
between a Liebert DSE, two Liebert MC condensers and a Liebert EconoPhase . . . . . . . . . . . . 39
Figure 4-4: CANbus communications and interlock connections
between a Liebert DS and Liebert MC condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 4-5: CANbus communication and interlock connections
between a Liebert CRV 600 mm (24 in.) and a Liebert MC premium condenser . . . . . . . . . . . . 41
Figure 4-6: CANbus communications and interlock connection
between Liebert CRV 300 mm (12 in.) and a Liebert MC premium condenser . . . . . . . . . . . . . . 42
Figure 4-7: CANbus communication and interlock connection
between Liebert PDX™ and a Liebert MC premium condenser . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 4-8: Typical connections, Premium Efficiency Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 5-1: Piping schematic—DX systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 5-2: Piping schematic—CRV 600 mm (24 in.) DX systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 5-3: Piping schematic—CRV300 mm (12 in.) DX systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 5-4: Piping schematic—DS DX systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 5-5: Piping schematic—Liebert DSE™, air-cooled DA050, DA080 and DA085 models . . . . . . . . . . . . . . . 53
Figure 5-6: Piping schematic—Liebert DSE™, air-cooled DA125, DA150 and DA165 models . . . . . . . . . . . . . . . 54
Figure 5-7: Liebert MC Condenser piping—Single-circuit, 1-, 2-, 3- and 4-fan units . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 5-8: Condenser piping for single-circuit condensers (with Liebert Lee-Temp™) . . . . . . . . . . . . . . . . . . . . . 57
Liebert® MC™ User Manual
iv
Figure 5-9: Piping: dimensions—Dual circuit two-fan and four-fan units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Figure 5-10: Piping: Dimensions with Liebert Lee-Temp™—Dual circuit condensers . . . . . . . . . . . . . . . . . . . . . . 59
Figure 5-11: Condenser and Liebert EconoPhase™,
typical unit arrangement diagram layout for dual-circuit system . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 5-12: Condenser and Liebert EconoPhase™,
typical unit arrangement diagram layout for single-circuit system . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 5-13: Typical receiver Liebert DSE mounting,
MCL110, MCL165 and MCL220 single-circuit condenser, left-side condenser outlet receiver . . 62
Figure 5-14: Typical receiver Liebert DSE mounting,
MCL110, MCL165 and MCL220 single-circuit condenser, right-side condenser outlet receiver . 63
Figure 5-15: Typical receiver Liebert DSE mounting,
MCL110 and MCL220 dual-circuit condenser, two outlet receivers . . . . . . . . . . . . . . . . . . . . . . . 64
Figure 5-16: Typical receiver Liebert DSE mounting, MCM160 dual-circuit condenser, two outlet receivers . . . . 65
Figure 9-1: Premium efficiency fan control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Figure 9-2: Premium Efficiency Control Interface - Human Machine Interface (HMI) . . . . . . . . . . . . . . . . . . . . . . 80
Figure 9-3: Initial controller display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 9-4: Main Menu operation and structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 9-5: Analog Signals Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Figure 9-6: Active alarms menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Figure 9-7: History alarms menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Figure 10-1: Seismic anchorage data for one-fan models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 10-2: Seismic anchoring for a two-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 10-3: Seismic anchoring loads for a three-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Figure 10-4: Seismic anchorage loads for a four-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 10-5: Seismic anchorage loads for 36-60” extended leg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 10-6: Seismic piping and wiring considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Figure 11-1: Ziehl-Abegg small, medium and large fan, Liebert MC series MCS, MCM and MCL . . . . . . . . . . . 105
Figure 11-2: EBM small and medium fan, Liebert MC series MCS/MCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Figure 11-3: EBM large fan—Liebert MC series MCL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Figure 11-4: Jumper locations on Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
v
Liebert® MC™ User Manual
List of Tables
Table 2-1: Condenser shipping weights, dimensions and volume, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2-2: Condenser and option net weights—Small condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2-3: Condenser and option net weights—Medium condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 2-4: Condenser and option net weights—Large condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 4-2: Electrical data, Liebert Lee-Temp™ receiver, 60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 4-1: Electrical data, three-phase, 60Hz condenser, premium models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 5-1: Liebert MC Condenser piping sizes—Single-circuit units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 5-2: Condenser piping connection sizes—Single-circuit condensers with Liebert Lee-Temp . . . . . . . . . . . 57
Table 5-3: Piping: dimensions—Dual-circuit, two-fan and four-fan units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 5-4: Condenser piping connection sizes—Dual-circuit condensers with Liebert Lee-Temp . . . . . . . . . . . . . 59
Table 5-5: Refrigerant required, R-407C, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Table 5-6: Refrigerant required, R-410A, approximate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Table 5-7: Recommended Refrigerant Line Sizes, OD Cu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 5-8: Interconnecting piping refrigerant charge for self-contained DX units with remote condenser . . . . . . . 68
Table 5-9: Charge amounts per 100 ft. (30m) of pipe by line size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table 5-10: Target subcooling for ambient outdoor temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Table 5-11: Liquid pressures and temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Table 8-1: Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Table 9-1: Analog signal definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Table 9-2: System alarm information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Table 9-3: EC Fan alarm information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Table 10-1: Seismic anchorage loads for one-fan models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table 10-2: Seismic anchoring loads for a two-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Table 10-3: Seismic anchoring loads for a three-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Table 10-4: Seismic anchorage loads for a four-fan Liebert MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Table 10-5: Seismic anchorage loads for 36-60” extended leg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Table 11-1: P-- menu items and definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Table 11-2: Premium Efficiency Control Board Configuration-parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Liebert® MC™ User Manual
vi
Important Safety Guidelines
Important Safety Guidelines
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and
maintenance of the Liebert MC. Read this manual thoroughly before attempting to install or operate this
unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in this
manual. Follow all operating and user instructions.
! WARNING
Risk of improper handling, installation and service. Can cause property damage, injury or death.
Only properly trained and qualified personnel should install or perform repairs or maintenance on
this unit. Read all installation, operation and safety alerts and instructions and wear appropriate
protective headgear, safety glasses, gloves and clothing before installing, operating or servicing
this unit.
! WARNING
Arc flash and electric shock hazard. Open all local and remote electric power disconnect switches,
verify with a voltmeter that power is Off and wear personal protective equipment per NFPA 70E
before working within the electric control enclosure. Failure to comply can cause serious injury or
death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit Off”
mode. Some internal components require and receive power even during the “Unit Off” mode of
Liebert iCOM control.
The factory-supplied disconnect switch is inside the unit. The line side of this switch contains live
high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
! WARNING
Risk of contact with high-speed, rotating fan blades. Can cause serious personal injury or death.
Fan blades can automatically start rotating without warning at any time during a cooling cycle or
after power is restored after a power failure. Open all local and remote electric power supply
disconnect switches, wait 10 minutes and verify with a voltmeter that power is Off before working
within the unit cabinet, removing the fan guards or servicing the fan speed control, fan blades or
EC fan motors.
! WARNING
Risk of electrical fire and short circuit. Can cause property damage, injury or death.
Select and install the line side electrical supply wire and overcurrent protection device(s) according
to the specifications on the unit nameplate(s), per the instructions in this manual and according to
the applicable national, state and local code requirements. Use copper conductors only.
Verify that all electrical connections are tight. Unit-specific wiring diagrams are provided on each
unit.
1
Liebert® MC™ User Manual
Important Safety Guidelines
! WARNING
Risk of electric shock. Can cause injury or death.
The fan speed control and the EC fan electrical enclosures may contain a stored electrical charge.
Open all local and remote electric power disconnect switches, verify with a voltmeter that power is
Off and wait 10 minutes before working within the fan speed control and the EC fan electrical
enclosures.
! WARNING
Risk of heavy condenser falling or tipping over. Can cause property damage, serious injury or
death.
Confirm that all components of the lifting system are rated for the weight of the condenser by an
OSHA Certified rating organization before attempting to lift and/or move the condenser. See
Tables 2-1 through 2-4 for the condenser weights.
! CAUTION
Risk of contact with hot surfaces. Can cause injury.
Fan motors, transformers, piping and other components may become extremely hot during normal
operation. Wear thermally insulated gloves and appropriate protective clothing and allow time for
components to cool when working within the cabinet or electric control enclosure.
! CAUTION
Risk of contact with sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes
and glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
! CAUTION
Risk of explosive discharge of high-pressure gas. Can cause injury.
Relieve system pressure and verify that the indoor and outdoor units are Off before making piping
connections/disconnections.
Do not exceed the design pressure rating that is marked on the nameplate.
Do not install a shutoff valve between the compressor and the field-installed pressure relief valve.
NOTICE
Risk of interference with building doorways, openings and passages. Can cause unit and/or
building damage.
Refer to the installation plans and measure the unit and building opening before moving the unit to
verify clearances.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep unit upright and protected from contact damage.
NOTICE
Risk of improper forklift handling. Can cause unit damage.
Keep the forklift tines level and at a height that will fit under the skid.
Liebert® MC™ User Manual
2
Important Safety Guidelines
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant R-407C and R-410A are blended refrigerants and must be introduced and charged
from the cylinder only as a liquid.
When adding liquid refrigerant to an operating system, it may be necessary to add the refrigerant
through the compressor suction service valve. Care must be exercised to avoid damage to the
compressor.
Emerson recommends connecting a sight glass between the charging hose and the compressor
suction service valve. This will permit adjusting the cylinder hand valve so that liquid can leave the
cylinder while allowing vapor to enter the compressor.
NOTICE
Risk of refrigerant overcharge. Can cause equipment damage.
Do not use the sight glass as an indicator when charging Liebert MC condenser systems.
NOTICE
Risk of using damaging cleaning agents, including non-base paint solvents. Can cause equipment
damage and damage to property and loss of refrigerant charge.
Using acid-based or sodium hydroxide-based cleaners can damage the Liebert MC condenser coil
and cause a loss of charge. This could cause equipment damage as well as damage to the
surrounding structure.
3
Liebert® MC™ User Manual
Liebert MC Nomenclature
Liebert MC Nomenclature
Model Number – Part 1/2
Model Details
Part 2/2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
M
C
M
0
4
0
E
1
A
D
0
A
0
V
U
0
0
0
0
0
0
*
*
*
*
1-2. Unit Family; MC = Microchannel Condenser
11. Coil Coating
0 = None
3. Platform Size
S = Small
E = E-Coat (Epoxy)
M = Medium
12. Panel Material
L = Large
A = Bright Aluminum
4-6. Nominal Condenser Capacity, kW
13. Connection Pipe Unit of Measurement
0 = Inches (Std. ACR Copper)
028, 056, 040, 055, 080, 110, 160, 165, 220
Example: 040 = 40kW @ 95°F(35°C) & 27°R (15°K) ITD
14. Legs Included
V = 18" Tall Legs (Std.)
7. Control/Fan Type
E = Premium & EC Fan
X = 36" Tall Legs with Bracing
Y = 48" Tall Legs with Bracing
8. Refrigerant Circuits/System Refrigerant type
1 = Single Refrigerant Circuit, R-410A
Z = 60" Tall Legs with Bracing
2 = Dual Refrigerant Circuit, R-410A
15. Agency Certification
7 = Single Refrigerant Circuit, R-407C, R-22
U = CSA Listed, Marked with CSA c-us logo
8 = Dual Refrigerant Circuit, R-407C, R-22
1 = IBC/OSHPD Seismic Certification,
IBC/FBC Wind Load Certification and
IBC Snow Load Certification.
9. Power Supply
16. Undefined - Reserved for Future Use
17. Liebert Lee-Temp™ Configuration
A = 460V / 3ph/60Hz
B = 575V / 3ph/60Hz
0 = No Receiver Leg/Software
Y = 208/230V/3ph/60Hz
1 = Liebert Lee-Temp Receiver Leg/Software
2 = 380V/3ph/60Hz
2 = Liebert DSE Receiver Leg/Software
10. Packaging
18-21. Undefined - Reserved For Future Use
D = Domestic, Non-Stackable (Horizontal Airflow Orientation)
E = Export Crating - Non-Stackable (Horizontal Airflow Orientation)
Liebert® MC™ User Manual
4
22-25. Factory Configuration Number
Introduction
1.0 Introduction
1.1 Product Description and Features
The Liebert MC condenser is a low-profile, direct-drive propeller fan-type air-cooled unit suitable for
mounting outdoors. It provides heat rejection for either one or two separate refrigeration circuits, matches
the heat rejection capacity corresponding with the outdoor ambient temperature and with each
corresponding compressor heat rejection requirements. Constructed with an aluminum cabinet, galvanized
steel frame and microchannel coil, the unit is quiet and corrosion resistant. The condenser is quickly and
easily installed, because all internal wiring is completed at the factory with only electrical connections to be
made at the job site. All electrical connections and controls are enclosed in an integral weatherproof
section of the condenser.
Figure 1-1 Two-fan Liebert MC
5
Liebert® MC™ User Manual
Introduction
1.2 Control, Fan Types and Features
1.2.1
Premium Efficiency Control/EC Fan
Premium Efficiency Controls and EC fans are matched to provide superior system energy efficiency. The
premium control board allows CANbus communication with the indoor unit’s Liebert iCOM® control. This
communication feature provides compressor run signals, condenser operating mode changes, condenser
alarm monitoring, simplified system charging procedures and outdoor temperature monitoring. The fans
are controlled by the premium control board using pressure transducer signals from the refrigerant circuit
and factory programming to control the refrigerant head pressure.
The Premium Efficiency Control board on a Liebert MC with a dual refrigeration circuit adjusts the speed of
fans on each circuit to match each circuit’s head pressure conditions. On a Liebert MC with multiple fans
and a single refrigeration circuit, the premium control adjusts the fans to the same speed to maintain head
pressure. The control system provides refrigerant head pressure control for outdoor ambient temperatures
as low as -30°F (-35°C), provided that the total design range (from minimum to maximum) is 125°F (70°C)
or less. For traditional DX applications, Liebert Lee-Temp™ kits are required only when the design
temperature ranges exceed 125°F (70°C) for standard match-ups and 115°F (65°C) for Liebert QuietLine™ match-ups.
1.2.1.1
Anti-Freezing Operation
The EC fans must be operated periodically in cold weather to reduce the possibility of lockup due to ice
and snow accumulation. During periods of inactivity and outdoor temperatures below 35°F (1.6°C), the EC
fans will spin for at least 30 seconds every 15 minutes at 60% of the maximum fan speed.
1.2.1.2
Fan Reversal for Cleaning
The Liebert iCOM® can be used to run the Premium EC fans in reverse to clear loose debris from the coil
between scheduled coil cleanings. The fan reversal may be done manually or automatically based on a
user-programmed schedule. Automatic fan reversal interval occurs when the indoor unit is Off (BMS Off,
U2U network standby or Remote Shut Down [RSD]).
1.2.1.3
Low-Noise Feature
The low-noise feature allows setting the condenser fans to operate at a specified speed to reduce
operating noise at certain times. Special match-ups of premium condensers are available for applications
needing to meet stringent sound regulations. Lower sound levels are achieved by oversizing the
condenser, which decreases the maximum airflow and sound level produced by the condenser. This
feature requires special setup of the indoor unit. One or more Liebert Lee-Temp receivers are required.
The premium control has gain schedules that will override the user-defined low-noise schedule to prevent
a high-pressure condition from occurring.
Liebert® MC™ User Manual
6
Introduction
1.3 Liebert Lee-Temp™ Refrigerant Control
The Liebert Lee-Temp head pressure control system utilizes head pressure control valve(s), extra
refrigerant and insulated refrigerant receiver(s) with heater pads to assist system starting. The Liebert LeeTemp control system also maintains proper operating head pressures in outdoor temperatures below the
rating point of the Liebert MC control type. The system works by flooding the condenser coil with liquid
refrigerant to a level that balances the system condensing requirements with the condenser coil surface
available to reject the system heat. During the summer, the system requires the entire condenser coil
surface for heat rejection and most of the refrigerant is stored in the receiver. In the winter, the same
amount of heat can be rejected by only a fraction of the coil surface. As head pressure begins to fall, the
control valve restricts the flow of liquid refrigerant from the condenser. This extra liquid refrigerant reduces
the effective condenser surface area available for heat transfer. The head pressure control valve also
bypasses hot gas into the receiver to warm the liquid and maintain liquid pressure for proper operation of
the expansion valve. Liebert Lee-Temp kit is optional for condensers and is field-installed. Condenser
control boards are factory-configured for Liebert Lee-Temp if they are ordered with Liebert Lee-Temp
receivers. They can be field-configured if a Liebert Lee-Temp system is added later.
1.4 Surge Protective Device
An optional Surge Protective Device (SPD) can be field-wired to protect the condenser from power surges
that threaten sensitive equipment. The condenser’s electrical panel provides a terminal block to allow the
SPD to be wired in parallel with the high-voltage power. An additional low-voltage terminal block is
provided on condensers with Premium Control Boards to allow monitoring of the SPD alarm circuit.
Emerson Network Power’s 420™ Series surge protective device provides 50kA per mode of surge current
protection. An illuminated green LED indicates the SPD is On and operating properly. An illuminated red
LED indicates that the device may require replacement.
When both LEDs are Off, there is no power to the condenser, either from a power failure or because the
condenser disconnect is in the Off position.
7
Liebert® MC™ User Manual
Introduction
Page intentionally left blank.
Liebert® MC™ User Manual
8
Site Preparation
2.0 Site Preparation
2.1 Site Considerations
• Condensers should be installed in a location offering maximum security and access for maintenance.
• Avoid ground-level sites with public access and areas prone to heavy snow or ice accumulations.
• To ensure adequate air supply, Emerson® recommends that condensers be installed in an area with
clean air, away from loose dirt and foreign matter that might clog the coil. In addition, condensers
should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.
• For roof installation, mount the condenser on suitable curbs or other supports in accordance with local
codes.
• Condensers must not be installed in a pit.
• Condensers must be installed on a level surface to ensure proper refrigerant flow.
• Use caution when installing condensers below the indoor unit. Condensers must not be installed more
than 15ft. (4.6m) below the indoor unit. Condensers with Liebert Lee-Temp™ receivers must be
installed at or above the level of the indoor units to maintain proper subcooling.
• Liebert Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation.
Contact Emerson Application Engineering Department for assistance with applications requiring
remote mounting of receivers.
• Condensers must be installed in vertical airflow orientation to maintain the electrical box’s NEMA 3R
rating.
9
Liebert® MC™ User Manual
Site Preparation
2.2 Dimensions and Weights
Table 2-1
Condenser shipping weights, dimensions and volume, approximate
Domestic Packaging
Export Packaging
Dimensions
(L x W x H)
in. (cm)
Volume
476 (216)
77 x 37 x 64
(196 x 94 x 163)
106 (3.0)
160 (4.5)
734 (333)
123 x 37 x 64
(312 x 94 x 163)
161 (4.8)
76 x 36 x 63
(193 x 91 x 160)
100 (2.8)
556 (252)
77 x 37 x 64
(196 x 94 x 163)
106 (3.0)
769
(349)
122 x 36 x 63
(310 x 91 x 160)
160 (4.5)
941 (427)
123 x 37 x 64
(312 x 94 x 163)
161 (4.8)
4
1509
(684)
256 x 36 x 63
(650 x 91 x 160)
336 (9.5)
1834 (832)
257 x 37 x 64
(653 x 94 x 163)
352 (10)
MCL055
1
552
(250)
76 x 36 x 63
(193 x 91 x 160)
100 (2.8)
669 (303)
77 x 37 x 64
(196 x 94 x 163)
106 (3.0)
MCL110
2
962
(436)
136 x 36 x 63
(345 x 91 x 160)
179 (5.0)
1134 (514)
137 x 37 x 64
(348 x 94 x 163)
188 (5.3)
MCL165
3
1364
(619)
196 x 36 x 63
(498 x 91 x 160)
257 (7.3)
1619 (734)
197 x 37 x 64
(500 x 94 x 163)
270 (7.7)
MCL220
4
1835
(832)
256 x 36 x 63
(650 x 91 x 160)
336 (9.5)
2160 (980)
257 x 37 x 64
(653 x 94 x 163)
352 (10)
Model #
Number
of Fans
Weight
lb (kg)
Dimensions
LxWxH
in. (cm)
MCS028
1
359
(163)
76 x 36 x 63
(193 x 91 x 160)
100 (2.8)
MCS056
2
562
(255)
122 x 36 x 63
(310 x 91 x 160)
MCM040
1
439
(199)
MCM080
2
MCM160
Volume
ft (m )
Weight
lb (kg)
3
3
ft3 (m3)
1. Packaged weights will increase with factory options, such as legs taller than 18" (457mm), coated coils, 575V and seismic/wind
options. See Tables 2-2, 2-3 and 2-4 for option weights to add to the packaged weights above. Consult factory for additional
information.
2. Receivers and 60" legs are shipped separately from the condenser.
2.2.1
Condenser and Options Net Weights
Total unit weight is the sum of the condenser weight with the selected legs plus the weight of any option.
Source: DPN003034, Rev. 1
Table 2-2
Condenser and option net weights—Small condensers
Condenser Model
Refrigeration Circuits
Condenser Dry
Weight, lb (kg)
MCS028
MCS056
1
2
18" Leg
154 (70)
270 (122)
36" Leg
286 (130)
419 (190)
48" Leg
318 (144)
451 (205)
60" Leg
349 (158)
482 (219)
55 (25)
110 (50)
4 (2)
8 (4)
575V
52 (24)
63 (29)
Seismic/Wind Bracing, 18-in. legs
40 (18)
40 (18)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp
Coated Coil
Liebert® MC™ User Manual
10
Site Preparation
Table 2-3
Condenser and option net weights—Medium condensers
Condenser Model
MCM040
Refrigeration Circuits
MCM080
MCM160
1
1
2
2
18" Leg
231 (105)
441 (200)
441 (200)
860 (390)
36" Leg
363 (165)
590 (268)
590 (268)
1066 (484)
48" Leg
395 (179)
622 (282)
622 (282)
1114 (505)
60" Leg
426 (193)
653 (296)
653 (296)
1160 (526)
55 (25)
100 (45)
110 (50)
220 (100)
Liebert DSE Receiver DA050
—
44 (20)
—
—
Liebert DSE Receiver DA080/085
—
—
—
88 (40)
Liebert DSE Receiver DA125/150/165
—
—
—
184 (83)
Condenser Dry
Weight, lb (kg)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp
Coated Coil
5 (2)
10 (5)
10 (5)
20 (9)
575V
52 (24)
63 (29)
63 (29)
76 (34)
Seismic/Wind Bracing, 18-in. legs
40 (18)
40 (18)
40 (18)
57 (26)
Table 2-4
Condenser and option net weights—Large condensers
Condenser Model
Refrigeration Circuits
MCL055
MCL110
MCL165
MCL220
1
1
2
1
1
2
18" Leg
344 (156)
602 (273)
602 (273)
891 (404)
1186 (538)
1186 (538)
36" Leg
486 (220)
766 (347)
766 (347)
1136 (515)
1453 (659)
1453 (659)
48" Leg
518 (235)
798 (362)
798 (362)
1184 (537)
1501 (681)
1501 (681)
60" Leg
549 (249)
829 (376)
829 (376)
1230 (558)
1547 (702)
1547 (702)
60 (27)
115 (52)
120 (54)
175 (79)
215 (98)
240 (109)
Liebert DSE Receiver DA050
—
45 (20)
—
45 (20)
—
—
Liebert DSE Receiver DA080/085
—
45 (20)
90 (41)
—
45 (20)
90 (41)
Liebert DSE Receiver DA125/150/165
—
94 (43)
188 (85)
94 (43)
94 (43)
188 (85)
Condenser Dry
Weight, lb (kg)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp
Coated Coil
8 (4)
16 (7)
16 (7)
24 (11)
32 (15)
32 (15)
575V
79 (36)
90 (41)
90 (41)
132 (60)
134 (61)
134 (61)
Seismic/Wind Bracing, 18-in. legs
40 (18)
40 (18)
40 (18)
57 (26)
57 (26)
57 (26)
11
Liebert® MC™ User Manual
Site Preparation
Figure 2-1 Condenser planning dimensional data—MCS028, MCM040 and MCL055
575V
Option
575V
Option
H
TOP OF
FAN GUARD
G
F
A*
2
A
Lee-Temp Receiver
C
Entering Hot Gas and
Leaving Liquid Piping
D
A
Anchor
Plan
Main
Electric
Box
End
M L K
6 1/2"
165mm
15 1/4"
387mm
Left Side of Unit
13/16"
21mm
Typ.
3 5/8"
93mm
Typ.
Ref.
K
Front View (Lee-Temp Shown)
1 7/8"
48mm
Typ.
Note:
1. Emerson recommends a clearance of
36” (915mm) on each side for proper
operation and component access.
7"
178mm
Typ.
Cross Bracing required for legs longer
than 18" (457.2mm). Quantity varies
per model & options selected.
2
DETAIL A
Typical all legs
1/2" (13mm) X 1" (25mm)
Obround Typ.
DPN003436
Rev. 0
Cabinet Dimensions
in. (mm)
Liebert
Model No.
A
A*
(575V only)
C
D
K
L
M
MCS028
50-5/8 (1287)
58-7/8 (1495)
44-1/8 (1120)
42-1/2 (1080)
42-1/2 (1080)
40-7/8 (1038)
35-7/8 (910)
MCM040
57-3/16 (1453)
65-3/8 (1661)
48 (1219)
46-5/16 (1177)
46 (1168)
44-3/8 (1127)
39-5/16 (999)
MCL055
68 (1727)
77 (1956)
56 (1422)
54-3/8 (1381)
55-1/2 (1410)
53-78 (1368)
48-3/4 (1238)
48 (1219)
60 (1524)
Leg-height Dimensions
in. (mm)
All Models
F
MCS028
MCM040
G
31-5/8 (803)
49-5/8 (1260)
61-5/8 (1565)
73-5/8 (1870)
H
39-5/8 (1006)
57-5/8 (1464)
69-5/8 (1768)
81-5/8 (2073)
G
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673)
77-7/8 (1978)
H
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870)
85-5/8 (2175)
MCL055
18 (457)
36 (914)
Source: DPN003436, Rev. 0
Liebert® MC™ User Manual
12
Site Preparation
Figure 2-2 Condenser planning dimensional data—MCS056, MCM080, MCL110
575V
Option
575V
Option
H
TOP OF
G FAN GUARD
A*
A
F
2
Lee-Temp or DSE Receiver
C
Entering Hot Gas and
Leaving Liquid Piping
D
A
Anchor Plan
Main
Electric
Box
End
Full height leg supplied for
each Lee-Temp or
DSE Receiver required
M L K
15 1/4"
387mm
Left Side of Unit
13/16"
21mm
Typ.
J
Lee-Temp or DSE Only
3
3
6 1/2"
165mm
3
6 1/2"
165mm Ref.
Ref.
Dual Circuit Only
15 1/4"
K
387mm
Dual Circuit Only
Front View (Lee-Temp Shown)
3
3 5/8"
93mm
Typ.
7"
178mm
Typ.
Note:
1. Emerson recommends a clearance of
36” (915mm) on each side for proper
operation and component access.
1 7/8"
48mm
Typ.
1/2" (13mm) X 1" (25mm)
Obround Typ.
2 Cross bracing required for legs longer
than 18" (457mm). Quantity varies per
model & options selected.
3 For DSE models only, 6-1/2" (165mm)
dimension is 9-1/4" (235mm) and
15-1/4 (387mm) dimension is not applicable.
DETAIL A
Typical All Legs
DPN00437
Rev. 2
Cabinet Dimensions
in. (mm)
J
Liebert
Model No.
A
A*
(575V only)
C
MCS056 94-7/8 (2411) 103-1/8 (2619)
88-3/8 (2245)
MCM080 105-1/4 2674) 113-7/16 (2882) 96-1/16 (2440)
MCL110 124-1/8 (3152) 133-1/8 (3381) 112-1/8 (2848)
Leg-height Dimensions
in. (mm)
D
Lee-Temp or
DSE Receivers
Only
L
M
86-3/4 (2203) 42-1/2 (1079) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910)
94-7/16 (2398) 45-5/19 (1177)
46 (1168)
44-3/8 (1127) 39-5/16 (999)
110-1/2 (2806) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-34 (1238)
All Models
F
18 (457)
36 (914)
48 (1219)
60 (1524)
MCS056
MCM080
G
31-5/8 (803)
49-5/8 (1260)
61-5/8 (1565)
73-5/8 (1870)
81-5/8 (2073)
MCL110
K
H
39-5/8 (1006)
57-5/8 (1464)
69-5/8 (1768)
G
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673) 77-7/8 (1978)
H
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870) 85-5/8 (2175)
Source: DPN003437, Rev. 2
13
Liebert® MC™ User Manual
Site Preparation
Figure 2-3 Condenser planning dimensional data—MCL165
575V
Option
575V
Option
B
Lifting Eyebolts
Typ. (4) Places
H
TOP OF
FAN GUARD
G
A
A*
F
2
C
E
Lee-Temp or DSE Receiver
Entering
Hot Gas and
Leaving
Liquid Piping
D
54 1/8"
1374mm
Typ.
A
Main
Electric
Box
End
Full height Leg
supplied for each
Lee-Temp or DSE
Receiver required
Anchor Plan
M L K
J
Lee Temp or DSE Only
Left Side of Unit
:
3 5/8"
93mm
Typ.
13/16"
21mm
Typ.
Ref.
K
Front View (Lee-Temp shown)
Note
1. Emerson recommends a clearance of
36” (915mm) on each side for proper
operation and component access.
7"
178mm
Typ.
2 Cross Bracing required for legs longer
than 18" (457.2mm). quantity varies per
model & options selected.
1 7/8"
48mm
Typ.
DETAIL A
3
6 1/2"
165mm
3
15 1/4"
387mm
3 For DSE models only, 6-1/2" (165mm)
dimension is 9-1/4" (235mm) and
15-1/4 (387mm) dimension is not applicable.
1/2" (13mm) X 1" (25mm)
Obround Typ.
DPN003438
Rev. 2
Typical All Legs
Dimensions
in. (mm)
Liebert
Model No.
MCL165
J
A
A*
(57V only)
B
C
D
E
180-1/4
(4578)
189-1/4
(4807)
73-7/16
(1866)
168-1/4
(4274)
110-1/2
(2806)
56-1/8
(1425)
Lee-Temp or DSE
Receivers Only
54-3/8 (1381)
K
L
M
55-1/2
(1410)
53-7/8
(1368)
48-3/4
(1238)
Leg-height Dimensions
in. (mm)
MCL165
F
18 (457)
36 (914)
48 (1219)
60 (1524)
G
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673)
77-7/8 (1978)
H
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870)
85-5/8 (2175)
Source: DPN003438, Rev. 2
Liebert® MC™ User Manual
14
Site Preparation
Figure 2-4 Condenser planning dimensional data—MCM160 and MCL220
575V
Option
B
575V
Option
Lifting Eyebolts
Typ. (4) Places
F
2
A*
A
G
H
TOP OF
FAN GUARD
Lee-Temp or DSE Receiver
Entering
Hot Gas and
Leaving
Liquid Piping
C
E
D
54 3/16"
1376mm
Typ.
A
Main
Electric
Box
End
Full height Leg
supplied for each
Lee-Temp or DSE
Receiver required
Anchor Plan
J
Lee-Temp or DSE Only
Left Side of Unit
3 5/8"
93mm
Typ.
13/16"
21mm
Typ.
M L K
3
6 1/2"
165mm Ref.
6 1/2"
165mm Ref.
Dual Circuit Only
15 1/4"
387mm
3
3
15 1/4"
387mm
Dual
Circuit
Only
3
K
1 7/8"
48mm
Typ.
Front View (Lee-Temp shown)
Note:
1. Emerson recommends a clearance of 36” (915mm)
on each side for proper operation and component access.
7"
178mm
Typ.
Cross bracing required for legs longer than 18" (457.2mm).
2 Quantity varies per model & options selected.
3 For DSE models only, 6-1/2" (165mm) dimension is 9-1/4" (235mm)
and 15-1/4 (387mm) dimension is not applicable.
1/2" (13mm) X 1" (25mm)
Obround Typ.
DETAIL A
DPN003439
Rev. 2
Typical all legs
Cabinet Dimensions
in. (mm)
J
Liebert
Model No.
MCM160
MCL220
A
A*
(575V only)
B
C
D
202-7/16
(5142)
236-5/16
(6003)
210-5/8
(5350)
245-5/16
(6231)
113-1/2
(2883)
129-9/16
(3291)
192-1/4
(4883)
224-3/8
(5699)
94-7/16
(2398)
110-1/2
(2806)
E
Lee-Temp or
DSE Receivers
Only
K
96-3/16
45-5/16 (1177) 46 (1168)
(2444)
112-1/4
55-1/2
54-3/8 (1381)
(2851)
(1410)
L
M
44-3/8
(1127)
53-7/8
(1368)
39-5/16
(999)
48-3/4
(1238)
Leg-height Dimensions
in. (mm)
All Models
MCM160
MCL220
F
18 (457)
36 (914)
48 (1219)
60 (1524)
G
31-5/8 (803)
49-5/8 (1260)
61-5/8 (1565)
73-5/8 (1870)
H
39-5/8 (1006)
57-5/8 (1464)
69-5/8 (1768)
81-5/8 (2073)
G
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673)
77-7/8 (1978)
H
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870)
85-5/8 (2175)
Source: DPN003439, Rev. 2
15
Liebert® MC™ User Manual
Site Preparation
Figure 2-5 Liebert DSE receiver mounting—MCL165 and MCL220, single-circuit condenser,
left-side condenser outlet receiver
RECEIVER MOUNTING HOLES
SINGLE CIRCUIT.
DETAIL A
A
TRIM PIPING
AS NEEDED
RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS AND
NEEDS TO BE ANCHORED WITH THEM.
11 1/8"
282.6mm
SMALL RECEIVER SHOWN. ACTUAL RECEIVER SIZE
MAY VARY.
36"
914mm
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
64 3/4"
1645mm
CROSS BRACING
NOT SHOWN
DPN002554
Pg. 1 Rev. 4
Liebert® MC™ User Manual
16
Site Preparation
Figure 2-6 Liebert DSE receiver mounting—MCL165 and MCL220, single-circuit condenser,
right-side condenser outlet receiver
RECEIVER MOUNTING HOLES
SINGLE CIRCUIT.
TRIM PIPING
AS NEEDED
DETAIL B
B
RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS AND
NEEDS TO BE ANCHORED WITH THEM.
11 1/8"
282.6mm
64 3/4"
1645mm
36"
914mm
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
SMALL RECEIVER SHOWN.
ACTUAL RECEIVER SIZE MAY VARY.
CROSS BRACING
NOT SHOWN
DPN002554
Pg. 2 Rev. 7
17
Liebert® MC™ User Manual
Site Preparation
Figure 2-7 Liebert DSE receiver mounting—MCL110 and MCL220, dual-circuit condenser
C
D
CIRCUIT 2
CIRCUIT 1
TRIM PIPING
AS NEEDED
DETAIL C
RECEIVER MOUNTING HOLES
DUAL CIRCUIT (CIRCUIT 2 ONLY).
TRIM PIPING
AS NEEDED
DETAIL D
RECEIVER LEG IS
SAME HEIGHT AS
OTHER LEGS AND
NEEDS TO BE
ANCHORED WITH THEM.
11 1/8"
283mm
74 1/16"
1881mm
36"
914mm
SMALL RECEIVER SHOWN.
ACTUAL RECEIVER SIZE MAY VARY.
TYP
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
CROSS BRACING
NOT SHOWN
Liebert® MC™ User Manual
DPN002554
Pg. 3 Rev. 7
18
Site Preparation
Figure 2-8 Liebert DSE receiver mounting—MCM160 dual circuit condenser
11.13"
282.6mm
64.63"
1641.7mm
36.00"
914.4mm TYP
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS.
CROSS BRACING
NOT SHOWN
DPN002383
Rev. 7
19
Liebert® MC™ User Manual
Site Preparation
Page intentionally left blank.
Liebert® MC™ User Manual
20
Inspection and Installation
3.0 Inspection and Installation
SAFETY INFORMATION
! WARNING
Risk of improper handling. Can cause equipment damage, injury or death.
Read all of the following instructions before attempting to move, lift, remove packaging from or
preparing unit for installation.
! WARNING
Risk of heavy condenser falling or tipping over. Can cause property damage, serious injury or
death.
Confirm that all components of the lifting system are rated for the weight of the condenser by an
OSHA Certified rating organization before attempting to lift and/or move the condenser. See
Tables 2-1 through 2-4 for the condenser weights.
! CAUTION
Risk of contact with sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes
and glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
NOTICE
Risk of interference with building doorways, openings and passages. Can cause unit and/or
building damage.
Refer to the installation plans and measure the unit and building opening before moving the unit to
verify clearances.
NOTICE
Risk of improper forklift handling. Can cause unit damage.
Keep the forklift tines level and at a height that will fit under the skid.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep unit upright and protected from contact damage.
21
Liebert® MC™ User Manual
Inspection and Installation
3.1 Equipment Inspection
Upon arrival of the unit and before unpacking, verify that the labeled equipment matches the Bill of Lading.
Carefully inspect all items for either visible or concealed damage. Damage should be immediately reported
to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your sales
representative.
If you have the seismic mounting kit, refer to Liebert MC Seismic Application—
Optional Unit Configuration
3.1.1
Packing Material
All material used to package this unit is recyclable. Save it for future use or dispose of the material
appropriately.
Figure 3-1 Equipment recommended for handling a Liebert condenser
Forklift
Liebert® MC™ User Manual
Lift Beam, Slings
and Spreader Bars
22
Crane
308111
Pg. 1, Rev. 3
Inspection and Installation
3.2 Handling Unit on the Skid
Transport unit using a fork lift or a crane with sling and spreader bars.
NOTICE
Risk of improper forklift handling. Can cause unit damage.
Keep the forklift tines level and at a height that will fit under the skid.
• If using a fork lift, make sure the forks (if adjustable) are spread to the widest allowable distance to still
fit under the skid.
• Type of fork lift used will be Dependant on the terrain the unit is be moved across during handling.
• Minimum fork lift fork length for use on one-fan and two-an unit must be 48" (1219mm).
• Minimum fork lift fork length for use on three-fan and four-fan unit must be 72" (1829mm).
• When moving the packaged unit, do not lift it any higher than 6" (152mm). If the unit must be lifted
higher than 6" (152mm), great care must be exercised and no one may be closer than 20' (6m) to the
lift point.
Figure 3-2 Forklift position with one-fan or two-fan condensers
308111
Pg. 1, Rev. 3
• When the Liebert MC is being moved with a forklift, Emerson recommends lifting one end off the
ground no more than 6" (152mm)and using the forklift to push or pull the unit.
• When the Liebert MC is lifted with a crane, Emerson recommends using slings rated for the unit
weight.
• Spreader bars must be used for sling stability and to keep the slings from pressing against the unit.
Make sure spreader bars are wider than the unit.
• Place the slings near the ends of the unit, under the top deck boards of the skid.
3.3 Unit Storage
Store the condenser in the original packaging in an area protected from excessive dirt, debris and contact
damage until final installation
23
Liebert® MC™ User Manual
Inspection and Installation
3.4 Unpacking the Condenser—All Unit Sizes
! CAUTION
Risk of contact with sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes
and glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
To unpack a condenser:
1. Remove the fence for domestic packaging (for export packaging, remove the crate).
2. Remove the exterior foam from around the unit and the electric box.
3. Remove the steel straps securing the unit to the skid.
4. Set the legs aside, but keep accessible if legs are shipped together with the unit.
5. Depending on the number of fans, more or less steel strap may be removed at this step.
6. Remove corrugated panels covering the Liebert MC’s coil(s).
7. Remove the bolts securing unit to the skid.
8. Remove the bolts securing the brackets to the unit and recycle the brackets.
Liebert® MC™ User Manual
24
Inspection and Installation
Figure 3-3 Removing protective material
Step 1-Domestic
Step 1 - Export
Step 2
Steps 3 - 5
Step 6
Legs for Liebert MC
Fasteners are in bag
attached to the legs
Step 7 - 8
Detail Area
25
308111
Rev. 3
Liebert® MC™ User Manual
Inspection and Installation
3.5 Preparing a Condenser for Moving and Installation
The following procedure is one method for removing a Liebert condenser from its shipping skid. Other
methods may be used, provided that they are safe for personnel, the condenser and other equipment.
3.5.1
Attaching 18" (457mm) Legs,
Removing the Skid and Attaching Slings
1. Attach legs to the unit at indicated locations, using the fasteners provided with the legs.
Recommended tools for attachment is a 1/2” (13mm) socket and ratchet.
More legs may be available for installation than are shown. This will depend on the unit type and
number of fans.
Units supplied with 36-60” (914-1524mm) legs go to 3.5.2 - Special Considerations for 36-60” (9141524mm) Legs
Figure 3-4 Attaching legs to one-fan or two-fan condensers
B
308111
Pg. 2, Rev. 3
Detail B
Liebert® MC™ User Manual
26
Inspection and Installation
2. Place slings around the unit between the unit and the top deck boards of the skid:
• One-fan and two-fan units: against the inside of the attached legs.
• Three-fan and four-fan units: against the outside of the attached eye bolts.
3. Use spreader bars, a lift beam and a crane to lift the unit off the skid. Make sure spreader bars are
wider than the unit.
NOTICE
Risk of improper lifting. Can cause equipment damage.
Make sure that the spreader bars wider are than the unit. If the spreader bars are too short, the
slings may crush the unit.
Figure 3-5 Securing slings to condensers for lifting off skid
Straps or chains go against
eye bolts on three-fan and
four-fan units
Straps go against
the legs on
one-fan and
two-fan units
308111
Pg. 3, Rev. 3
4. Lift the unit 24" (610mm) off the top deck of the skid.
5. Remove the skid from under the unit.
6. A mechanized method is recommended, but if one is not available, use a minimum of four properly
protected individuals to rotate the elevated unit 90 degrees.
Unit legs are to be pointing toward the ground.
Figure 3-6 Remove skid, set condenser on floor
308111
Pg. 3, Rev. 3
27
Liebert® MC™ User Manual
Inspection and Installation
7. Set the upright unit on the ground so the legs support unit weight.
8. Remove the straps from around unit.
9. One-fan and two-fan units: Route the straps through the large holes in the side of the legs. Spreader
bars are still required. Make sure that the spreader bars are wider than the unit.
On three-fan and four-fan units: Secure straps or chains to the eye bolts on top of the unit. Spreader
bars are still required. Make sure that the spreader bars are wider than the unit.
NOTICE
Risk of improper lifting. Can cause equipment damage.
Make sure that the spreader bars wider are than the unit. If the spreader bars are too short, the
slings may crush the unit.
The unit is ready to be lifted and moved to its installation location.
Figure 3-7 Lifting condensers with one, two, three or four fans
Spreader Bars
(must be wider
than the
Liebert MC to
prevent crushing
force)
Straps or chains go through
eye bolts on three-fan and
four-fan units
Straps go through holes in legs
on one-fan and two-fan units
Liebert® MC™ User Manual
28
308111
Pg. 3, Rev. 3
Inspection and Installation
3.5.2
Special Considerations for 36-60” (914-1524mm) Legs
Figure 3-8 Recommended bolt locations
Recommended
Bolt Location
(4 Places)
Detail C
Secondary
Bolt Location
(4 Places)
Cross-Bracing on Condensers
Using Four Legs (example)
Detail C
308111
Pg. 4, Rev. 3
1. Insert four leg bolts into the threaded holes near the corners along the long edges of the unit, leaving
approximately 1/4” (6mm) of the fastener threads exposed (see Figure 3-8). These will serve as sling
containment guides during condenser lifting and rotation. This will also permit leg attachment at the
secondary bolt locations while using the slings to lift and support the condenser weight.
2. Assemble the leg structure according to the instructions supplied with the legs.
NOTE
When assembling the leg structure, DO NOT tighten the cross-brace hardware until the condenser
cabinet is fastened to the legs.
3. Place slings around the first and second fan units against the inside of the inserted leg bolts.
4. Place slings around the third and fourth fan units against the outside of the attached eye bolts.
5. Slings are to be placed between the unit and the top deck boards of the skid.
6. Use spreader bars, lift beam and crane to lift the unit off the skid. Make sure spreader bars are wider
than the unit.
29
Liebert® MC™ User Manual
Inspection and Installation
Figure 3-9 Remove bolts along the long edge of the unit
Rotate
Liebert MC
90 Degrees
308111
Pg. 4, Rev. 3
D
Detail D
7. Lift the unit 24" (610mm) off the skid. Remove the skid from under the unit.
8. A mechanized method is recommended, but if one is not available, use a minimum of four properly
protected people to rotate the elevated unit 90 degrees. The fans will be facing up.
9. Place the unit on the leg structure, resting the unit on its legs (see Figure 3-9).
10. Remove the bolts inserted in the long edges. If the secondary locations are used, the bolts must be
removed just before setting the unit on its legs.
11. Align, insert and tighten all hardware securing the Liebert MC to the leg structure.
12. Square up the leg structure and tighten all cross-brace angle hardware.
Liebert® MC™ User Manual
30
Inspection and Installation
Figure 3-10 Lifting the unit for installation
308111
Pg. 4, Rev. 3
13. Lower the unit so the leg structure supports the weight of the unit.
14. Remove the straps from around the unit.
15. On one- and two-fan units, route the straps through the large holes on the side of the legs. Spreader
bars are still required; they must be wider than the unit.
16. On three- and four-fan units, use the eye bolts on top of the unit to secure straps or chains. Spreader
bars are still required. Make sure spreader bars are wider than the unit.
The unit is now ready to be lifted into position for installation.
31
Liebert® MC™ User Manual
Inspection and Installation
3.6 Mounting the Condenser
The condenser must be installed so that it is level within 1/2” (13mm) to ensure proper refrigerant flow. For
roof installation, mount the condenser on suitable curbs or other supports. Follow all local and national
codes.
3.6.1
Standard Mounting Requirements
Secure the legs to the mounting surface using field-supplied 3/8” (9.5mm) diameter Grade 5 bolts with a
flat washer in each of the two 1/2” x 1" (12.7 x 25.4mm) obround holes in each leg. See Figures 2-1
through 2-4 for anchor dimensions.
3.6.2
Seismic-Certified and Wind-Certified Mounting Requirements
Mounting requirement details such as anchor brand, type, embedment depth, edge spacing,
anchor-to-anchor spacing, concrete strength, special inspection and attachment to non-building structures
must be outlined and approved by the engineer of record for the project or building.
Structural floors and housekeeping pads must also be designed and approved by the project or building
structural engineer of record to withstand the seismic or wind anchor loads as defined on the installation
drawings. The installing contractor is responsible for the proper installation of all anchors and mounting
hardware, observing the mounting requirements detailed in the seismic or wind installation drawings and
additionally outlined by the engineer of record.
At a minimum, 3/8” Grade 5 anchors with American National Standard Series W, Type A, plain washers
(ANSI B18.22.1-1965, R1975) selected to match the nominal anchor diameter must be installed at each
anchor location between the anchor head and equipment for tension load distribution. See 10.0 - Liebert
MC Seismic Application—Optional Unit Configuration for additional information.
Liebert® MC™ User Manual
32
Electrical Connections
4.0 Electrical Connections
Line voltage electrical service is required for all models. Refer to the equipment’s nameplate regarding wire
size and circuit protection requirements. Electrical service must conform to national and local electrical
codes. Refer to Figure 4-8 for electrical service entrances into unit. Refer to electrical schematic when
making connections.
A manual electrical disconnect switch should be installed in accordance with local codes. Consult local
codes for external disconnect requirements.
All internal wiring is completed at the factory.
! WARNING
Risk of electrical shock. Can cause injury or death.
The fan speed control and the EC fan electrical enclosures may contain a stored electrical charge.
Open all local and remote electric power disconnect switches, wait 10 minutes and verify with a
voltmeter that power is Off before working within the fan speed control and the EC fan electrical
enclosures.
The Liebert MC contains lethal voltage in some circuits. The line side of the disconnect remains
energized when the condenser unit disconnect is switched to the Off position.
Use a voltmeter to verify that the line-side electrical power is Off before making any electrical
connections or performing any electrical and/or mechanical service and/or maintenance
operations.
! WARNING
Risk of contact with high-speed, rotating fan blades. Can cause serious injury or death.
Fan blades can automatically start rotating without warning at any time during a cooling cycle or
after power is restored after a power failure. Open all local and remote electric power supply
disconnect switches and verify with a voltmeter that the power is Off and that the fan blades have
stopped rotating before working within the cabinet or servicing fan motors.
Each unit is shipped from the factory with all internal wiring completed. Refer to the electrical
schematic supplied with the condenser when making line voltage supply, low-voltage indoor unit
interlock and any low-voltage alarm connections. All wiring must be done in accordance with all
applicable local, state and national electrical codes.
NOTE
Installation and service of this equipment should be done only by properly trained and qualified
personnel who have been specially trained in the installation of air conditioning equipment.
NOTE
Use copper wiring only. Make sure that all connections are tightened to the proper torque
mentioned on the component.
33
Liebert® MC™ User Manual
Electrical Connections
4.1 Line Voltage Wiring
! WARNING
Risk of electrical fire and short circuit. Can cause property damage, injury or death.
Select and install the line side electrical supply wire and overcurrent protection device(s) according
to the specifications on the unit nameplate(s), per the instructions in this manual and according to
the applicable national, state and local code requirements. Use copper conductors only.
Verify that all electrical connections are tight. Unit-specific wiring diagrams are provided on each
unit.
NOTE
The Liebert MC Condenser is designed to operate with Wye-connected power with a solidly
grounded neutral. It will not operate properly with Wye-connected power with high-resistance (or
impedance) ground or with delta-connected power. Refer to 4.1.1 - Wye- vs. Delta-Connected
Power Supply.
Condenser-rated voltage should be verified with available power supply before installation. Refer to the
unit’s electrical schematic and serial tag for specific electrical requirements.
Liebert MC condenser power connections are provided for three-phase wires and 1 earth ground wire.
Line voltage electrical service is required for all condensers at the location of the condenser. The voltage
supply to the condenser may not be the same voltage supply as required by the indoor unit. Consider
using a UPS on both data center cooling units and Liebert MC condensers to maintain uninterrupted
cooling capability. Refer to the unit’s serial tag for specific condenser electrical requirements. A unit
disconnect is standard. However, a site disconnect may be required by local code to isolate the unit for
maintenance. Route the supply power to the site disconnect switch and then to the unit. Route the conduit
to the knockout provided in the bottom right end of the electrical control enclosure. Connect the earth
ground wire lead to the marked earth ground connection terminal provided near the factory-installed
disconnect switch (see Figure 4-8).
NOTE
Liebert Lee-Temp™ kits require a separate line voltage electrical supply for the heated receivers.
See Table 4-2 for power requirements.
Liebert® MC™ User Manual
34
Electrical Connections
Table 4-1
Electrical data, three-phase, 60Hz condenser, premium models
Model
Small Platform
MCS028
MCS056
Voltage
FLA
WSA
OPD
208/230V
380V
460V
575V
208/230V
380V
460V
575V
3.0
1.4
1.4
1.2
6.0
2.8
2.8
2.3
3.8
1.8
1.8
1.5
6.8
3.3
3.3
2.8
15
15
15
15
15
15
15
15
208/230V
380V
460V
575V
208/230V
380V
460V
575V
208/230V
380V
460V
575V
2.3
1.4
1.4
1.2
4.6
2.8
2.8
2.3
9.2
5.6
5.6
4.7
3.2
1.9
1.9
1.6
5.5
3.3
3.3
2.8
9.8
6.0
6.0
5.0
15
15
15
15
15
15
15
15
15
15
15
15
208/230V
380V
460V
575V
208/230V
380V
460V
575V
208/230V
380V
460V
575V
208/230V
380V
460V
575V
5.7
2.8
2.8
2.3
11.4
5.6
5.6
4.7
17.1
8.4
8.4
7.0
22.8
11.2
11.2
9.3
7.1
3.5
3.5
2.9
12.8
6.3
6.3
5.3
18.5
9.1
9.1
7.6
24.2
11.9
11.9
9.9
15
15
15
15
15
15
15
15
20
15
15
15
25
15
15
15
Medium Platform
MCM040
MCM080
MCM160
Large Platform
MCL055
MCL110
MCL165
MCL220
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
2. 208V–575V premium models must be connected to Wye three-phase systems.
3. Wye 3-phase systems with solidly grounded neutral. Refer to 4.1.1 - Wye- vs. Delta-Connected
Power Supply.
Table 4-2
Electrical data, Liebert Lee-Temp™ receiver, 60Hz
Rated Voltage - Single-Phase
Watts/Receiver
Amps
Wire Size Amps
Maximum Overcurrent
Protection Device, Amps
120
208/230
150
1.4
1.8
300
2.8
3.5
150
0.7
0.9
300
1.4
1.8
15
15
15
15
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The condenser is
not designed to supply power to the receiver heater pads.
35
Liebert® MC™ User Manual
Electrical Connections
4.1.1
Wye- vs. Delta-Connected Power Supply
Figure 4-1 Wye- vs. delta-connected power supply connection diagram
Delta-Connected Power Diagram
Wye-Connected Power Diagram
Phase A
Phase B
Phase A
Winding
A-B
Winding
C-A
Phase B
Winding B-C
Phase C
Phase C
Ground
NOTICE
Risk of improper input power. Can cause equipment damage.
The Liebert MC Condenser is designed to operate with Wye-connected power with a solidly
grounded neutral. It will not operate properly with Wye-connected power with high-resistance (or
impedance) ground or with delta-connected power. Refer to 4.1.1 - Wye- vs. Delta-Connected
Power Supply
NOTE
A separate neutral wire does not need to be run to the Liebert MC.
4.1.1.1
Acceptable Power Supplies—208V to 575V Nominal Units
• 208V Wye with solidly grounded neutral and 120V line-to-ground
• 380V Wye with solidly grounded neutral and 220V line-to-ground
• 480V Wye with solidly grounded neutral and 277V line-to-ground
• 575V Wye with solidly grounded neutral and 332V line-to-ground (uses step-down tranformers)
4.1.1.2
Unacceptable Power Supplies—208V to 575V Nominal Units
• Wye with high-resistance (or impedance) ground
• Delta without ground or with floating ground
• Delta with corner ground
• Delta with grounded center tap
Liebert® MC™ User Manual
36
Electrical Connections
4.2 Low-voltage Control Wiring—CANbus Communication
and Interlock Connections
NOTICE
Risk of control malfunction. Can cause improper unit operation.
Verify that all low-voltage electrical wiring has been performed per the schematic diagram provided
and that all low-voltage wiring connections are tight.
CANbus communication and interlock wiring are required between the indoor and the outdoor units.
CANbus cables are supplied by others to connect the indoor unit to the outdoor condenser. No special
considerations are required when the total external cable connection between the indoor unit and outdoor
unit is less than 450 ft. (137m). A CANbus isolator is required for total external cable connections longer
than 450 ft. (137m) but less than 800 ft. (243m).
CANbus Cable Requirements
• conductors 22-18AWG stranded tinned copper
• twisted pair (minimum four twists per foot)
• braided shield or foil shield with drain wire
• shield must always be wired to ground at the indoor unit
• low capacitance (15pF/ft or less)
• UL-approved temperature rated to 75°C
• UL-approved voltage rated to 300V
• UV-resistant and moisture-resistant if not run in conduit
• plenum-rated NEC Type CMP, if required by national or local codes
• Examples include: Belden 89207 (plenum-rated), or Alpha Wire 6454 Category 5, 5e or higher
Interlock wiring is field-supplied wiring between Terminals 70 and 71 for single-circuit models and Terminal
230 also for dual-circuit models. Total interlock wire length must be less than 1000 ft. (305 m).
Field-Supplied Interlock Wire
• 18AWG or greater
• rated 600V
Notes on Electrical Connections
• Do not run CANbus cable and interlock wires in same conduit, racewary or chase as high-voltage
wiring.
• No special considerations are required when the total external cable connection between the indoor
unit and outdoor unit(s) is less than 450 ft. (137m). A CANbus isolator is required for total external
cable connections greater than 450 ft. (137m) but less than 800 ft. (243m).
• All wiring must be sized and selected for insulation case per NEC and other applicable codes.
• Do not bend cables to less than four times the diameter of the cable.
• Do not deform cables when securing in bundles or when hanging them.
• Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights,
and electronics.
• Avoid stretching cables.
• Keep CANbus cables at least 12 inches (305mm) from high-voltage sources, including wiring.
37
Liebert® MC™ User Manual
Electrical Connections
Figure 4-2 CANbus communication and interlock connections
between a Liebert DSE, one premium Liebert MC and a Liebert EconoPhase
FACTORY WIRING BETWEEN
CONTROL BOARDS AND
TERMINAL STRIP.
ECONOPHASE
CONTROL BOARD
SINGLE CIRCUIT
(FACTORY SET)
ECONOPHASE
CONTROL BOARD
DUAL CIRCUIT
(FACTORY SET)
CIRCUIT ONE
CIRCUIT ONE
1
1
J6
J6
4
3
3
ON
ON
CAN SW6
CAN SW6
CIRCUIT TWO
1
NO SHIELD
CONNECTION
CANbus
ADDRESSING
SWITCH
J6
3
DETAIL 4
CAN CABLE CONNECT ION (B)
ECONOPHASE UNIT
ON
CAN
LAST DEVICE ON CANBUS
(IF PRESENT)
SW6
B
P80
ONE
CONDENSER
TB50
D58
L
CAN L
1
CAN H
J6
H
1
J6
B CANBUS COMMUNICATION CABLE
TB49
3
L
ON
ON
1
1
2
3
J4
3
INPUT
3
TB49
ONE CONDENSER
WITH ECONOPHASE
1
OUTPUT
1
2
3
P15
A
H
TB50
B
3
CAN
CAN SW6
SW6
BOOTPSWD SYS APP
A
1
2
3
1
2
3
CANbus
ADDRESSING
SWITCH
ON
CAN SW6
DETAIL 3
CAN CABLE CONNECT ION (A) (B)
3
SHIELD CONNECTION
B
A
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
70
71
230
F
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
CONDENSER
J6
REMOVE JUMPER
FOR DUAL CIRCUIT
HEAT REJECTION
F INTERLOCK WIRE
HEAT REJECTION INTERLOCK (F)
DETAIL 2
HEAT REJECTION INTERLOCK (F)
70 71 230
F
SHIELD CONNECTION
SH
49-1
49-3
COMMUNICATION
A CANBUS
CABLE
2
1
A
DETAIL 1 CAN CABLE CONNECTION (A)
FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP.
INDOOR DSE UNIT
DPN003284
Pg. 1 Rev. 1
CANbus Cable: A, B
Interlock Wire: F
See Section 4.2 for cable and wire requirements.
Liebert® MC™ User Manual
38
Electrical Connections
Figure 4-3 CANbus communications and interlock connections
between a Liebert DSE, two Liebert MC condensers and a Liebert EconoPhase
ECONOPHASE CONTROL
BOARD DUAL CIRCUIT
(FACTORY SET)
ECONOPHASE CONTROL
BOARD SINGLE CIRCUIT
(FACTORY SET)
CIRCUIT ONE
CIRCUIT ONE
1
1
FACTORY WIRING BETWEEN
CONTROL BOARDS AND
TERMINAL STRIP.
J6
J6
3
3
ON
4
ON
CAN
CAN
SW6
SW6
CIRCUIT TWO
1
J6
3
NO SHIELD
CONNECTION
CANbus
ADDRESSING
SWITCH
DETAIL 4
CAN CABLE CONNECTION (C)
ECONOPHASE UNIT
ON
TWO
CONDENSERS
TWO CONDENSERS
WITH ECONOPHASE
CONDENSER 2
CONDENSER 2
1
1
J6
J6
CONDENSER 2
CAN SW6
CONDENSER 1
3
J6
A (CONDENSER 1)
B (CONDENSER 2)
DETAIL 3
CAN CABLE CONNECTION
CONDENSER 1 (B) (A)
CONDENSER 2 (C) (B)
ON
F
1
2
3
3
ON
CAN SW6
HEAT REJECTION
INTERLOCK WIRE
CONDENSER 2
B
SH
SHIELD
CONNECTION
REMOVE
JUMPER
CONDENSER 1
A
1
2
3
J6
CAN SW6
SHIELD CONNECTION
B
CONDENSER 1
CANbus
ADDRESSING
SWITCH
3
3
(CONDENSER 1) B
(CONDENSER 2) C
J6
1
1
1
1
2
3
TB49
H
CAN SW6
L
TB49
ON
ON
CAN SW6
INPUT
C CANBUS
COMMUNICATION CABLE
H
CAN L
TB50
ON
CAN H
L
1
2
3
3
3
TB50
OUTPUT
LAST DEVICE ON CANBUS
(IF PRESENT)
CAN SW6
C
70
71
230
70
71
230
G
G
CONDENSER 1
SH
1
2
3
1
2
3
B G
3
HEAT REJECTION INTERLOCK
F
FACTORY WIRING BETWEEN
iCOM AND TERMINAL STRIP
SH
49-1
49-3
HEAT REJECTION INTERLOCK WIRE
A CANBUS COMMUNICATION CABLE
A
2
1
DETAIL 1 CAN CABLE CONNECTION (A)
70 71 230
F
DETAIL 2
HEAT REJECTION INTERLOCK (F)
INDOOR DSE UNIT
DPN002361
Pg. 1 Rev. 8
CANbus Cable: A, B, C
Interlock Wire: F, G
See Section 4.2 for cable and wire requirements.
39
Liebert® MC™ User Manual
Electrical Connections
Figure 4-4 CANbus communications and interlock connections between a Liebert DS
and Liebert MC condenser
B
P15
A
CAN L
TB50
CAN H
D58
J6
L
OUTPUT
1
2
3
1
TB50
1
H
3
J6 TERMINATION JUMPER
MUST BE SET TO PINS 1 AND 2.
TB49
J4
L
1
2
3
CANbus ADDRESSING SWITCH
1
1
2
3
3
TB49
INPUT
CONDENSER
H
P80
ON
3
J6
CAN
1
2
3
3
SW6
BOOTPSWD SYS APP
ON
CAN SW6
DETAIL 3
CAN CABLE CONNECTION (A)
A
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
F
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
SHIELD CONNECTION
REMOVE JUMPER
FOR DUAL CIRCUIT
70
71
230
F HEAT REJECTION INTERLOCK
HEAT REJECTION INTERLOCK (F)
A
DETAIL 2
HEAT REJECTION INTERLOCK (F)
CANbus CONNECTION
2
70 71 230
1
SHIELD CONNECTION
F
SH
49-1
49-3
A
INDOOR DS UNIT
DETAIL 1 CAN CABLE CONNECTION (A)
FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP.
CANbus Cable: A
Interlock Wire: F
See Section 4.2 for cable and wire requirements.
Liebert® MC™ User Manual
40
DPN003267
Rev. 1
Electrical Connections
Figure 4-5 CANbus communication and interlock connections between a Liebert CRV 600 mm (24 in.)
and a Liebert MC premium condenser
TB50
CAN H
CAN L
D58
CONDENSER
J6
L
1
2
3
J6 TERMINATION JUMPER
MUST BE SET TO PINS 1 AND 2.
P15
A
1
TB50
OUTPUT
B
H
P80
1
H
3
J4
TB49
1
2
3
L
INPUT
3
TB49
1
ON
3
J6
CANbus
ADDRESSING
SWITCH
CAN SW6
TB50
OUT P UT
1
2
3
CAN H
CAN L
TB49
INPUT
1
2
3
1
BOOTPSWDSYS APP
ON
CAN SW6
DETAIL1
CAN CABLE CONNECTION (A)
SHIELD CONNECTION
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
A
B
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
70
71
230
B
HEAT REJECTION INTERLOCK WIRE
A
CANBUS COMMUNICATION CABLE
HEAT REJECTION INTERLOCK (B)
P78
1
3
P78 TERMINATION JUMPER
FACTORY SET TO PINS 2 AND 3,
FIELD MUST REMOVE JUMPER
AND REPLACE ON PINS 1 AND 2.
SHIELDED CONNECTION
PARTIAL VIEW SHOWN FOR CLARITY
FACTORY WIRING BETWEEN
ICOM & TERMINAL STRIP
PARTIAL VIEW SHOWN FOR CLARITY
DPN002841
Pg. 1 Rev. 4
CANbus Cable: A
Interlock Wire: B
See Section 4.2 for cable and wire requirements.
41
Liebert® MC™ User Manual
Electrical Connections
Figure 4-6 CANbus communications and interlock connection between Liebert CRV 300 mm (12 in.)
and a Liebert MC premium condenser
CAN L
TB50
CAN H
D58
J6
L
1
2
3
P15
A
1
OUTPUT
B
H
P80
TB50
J6 TERMINATION JUMPER
MUST BE SET TO PINS 1 AND 2.
CONDENSER
1
H
3
TB49
J4
L
CANbus
ADDRESSING
SWITCH
1
1
2
3
3
TB49
INPUT
ON
3
J6
CAN SW6
1
2
3
1
2
3
1
BOOTPSWD SYS APP
ON
CAN SW6
DETAIL1
CAN CABLE CONNECTION (A)
SHIELD CONNECTION
A
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
A CANbus CABLE CONNECTION
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
B
70
71
230
B
HEAT REJECTION INTERLOCK
HEAT REJECTION INTERLOCK (B)
CRV300 INDOOR UNIT
SHIELD CONNECTION
PARTIAL VIEW SHOWN FOR CLARITY
P78
1
3
P78 TERMINATION JUMPER
FACTORY SET TO PINS 2 AND 3,
FIELD MUST REMOVE JUMPER
AND REPLACE ON PINS 1 AND 2.
FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP.
CANbus Cable: A
Interlock Wire: B
See Section 4.2 for cable and wire requirements.
Liebert® MC™ User Manual
42
DPN003036
Rev. 2
Electrical Connections
Figure 4-7 CANbus communication and interlock connection between Liebert PDX™
and a Liebert MC premium condenser
CAN L
TB50
CAN H
D58
J6
L
1
2
3
P15
A
1
OUTPUT
B
H
P80
TB50
J6 TERMINATION JUMPER
MUST BE SET TO PINS 1 AND 2.
CONDENSER
1
H
3
J4
TB49
1
2
3
CANbus
ADDRESSING
SWITCH
L
INPUT
3
TB49
1
ON
3
J6
CAN
SW6
1
1
2
3
1
2
3
BOOTPSWD SYS APP
ON
CAN SW6
DETAIL1
CAN CABLE CONNECTION (A)
SHIELD CONNECTION
A
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
B
A
B
HEAT REJECTION INTERLOCK WIRE
CANbus CABLE CONNECTION
70
71
230
HEAT REJECTION INTERLOCK (B)
INDOOR UNIT
58
58
59
49-3
82
SH
83
37-C
88
38-C
89
87-B
75
88-B
76
38
95
24
24
96
50
50
97
51
51
91
55
55
92
56
56
93
70
70
80
71
71
81
94
49-1
38
94
88-B
76
87-B
75
38-C
89
37-C
88
SH
83
49-3
82
49-1
59
95
96
97
91
92
93
80
81
PARTIAL VIEW SHOWN FOR CLARITY
DPN003266
Pg. 1 Rev. 1
CANbus Cable: A
Interlock Wire: B
See Section 4.2 for cable and wire requirements.
43
Liebert® MC™ User Manual
Electrical Connections
4.2.1
Electrical Field Connection Descriptions
Figure 4-8 Typical connections, Premium Efficiency Control
FAN2
Lee-Temp receiver tank (1 per circuit).
FAN1
NOTE: Heater pad voltage available for
FAN 2
120V/1 phase/60 Hz or 230V/1 phase/60Hz
150 or 300 Watt, varies by condenser.
Electrical connection box with cover.
(Cover removed for clarity.)
FAN 1
Electrical service connection. Pigtails in electric handy box
are factory wired to Lee-Temp heater pads for field connection
of separate continuous electric source, wire not by Liebert.
8
10
SH
12
9
13
70
71
230
DPN002169
Rev. 7
4.2.1.1
DPN002374
Rev. 6
Key Electrical Details—Typical Connections,
Premium Efficiency Control
Source: DPN002169, Rev. 7 and DPN002374, Rev. 6. The following numbered items correspond to the
callouts in Figure 4-8.
1. Three-Phase Electrical Service—Terminals are on the top of the disconnect switch for one-fan and
two-fan units. Terminals are on the bottom of the disconnect switch for three-fan and four-fan units.
Three-phase service not by Emerson. See NOTICE on page 37.
2. Earth Ground—Field lug terminal for earth ground connection. Ground terminal strip for fan motor
ground connection.
Liebert® MC™ User Manual
44
Electrical Connections
3. Primary High-Voltage Entrance—Two knockouts, each 7/8” (22.2mm) diameter, located at the
bottom of the enclosure.
4. SPD Field Connection Terminals—High-voltage surge protective device (SPD) terminals. SPD is an
optional device.
5. CANbus Terminal Connections—Field terminals for CANbus cable connection.
• 5A is the CANbus connectors
• TB49-1 is the input terminal for CANbus high.
• TB49-3 is the input terminal for CANbus low.
• TB50-1 is the output terminal for CANbus high.
• TB50-3 is the output terminal for CANbus low.
• Each CANbus cable shield is connected to terminal “SH;” see 9 below.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH.” CANbus cable not by Emerson. See
requirements in Notes on Electrical Connections on page 37.
6. Remote Unit Shutdown—Replace exiting jumper between Terminals TB38-1 and TB38-2 with fieldsupplied, normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1
wiring. (This is an optional feature.)
7. Alarm Terminal Connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common; TB74-2 is
normally open; and TB74-3 is normally closed. 1A 24VAC is the maximum load. Use field-supplied
Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power or when a critical alarm has
occurred that shuts down the condenser unit. TB74-4 is common; TB74-5 is normally open; and
TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied Class 1 wiring.
8. Indoor Unit Interlock and SPD Alarm Terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 and 71
for Circuit 1 and normally open contact is closed across Terminals 70 and 230 for Circuit 2 from
indoor unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 and 13. (SPD is an
optional device.)
9. CANbus Shield Terminal—Terminal for field shield connection of the CANbus field-supplied cables.
The shield of CANbus field-supplied cables must not be connected to ground at the condenser.
10. Primary Low-Voltage Entrance—One knockout, 7/8” (22.2mm) diameter, that is free for customer
low-voltage wiring.
11. SPD entrance—One knockout, 7/8” (22.2mm) diameter at the bottom of the enclosure. (High-voltage
surge protective device is optional.)
45
Liebert® MC™ User Manual
Electrical Connections
Page intentionally left blank.
Liebert® MC™ User Manual
46
Piping
5.0 Piping
! WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause equipment damage, injury
or death.
Relieve pressure before working with or cutting into piping.
! WARNING
Risk of refrigerant system rupture or explosion from overpressurization. Can cause equipment
damage, injury or death.
Local building and plumbing codes may require that a fusible plug or other type of pressure relief
device be installed in the system. Do not install a shutoff valve between the compressor and the
field-installed relief device.
Consult local building and plumbing codes for installation requirements of additional pressure relief
devices when isolation valves are installed as shown in Figure 5-1. Do not isolate any refrigerant
circuits from over-pressurization protection.
NOTE
POE (polyol ester) oil, required with R-407C/R-410A and used with some R-22 systems, is much
more hygroscopic than mineral oils. This means that POE oil absorbs water at a much faster rate
when exposed to air than previously used mineral oils. Because water is the enemy of a reliable
refrigeration system, extreme care must be used when opening systems during installation or
service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed
through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils
also have a property that makes them act as a solvent in a refrigeration system. Maintaining
system cleanliness is extremely important because the oil will tend to bring any foreign matter
back to the compressor or plug the microchannel coil. Always use a flow of dry nitrogen when
brazing.
5.1 Piping Guidelines
Indoor units and condensers both ship with holding charges of inert gas. Do not vent the condenser until all
refrigerant piping is in place, ready for connection to indoor unit and condenser.
• Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as SilFos. Avoid soft solders such as 50/50 or 95/5.
• Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide scale
inside the piping. When copper is heated in the presence of air, copper oxide forms. POE oil will
dissolve these oxides from inside the copper pipes and deposit them throughout the system, clogging
filter driers and affecting other system components.
• A pure dry nitrogen flow of 1-3 ft3/min (0.5-1.5 l/s) inside the pipe during brazing is sufficient to displace
the air. Control the flow using a suitable metering device.
• Ensure that the tubing surfaces to be brazed are clean and that the ends of the tubes have been
carefully reamed to remove any burrs.
• Ensure that all loose material has been cleaned from inside the tubing before brazing.
• Protect all refrigerant line components within 18" (460mm) of the brazing site by wrapping them with
wet cloth or suitable heat sink compound.
• Isolate piping from building using vibration isolating supports.
• Refer to the indoor unit’s user manual for appropriate piping sizes.
• Install traps on the hot gas (discharge) lines at the bottom of any rise over 5 feet high. If the rise
exceeds 25 feet (7.5m), then install a trap in 20 foot (6m) increments or evenly divided.
47
Liebert® MC™ User Manual
Piping
• Pitch horizontal hot gas piping down at a minimum rate of 1/2” per 10 ft. (42mm per 10m) so that
gravity will aid in moving oil in the direction of refrigerant/oil flow.
• Consult factory if Liebert Lee-Temp™ condenser is below the evaporator or if a condenser not
equipped with Liebert Lee-Temp is more than 15 ft (4.6m) below the evaporator.
• Consult factory if piping run exceeds 150 feet (46m) equivalent length on traditional R-407C DX units.
• Consult factory if piping run exceeds 300 feet (91m) equivalent length on traditional R-410A DX units.
• Consult factory if piping run exceeds 300 feet (91m) actual length or 450 feet (137m) equivalent length
on units installed with Liebert EconoPhase units.
• Keep piping clean and dry, especially on units with POE oil (R-407C, R-410A or R-22 refrigerant).
• Avoid piping runs through noise-sensitive areas.
• Do not run piping directly in front of indoor unit discharge air stream.
• Refrigerant oil – do not mix oil types or viscosities. Consult indoor unit for refrigerant type and oil
requirements.
NOTE
Failure to use compressor oils recommended by compressor manufacturer will void compressor
warranty. Consult Emerson or the compressor manufacturer for further recommendations or if you
have questions about compressor oils.
Refer to ASHRAE Refrigeration Handbook for general good practices for refrigeration piping. The
Liebert indoor cooling unit has a factory-installed high-pressure safety switch in the high side
refrigerant circuit. A pressure relief valve is provided with Liebert Lee-Temp™ receivers. A fusible
plug is factory installed in the Liebert DSE™ receivers. Consult local building codes to determine if
condensers without receivers will require field-provided pressure relief devices. A fusible plug kit is
available for field installation.
Liebert® MC™ User Manual
48
Piping
Figure 5-1 Piping schematic—DX systems
Check Valve
Relief Valve
Service
Valve
LIQUID RETURN
Head Pressure
Control Valve
LEE-TEMP RECEIVER
Check Valve
CONDENSER COIL
CONDENSER COIL
(Includes factory provided
inverted trap. No
external trap required)
(Includes factory provided
inverted trap. No
external trap required)
OPTIONAL FIELD INSTALLED
FUSIBLE PLUG
HOT GAS DISCHARGE
LEE-TEMP
LIQUID
Sensing
Bulb
EVAPORATOR
COIL
3
SUCTION
Service
Valve
Check
Valve
COMPRESSOR
Service
Valve
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided
Field installed relief valve(s) required
for 50Hz EU CE units.
External
Equalizer
3
4
Expansion Solenoid
Valve
Valve
Sight
Glass
HOT GAS DISCHARGE
LIQUID LINE
Filter Drier
3
3
REFRIGERANT PIPING
FIELD PIPING
Isolation
Valve
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
Isolation
Valve
Trap at base of risers
over 5ft. (1.5m)
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
Notes:
1. Single refirigeration circuit shown for clarity.
2. Schematic representation shown. Do not use for specific connection locations.
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor.
4. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
49
DPN002188
Rev. 4
Liebert® MC™ User Manual
Piping
Figure 5-2 Piping schematic—CRV 600 mm (24 in.) DX systems
LIEBERT MC CONDENSER
WITH LEE-TEMP RECEIVER
LIEBERT MC CONDENSER
Pressure
Transducer
Head Pressure
Control Valve
Optional Field
Installed Fusible
Plug
Pressure
Transducer
Liquid
Condenser Coil
Includes factory provided
inverted trap. No external
trap required.
Condenser Coil
Liquid
Includes factory provided
inverted trap. No external
trap required.
Hot Gas Discharge
Relief Valve
Service
Valve
Check Valve
Lee-Temp Receiver
Liquid Return
Hot Gas Discharge
Liebert CRV Unit and associated Piping
Filter
Drier
Sight
Glass
Expansion
Valve
Solenoid
Valve
Distributor
Evaporator Coil
Sensing
Bulb
External Equalizer
Service Valve
CR020 Digital
Solenoid Valve
* For rises over
25ft (7.6m), trap
every 20ft (6m)
or evenly divided.
High Pressure
Transducer
Vibration Absorber
High Pressure
Cut Out
Suction Line
Low Pressure Transducer
CR035 Digital
Solenoid Valve
Digital Scroll
Compressor
Service Valve
*Isolation Valve
Hot Gas Discharge
Check Valve
Vibration Absorber
Isolation Valve
*Isolation Valve
Liquid Return
FACTORY REFRIGERANT PIPING
FIELD PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTES:
1. SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
2. ONE OR MORE ADDITIONAL PRESSURE RELIEF VALVES ARE REQUIRED DOWNSTREAM OF ANY
AND ALL FIELD-INSTALLED ISOLATION. DO NOT ISOLATE ANY REFRIGERANT CIRCUITS FROM
OVERPRESSURIZATION PROTECTION.
Liebert® MC™ User Manual
50
* Components are not supplied by
Liebert but are recommended for
proper circuit operation and
maintenance. Should be located
near the indoor Liebert CRV unit.
DPN002858
Rev. 1
Piping
Figure 5-3 Piping schematic—CRV300 mm (12 in.) DX systems
LIEBERT MC CONDENSER
WITH LEE-TEMP RECEIVER
LIEBERT MC CONDENSER
Optional Field
Installed Fusible
Plug
Pressure
Transducer
Condenser Coil
Includes factory provided
inverted trap. No external
trap required.
Pressure
Transducer
Liquid
Head Pressure
Control Valve
Condenser Coil
Liquid
Includes factory provided
inverted trap. No external
trap required.
Hot Gas Discharge
Check Valve
Relief Valve
Service
Valve
Lee-Temp Receiver
Liquid Return
Hot Gas Discharge
LIEBERT CRV UNIT AND ASSOCIATED PIPING
Filter
Drier
Solenoid
Valve
Sight
Glass
Expansion
Valve
Distributor
Evaporator Coil
Sensing
Bulb
External Equalizer
CR019 Digital Solenoid Valve
High Pressure
Transducer
* For rises over
25ft (7.6m), trap
every 20ft (6m)
or evenly divided.
Low Pressure Transducer
Suction Line
Digital Scroll
Compressor
Check Valve
Hot Gas Discharge
*Isolation Valve
*Isolation Valve
Liquid Return
FACTORY REFRIGERANT PIPING
FIELD PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTES:
1. SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
2. ONE OR MORE ADDITIONAL PRESSURE RELIEF VALVES ARE REQUIRED DOWNSTREAM OF ANY
AND ALL FIELD-INSTALLED ISOLATION. DO NOT ISOLATE ANY REFRIGERANT CIRCUITS FROM
OVERPRESSURIZATION PROTECTION.
3. REFER TO OUTDOOR CONDENSER DOCUMENTS ABOVE FOR PROPER TRAP PLACEMENT.
51
* Components are not supplied by
Liebert but are required for
proper circuit operat ion and
maintenance. Isolation valves
should be located near the indoor
Liebert CRV unit.
DPN002808
Rev. 3
Liebert® MC™ User Manual
Piping
Figure 5-4 Piping schematic—DS DX systems
Check Valve
Relief Valve
Service
Valve
LIQUID RETURN
Head Pressure
Control Valve
LEE-TEMP RECEIVER
Check Valve
CONDENSER COIL
CONDENSER COIL
(Includes factory provided
inverted trap. No
external trap required)
(Includes factory provided
inverted trap. No
external trap required)
OPTIONAL FIELD INSTALLED
FUSIBLE PLUG
HOT GAS DISCHARGE
LEE-TEMP
LIQUID
Sensing
Bulb
28-42kW digital
Solenoid Valve
53-70kW digital
Solenoid Valve
Service
Valve
Check
Valve
COMPRESSOR
EVAPORATOR
COIL
3
SUCTION
Service
Valve
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided
Field installed relief valve(s) required
for 50Hz EU CE units.
External
Equalizer
3
5 Muffler
4
Expansion Solenoid
Sight
Valve
Glass
Valve
OPTIONAL FACTORY PIPING
HOT GAS DISCHARGE
LIQUID LINE
Filter Drier
3
3
REFRIGERANT PIPING
FIELD PIPING
Isolation
Valve
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
Isolation
Valve
Trap at base of risers
over 5ft. (1.5m)
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
Notes:
1. Single refirigeration circuit shown for clarity.
2. Schematic representation shown. Do not use for specific connection locations.
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor.
4. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
5. Component supplied by Liebert and must be field installed on units with semi-hermetic compressors (70kW, 77kW, & 105kW models only).
Liebert® MC™ User Manual
52
DPN003730
Rev. 0
Piping
Figure 5-5 Piping schematic—Liebert DSE™, air-cooled DA050, DA080 and DA085 models
Differential
Check Valve
1-3/8" Liquid from Condenser
see note 2.
LIEBERT MC CONDENSER
Optional "EconoPhase" UNIT
Check
Valve
LIEBERT DSE
RECEIVER
7/8" Liquid to Indoor Unit
see note 2.
Solenoid
Valve
Ball
Valve
HOT GAS DISCHARGE
Ball
Valve
1-1/8" Hot Gas Discharge
from Indoor Unit
see note 2.
Includes Factory traps.
No external trap required.
DA050, DA080, & DA085
Differential
Check Valve
LIQUID
EVAPORATOR
COIL
Service
Valve
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided*
SUCTION
Check
Valve
Field installed relief valves
required for 50Hz EU CE
units rated maximum
650 PSIG (45 bar)
Trap at base
of risers
over 5ft. (1.5m)*
*Full Ported
Ball Valve
See note 4.
Service
Valve
Check
Valve
HOT GAS DISCHARGE
see note 2.
LIQUID RETURN
Electronic
Expansion
see note 2.
Valve
REFRIGERANT PIPING
FIELD PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE.
*Full Ported
Ball Valve
See note 4.
Differential
Check Valve
(Required)
SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE.
1. Two refrigeration circuits provided on DA080 & DA085. Single refrigeration circuit provided on DA050.
Single refrigeration circuit shown for clarity.
* Components are not supplied by
2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit.
Liebert but are required for
Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit.
proper circuit operation and
3. Schematic representation shown. Do not use for specific connection locations.
4. Port in ball must be the same diameter as the piping I.D.
maintenance.
5. Length of piping between condenser and indoor unit shall be no greater than
300 ft (91.4 m) [Maximum equivalent length of 450 ft (137.2 m)].
6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m).
7. All indoor and outdoor field refrigerant piping must be insulated,
1/2" minimum thickness. All outdoor insulation must be UV and ozone resistant.
53
DPN002615
Rev. 5
Liebert® MC™ User Manual
Piping
Figure 5-6 Piping schematic—Liebert DSE™, air-cooled DA125, DA150 and DA165 models
Differential
Check Valve
Check
Valve
1-3/8" Liquid from Condenser
see note 2.
LIEBERT MC CONDENSER
Differential
Check Valve
Optional "EconoPhase" UNIT
DA125 - 7/8"
DA150/165 - 7/8" or 1-1/8"
Liquid to Indoor Unit
(Depending on length of line)
see note 2.
LIEBERT DSE
RECEIVER
Ball Valve
Solenoid Ball Valve
Valve
HOT GAS DISCHARGE
1-3/8" Hot Gas Discharge from Indoor Unit
see note 2.
Includes Factory traps.
No external trap required.
DA125 & DA150
LIQUID
EVAPORATOR
COIL
Service
Valve
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided*
SUCTION
Field installed relief valves
required for 50Hz EU CE
units rated maximum
650 PSIG (45 bar)
Check
Valve
Trap at base of risers
over 5ft. (1.5m)*
*Full Ported
Ball Valve
See note 4.
Service
Valve
Check
Valve
HOT GAS DISCHARGE
see note 2.
LIQUID RETURN
see note 2.
Electronic
Expansion
Valve
REFRIGERANT PIPING
FIELD PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE.
SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE.
1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit.
Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit.
3. Schematic representation shown. Do not use for specific connection locations.
4. Port in ball must be the same diameter as the piping I.D.
5. Length of piping between condenser and indoor unit shall be no greater than
300 ft (91.4 m) [Maximum equivalent length of 450 ft (137.2 m)].
6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m).
7. All indoor and outdoor field refrigerant piping must be insulated,
1/2" minimum thickness. All outdoor insulation must be UV and ozone resistant.
Liebert® MC™ User Manual
54
*Full Ported
Ball Valve
See note 4.
Differential
Check Valve
(Required)
* Components are not supplied by
Liebert but are required for
proper circuit operation and
maintenance.
DPN002340
Rev. 8
Piping
5.2 Field Piping Guidelines
One discharge line and one liquid line must be field-installed for each circuit of the indoor unit and the
outdoor condenser(s). Dual circuit condensers are available for most dual circuit indoor unit applications.
Refer to Figures 5-1 through 5-8 for additional field-installed piping needed at the condenser. This piping
is needed for proper system performance and for installation/interconnecting receivers and head pressure
control valves for Liebert Lee-Temp™ systems.
NOTE
Keep the evaporator unit and condenser closed with their factory charge of inert gas while all field
piping is installed. Keep the field piping clean and dry during installation, and do not allow it to
stand open to the atmosphere.
When all the field interconnecting piping is in place, vent the condenser’s inert gas charge and
connect to the field piping. Finally, vent the evaporator unit’s charge of inert gas and make its
piping connection last.
Follow all proper brazing practices, including a dry nitrogen purge to maintain system cleanliness.
The condenser connection pipes must be wrapped with a wet cloth to keep the pressure and
temperature sensors cool during any brazing.
55
Liebert® MC™ User Manual
Piping
5.2.1
Field Piping Guidelines
for a Liebert DX System and Liebert MC Condenser
Figure 5-7 Liebert MC Condenser piping—Single-circuit, 1-, 2-, 3- and 4-fan units
COVER*
LEAVING LIQUID
LINE
INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER
ENTERING HOT
GAS LINE
FIELD PIPING
VERTICAL
OPTIONAL FUSIBLE PLUG SERVICE KIT TO BE BRAZED INTO THE LIQUID LINE(S) IN
EITHER THE VERTICAL OR HORIZONTAL POSITION. (WHERE REQUIRED)
HORIZONTAL
HORIZONTAL
DETAIL A
(VERTICAL POSITION IS PREFERRED, HORIZONTAL POSITION IS OPTIONAL.)
VERTICAL
LEAVING LIQUID
LINE
MCS028 ONLY
ENTERING HOT GAS LINE
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
Table 5-1
DPN002166
Rev. 3
Liebert MC Condenser piping sizes—Single-circuit units
Model No.
Number
of Fans
Condenser
Circuits
Connection Sizes, OD, in (mm)
Hot Gas Line
Liquid Line
MCS028
1
1
7/8
5/8
MCM040
1
1
7/8
5/8
MCM080
2
1
1-1/8
7/8
MCL055
1
1
1-1/8
7/8
MCL110
2
1
1-3/8
1-1/8
MCL165
3
1
1-3/8
1-1/8
MCL220
4
1
1-5/8
1-3/8
Source: DPN002166, Rev. 3
Liebert® MC™ User Manual
56
Piping
Figure 5-8 Condenser piping for single-circuit condensers (with Liebert Lee-Temp™)
HOT GAS LINE
TO CONDENSER
ENTERING HOT
GAS LINE
COVER *
B VIEW
METAL CLAMP
POSITION ELBOW TO
DIRECT RELIEF VALVE
DOWNWARD
ISOLATOR
FASTEN HOT GAS LINE TO CABINET
USING FLAT SURFACE CLAMPS WITH
ISOLATORS(FIELD SUPPLIED)
SEE DETAIL A-A
B VIEW
DETAIL A
FIELD PIPING
LIQUID LINE
FROM CONDENSER
LEAVING
LIQUID LINE
GENERAL ARRANGEMENT
LIEBERT SUPPLIED PIPING ASSEMBLY
WILL INCLUDE 1 TO 3 HEAD PRESSURE
VALVES AND CHECK VALVES DEPENDENT
ON CONDENSER CAPACITY AND REFRIGERANT.
NOTE:
1.THE FOLLOWING MATERIALS ARE SUPPLIED BY LIEBERT,SHIPPED LOOSE FOR EACH CIRCUIT AND FOR FIELD INSTALLATION:
INSULATED LEE-TEMP RECEIVER TANK WITH ELECTRIC HEATER PADS AND SIGHT GLASSES, PIPING ASSEMBLY WITH HEAD PRESSURE
CONTROL VALVE AND CHECK VALVE, ROTO-LOCK VALVE AND PRESSURE RELIEF VALVE. ALL OTHER PIPING AND ELECTRICAL WIRING
TO BE SUPPLIED AND INSTALLED BY OTHERS. ADDITIONAL CONDENSER LEG PER CIRCUIT WHEN REQUIRED, SHIPS WITH THE CONDENSER.
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
Table 5-2
DPN002167
Rev. 6
Condenser piping connection sizes—Single-circuit condensers with Liebert Lee-Temp
Condenser
Connections, OD, In
Liebert Lee-Temp Connections
Model #
Hot Gas
Liquid
Hot Gas Tee
IDS, In.
MCS028
7/8
5/8
7/8
Liquid Line
to Liebert Lee-Temp
Valve, ODS, In.
Receiver Out
Rotalock, IDS, In.
5/8
5/8
MCM040
7/8
5/8
7/8
5/8
5/8
MCM080
1-1/8
7/8
1-1/8
7/8
1-1/8
MCL055
1-1/8
7/8
1-1/8
7/8
7/8
MCL110
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
MCL165
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
MCL220
1-5/8
1-3/8
1-5/8
1-3/8
1-3/8
Source: DPN002167, Rev. 6
57
Liebert® MC™ User Manual
Piping
Figure 5-9 Piping: dimensions—Dual circuit two-fan and four-fan units
COVER *
VERTICAL
INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER
FIELD PIPING
LEAVING LIQUID
LINE
HORIZONTAL
ENTERING HOT
GAS LINE
DETAIL A
CIRCUIT #1
CIRCUIT #2
OPTIONAL FUSIBLE PLUG SERVICE KIT TO
BE BRAZED INTO THE LIQUID LINE(S) IN
EITHER THE VERTICAL OR HORIZONTAL
POSITION (WHERE REQUIRED).
(VERTICAL POSITION IS PREFERRED,
HORIZONTAL POSITION IS OPTIONAL.)
FOR TWO CIRCUIT SYSTEMS, ONE
FUSIBLE PLUG KIT WILL NEED TO
BE INSTALLED IN EACH CIRCUIT.
A
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
Table 5-3
Piping: dimensions—Dual-circuit, two-fan and four-fan units
Model #
Condenser
Circuits
Hot Gas Line
MCS056
2
2
7/8
5/8
MCM080
2
2
7/8
5/8
Liquid Line
MCL110
2
2
1-1/8
7/8
MCM160
4
2
1-1/8
7/8
MCL220
4
2
1-3/8
1-1/8
Source: DPN002425, Rev. 5
Liebert® MC™ User Manual
Connection Sizes, OD, in
# of
Fans
58
DPN002425
Rev. 5
Piping
Figure 5-10 Piping: Dimensions with Liebert Lee-Temp™—Dual circuit condensers
METAL CLAMP
HOT GAS LINE
TO CONDENSER
ENTERING HOT
GAS LINE
ISOLATOR
DETAIL A-A
FIELD PIPING
C VIEW
B VIEW
COVER*
* SHIPPING COVER IS NOT NECESSARY FOR PROPER
CONDENSER OPERATION AND MAY BE RECYCLED IF FIELD
PIPING INTERFERES WITH PROPER REATTACHMENT.
POSITION ELBOW TO
DIRECT RELIEF VALVE
DOWNWARD
LEAVING
LIQUID LINE
B VIEW
LIQUID LINE
FROM CONDENSER
FASTEN HOT GAS LINE TO CABINET
USING FLAT SURFACE CLAMPS WITH
ISOLATORS(FIELD SUPPLIED)
SEE DETAIL A-A
HOT GAS LINE
TO CONDENSER
GENERAL ARRANGEMENT
LIEBERT SUPPLIED PIPING ASSEMBLY
WILL INCLUDE 1 OR 2 VALVE AND CHECK
VALVES DEPENDENT ON CONDENSER
CAPACITY AND REFRIGERANT
ENTERING HOT
GAS LINE
C VIEW
LIQUID LINE
FROM CONDENSER
POSITION ELBOW TO
DIRECT RELIEF VALVE
DOWNWARD
LEAVING
LIQUID LINE
NOTE:
1. THE FOLLOWING MATERIALS ARE SUPPLIED BY LIEBERT, SHIPPED LOOSE FOR EACH CIRCUIT, AND FOR FIELD INSTALLATION:
INSULATED LIEBERT LEE-TEMP RECEIVER TANK WITH ELECTRIC HEATER PADS AND SIGHT GLASSES, PIPING ASSEMBLY WITH HEAD
PRESSURE CONTROL VALVE AND CHECK VALVE, ROTO-LOCK VALVE AND PRESSURE RELIEF VALVE.
ALL OTHER PIPING AND ELECTRICAL WIRING TO BE SUPPLIED AND INSTALLED BY OTHERS. AN ADDITIONAL CONDENSER LEG PER
CIRCUIT TO BE SHIPPED WITH THE CONDENSER.
2.FOR RUNS LONGER THAN 150FT.(45.7M)EQUIV. LENGTH, CONSULT FACTORY FOR PROPER LINE SIZING.
Table 5-4
Condenser piping connection sizes—Dual-circuit condensers with Liebert Lee-Temp
Condenser Connections, OD.In
Model #
DPN002426
Rev. 6
Condenser
Circuits
Hot Gas
Liquid
Liebert Lee-Temp Connections
Hot Gas Tee
IDS In.
Liquid Line
to Lee-Temp Valve
ODS, In.
Receiver Out
Rotalock
IDS In.
MCS056
2
7/8
5/8
7/8
5/8
5/8
MCM080
2
7/8
5/8
7/8
5/8
5/8
MCL110
2
1-1/8
7/8
1-1/8
7/8
78
MCL160
2
1-1/8
7/8
1-1/8
7/8
1-1/8
MCL220
2
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
Source: DPN002426, Rev. 6
59
Liebert® MC™ User Manual
Piping
5.2.2
Field Piping Guidelines
for a Liebert DSE and Liebert Premium MC Condenser
Figure 5-11 Condenser and Liebert EconoPhase™, typical unit arrangement diagram layout
for dual-circuit system
TOP VIEW
CIRCUIT 1
CIRCUIT 2
Air Cooled Condenser
Entering Hot Gas Line
CIRCUIT 1
42"
1067mm
Minimum
Clearance
Air Cooled Condenser
LIQUID LINE
TO ECONOPHASE
UNIT FROM BOTTOM
OF RECEIVER
Entering Hot Gas Line
CIRCUIT 2
TOP VIEW
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2 in. per 10 ft.) down towards
EconoPhase unit.
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2 in. per 10 ft.) down towards
EconoPhase unit.
EconoPhase Unit
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2" per 10') down towards
EconoPhase unit.
CIRCUIT 1
CIRCUIT 2
60"
1524mm
60" leg height
Typical, see note 1.
FACTORY SUPPLIED, FIELD INSTALLED
FIELD PIPING
Notes:
1. For proper pump function, a minimum elevation difference of 60” (1524 mm)
must be maintained between the bottom of condenser box to the bottom
of EconoPhase unit.
2. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum.
All outdoor insulation must be UV and ozone resistant.
Liebert® MC™ User Manual
* Components are not supplied by
Liebert but are required
for proper circuit operation and
maintenance.
* * Components supplied by
Liebert and must be
DPN002324
field installed.
Rev. 7
60
Piping
Figure 5-12 Condenser and Liebert EconoPhase™, typical unit arrangement diagram layout
for single-circuit system
TOP VIEW
Air Cooled Condenser
Entering Hot Gas Line
42"
1067mm
Minimum
Clearance
TOP VIEW
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2 in. per 10 ft.) down towards
EconoPhase unit.
EconoPhase Unit
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2" per 10') down towards
EconoPhase unit.
60"
1524mm
60" leg height
Typical, see note 1.
EconoPhase Unit
FACTORY SUPPLIED, FIELD INSTALLED
FIELD PIPING
Notes:
1. For proper pump function, a minimum elevation difference of 60” (1524 mm)
must be maintained between the bottom of condenser box to the bottom
of EconoPhase unit.
2. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum.
All outdoor insulation must be UV and ozone resistant.
61
* Components are not supplied by
Liebert but are required
for proper circuit operation and
maintenance.
DPN003552
Rev. 0
Liebert® MC™ User Manual
Piping
Figure 5-13 Typical receiver Liebert DSE mounting, MCL110, MCL165 and MCL220 single-circuit
condenser, left-side condenser outlet receiver
RECEIVER MOUNTING HOLES
SINGLE CIRCUIT.
TYP. (4) PLACES 4 3 2
1
DETAIL A
TRIM PIPING
AS NEEDED
A
16 15
3
1
7
14
4
8
13 12
2
11 1/8"
282.6mm
3
4
36"
914mm
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
64 3/4"
1645mm
CROSS BRACING
NOT SHOWN
NOTES:
1. USE ITEMS 15 AND 16 AS NEEDED
FOR MOUNTING OF ITEM 1.
2. ITEM 12 TO BE USED ON MCL110 & MCL165 UNITS.
ITEM 13 TO BE USED ON MCL220 UNITS.
3. SMALL RECEIVER SHOWN. ACTUAL RECEIVER SIZE
MAY VARY.
4. RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS AND
NEEDS TO BE ANCHORED WITH THEM.
Item No.
DPN002554
Pg. 1 Rev. 7
Description
Qty
1
Receiver and Bracket Assembly
1
2
Cap Screw HXDIN933M8-1.25X25A2
8
3
Fender Washer DIN9021 M8X24 A2
12
4
Lock Nut Hex NYL INSR M8
8
7
90° Elbow FTGXFTG 7/8” Copper
1
8
Copper Formed Tube 1-1/8”
1
12
Coupling Copper 1-1/8”
1
13
Reducer Copper CXC 1-3/8”x1-1/8”
1
14
Reducer Copper CXC 1-1/8”x7/8”
1
15
Support Leg
1
16
Fastener Assembly: Cap Screw, Lock Washer, Fender Washer
4
Liebert® MC™ User Manual
62
Piping
Figure 5-14 Typical receiver Liebert DSE mounting, MCL110, MCL165 and MCL220 single-circuit
condenser, right-side condenser outlet receiver
RECEIVER MOUNTING HOLES
SINGLE CIRCUIT.
TRIM PIPING
AS NEEDED
2
12 13
8
2 3 4 TYP. (4) PLACES
B
1
7
3
15 16
1
DETAIL B
4
14
9
5 6
11 1/8"
282.6mm
64 3/4"
1645mm
36"
914mm
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
3
4
NOTES:
1. USE ITEMS 15 AND 16 AS NEEDED
FOR MOUNTING OF ITEM 1.
CROSS BRACING
NOT SHOWN
2. ITEM 12 TO BE USED ON MCL110 & MCL165 UNITS.
ITEM 13 TO BE USED ON MCL220 UNITS.
3. SMALL RECEIVER SHOWN. ACTUAL RECEIVER SIZE
MAY VARY.
4. RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS AND
NEEDS TO BE ANCHORED WITH THEM.
Item No.
1
2
3
4
5
6
7
8
9
12
13
14
15
16
DPN002554
Pg. 2 Rev. 7
Description
Qty
Receiver and Bracket Assembly
Cap Screw HXDIN933M8-1.25X25A2
Fender Washer DIN9021 M8X24 A2
Lock Nut Hex NYL INSR M8
Clamp Omega 7/8”
Screw SD HWH YZ 10-16 x 5/8
90° Elbow FTGXFTG 7/8” CU
Copper Formed Tube 1-1/8”
Copper Formed Tube 1-1/8”
Coupling Copper 1-1/8”
Reducer Copper CXC 1-3/8”x1-1/8”
Reducer Copper CXC 1-1/8”x7/8”
Support Leg
Fastener Assembly: Cap Screw, Lock Washer, Fender Washer
1
8
12
8
7
2
1
1
2
1
1
2
1
4
63
Liebert® MC™ User Manual
Piping
Figure 5-15 Typical receiver Liebert DSE mounting, MCL110 and MCL220 dual-circuit condenser,
two outlet receivers
C
4 3 2
TYP (4) PLACES
5
1
16 15
3
19 20
D
1
12 14
7
14
8
19 20
CIRCUIT 2
CIRCUIT 1
18
2
8
TRIM PIPING
AS NEEDED
4
18
DETAIL C
8
12 14
2
RECEIVER MOUNTING HOLES
DUAL CIRCUIT (CIRCUIT 2 ONLY).
TRIM PIPING
AS NEEDED
DETAIL D
2 3 4
TYP (4) PLACES
8
8
15 16
1
11 1/8"
283mm
5 6
74 1/16"
1881mm
36"
914mm
5
14
9
NOTES:
1. USE ITEMS 15 AND 16 AS NEEDED
FOR MOUNTING OF ITEM 1.
TYP
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS
CROSS BRACING
NOT SHOWN
3
1
7
2. ITEM 14 TO BE USED ON MCL110 UNITS.
ITEM 12 TO BE USED ON MCL220 UNITS.
3. SMALL RECEIVER SHOWN. ACTUAL RECEIVER SIZE
MAY VARY.
4. ITEM 20 TO BE USED ON MCL110 UNITS.
ITEM 19 TO BE USED ON MCL220 UNITS.
5. RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS AND
NEEDS TO BE ANCHORED WITH THEM.
Item No.
1
2
3
4
5
6
7
8
9
12
14
15
16
18
19
20
Liebert® MC™ User Manual
Description
Receiver and Bracket Assembly
Cap Screw HXDIN933M8-1.25X25A2
Fender Washer DIN9021 M8X24 A2
Lock Nut Hex NYL INSR M8
Clamp Omega 7/8”
Screw SD HWH YZ 10-16 x 5/8
90° Elbow FTGXFTG 7/8” Copper
Copper Formed Tube 1-1/8”
Copper Formed Tube 1-1/8”
Coupling Copper 1-1/8”
Reducer Copper CXC 1-1/8”x7/8”
Support Leg
Fastener Assembly: Cap Screw, Lock Washer, Fender Washer
Copper Tube 1-1/8” Swaged
90° Elbow CXC 1-1/8” Copper
90° Elbow CXC 1-1/8”X7/8” Copper
64
DPN002554
Pg. 3 Rev. 7
Qty
2
12
20
12
1
2
2
2
1
1
3
2
8
1
1
1
Piping
Figure 5-16 Typical receiver Liebert DSE mounting, MCM160 dual-circuit condenser, two outlet receivers
7
4
3
CIRCUIT 2
CIRCUIT 1
2
TYP (4) PLACES
2
TRIM PIPING
AS NEEDED
A
12
DETAIL A
8
16 15
1
12
1
7
8
7
8
TRIM PIPING
AS NEEDED
2
3
4
TYP (4) PLACES
8
15 16
8
11.13"
282.6mm
7
1
64.63"
1641.7mm
36.00"
914.4mm TYP
CLEARANCE REQUIRED FOR
VIEWING SIGHT GLASS.
9
6
2
NOTES
1. SMALL RECEIVER SHOWN. ACTUAL RECEIVER
SIZE MAY VARY.
2. RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS
AND NEEDS TO BE ANCHORED WITH THEM.
CROSS BRACING
NOT SHOWN
Item No.
5
1
Description
DPN002383
Rev. 7
Qty
1
Receiver and Bracket Assembly
2
2
Cap Screw HXDIN933M8-1.25X25A2
12
3
Fender Washer DIN9021 M8X24 A2
20
4
Lock Nut Hex NYL INSR M8
12
5
Clamp Omega 7/8”
1
6
Screw SD HWH YZ 10-16 x 5/8
2
7
90° Elbow FTGXC 7/8” Copper
3
8
Copper Formed Tube 7/8”
2
9
Copper Formed Tube 7/8”
1
12
Copper Tube 7/8” Swaged
1
15
Support Leg
1
16
Fastener Assembly: Cap Screw, Lock Washer, Fender Washer
4
65
Liebert® MC™ User Manual
Piping
5.3 Refrigerant Planning Values
Planning for the refrigerant requirements of the completed system is the total of the charges from Indoor
Unit, Condenser (including Liebert Lee-Temp™ receiver, if used) and the interconnecting piping. Tables 55, 5-6, 5-8 and 5-9 provide the approximate charge required for the condensers, recommended refrigerant
pipe sizes and the interconnecting piping. Consult indoor unit manuals for indoor unit charge requirements.
These values can be used for obtaining adequate refrigerant for the system, but should not be used for
final charging.
NOTE
Due to the much smaller coil volume, the performance, especially subcooling, of a Liebert MC
condenser is quite sensitive to the amount of refrigerant charge. Ensure that an accurate amount
of refrigerant charge is added.
Table 5-5
Condenser Models
Refrigerant required, R-407C, approximate
Single Circuit, lb/circuit (kg/circuit)
Dual Circuit, lb/circuit (kg/circuit)
Approximate
R-407C
Refrigerant Needed
Condensers without
Liebert Lee-Temp
Condensers with
Liebert Lee-Temp
MCS028
2.2 (1.0)
23.1 (10.5)
—
—
MCS056
N/A
N/A
2.2 (1.0)
23.1 (10.5)
Condensers without
Liebert Lee-Temp
Condensers with
Liebert Lee-Temp
MCM040
3.0 (1.4)
23.9 (10.8)
N/A
N/A
MCM080
7.5 (3.4)
44.5 (20.2)
3.0 (1.4)
23.9 (10.8)
MCM160
—
—
7.5 (3.4)
44.5 (20.2)
MCL055
5.0 (2.3)
25.9 (11.7)
—
—
MCL110
10.5 (4.8)
52.1 (23.7)
5.1 (2.3)
26.0 (11.8)
MCL165
18.3 (8.3)
84.8 (38.5)
—
—
MCL220
27.0 (12.3)
108.9 (49.4)
12.2 (5.6)
53.8 (24.4)
Source: DPN002411, Rev. 7
Table 5-6
Refrigerant required, R-410A, approximate
Single Circuit, lb/circuit (kg/circuit)
Condenser
Models
Condensers
w/o Liebert
Lee-Temp
Condensers
with Liebert
Lee-Temp
MCS028
2.5 (1.2)
21.7 (9.8)
Dual Circuit, lb/circuit (kg/circuit)
Condensers
with
Condensers
Liebert DSE
Small Receiver/ w/o Liebert Condensers with
Large Receiver 1 Lee-Temp Liebert Lee-Temp
Condensers
with
Liebert DSE
Small Receiver/
Large Receiver 1
—
—
—
—
MCS056
—
—
—
2.5 (1.2)
21.7 (9.8)
—
MCM040
3.5 (1.6)
22.7 (10.3)
—
—
—
—
MCM080
8.5 (3.8)
39.8 (18.1)
17.0 (7.7)
3.5 (1.6)
22.7 (10.3)
—
MCM160
—
—
—
8.5 (3.8)
39.8 (18.1)
17 (7.7) / 24 (10.9)
MCL055
5.0 (2.3)
24.2 (11.0)
—
—
—
—
MCL110
10.7 (4.9)
49.1 (22.3)
19.2 (8.7)
5.2 (2.4)
24.4 (11.1)
13.7 (6.2)
MCL165
18.4 (8.4)
79.9 (36.2)
26.9 (12.2)/
33.9 (15.4)
—
—
—
MCL220
27.0 (12.3)
102.9 (46.7)
42.5 (19.3)
12.3 (5.6)
50.7 (23.0)
20.8 (9.4) / 27.8 (12.6)
1. Small receiver is used with DA050, DA080 and DA085; large receiver is used with DA125, DA150 and DA165.
2. Source: DPN002411, Rev. 7
Liebert® MC™ User Manual
66
Piping
5.3.1
Recommended Refrigerant Line Sizes
Table 5-7
Recommended Refrigerant Line Sizes, OD Cu
System Fluid : R-410A
Model
CR019RA/
CR020RA
CR035RA
PX011
50 ft (15m)
100 ft (30m)
150 ft (45m)
300 ft (91m)
450ft (137m)
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
3/4
5/8
7/8
3/4
3/4
5/8
7/8
3/4
3/4
5/8
7/8
3/4
7/8
3/4
1-1/81
7/8
—
—
—
—
Hot Gas Line
1/2
5/81
1/2
5/8
1/2
3/4
5/8
7/8
5/8
1-1/8
7/8
1-3/8
7/8
1-3/8
5/81
1/2
5/8
1/2
3/4
5/8
7/8
5/8
1-1/8
7/8
1-3/8
7/8
1-3/8
5/81
—
1-1/82
1-3/8
1-1/82
1-3/8
1-1/82
1-1/82
Liquid Line
Hot Gas Line
PX018
Liquid Line
Hot Gas Line
PX023
Liquid Line
Hot Gas Line
PX029
Liquid Line
DA050/ DA080/ Hot Gas Line
DA085
Liquid Line
Hot Gas Line
DA125
Liquid Line
Hot Gas Line
DA150
Liquid Line
Hot Gas Line
DA165
Liquid Line
System Fluid : R-407C
Model
DS028
DS035
DS042
DS053
DS070
DS0773
DS1053
Standard and Digital Scroll Models
Equivalent
Length, in.
3/8
5/8
1/2
3/4
5/8
7/8
5/8
1-1/8
7/8
1-3/8
7/8
1-3/8
7/8
1-3/8
7/8
Standard Scroll Models (Non-Digital Scroll)
1
1/2
—
—
—
1
—
7/8
5/8
—
—
1-1/81
3/4
—
1-1/8
1-1/8
7/8
7/8
1-3/8
1-3/8
7/8
7/8
1-3/8
1-3/8
1-1/8
1-1/8
1-3/8
1-3/8
1-1/8
1-1/8
4-Step Semi-Hermetic
or Digital Scroll Models
3/41
5/8
Equivalent
Length, in.
50 ft (15m)
100 ft (30m)
150 ft (45m)
50 ft (15m)
100 ft (30m)
150 ft (45 m)
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
7/8
1/2
7/8
1/2
7/8
1/2
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-3/8
7/8
7/8
5/8
7/8
5/8
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
1-3/8
7/8
7/8
5/8
7/8
5/8
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
1-3/8
1-1/8
3/4
1/2
3/4
1/2
7/8
5/8
7/8
7/8
3/4
5/8
7/8
5/8
7/8
5/8
7/8
5/8
7/8
5/8
1-1/81
5/8
1-1/81
7/8
1-1/81
7/8
1-1/81
7/8
1-1/8
7/8
1-3/8
7/8
1-1/81
7/8
1-1/8
7/8
1-3/8
7/8
1-1/81
7/8
1-1/8
7/8
1-3/8
1-1/8
Consult factory for proper line sizing for R-410A DX-only system-piping runs longer than 300 ft. (91.4 m), R410A Liebert DSE system piping runs
longer than 450 ft. (137 m), or R407-C runs longer than 150 ft. (45.7 m) equivalent length.
1. Downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 5/8” to 1/2”).
2. When the vertical elevation between the indoor DA150/165 unit exceeds 25 ft., the liquid-line pipe diameter can be 7/8”.
3. Digital scroll not available on 077 and 105 models.
67
Liebert® MC™ User Manual
Piping
Table 5-8
Interconnecting piping refrigerant charge for self-contained DX units with remote condenser
R-407C, lb/100ft. (kg/30m)
R-410A, lb/100ft. (kg/30m)
Line Size
O.D., in.
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
3/8
—
3.6 (1.6)
—
3.2 (1.4)
1/2
0.5 (0.2)
6.7 (3.0)
0.7 (0.3)
5.9 (2.7)
5/8
0.8 (0.4)
10.8 (4.8)
1.1 (0.5)
9.6 (4.3)
3/4
1.2 (0.5)
16.1 (7.2)
1.6 (0.7)
14.3 (6.4)
7/8
1.7 (0.8)
22.3 (10.0)
2.3 (1.0)
19.8 (8.8)
1-1/8
2.9 (1.3)
38.0 (17.0)
3.9 (1.7)
33.8 (15.1)
1-3/8
4.4 (2.0)
57.9 (25.9)
5.9 (2.6)
51.5 (23.0)
1-5/8
6.2 (2.8)
—
8.4 (3.7)
—
1. Data based on 50°F Evap 15°F superheat 125°F SCT 10°F subcooling
2. Source: DPN003099, Rev. 0
5.4 Equipment Application Guidelines
Pump-down must be disabled on the indoor unit when using the Liebert MC condenser, due to the reduced
volume in the condenser coil.
Emerson® recommends adding a discharge line check valve and crankcase heater when connecting the
Liebert MC condenser to Liebert indoor units built before 2012. The check valve and crankcase heater are
needed for compressor protection. Additional liquid line Schrader ports are required at the indoor unit to
properly charge systems with Liebert MC condensers.
5.5 Refrigerant Oil Addition Procedures
Consult the user manual for the indoor unit to determine whether additional oil is required for each circuit.
Factors such as compressor, condenser type, piping lengths, receiver and total circuit refrigerant charge
influence this requirement.
5.6 System Dehydration/Leak Test
Procedures for leak check and evacuation of the entire refrigeration system are contained in the indoor
unit’s installation manual. Use the proper manual section corresponding to the winter control system used
on the condenser (with or without Liebert Lee-Temp™ or Liebert DSE™ receivers) and the refrigerant to be
charged into the system.
5.7 System Charging with Liebert MC
5.7.1
Liebert MC Charging, Units with Liebert Lee-Temp™ Receivers
Consult the indoor unit’s manual for charging systems with Liebert Lee-Temp receivers. These procedures
will be identical to systems with fin/tube condenser coils, but the refrigerant volumes will be much lower.
Consult Tables 5-5 and 5-6 for refrigerant required by a condenser with Liebert Lee-Temp.
5.7.2
Liebert MC Condenser Charging with Liebert DSE™ Receivers
Consult the Liebert DSE manual (SL-18925) for charging Liebert DSE systems. All Liebert DSE require
installation of a Liebert DSE receiver on each condenser circuit, with or without a Liebert EconoPhase
pump module installed. Consult Table 5-6 for condenser and receiver refrigerant requirements.
Liebert® MC™ User Manual
68
Piping
5.7.3
Liebert MC Charging, Premium Efficiency Control, Units without
Receivers
Source: DPN002411, Rev. 7
Liebert MC condensers are charge-sensitive and require accurate calculation of the system charge to
avoid overcharging. To avoid overcharge, additional guidelines are recommended to ensure trouble-free
operation.
• When charging system in an outdoor ambient below 50°F (10°C), recheck the subcooling against
Table 5-10 when the ambient temperature is above 60°F (15.6°C)
• The indoor space should be maintained at 70-80°F (21-26.7°C) return air before final charge
adjustments are made.
• Charging a unit at temperatures above 80°F (26.7°C) return air may result in the unit being
overcharged.
• Charge by subcooling measurement at the indoor unit. See Table 5-10 for target subcooling
temperatures.
• Pressure and temperature measuring instruments should be capable of measuring to ±10 psig
(68.9kPa) and ± 2°F (1.1°C) for best subcooling measurement.
1. Check the nameplate on the indoor unit for refrigerant type to be used. Unit control configurations differ
depending on refrigerant type.
2. Refrigerant charging requires the unit to be in operation. Refer to the indoor unit’s user manual for the
Checklist for Completed Installation.
3. Calculate the amount of charge for the system. Refer to the indoor unit user manual, and condenser
and refrigerant line charge data in Tables 1 and 2.
4. Weigh in as much of the system charge as possible before starting the unit.
Do not exceed the calculated charge by more than 0.5 lb. (0.23kg).
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant R-407C and R-410A are blended refrigerants and must be introduced and charged
from the cylinder only as a liquid.
When adding liquid refrigerant to an operating system, it may be necessary to add the refrigerant
through the compressor suction service valve. Care must be exercised to avoid damage to the
compressor.
Emerson recommends connecting a sight glass between the charging hose and the compressor
suction service valve. This will permit adjusting the cylinder hand valve so that liquid can leave the
cylinder while allowing vapor to enter the compressor.
NOTICE
Risk of refrigerant overcharge. Can cause equipment damage.
Do not use the sight glass as an indicator when charging Liebert MC condenser systems.
5. Turn On the Liebert MC disconnect switch.
6. Turn on the indoor unit disconnect switch. Operate the unit for 30 minutes using the charging function
of the indoor unit control for each circuit of the system. The charging function is in the diagnostic
section of the Liebert iCOM® (see Liebert iCOM user manual, SL-18847, available at the Liebert Web
site (www.liebert.com).
69
Liebert® MC™ User Manual
Piping
The charging function operates the compressor(s) at full capacity and energizes the liquid line solenoid
valve(s). The reheat and humidifier are disabled. Manual operation of the indoor fans from the
diagnostic menu of the Liebert iCOM is required. A minimum 20psig (138kPa) must be established and
maintained for the compressor to operate. The charging function can be reset as many times as
required to complete unit charging.
Table 5-9
Line Size
O.D., in.
3/8
Charge amounts per 100 ft. (30m) of pipe by line size
R-407C (R-22), lb/100 ft. (kg/30m)
R-410A, lb/100 ft. (kg/30m)
Hot Gas Line
Liquid Line
Hot Gas Line
Liquid Line
—
3.6 (1.6)
—
3.2 (1.4)
1/2
0.5 (0.2)
6.7 (3.0)
0.7 (0.3)
5.9 (2.7)
5/8
0.8 (0.4)
10.8 (4.8)
1.1 (0.5)
9.6 (4.3)
3/4
1.2 (0.5)
16.1 (7.2)
1.6 (0.7)
14.3 (6.4)
7/8
1.7 (0.8)
22.3 (10.0)
2.3 (1.0)
19.8 (8.8)
1-1/8
2.9 (1.3)
38.0 (17.0)
3.9 (1.7)
33.8 (15.1)
1-3/8
4.4 (2.0)
57.9 (25.9)
5.9 (2.6)
51.5 (23.0)
1-5/8
6.2 (2.8)
—
8.4 (3.7)
—
Data based on 50°F Evap, 15°F superheat, 125°F SCT, 10°F subcooling.
Source: DPN002411, Rev. 7
7. Attach pressure and temperature instruments to the liquid line of the indoor unit. Measure the initial
subcooling and continue to add charge until reaching the recommended subcooling for the current
outdoor ambient temperature (see Table 5-10). The outdoor ambient can be read from the Liebert MC
condenser control menu ID F02.
NOTE
To determine subcooling measurement, a liquid line pressure reading (at the factory-installed
Schrader tap) needs to be measured along with obtaining a temperature reading on the liquid line.
Convert the liquid line pressure reading into a temperature by utilizing a Pressure-Temperature
Guide or Table 5-11. The difference between this converted temperature and the actual
temperature will determine the system’s subcooling. For R-407C make sure to use the saturated
liquid temperature to calculate subcooling.
Table 5-10 Target subcooling for ambient outdoor temperature
Ambient Temp
°F (C°)
Subcooling
°F (C°)
0 (-17.8)
22 (12.0)
10 (-12.2)
22 (12.0)
20 (-6.7)
22 (12.0)
30 (-1.1)
22 (12.0)
40 (4.4)
22 (12.0)
50 (10.0)
21 (11.7)
60 (15.6)
19 (10.8)
70 (21.1)
17 (9.3)
80 (26.7)
13 (7.2)
90 (32.2)
9 (5.0)
95 (35.0)
7 (3.9)
100 (37.8)
5 (2.9)
105 (40.6)
3 (1.8)
110 (43.3)
1 (0.7)
125 (51.7)
0
DPN002411, Rev. 7
Liebert® MC™ User Manual
70
Piping
8. As head pressure builds, the variable fan speed controlled condenser fan begins rotating. The fan will
run at full speed when sufficient head pressure is developed.
Table 5-11 Liquid pressures and temperatures
Pressure
Psig (Bar)
R407C 1
°F (°C)
R410A 1
°F (°C)
R22
°F (°C)
170 (11.7)
81.5 (27.5)
59.8 (15.4)
90.6 (32.6)
180 (12.4)
85.1 (29.5)
63.1 (17.3)
94.3 (34.6)
190 (13.1)
88.6 (31.5)
66.3 (19.1)
97.9 (36.6)
200 (13.8)
92.0 (33.3)
69.5 (20.8)
101.4 (38.6)
210 (14.5)
95.2 (35.1)
72.5 (22.5)
104.7 (40.4)
220 (15.2)
98.3 (36.8)
75.4 (24.1)
108.0 (42.2)
230 (15.9)
101.4 (38.5)
78.2 (25.7)
111.1 (44.0)
240 (16.6)
104.3 (40.2)
80.9 (27.2)
114.2 (45.7)
250 (17.2)
107.2 (41.8)
83.6 (28.7)
117.1 (47.3)
260 (17.9)
109.9 (43.3)
86.2 (30.1)
120.0 (48.9)
270 (18.6)
112.6 (44.8)
88.7 (31.5)
122.8 (50.4)
280 (19.3)
115.3 (46.3)
91.1 (32.8)
125.5 (52.0)
290 (20.0)
117.8 (47.7)
93.5 (34.2)
128.2 (53.4)
300 (20.7)
120.3 (49.1)
95.8 (35.5)
130.8 (54.9)
310 (21.4)
122.8 (50.4)
98.1 (36.7)
133.3 (56.3)
320 (22.1)
125.2 (51.8)
100.3 (38.0)
135.8 (57.7)
330 (22.8)
127.5 (53.1)
102.5 (39.2)
138.2 (59.0)
340 (23.4)
129.8 (54.3)
104.6 (40.3)
140.6 (60.3)
350 (24.1)
132.1 (55.6)
106.7 (41.5)
142.9 (61.6)
360 (24.8)
134.3 (56.8)
108.7 (42.6)
145.2 (62.9)
370 (25.5)
136.4 (58.0)
110.7 (43.7)
147.4 (64.1)
380 (26.2)
138.6 (59.2)
112.7 (44.8)
149.6 (65.4)
390 (26.9)
140.6 (60.3)
114.5 (45.9)
151.8 (66.5)
400 (27.6)
142.7 (61.5)
116.4 (46.9)
153.9 (67.7)
500 (34.5)
161.3 (71.8)
133.5 (56.4)
173.1 (78.4)
600 (41.4)
177.4 (80.8)
148.1 (64.5)
189.5 (87.5)
1. Values are for saturated liquid.
2. Source: DPN002411, Rev. 7
71
Liebert® MC™ User Manual
Piping
Page intentionally left blank.
Liebert® MC™ User Manual
72
Checklist for Completed Installation
6.0 Checklist for Completed Installation
6.1 Moving and Placing Equipment
___ 1. Unpack and check received material.
___ 2. Proper clearance for service access has been maintained around the equipment.
___ 3. Equipment is level and mounting fasteners are tight.
6.2 Electrical
___ 1. Line voltage connected and matches equipment nameplate.
___ 2. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 3. Control wiring connections completed between indoor cooling unit and condenser.
___ 4. All internal and external high-voltage and low-voltage wiring connections are tight to the proper
torque ratings shown on the components.
___ 5. Confirm that unit is properly grounded to an earth ground.
___ 6. Electrical service conforms to national and local codes.
___ 7. Monitoring wiring connections completed, when equipped, to indoor cooling unit or external
monitoring panel.
___ 8. Verify that the Premium EC fan condenser is not connected to a delta power supply.
___ 9. Verify that the CANbus wiring, CANbus “END of Line” jumper position and the CANbus “Device
Address DIP Switch” setting is correct according to the application at the job site.
___ 10. Verify that Terminals 70, 71 and 230 (when applicable) are used and that they are properly wired,
particularly on systems that use two condensers for one indoor unit.
6.3 Piping
___ 1. Piping is completed to corresponding indoor cooling unit refrigeration circuit.
___ 2. Piping is leak-checked, evacuated and charged with specified refrigerant.
___ 3. Additional refrigerant oil added, if required, per circuit.
___ 4. Piping is properly sized, sloped and trapped for proper oil return.
___ 5. Piping is routed to reduce potential of rub-through or chaffing.
___ 6. Hot gas line on Liebert Lee-Temp™ is fastened to the side of the cabinet and isolated for vibration
reduction.
6.4 Other
___ 1. Foreign material removed from in and around all equipment installed (construction materials,
construction debris, etc.).
___ 2. Installation materials and tools have been removed from in and around all equipment (literature,
shipping materials, tools, etc.).
___ 3. Blank startup sheet located, ready for completion by installer or start-up technician.
73
Liebert® MC™ User Manual
Checklist for Completed Installation
Page intentionally left blank.
Liebert® MC™ User Manual
74
Initial Startup Checks and Commissioning
7.0 Initial Startup Checks and Commissioning
! WARNING
Arc flash and electric shock hazard. Open all local and remote electric power disconnect switches,
verify with a voltmeter that power is Off and wear personal protective equipment per NFPA 70E
before working within the electric control enclosure. Failure to comply can cause serious injury or
death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM® microprocessor does not isolate power from the unit, even in the “Unit Off”
mode. Some internal components require and receive power even during the “Unit Off” mode of
Liebert iCOM control.
The factory-supplied disconnect switch is inside the unit. The line side of this switch contains live
high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
! WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote unit electric power supply disconnect switches, wait 10 minutes and
verify with a voltmeter that power is Off before working within the fan speed control, the EC fan
electrical enclosures or checking any electrical connections or functions. Unit contains potentially
lethal electrical voltage. Line side of factory disconnect remains energized when disconnect is Off.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning
operation.
! WARNING
Risk of high-speed, rotating fan blades. Can cause injury or death.
Fan blades can start rotating without warning at any time during a cooling cycle or after power is
restored after a power failure. Open all local and remote unit electrical power supply disconnect
switches, verify with a voltmeter that the power is Off and verify that all fan blades have stopped
rotating before working on or near the fans.
7.1 Startup Checklist
Refer to 6.0 - Checklist for Completed Installation and verify that all installation items have been
completed before beginning to start the condenser.
7.2 Initial Startup
1. Locate Liebert MC Condensers Warranty Inspection Check Sheet, Document # PSWI-8542-408CO.
2. Turn the condenser disconnect On.
3. Turn the indoor unit ON and set for cooling to allow operation of condenser.
4. Check the fans for proper rotation: Counterclockwise when viewing the unit from the fan guard (top)
side.
75
Liebert® MC™ User Manual
Initial Startup Checks and Commissioning
5. Check that air is being drawn through the coil and discharged out the fan assembly.
6. Complete Liebert MC Condensers Warranty Inspection Check Sheet, Document # PSWI-8542408CO.
NOTE
This document must be completed and forwarded to your local Emerson sales office to validate
warranty.
• Contact your local Emerson sales representative or Emerson Network Power® Liebert Services
support about any questions or problems during unit startup and commissioning.
Local Emerson sales offices and Liebert Thermal Management support contacts can be found at
www.liebert.com or by calling 1-800-LIEBERT.
Liebert® MC™ User Manual
76
Troubleshooting
8.0 Troubleshooting
Table 8-1
Symptom
Condenser will not start
Troubleshooting
Possible Cause
Check or Remedy
No power to condenser.
Check voltage at input terminal block.
Circuit breaker or fuse for low-voltage
transformer in condenser is tripped.
Locate problem in condenser electrical panel and
repair.
No low-voltage signal to/from indoor unit. Locate open circuit and repair.
Low discharge pressure
High discharge pressure
SPD green and red LEDs
are extinguished
SPD red LED is illuminated
Faulty head pressure control valve or
premium efficiency control board.
Replace if defective.
Dirty condenser fins.
Clean coil.
Check for low-voltage signal from indoor unit.
Condenser fans not operating.
Check fan motors and fuses.
High refrigerant charge
Check refrigerant charge.
No voltage or improper phasing exists at
condenser.
Check voltage at input terminal block.
Electrical connections to SPD are faulty.
Locate connection problem and repair.
Condenser disconnect is turned Off.
Recheck lights with disconnect switch in the On
position.
A surge exceeding the rating of the SPD
has occurred.
Replace SPD and inspect other components for
damage and replace them if necessary.
Check the connection to P24 to verify that is
connected securely.
Connection to P24 is loose or
disconnected.
Check the connector from the transformer for loose
terminals.
Fuse located next to P24 has blown.
Verify that the fuses next to P24 have not blown.
Replace as needed.
24V transformer has failed.
With a voltmeter verify that the output from the
transformer is 24Vac ±10%. If the value exceeds
±10%, verify that the correct primary leads are being
used.
Premium Efficiency Control Board has
failed.
If there is no output voltage, verify that the primary
connections are secure and receiving the correct
voltage. If they are, replace the transformer.
Jumper not installed between 24V and
DIN1 (for Ziehl-Abegg fan motor).
Install jumper between 24V and DIN1 (for Ziehl Abegg
fan motor).
Control Board LEDs do not
light.
Fan will not run
77
Liebert® MC™ User Manual
Troubleshooting
Page intentionally left blank.
Liebert® MC™ User Manual
78
Control Operation
9.0 Control Operation
The Liebert MC Premium Efficiency Control takes approximately 30 seconds to boot up once power is
applied to the condenser. The LED on the Premium Efficiency Control Board reads “888” while the board is
booting up. Once the control has booted up, the display shows “F00” and then the value for F00. With the
control operational, the condenser fan(s) turn in less than 5 seconds after receiving a signal from the
indoor unit that the compressor(s) are On. Consider using UPS equipment on both data center cooling
units and Liebert MC condensers to maintain uninterrupted cooling capability.
For the first 60 seconds of operation after the compressor turns on, the condenser fan(s) will run at a fixed
speed, set at the factory, based on ambient temperature: faster at higher temperatures, slower at lower
temperatures. After 60 seconds, the control adjusts the fan speed based on the liquid pressure transducer.
If the liquid pressure transducer fails, the condenser uses temperature sensors to control the fan speed
based on the liquid line temperature. The condenser fans continue to operate for approximately 30
seconds after compressors turn Off.
The Liebert MC fans have various alarm conditions, such as loss of voltage and loss of control signal, that
will stop the condenser fans. Once the alarm condition is no longer present the Liebert MC fans will turn on
automatically if compressors are On.
9.1 Premium Efficiency Control Board and Interface
The Liebert MC Premium Efficiency Control board has a stacked board arrangement. There are three
seven-segment LED’s and four keys as human machine interface (see Figure 9-2).
NOTE
Indicator lights should be On to indicate signal is present. See Figure 9-1, #1, 2 and 3.
79
Liebert® MC™ User Manual
Control Operation
Figure 9-1 Premium efficiency fan control board
Spare Analog
Outputs (Not Used)
RS485 Service
Terminal
1
A
1
BAR CODE
P15
A
1 P81
B
A
B
1 P79
H
B
TB57
P80
RS485
Communications to Fans
1
P54
See Note 1
1
D58
TB56
TB50
1
L
Communication
from Indoor
Unit
H
1
CANbus
P64
J4
1
TB49
3
1
J5
P29
1
L
Communication
from Indoor
Unit
1
P28
Indicator lights:
ON - signal present
Temperature
Inputs
Circuit1
#1
P27
LED1
LED2
LE
Circuit 2
Circuit1
#3
D57 D2
Call for
Cooling
Ethernet and CANbus addressing
and signal indication
ENT
P21
F3 T3.15A, 250Vac
1
ACM01M1
TB74
Fan 1
UP
Indicator lights: ON - signal present
1
Fan
Contactor
Output
SW1
1
Circuit2
Fan2
1
J2
J8
J7
J6
DOWN
1
P20
Ambient
P19
1
See Note 2
1
Earth
Ground
Remote
Shutdown
CAUTION:
E1
Alarm & Shutdown
Circuits
24VAC
1
F2 T3.15A, 250Vac
Motherboard
VER:A02
2010.08.10
1
#2
TB38
Circuit2
P18
1
Fan 3
1
P23
P67
CPU
Board
BOOTPSWD SYS APP
X Y
No.
P17
1
Fan 4
TB11
BAR CODE
Circuit1
Pressure
Inputs
ACM01U1 VER:A03 2010.08.10
3
J6
1
Service
Spare Digital
Outputs
(Not Used)
P24
24VAC
For Continued Protection Against Risk of Fire,
Replace Only With Same Type and Rating of Fuse.
Control Fuses
NOTE:
1. J6 is the CANbus termination jumper. J4 is the RS485 service termination jumper. If the condenser is the last device in the CANbus
communication line, the jumper must be placed between Pins 1 and 2 of J6. If the condenser is not the last device in the CANbus
communication line, the jumpers on J6 must be placed on Pins 2 and 3. If the jumper is not in the correct positions, CANbus
communication errors may occur. The jumper on J4 will always be placed between Pins 1 and 2.
2. A jumper must be present at J2. If a jumper is not present, the control board will not boot properly during power startup.
Max. Fuse Rating:
3A/250V
301471
Pg. 2, Rev. 4
Figure 9-2 Premium Efficiency Control Interface - Human Machine Interface (HMI)
The Premium Efficiency Controls are factory-configured for refrigerant type and whether the condenser
was sold with or without a Liebert Lee-Temp™ or Liebert DSE system. No field-configuration is necessary
for proper and efficient condenser operation.
Liebert® MC™ User Manual
80
Control Operation
9.1.1
Initial Screen Upon Power-On
The controller displays the initial screen after it is powered On. The initial screen shows the first item of
analog signals menu. The F00 and value of condenser pressure 1 are displayed alternatively and F00
means the item ID of condenser pressure 1. The display sequence is shown Figure 9-3. In the figure, 16.1
is an example and the value is dependent on the sampling result.
Figure 9-3 Initial controller display
F00
9.1.2
16.1
F00
16.1
Main Menu Description
In initial screen, presses ESC key, the LED enters the first menu of the main menu. The main menu
includes four menus:
• Analog Signals Menu
• Active Alarms Menu
• History Alarms Menu
• Configuration Menu
In the Main Menu, press Up and Down keys to switch to different menus, and press the ENT key to enter
the sub menus of the current menu. The operation and structure of main menu are shown in the following
figure.
Figure 9-4 Main Menu operation and structure
F-------Analog Signals
Menu
A-------Active Alarms
Menu
H--------0
C--------
History Alarms
Menu
Configuration
Menu
Down
Up
NOTICE
Risk of improperly altered configuration menu settings. Can compromise equipment operation.
Changing the configuration menu settings can cause unanticipated results. These settings should
be changed only by properly trained and qualified personnel or as directed by the factory.
81
Liebert® MC™ User Manual
Control Operation
9.1.3
Analog Signals Menu Description
In analog signals menu F-----------, press the ENT key to enter its items. The information of analog signal
items includes condenser pressure, temperature and EC Fan actual speed. The display mode is that the
item ID and signal value are displayed alternatively. The operation and item structure of analog signals
menu are shown in Figure 9-5. Table 9-1 defines the signals.
Figure 9-5 Analog Signals Menu
F-------
ENT
Down
F00
16.1
F01
15
F02
0
F03
-15
F04
20
F10
200
...
...
F92
000
Initial Screen
ESC
Liebert® MC™ User Manual
82
Up
Control Operation
Table 9-1
Analog signal definitions
Units (C90)
Item ID
Imperial
Metric
F00
Condenser pressure 1
Meaning
psi
bar
F01
Condenser pressure 2
psi
bar
F02
Ambient temperature
°F
°C
F03
Refrigerant temperature 1
°F
°C
F04
Refrigerant temperature 2
°F
°C
F10
EC Fan 1 actual speed
RPM
RPM
F11
EC Fan 1 requested speed
%
%
F12
EC Fan 1 power
kW
kW
F13
EC Fan 1 firmware version
F20
EC Fan 2 actual speed
F21
Hex format Hex format
RPM
RPM
EC Fan 2 requested speed
%
%
F22
EC Fan 2 power
kW
kW
F23
EC Fan 2 firmware version
F30
EC Fan 3 actual speed
F31
Hex format Hex format
RPM
RPM
EC Fan 3 requested speed
%
%
F32
EC Fan 3 power
kW
kW
F33
EC Fan 3 firmware version
F40
EC Fan 4 actual speed
F41
Hex format Hex format
RPM
RPM
EC Fan 4 requested speed
%
%
F42
EC Fan 4 power
kW
kW
F43
EC Fan 4 firmware version
F50
Subcooling 1
°F
°C
F51
Subcooling 2
°F
°C
F90
Firmware Version Major
F91
Firmware Version Minor
—
1.02.004
F92
Firmware Version Build
—
Hex format Hex format
Source: 303847P1 Rev. 4
83
Liebert® MC™ User Manual
Control Operation
9.2 Premium Efficiency Condenser Alarm Codes
The following procedure and chart details the alarm codes that may be displayed from the Active and
History Alarm registers.
9.2.1
Active Alarms Menu Description
In active alarms menu “A——,” press the ENT key to enter its items. The active alarm item displays all the
active alarms of condenser. When there is an active alarm, the alarm information ID will be directly
displayed. When there is no alarm, “---” is displayed. When there are multiple alarms, the alarm information
IDs will be displayed according to the time sequence (the most-recent alarm will be displayed first). The
operation and items structure of active alarms menu are shown in the following figure. The meanings of
alarm information ID are found in Tables 9-2 and 9-3.
Figure 9-6 Active alarms menu
A-------
ENT
Down
---
or
No Alarm
001
105
ESC
304
210
033
Liebert® MC™ User Manual
84
Up
Control Operation
9.2.2
History Alarms Menu Description
In history alarms menu “H——―”, press ENT key to enter its items. The history alarm items display 100
history alarm records of the condenser. The item ID is for the sequence number of the history alarms. The
display mode is that the item ID and alarm information ID are displayed alternatively. When there is no
alarm, “---” is displayed. Alarm history can be cleared using the C98 configuration menu item. The
operation and items structure of history alarms menu are shown in the following figure. The meanings of
alarm information ID are given in Tables 9-2 and 9-3.
Figure 9-7 History alarms menu
H-------
ENT
Down
H01
or
001
H02
105
H03
304
H04
---
---
---
H00
--
ESC
85
Up
Liebert® MC™ User Manual
Control Operation
Table 9-2
Alarm ID
System alarm information
Meaning
Possible Cause
Handling Method
000
CAN communication failure
Communication circuit missing or
damaged
Check communication circuit.
Ignore alarm on condensers
without CAN connections
001
Ethernet communication failure
Ethernet hardware or connection
failure
Ignore alarm, Ethernet connection
is not present
002
USB communication failure
USB device or file is damaged.
Replace USB device or file.
003
Data corruption
Memory chip is damaged
Replace PCB board
004
System error
Internal error
Reboot. If reboot fails, consult
factory.
005
Remote shutdown
1. Remote shutdown signal is
available
2. TB38 is not connected
For Cause 1, check the remote
shutdown signal.
For Cause 2, connect TB38.
006
Shutdown due to EC Fan alarm
All fans have failed
Consult factory
007
SPD alarm
SPD damaged
Replace SPD
008
Condenser pressure Sensor 2 failure
Condenser pressure Sensor 1
damaged
Replace condenser pressure
Sensor 1
009
Condenser pressure Sensor 2 failure
Condenser pressure Sensor 2
damaged
Replace condenser pressure
Sensor 2
010
Condenser pressure 1 high alarm
011
Condenser pressure 2 high alarm
012
Condenser pressure 1 low alarm
013
Condenser pressure 2 low alarm
014
EC Fan speed mode maximum must
be overridden due to condenser
pressure 1 high
Condenser pressure 1 high
No action is needed.
015
EC Fan speed mode maximum must
be overridden due to condenser
pressure 2 high
Condenser pressure 2 high
No action is needed.
016
Ambient temperature sensor failure
Ambient temperature sensor
damaged
Replace ambient temperature
sensor
017
Ambient temperature high alarm
Ambient temperature high
No action is needed.
018
Ambient temperature low alarm
Ambient temperature low
No action is needed.
019
Condenser temperature Sensor 2
failure
Condenser temperature Sensor 2
damaged
Replace condenser temperature
Sensor 1
020
Condenser temperature Sensor 2
failure
Condenser temperature Sensor 2
damaged
Replace condenser temperature
Sensor 2
021
Condenser temperature 1 high alarm
022
Condenser temperature 2 high alarm
023
Condenser temperature 1 low alarm
024
Condenser temperature 2 low alarm
High temperature: Fan failure,
clogged coils.
Low temperature: Consult factory
High-temperature alarms: Fix fan
and clean coils.
Low-temperature alarms: consult
factory.
025
EC Fan speed mode maximum must
be overridden due to refrigerant
temperature 1 high
Refrigerant temperature 1 high
No action is needed.
026
EC Fan speed mode maximum must
be overridden due to refrigerant
temperature 2 high
Refrigerant temperature 2 high
No action is needed.
Liebert® MC™ User Manual
High-pressure alarms: Fix fan and
High pressure: Fan failure, clogged
clean coil.
coils.
Low-pressure alarms: Check for
Low pressure: Loss of charge
refrigerant leak.
86
Control Operation
Table 9-3
Alarm ID
EC Fan alarm information
Meaning
Possible Cause
Handling Method
(1-4) 00
EC Fan high link current
1. EC Fan is locked.
2. EC Fan is damaged.
For cause 1, check if EC Fan is
locked.
For cause 2, replace EC Fan
(1-4) 01
EC Fan drive error
EC Fan is damaged.
Replace EC Fan
(1-4) 02
EC Fan earth to ground fault
EC Fan is damaged.
Replace EC Fan
(1-4) 03
EC Fan electronics heat sink thermal
overload
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too high
For cause 1, check if EC Fan is
locked.
For cause 2, replace EC Fan
For cause 3, check ambient
temperature.
(1-4) 04
EC Fan Hall failure
EC Fan is damaged.
Replace EC Fan
(1-4) 05
EC Fan IGBT failure
EC Fan is damaged.
Replace EC Fan
(1-4) 06
EC Fan line fault
Power supply abnormal
Check power supply
(1-4) 07
EC Fan motor locked
Motor is locked
Check if EC Fan is locked.
(1-4) 08
EC Fan motor thermal overload
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too high
For cause 1, check if EC Fan is
locked.
For cause 2, replace EC Fan
For cause 3, check ambient
temperature.
(1-4) 09
EC Fan phase failure alarm
Phase failure
Check power supply
(1-4) 10
EC Fan-specific uncategorized alarm
detected
Internal EC Fan issue
Re-boot condenser if fans not
running. If alarm persists and fans
not running, replace fan.
For cause 1, check if EC Fan is
locked.
For cause 2, replace EC Fan
For cause 3, check ambient
temperature.
(1-4) 11
EC Fan-specific uncategorized
warning detected
(1-4) 12
EC Fan electronics high-temperature
condition.
1. EC Fan is locked.
2. EC Fan is damaged.
3. Ambient temperature is too high
(1-4) 13
EC Fan high link voltage
1. EC Fan input power supply high
voltage
2. EC Fan is damaged.
(1-4) 14
EC Fan low link voltage
1. EC Fan input power supply low
voltage
2. EC Fan detection error
EC Fan 485 communication failure
1. Communication between EC Fan
and PCB board failure
2. EC Fan 485 communication
failure
3. Board has problems
4. EC fan not receiving power
(1-4) 15
For cause 1, measure power supply
voltage and check if the voltage is
normal
For cause 2, replace EC Fan
For cause 1, check EC Fan
communication circuit
For cause 2, replace EC Fan
For cause 3, replace PCB board
For cause 4, check fan model is not
set for “0”, check that the contactor
for the particular fan is energized,
and check fan fuses.
NOTE
(1-4) means the EC Fan addresses. For example, (1-4) 00 means 100 for EC Fan1, and means
200 for EC Fan2, and means 300 for EC Fan3, and means 400 for EC Fan4.
87
Liebert® MC™ User Manual
Control Operation
Page intentionally left blank.
Liebert® MC™ User Manual
88
Liebert MC Seismic Application—Optional Unit Configuration
10.0 Liebert MC Seismic Application—
Optional Unit Configuration
10.1 Seismic Anchoring Considerations
• Mounting requirement details such as anchor brand, type, embedment depth, edge spacing, anchorto-anchor spacing, concrete strength, special instruction and attachment to non-building structures
must be outlined and approved by the engineer of record for the project or building. Structural floors
and housekeeping pads must also be seismically designed and approved by the project or building
structural engineer of record to withstand the seismic anchor loads defined in Table 10-1. The
installing contractor is responsible for the proper installation of all anchors and mounting hardware,
observing the mounting requirements detailed in the seismic installation drawings as outlined by the
engineer of record.
• All braces and fasteners are required to maintain IBC/OSHPD certification of conformity.
• Use a washer, lock washer and screw to connect the brace to the bottom beam of the condenser. (See
Figure 10-2.)
• Use a washer, lock washer and screw to connect the brace to the condenser leg. (See Figure 10-2)
• Place anchorage plate inside each condenser foot of 18-in. legs prior to fastening to the structure. MC
condensers with 36-in., 48-in. or 60-in. legs do not require separate anchorage plates for the legs. Use
a flat washer, lock washer and nut to connect the condenser to the customer-supplied anchor on the
solid surface (reference Detail A in Figure 10-1). As a minimum, 3/8” grade anchors with American
National Standard Series W, Type A, plain washers (ANSI B18.22.1-1965, R1975) selected to match
the nominal anchor diameter must be installed at each anchor location between the anchor head and
equipment for tension load distribution.
89
Liebert® MC™ User Manual
Liebert MC Seismic Application—Optional Unit Configuration
Figure 10-1 Seismic anchorage data for one-fan models
WITH RECIEVER
(VIEWS SHOW RECEIVER BRACKET ONLY.
RECEIVER REMOVED FOR CLARITY).
WITHOUT RECIEVER
A
FIGURE 2
FIGURE 1
CUSTOMER SUPPLIED:
-NUT
-LOCK WASHER
-FLAT WASHER
-ANCHOR
ANCHORAGE PLATE
(LIEBERT SUPPLIED FOR 18"
ALUMINUM LEGS ONLY)
DETAIL A
TYPICAL ALL 18"
ALUMINUM LEGS
DPN002414
Pg. 1 Rev. 3
Table 10-1 Seismic anchorage loads for one-fan models
Importance Factor Iρ = 1.0
Figure #
in Figure 10-1
Maximum
Compressive
Reaction
lb
Without Receiver
Figure 1
With Receiver
Importance Factor Iρ = 1.5
Tensile
lb
Shear
lb
Maximum
Compressive
Reaction
lb
37
14
14
Figure 2
43
15
Without Receiver
Figure 1
37
With Receiver
Figure 2
43
Without Receiver
Figure 1
With Receiver
Figure 2
Models
Maximum Anchor
Maximum Anchor
Tensile
lb
Shear
lb
47
24
21
23
56
27
35
14
14
47
24
21
15
23
56
27
35
37
14
14
47
24
21
43
15
23
56
27
35
MCS028
MCM040
MCL055
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
Liebert® MC™ User Manual
90
Liebert MC Seismic Application—Optional Unit Configuration
Figure 10-2 Seismic anchoring for a two-fan Liebert MC
WITHOUT RECEIVER
WITH RECEIVER
(VIEWS SHOW RECEIVER BRACKET ONLY.
RECEIVER NOT SHOWN FOR CLARITY)
B
FIGURE 3
FLAT WASHER
LOCK
WASHER
FIGURE 4
SCREW
BRACE
NUT
SCREW
DETAIL B
TYPICAL
FIGURE 5
DPN002414
Pg. 2 Rev. 3
Table 10-2 Seismic anchoring loads for a two-fan Liebert MC
Importance Factor Iρ = 1.0
Model #
Importance Factor Iρ = 1.5
Maximum
Maximum Anchor
Maximum
Maximum Anchor
Compressive
Compressive
Figure #
Reaction
Reaction
Tensile
Shear
Tensile
Shear
in Figure 10-2
lb
lb
lb
lb
lb
lb
MCS056
Without Receiver
Figure 3
63
20
23
78
35
34
With Receiver
Figure 5
69
15
30
75
30
45
Single or Dual Circuit without
Receivers
Figure 3
94
30
34
116
53
50
Single Circuit with Receiver
Figure 4
87
34
38
99
59
57
Dual Circuit with Receivers
Figure 5
90
24
38
98
44
57
Single or Dual Circuit without
Receivers
Figure 3
146
42
55
179
76
82
Single Circuit with Receiver
Figure 4
131
47
53
158
83
80
Dual Circuit with Receivers
Figure 5
117
31
51
136
59
77
MCM080
MCL110
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
91
Liebert® MC™ User Manual
Liebert MC Seismic Application—Optional Unit Configuration
Figure 10-3 Seismic anchoring loads for a three-fan Liebert MC
WITH RECEIVER
(VIEWS SHOW RECEIVER BRACKET ONLY.
RECEIVER NOT SHOWN FOR CLARITY)
WITHOUT RECEIVER
FLAT WASHER
FIGURE 6
DPN002414
Pg. 3 Rev. 3
FIGURE 7
LOCK
WASHER
SCREW
BRACE
NUT
SCREW
DETAIL B
TYPICAL
Table 10-3 Seismic anchoring loads for a three-fan Liebert MC
Importance Factor Iρ = 1.0
Model #
Importance Factor Iρ = 1.5
Maximum Anchor
Maximum Anchor
Maximum
Maximum
Loads
(ASD)
Loads (ASD)
Compressive
Compressive
Figure #
Reaction
Reaction
Tensile Shear
Tensile Shear
in Figure 103
lb
lb
lb
lb
lb
lb
MCL165
Single Circuit without Receiver
Figure 6
158
39
62
181
73
93
Single Circuit with Receiver
Figure 7
153
38
65
170
73
97
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
Liebert® MC™ User Manual
92
Liebert MC Seismic Application—Optional Unit Configuration
Figure 10-4 Seismic anchorage loads for a four-fan Liebert MC
WITHOUT RECEIVER
FLAT WASHER
LOCK
WASHER
SCREW
FIGURE 8
BRACE
WITH RECEIVER
NUT
(VIEWS SHOW RECEIVER BRACKET ONLY.
RECEIVER NOT SHOWN FOR CLARITY)
SCREW
DETAIL B
TYPICAL
FIGURE 9
FIGURE 10
DPN002414
Pg. 4 Rev. 3
FIGURE 11
Table 10-4 Seismic anchorage loads for a four-fan Liebert MC
Importance Factor Iρ = 1.0
Importance Factor Iρ = 1.5
Maximum Anchor
Maximum Anchor
Maximum
Maximum
Loads, ASD
Loads, ASD
Compressive
Compressive
Reaction
Reaction
Tensile
Shear
Tensile
Shear
lb
lb
lb
lb
lb
lb
Models
Figure #
in Figure 10-4
Dual Circuit without Receivers
Figure 8
122
37
42
148
65
62
Dual Circuit with Receivers
Figure 9
120
33
42
145
59
63
Single or Dual Circuit
without Receivers
Figure 8
194
53
69
232
95
104
Single Circuit with Receiver
Figure 10
191
51
74
221
92
110
Dual Circuit with Receivers
Figure 11
176
45
60
211
82
90
MCM160
MCL220
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
93
Liebert® MC™ User Manual
Liebert MC Seismic Application—Optional Unit Configuration
Figure 10-5 Seismic anchorage loads for 36-60” extended leg
1 TO 4 FAN WITH RECEIVER(S) TYPICAL.
VIEW SHOWS RECEIVER BRACKET ONLY.
RECEIVER NOT SHOWN FOR CLARITY.
1 TO 4 FAN TYPICAL
DPN002414
Pg. 5 Rev. 3
Table 10-5 Seismic anchorage loads for 36-60” extended leg
Importance Factor Iρ = 1.0
Models
MCS028 and MCS056
MCS028 without Receiver
MCS028 with Receiver
MCS056 without Receiver
MCS056 Dual Circuit with Receivers
MCM040 through MCM160
MCM040 without Receiver
MCM040 with Receiver
MCM080 without Receiver
MCM080 Single Circuit with Receiver
MCM080 Dual Circuit with Receivers
MCM160 Dual Circuit without Receivers
MCM160 Dual Circuit with Receivers
MCL055 through MCL220
MCL055 without Receiver
MCL055 with Receiver
MCL110 Single or Dual Circuit without Receivers
MCL110 Single Circuit with Receiver
MCL110 Dual Circuit with Receiver
MCL165 Single Circuit without Receiver
MCL165 Single Circuit with Receiver
MCL220 Single or Dual Circuit without Receivers
MCL220 Single Circuit with Receiver
MCL220 Dual Circuit with Receivers
Maximum
Compressive
Reaction
lb
Maximum Anchor
Loads (ASD)
Tensile
lb
Shear
lb
104
110
126
107
42
43
43
36
31
40
40
44
132
141
157
131
70
74
73
65
46
60
61
66
103
114
154
129
123
190
182
39
40
50
56
40
60
54
32
40
51
53
51
62
60
130
144
191
159
154
234
221
66
70
87
96
73
104
94
48
61
77
79
77
93
90
165
176
223
191
162
201
188
265
248
232
57
58
63
70
47
53
51
72
68
61
56
64
80
73
67
78
79
93
94
78
207
220
273
230
201
235
211
322
287
278
98
102
113
122
87
97
95
130
124
109
84
95
119
110
101
118
118
140
141
117
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
Liebert® MC™ User Manual
Importance Factor Iρ = 1.5
Maximum
Compressive
Reaction
lb
94
Maximum Anchor
Loads (ASD)
Tensile
lb
Shear
lb
Liebert MC Seismic Application—Optional Unit Configuration
10.2 Seismic piping considerations
Condensers for seismic application must be attached to the piping system with field-supplied, flexible loops
designed for seismic movement. Flexible loops must be capable of movement in three dimensions and
must isolate the condenser from the field piping. The loops must be suitable for the operating pressure and
temperature of the system. Follow manufacturer’s installation instructions for proper seismic application of
flexible loops. The selection of isolation brand and type must be outlined and approved by the engineer of
record for the project or building.
10.3 Seismic wiring considerations
Condensers for seismic application must be connected to power and control circuits using field-supplied
flexible conduit and conductors to allow movement of the condenser in three dimensions during a seismic
event. The flexible conduit must have at least one bend between the rigid connection at the unit cabinet
and the connection to rigid conduit or foundation.
Figure 10-6 Seismic piping and wiring considerations
ELECTRICAL SEISMIC
ISOLATION
PIPING SEISMIC ISOLATION
DPN002414
Pg. 6 Rev. 3
95
Liebert® MC™ User Manual
Liebert MC Seismic Application—Optional Unit Configuration
Page intentionally left blank.
Liebert® MC™ User Manual
96
System Maintenance
11.0 System Maintenance
! WARNING
Arc flash and electric shock hazard. Open all local and remote unit electric power disconnect
switches, verify with a voltmeter that power is Off and wear protective equipment per NFPA 70E
before working within the electric control enclosure. Failure to comply can cause injury or death.
Unit contains potentially lethal voltage in some circuits.
! WARNING
Risk of electric shock. Can cause serious injury or death.
Open all local and remote unit electric power disconnect switches, wait 10 minutes and verify with
a voltmeter that power is Off before working within the unit electric connection enclosures or
working within the fan speed control and the EC fan enclosures. These devices can retain a stored
high-voltage electrical charge for up to 10 minutes.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning.
! WARNING
Risk of contact with high-speed, rotating fan blades. Can cause serious personal injury or death.
Fan blades can automatically start rotating without warning at any time during a cooling cycle or
after power is restored after a power failure. Open all local and remote electric power supply
disconnect switches, wait 10 minutes and verify with a voltmeter that power is Off before working
within the unit cabinet, removing the fan guards or servicing the fan speed control, fan blades or
EC fan motors.
11.1 General Procedures
NOTE
When ordering replacement parts for equipment, it is necessary to specify unit model number,
serial number and voltage. Please record those numbers in the spaces below.
• Model Number ________________
• Serial Number ________________
• Voltage / Phase / Frequency ________________
Periodic attention is necessary for continued satisfactory operation of your unit. Restricted air flow through
the condenser coil, reduced airflow from non-functioning fans and low refrigerant system charge levels will
reduce the operating efficiency of the unit and can result in high condensing temperatures and loss of
cooling. In winter, do not permit snow to accumulate around the sides or underneath the condenser coil.
Monthly and semi-annual inspections and maintenance are recommended for proper system operation.
Use copies of 12.0 - Preventive Maintenance Checklist for each of these inspections.
If performance or operation problem are detected at anytime, refer to 9.2 - Premium Efficiency
Condenser Alarm Codes for required action.
97
Liebert® MC™ User Manual
System Maintenance
11.2 Condenser Cleaning
Keeping the outdoor condenser coils clean is an important factor in maintaining peak efficiency, reliability
and long life of the equipment. The unit will operate more efficiently with frequent cleanings. Delaying
cleaning until heavy buildup occurs may create head pressure problems with the evaporator units.
11.2.1 When to Clean the Condenser Coil
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions such as
cottonwood trees, construction, etc., can increase cleaning frequency. On your standard monthly
preventive maintenance schedule, Emerson recommends a visual inspection of the coil to monitor
conditions.
11.2.2 What to Use to Clean the Condenser Coil
The best overall condenser coil cleaner to use is plain water. If the coil has been maintained and cleaned
at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy build up on the
exterior of the fins can be removed with a brush. Water pressure from a garden hose and sprayer usually
works well. If a pressure washer is used, make sure the equipment is set to a lower pressure setting and
that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins could result. If a cleaner is
required, Emerson recommends using a neutral cleaner, neither acidic nor base. Acid-type cleaners can
damage the coil fins and surrounding areas. Many sites do not allow the use of acidic cleaners for
environmental reasons.
11.2.3 How to Clean the Condenser Coil
The Liebert MC coil is accessible for cleaning through the innovative cleaning window design, allowing you
to clean the coil without removing the fans from the unit. First, this requires disconnecting the power supply
before working on the unit and then opening the cleaning window(s) on the side of the unit by loosing the
mounting screws. Then insert a spray nozzle on the end of a suitable extension and apply the
water/cleaning solution, working back and forth across the coil face. The solution will push the dirt and
debris out the bottom of the coil. If you are using a cleaner along with the spraying process, follow
recommended manufacturer instructions and be sure to rinse the coil thoroughly. Any residue left on the
coil can act as a magnet to dirt. Reinstall the cleaning window(s) and reconnect the power supply to the
condenser.
Spraying the coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins
and continue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for
an extended time. A scheduled shutdown with the operator may be in order.
NOTICE
Risk of using damaging cleaning agents, including non-base paint solvents. Can cause equipment
damage and damage to property and loss of refrigerant charge.
Using acid-based or sodium hydroxide-based cleaners can damage the Liebert MC condenser coil
and cause a loss of charge. This could cause equipment damage as well as damage to the
surrounding structure.
NOTE
Clean the EC fan with water only when temperatures are greater than 50°F (10°C)
• Make sure that no water gets into the inside of the motor.
• Do not hold the jet spray directly on the motor openings and seals.
• During cleaning work using a jet spray, no guarantee is assumed regarding corrosion
formation/paint adhesion for unpainted/painted fans.
Liebert® MC™ User Manual
98
System Maintenance
11.3 Fan Replacement
Source: INST-9168, Rev. 3
! WARNING
Arc flash and electric shock hazard. Open all local and remote unit electric power disconnect
switches, verify with a voltmeter that power is Off and wear protective equipment per NFPA 70E
before working within the electric enclosure. Failure to comply can cause injury or death.
Unit contains potentially lethal voltage in some circuits.
Only properly trained and qualified personnel may perform repair, maintenance and cleaning on
these units.
! WARNING
Risk of electric shock. Can cause serious injury or death.
The fan motor control can contain a residual electric charge after power is disconnected. Do not
open the motor electrical-connection enclosure within the first 10 minutes after disconnection of all
phases.
! WARNING
Risk of contact with high-speed, rotating fan blades. Can cause injury or death.
The fan blades can start rotating without warning any time during a cooling cycle or after power is
restored after a power failure. Disconnect all local and remote electrical power supplies to the unit,
wait 10 minutes and verify with a voltmeter that the power is Off and that all fan blades have
stopped rotating before working on or near the fans.
! CAUTION
Risk of contact with hot surfaces. Can cause injury.
Use proper skin protection when touching the electronics housing or allow time for the housing to
cool before replacing parts. The electronics housing can get hot and can cause severe burns.
The fan motors and refrigerant discharge lines are extremely hot during unit operation. Allow
sufficient time for them to cool before working within the unit cabinet. Use extreme caution and
wear protective gloves and arm protection when working on or near fan motors and discharge
lines.
! CAUTION
Risk of improper moving, lifting and handling of heavy fan modules. Can cause equipment
damage or injury.
Only properly trained and qualified personnel should work on this equipment. Fan modules for
MCL models weigh in excess of 92lb. (40.8kg) each and fan modules for MCS and MCM models
weigh in excess of 40lb. (18.1kg.) each. Use OSHA-approved lifting techniques, proper body
mechanics and extreme caution to avoid injury and dropping of fans during removal and
installation.
NOTE
If at any time a parameter is entered and the display does not show 888 or if the display shows Err,
re-enter the parameter. If the display still shows Err after ENT is pressed, power cycle the control
board by unplugging P24, waiting 15 seconds and plugging P24 back in. Contact the factory if the
parameter still displays Err after ENT is pressed.
1. Turn Off power to the unit using the disconnect.
2. Use a voltmeter verify that voltage is no longer present at the unit. Wait a minimum of 10 minutes to
allow the EC fan capacitors to discharge before proceeding.
99
Liebert® MC™ User Manual
System Maintenance
3. Remove the fan cover, disconnect electrical connections internal to the EC fan and remove the cable
glands from the EC fan to be replaced (see Figures 11-2, 11-3 and 11-1).
4. Remove hardware that attaches the EC fan to the condenser.
5. Use lifting equipment or an adequate number of personnel to remove the EC fan from the Liebert MC.
NOTE
A spreader bar may be required for the lifting equipment if only one technician is performing the
fan replacement.
6. Install a spreader bar over the new EC fan if only one technician is performing the fan replacement.
7. Verify that the wire harness on the new EC fan is secured out of the way before lifting the fan.
8. Verify that the lifting cable/chains are not coming into contact with fan blades before lifting the new fan
into place on the condenser.
9. Install the new fan in the Liebert MC and connect the mounting hardware.
10. Verify that the fan blades rotate freely when installed in unit.
11. Install the new cable glands included with the new EC Fan. Torque for the cable glands is:
• 630mm and 710mm fans: 19.5 to 24.75 in-lb (2.2 to 2.8 Nm)
• 800mm fans: 32.75 to 38 in-lb (3.7 to 4.3Nm)
Dispose of the old cable glands once the new glands are installed.
12. Add a compression nut to the wire—Do not tighten the nut.
13. Reconnect the wiring to the proper terminals and verify that the run jumper is in place. Refer to
Figures 11-2, 11-3 and 11-1 for wiring details.
The torque for the electrical terminals is 11.5 in-lb (1.3 Nm). Tighten the compression nut to a torque of
22 in-lb (2.5 Nm).
14. With the PCB powered, the display should read F00. Refer to Figures 9-1 and 9-2.
15. Press the ESC button.
16. Press the Up arrow key once—If P- - is displayed, perform Step 17; if P- - is not displayed, perform
Steps 18 through 49.
Liebert® MC™ User Manual
100
System Maintenance
17. If P- - is displayed, press the ENT button to enter the P- - Menu.
The P- - Menu allows for compact setup/preparation of the unit either in the factory or in the field. Use
these functions in the table below to establish a default control configuration for the board. Items in the
preparation menu are described in Table 11-1.
Table 11-1 P-- menu items and definitions
Item ID
P01
Meaning
Default
Notes
0
Setting this value to ‘1’ will enable preparation mode. All other ‘P—‘menu
items will be disabled until this value is ‘1’. Note that control operations may
be affected during preparation mode therefore the indoor unit should be off.
Setting this value back to ‘0’ will cause the board to create new default
values based upon selections in this menu. After default values are
established the board will exit preparation mode and reboot.
Enter
Preparation
Mode
P02
Automatic VSD
Configuration
1
This item should only be used to address the VSDs for the unit. The value
entered indicates the model of the VSD:
1 – EBM
2 – Ziehl-Abegg
3 – Fans Tech
All fans must be the same model to use this parameter. When ENT is
pressed, the board will operate and power contactors for the VSDs and
assign ModBus addresses. This procedure may take up to 5 minutes to
complete.
P03
Refrigerant
Type
2
1 = R22
2 = R407C
3 = R410A
P04
Number
of Circuits
1
1 = Single Circuit
2 = Dual Circuit
P05
Liebert
Lee Temp
Option
0
0 = No Lee Temp installed
1 = Liebert Lee-Temp installed
P06
Condenser
1
0 = Small
18. Turn the power On.
19. The control board will flash F00 on the display when it has completed its boot cycle.
20. Press the ESC button.
21. Use the Up or Down arrow key until C-- is on the display.
22. Press the ENT button.
23. Use the Up or Down arrow until C03 is on the display
24. Press the ENT button.
25. Use the Up or Down arrow key to select one of three options.
Configuration
Code
Fan #
C03
Fan 1
C04
Fan 2
C05
Fan 3
C06
Fan 4
Value
0 = No Fan
1 = EBM Papst
2 = Ziehl-Abegg
26. Press the ENT button.
27. If the new value was entered into the control board, the display will flash 888.
28. Press the ESC button for C03 to show on the display.
101
Liebert® MC™ User Manual
System Maintenance
29. Repeat Steps 20 through 27 for the remaining fans’ configuration codes, C04, C05 and C06.
30. Unplug all the contactor output plugs except for the fan to be addressed. Plugs are:
• P23 = Fan 1
• P27 = Fan 2
• P28 = Fan 3
• P29 = Fan 4
31. Wait 30 seconds.
32. Use the Up or Down arrow to select one of the following parameters.
The correct parameter depends on the supplier of the fan that will be addressed.
• C00—EBM Papst fan
• C01—Ziehl-Abegg fan
33. Press the ENT button.
34. Use the Up or Down arrow to the correct fan address number. Fan 1 should be 1 (fan closest to electric
panel end). Fan 2 should be 2, etc.
35. Press the ENT button. The display will flash 888 when the command is accepted.
36. Press the ESC button for the parameter to be shown on the display.
37. Repeat Steps 30 through 36 for the rest of the fans that need to be addressed.
38. After the last fan is addressed, unplug the power plug, P24, from the control board.
39. Wait 30 seconds.
40. Plug all the contactor output plugs back into the board in their correct positions.
41. Plug P24 back into the control board.
42. Once the control board has completed its boot cycle and all the contactors are energized, wait
5 seconds.
43. Press the ESC button.
44. Use the Up or Down arrow until A-- is on the display.
45. Press ENT button.
46. Use the Up or Down arrow to see if any of the following errors are shown.
• 115: Unable to communicate with Fan 1.
• 215: Unable to communicate with Fan 2.
• 315: Unable to communicate with Fan 3.
• 415: Unable to communicate with Fan 4.
47. If any of these errors appear, check the communication wiring at the problem fan and the fan before it.
48. If the wiring is correct and properly wired to the terminal, repeat the fan addressing procedure in
Steps 30 through 36.
49. If none of the errors in Step 46 is displayed, press the ESC button.
Liebert® MC™ User Manual
102
System Maintenance
11.3.1 Verify the Fan Address
Verify that each fan has a unique address by:
1. Use the Up or Down arrow until C-- is on the display.
2. Press the ENT button.
3. In the Manual/System Control Selection parameter use the Up or Down arrow until C24 is on the
display.
4. In the Manual Control configuration parameter, press the ENT button.
5. Use the Up or Down arrow to select 0.
6. Press the ENT button. The display will read 888 if the command was accepted.
7. Press the ESC button for C24 to show on the display.
8. Use the Up or Down arrow until C34 is on the display.
9. Press ENT button.
10. If Fan 1 is running, the fans speed should be displayed in terms of percentage of full speed. If Fan 1 is
not running, 0.00 should be displayed.
11. Use the Up or Down arrow to enter 100% speed.
12. Press the ENT button. The display will read 888 if the command was accepted.
• Fan 1 should speed up to 100%, and all the other fans should stay the same speed.
13. If Fan 1 is not running or if any of the other fans also speed up to 100%, the fan-addressing procedure
(Steps 30 through 36) must be repeated.
14. Press the ESC button for the parameter to be shown on the display.
15. Repeat Steps 3 through 8 for the rest of the fans, if present.
• C35: for Fan 2.
• C36: for Fan 3.
• C37: for Fan 4.
16. All fans should be at 100% speed.
17. Use the Up or Down arrow until C24 is on the display.
18. Press the ENT button.
19. In the System Control configuration parameter, use the Up or Down arrow to select 1.
20. Press the ENT button. The display will flash 888 if the command was accepted.
21. Press the ESC button for C24 to be shown on the display.
All fans should return to a normal speed based on the pressure input and the state of indoor unit’s
compressor.
Premium Efficiency Control Board Configuration Notes
• J6 is the CANbus termination jumpers. If the condenser is the last device in the CANbus
communication line, the jumper must be placed between Pins 1 and 2 of J6. If the condenser is not the
last device in the CANbus communication line, then the jumper on J6 must be placed on Pins 2 and 3.
CANbus communication errors may occur if the jumpers are not in the correct positions.
• A jumper must be present at J2. If a jumper is not present, the control board will not boot properly
during power startup.
103
Liebert® MC™ User Manual
System Maintenance
Table 11-2 Premium Efficiency Control Board Configuration-parameter List
Default R407c
Submenu
ID
Meaning
Metric
Default R410a
Imperial Metric
Default R407C
W/LT
Default R410a
W/LT
Comments
Imperia
Imperial Metric Imperial Metric
l
C00
EBM address
1
1
1
1
C01
ZIEHL_ABEGG address
1
1
1
1
C02
FANS_TECH address
1
1
1
1
C03
EC Fan 1 model ID
0
0
0
0
C04
EC Fan 2 model ID
0
0
0
0
C05
EC Fan 3 model ID
0
0
0
0
C06
EC Fan 4 model ID
0
0
0
0
C07
System model ID
0
0
0
0
"0" = Single, "1" = Dual
C09
System refrigerant type
2
3
2
3
"2" = R407c, "3" = R410a
C10
Condenser pressure absolute max 1 18.0 bar 261 psi 28.0 bar 406 psi 18.0 bar 261 psi 28.0 bar 406 psi R407c - 17-25 bar; 247-362 psi
C11
Condenser pressure absolute max 2 18.0 bar 261 psi 28.0 bar 406 psi 18.0 bar 261 psi 28.0 bar 406 psi R410a - 25-38 bar; 363-550 psi
C12
Condenser pressure absolute min 1 12.0 bar 174 psi 18.0 bar 261 psi 14.0 bar 203 psi 20.0 bar 290 psi R407c - 11-17 bar; 160-246 psi
C13
Condenser pressure absolute min 2 12.0 bar 174 psi 18.0 bar 261 psi 14.0 bar 203 psi 20.0 bar 290 psi R410a - 16-24 bar; 232-347 psi
C14
Condenser pressure PID Kp
1.00
1.00
1.00
1.00
C15
Condenser pressure PID Kip
0.02
0.02
0.02
0.02
C16
Condenser pressure PID Kdp
C17
Refrigerant temperature max 1
35°C
95.0°F
35°C
95.0°F
35°C
95.0°F
35°C
95.0°F
C18
Refrigerant temperature max 2
35°C
95.0°F
35°C
95.0°F
35°C
95.0°F
35°C
95.0°F
0.00
0.00
0.00
Do not change unless properly
instructed.
Do not change unless properly
instructed.
0.00
C19
Refrigerant temperature min 1
25°C
77.0°F
25°C
77.0°F
25°C
77.0°F
25°C
77.0°F
C20
Refrigerant temperature min 2
25°C
77.0°F
25°C
77.0°F
25°C
77.0°F
25°C
77.0°F
Range 30 - 40°C; 86 - 104°F
Range 20 - 30°C, 68 - 86°F
C21
Refrigerant temperature PID Kp
0.36
0.36
0.36
0.36
C22
Refrigerant temperature PID Kip
162.00
162.00
162.00
162.00
C23
Refrigerant temperature PID Kdp
1.00
1.00
1.00
1.00
C24
System control state
1
1
1
1
C25
Condenser pressure setting point 1
14.0 bar 203 psi 20.0 bar 290 psi 16.0 bar 232 psi 22.0 bar 319 psi R407c - 12-18 bar; 174-261 psi
C26
Condenser pressure setting point 2
14.0 bar 203 psi 20.0 bar 290 psi 16.0 bar 232 psi 22.0 bar 319 psi R410a - 18-26 bar; 261-376 psi
C27
Lee Temp Option
C28
Minimum Speed with LeeTemp
C32
Refrigerant temp. set point 1
1.67°C
35°F
1.67°C
35°F
1.67°C
35°F
1.67°C
35°F
C33
Refrigerant temp. set point 2
1.67°C
35°F
1.67°C
35°F
1.67°C
35°F
1.67°C
35°F
0
0
10%
0
10%
"0" = Manual, "1" = Auto
"0" - No Lee Temp installed,
"1" - Lee Temp installed
0
10%
Do not change unless properly
instructed.
10%
Range 8 - 20%
Range -40 - +40°C;
-39.9 - +104°F
C34
EC Fan1 request speed
0%
0%
0%
0%
C35
EC Fan2 request speed
0%
0%
0%
0%
C36
EC Fan3 request speed
0%
0%
0%
0%
C37
EC Fan4 request speed
0%
0%
0%
0%
C38
EC Fan Reverse Request
0
0
0
"0" = Off, "1" - On
C39
EC Fan startup speed offset for
pressure mode
0
0
0
Offset to the startup speed of
the EC Fan in range
-10% to 10%
1
1
1
"0" = Metric (bar, °C)
"1" = Imperial(psi, °F)
C50-C58
0
Manually sets fan speed (RPM)
when C24 is set to "0".
Internal system use only!
C90
Prefered display units.
1
C91
Save configuration to USB flash drive. Pressing ENT will execute the function immediately.
C92
Load configuration from USB flash drive. Pressing ENT will execute the function immediately.
C98
Clear alarm history.
C99
Restore Factory Defaults except EC fan control parameters
Note: Please consult factory before making any changes to the parameter settings. Changing the parameters without proper instructions can lead
to poor system performance.
Liebert® MC™ User Manual
104
System Maintenance
Figure 11-1 Ziehl-Abegg small, medium and large fan, Liebert MC series MCS, MCM and MCL
Not used on last fan
or single-fan models
Maximum torque value
on power and GND
terminals is 22 lb-in (2.5Nm)
GND
A (RSA)
B (RSB)
ID
GND
A (RSA)
B (RSB)
ID
L1
L2
L3
+24V
+10V
D1
E1
123
Maximum torque value
on module terminals
is 11 lb-in (1.3Nm)
GND
Edge of cable outer jacket
should extend into the enclosure
only as far as necessary to make
the electrical connections
Communication cable
connection from previous
fan or electrical box
Tightening torque of the cable gland
to the enclosure and around the cable
MCS and MCM: 22 lb-in (2.5Nm);
MCL: 35 lb-in (4Nm).
Communication cable
connection to the next fan;
not used on last fan
300307DWG01
Pg. 13, Rev. 11
105
Liebert® MC™ User Manual
System Maintenance
Figure 11-2 EBM small and medium fan, Liebert MC series MCS/MCM
OUT
GND
0-10V/PWM
+10V
+20mA
+20V
GND
RSB
RSA
RSB
L3
GND
L2
RSA
123
L1
A
0-10V/PWM
Not used on last fan
or single fan models
Communication cable
connection from previous
fan or electrical box
Communication cable
connection to the next fan;
not used on last fan
DETAIL A
300307DWG01,
Pg. 16, Rev. 11
MCS, MCM
Tightening torque of the cable gland
to the enclosure and around the cable
22 lb-in (2.5Nm)
AIN 21
+20V
AIN 2U
GND
DIN3
DIN2
Figure 11-3 EBM large fan—Liebert MC series MCL
L2
DIN1
+10V
AIN 1U
RSB
GND
L3
L1
A
RSA
123
RSB
Not used on last fan
or single fan models
GND
Edge of cable outer
jacket should only
extend far enough
into enclosure to be
able to make the
electrical connections.
1
Communication cable
connection from previous
fan or electric box.
DETAIL A
Tightening torque of the cable gland
to the enclosure and around the cable
35 lb-in (4Nmn)
Communication cable
NOTE:
connection to the next fan;
The existing terminal must be removed from the end of the wires on the communication cable for all fans
not used on last fan 1.
except the last fan. The same labeled conductors of the input and output communication cable.
insert the wires into the properly marked terminal on the fan, two wires per RSA, RSB and GND terminal
300307DWG01
as shown in Detail A.
Pg. 16. Rev. 11, MCL
Liebert® MC™ User Manual
106
System Maintenance
11.4 Premium Efficiency Control Board Replacement
! WARNING
Arc flash and electric shock hazard. Open all local and remote electric power disconnect switches,
verify with a voltmeter that power is Off and wear personal protective equipment per NFPA 70E
before working within the electric enclosure.
Failure to comply can cause serious injury or death.
This kit should be installed by properly trained and qualified personnel.
11.4.1 Replacement Preparation
1. Verify that the following jumpers are installed on the new board (see Figure 11-4):
• Jumper at J4 and J6 on Pins 2 and 3.
• Jumper on J2.
• Jumper on J5 on Pins 1 and 2.
2. Locate the latest revision of the HMI parameters label, 303847P1, included with the new control board.
Figure 11-4 Jumper locations on Control Board
J4
RS485 Service
Terminal
1
A
Spare Analog
Outputs (Not Used)
1
BAR CODE
RS485
Communications to Fans
P15
A
1 P81
B
A
B
J2
1 P79
H
B
J5
TB57
P80
J6
1
P54
See
Note 1
D58
1
TB56
TB50
1
L
Communication
from Indoor
Unit
H
1
CANbus
P64
J4
1
TB49
3
1
J5
P29
1
L
Communication
from Indoor
Unit
1
P28
P19
P27
See Note 2
Fan2
Fan
Contactor
Output
LED1
LED2
P23
1
J2
J8
J7
J6
LE
Fan 1
SW1
Circuit 2
Circuit1
UP
D57 D2
DOWN
1
Call for
Cooling
Ethernet and CANbus addressing
and signal indication
ENT
1
1
Indicator lights: ON - signal present
P21
Circuit2
Fan 3
1
F3 T3.15A, 250Vac
1
ACM01M1
1
TB74
Mother
Board
CAUTION:
E1
1
Earth
Ground
Alarm & Shutdown
Circuits
P24
24VAC
NOTE:
1. J6 is the CANbus termination jumper. J4 is the RS485 service termination jumper. If the condenser is the last device in the CANbus
communication line, the jumper must be placed between Pins 1 and 2 of J6. If the condenser is not the last device in the CANbus
communication line, the jumpers on J6 must be placed on Pins 2 and 3. If the jumper is not in the correct positions, CANbus
communication errors may occur. The jumper on J4 will always be placed between Pins 1 and 2.
2. A jumper must be present at J2. If a jumper is not present, the control board will not boot properly during power startup.
107
Remote
Shutdown
1
F2 T3.15A, 250Vac
VER:A02
2010.08.10
24VAC
TB38
Circuit1
Fan 4
TB11
P67
P17
P18
Indicator lights:
ON - signal present
P20
Temperature
Inputs
CPU
Board
1
1
Ambient
1
BOOTPSWD SYS APP
X Y
No.
Circuit2
BAR CODE
Circuit1
Pressure
Inputs
ACM01U1 VER:A03 2010.08.10
3
J6
1
Service
Spare Digital
Outputs
(Not Used)
For Continued Protection Against Risk of Fire,
Replace Only With Same Type and Rating of Fuse.
Control Fuses
Max. Fuse Rating:
3A/250V
301471
Pg. 2, Rev. 4
Liebert® MC™ User Manual
System Maintenance
11.4.2 Installation
! WARNING
Risk of arc flash and electric shock hazard. Open all local and remote electric power supply
disconnect switches, verify with a voltmeter that power is Off and wear appropriate personal
protective equipment per NFPA 70E before working within the electric control enclosure or the fan
motor connection box(es). Failure to comply can cause serious injury or death.
This unit contains lethal voltage. The line side of the unit disconnect switch remains energized
when the unit disconnect switch is in the “Off” position. Use a voltmeter to verify that the line side
input electric power to the unit disconnect switch is Off before working on any electrical
components or connections.
1. Turn Off the disconnect switch on the enclosure cover.
2. Open the control enclosure cover.
3. Manually turn On the disconnect switch. Power is On and a shock hazard exists with exposure to
hazardous voltage components.
4. If the board can still be powered up and has a display, record the parameter settings. To obtain
parameters go to the C-- menu and press the Up or Down button to read and record the values for
C03-09 and C27.
5. Record all of the DIP switch positions for the CANbus DIP switch package. Retain these for setting up
the new board.
6. Record the positions of the jumpers for J2, J4, J5 and J6 on control board in the unit. Retain these for
setting up the new board.
7. Disconnect power from the Liebert MC by turning Off the main disconnect switch.
8. Use a voltmeter to verify that voltage is no longer present in the unit.
9. Remove the plugs and field-installed wires from the old board. Note the polarity for the CANbus wiring
going to P49 and P50, if present.
10. Mark wires P49-1, P49-3, etc, if they are not already marked.
11. Remove the mechanical fasteners holding the control board in place and remove the old control board.
12. Install the new control board using the fasteners removed in Step 11.
13. Reattach the plugs. Refer to the hot-stamps on the wire harnesses that correspond to the correct plug
on the board. Verify that the plugs are installed properly.
14. Change the CANbus DIP switch positions so they match the control board that was removed. If the
Liebert MC is the second condenser on the CANbus communication line, set Position 1 of the CANbus
DIP switch from On to Off.
15. Change the jumper positions for J2, J4, J5 and J6 to match the control board that was removed. If the
Liebert MC is the last device on the CANbus communication line, move the jumper at J6 from Pins 2
and 3 to Pins 1 and 2 (see Figure 11-4).
16. Power up the unit.
17. Change the parameters to match the parameters from the control board that was removed if they were
obtained from the old board in Step 4. See Step 18 if the parameters were unavailable.
18. If the old board parameters were unavailable, use the new HMI label included in kit to obtain the proper
settings. Parameters C03, C04, C05 and C06 must be programmed with the proper EC fan supplier
used on the unit.
19. Address the fans (refer to 11.3 - Fan Replacement).
Liebert® MC™ User Manual
108
System Maintenance
20. Compare the HMI label on the unit with the latest revision.
• If there are differences, clean and dry the surface of the old HMI label; attach the new label on top
of the old label, covering the old label with the new one.
21. Verify that the control board is reading pressure and temperature.
22. Verify that there are no communication alarms with the fans or with the cooling unit the Liebert MC is
serving.
23. Verify proper fan operation by adjusting the cooling unit that this condenser serves so that it calls for
cooling.
109
Liebert® MC™ User Manual
System Maintenance
Page intentionally left blank.
Liebert® MC™ User Manual
110
Preventive Maintenance Checklist
12.0 Preventive Maintenance Checklist
Source: DPN003119, Rev. 0
MC Preventive Maintenance Worksheet
Preventive Maintenance Worksheet
Inspection Date
Job Name
Indoor Unit Model #
Indoor Unit Serial Number #
Condenser/Drycooler Model
#
Condenser/Drycooler Serial
#
Room Temperature/Humidity
°
% Ambient Temperature
°
Good maintenance practices are essential to minimizing operation cost and maximizing product life. Read
and follow all applicable maintenance checks listed below. At a minimum, these checks should be
performed semi-annually. However, maintenance intervals may need to be more frequent based on sitespecific conditions. Review the unit user manual for further information on unit operation. Emerson
recommends the use of trained and authorized service personnel, extended service contracts, and
factory-certified replacement parts. Contact your local Emerson Representative for more details.
Check all that apply:
Air-Cooled Fin-and-Tube Condenser/Drycooler (if equipped)
___ 1. Coil clean free of debris
___ 2. Motor mounts tight
___ 3. Piping support/clamps secure
___ 4. Check/Re-torque wire connections
___ 5. Check contactors for pitting (replace if pitted)
___ 6. Check fuses
___ 7. Verify fan operation
___ 8. Check surge-protection device status-indicator lights (if equipped)
___ 9. Ambient thermostat settings ______
______
______
______
___ 10. Refrigerant level (Lee-Temp™ )
___ 11. Glycol level
___ 12. Glycol solution __________________%
___ 13. Water/Glycol solution flowing continuously/clean and free of debris
___ 14. Water-treatment plan established and followed for open cooling-tower application
___ 15. Check refrigerant/glycol lines for signs of leaks/repair as found
___ 16. Motor amp draw
#1
L1
L2
L3
#2
L1
L2
L3
#3
L1
L2
L3
#4
L1
L2
L3
#5
L1
L2
L3
#6
L1
L2
L3
#7
L1
L2
L3
#8
L1
L2
L3
111
Liebert® MC™ User Manual
Preventive Maintenance Checklist
Glycol Pump (if equipped)
___ 1. Check pump rotation
___ 2. Check for glycol leaks
___ 3. Pump pressures
#1
Suction
Discharge
#2
Suction
Discharge
#3
Suction
Discharge
___ 4. Amp Draw
#1
L1
L2
L3
#2
L1
L2
L3
#3
L1
L2
L3
___ 5. Verify pump changeover (if multiple pumps)
Liebert MC Condenser (if equipped)
___ 1. Coil clean
___ 2. Fans free of debris
___ 3. Fans securely mounted
___ 4. Motor bearings in good condition
___ 5. Check all refrigerant lines for vibration isolation. Support as necessary
___ 6. Check for refrigerant leaks
___ 7. Check surge-protection device (if installed) status-indicator lights
___ 8. Check/Re-torque wire connections
___ 9. Check contactors for pitting (replace if pitted)
___ 10. Verify operation sequence/set points
___ 11. Charge verification:
___ a. Outdoor Ambient Temperature __________
___ b. Subcooling __________
___ c. Indoor-unit Return-air Temperature __________
___ d. Sight-glass level (if Lee-Temp or pumped refrigerant) __________
___ 12. Motor amp draw
#1
L1
L2
L3
(L1 and L2 on Fan Speed Control Motor)
#2
L1
L2
L3
#3
L1
L2
L3
#4
L1
L2
L3
#5
L1
L2
L3
#6
L1
L2
L3
#7
L1
L2
L3
#8
L1
L2
L3
Liebert® MC™ User Manual
112
Preventive Maintenance Checklist
Liebert EconoPhase Pumped-refrigerant Economizer (if equipped)
___ 1. Check for refrigerant leaks
___ 2. Check/Re-torque wire connections
___ 3. Check contactors for pitting (replace if pitted)
___ 4. Verify pump-speed control operation
___ 5. Check pump mounting
113
Liebert® MC™ User Manual
Preventive Maintenance Checklist
Maintenance Notes
Name
Signature
Company
Make photocopies for your records. Compare readings/information to previous maintenance worksheet.
To locate your local Liebert representative for Liebert engineered parts, check the Liebert Web site :
www.liebert.com or Ccall 1-800-Liebert.
Liebert® MC™ User Manual
114
Technical Support / Service
Web Site
www.liebert.com
Monitoring
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
[email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims
all liability for damages resulting from use of this information or for any errors or omissions.
© 2016 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to changewithout notice.
® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-19536_REV4_4-16
590-1329-501A
Emerson Network Power
Liebert
www.emersonnetworkpower.com