Current sensitive relays are available for single and
three phase applications. Voltage controlled
overcurrent relays protect generators against fault
currents below the full rated value, when the fault
produces a voltage drop as in the case of short
circuits or grounds. Phase balance relays are available to sense and control unbalanced current flow in
three phase systems. Current differential relays
operate when the differential between two currents
exceeds preset values. Over/under current phaseband relays are also available.
31
3 7 /2
/8
3.0
23
3 1 /4
/2
See next page for WCT can
dimensions
Typical Curves (WC1 Series)
8
6
11 /64" DIA.
4 MTG. HOLES
4
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
2
PART NUMBER SELECTION
Time Delay
0
Standard Time Delay (WC1 Series)
A fixed inverse time delay is incorporated in all
overcurrent relays and is represented by the typical curves shown.
Adjustable Time Delay (WCT1 Series)
The time delay is field adjustable. The standard time
delay can be increased by any value between 0.5 and 20 seconds.
PRODUCT SPECIFICATIONS
Part Number
WC1 & WCT1
Line Current ..................................... Single Phase, AC current, 50-400 Hz Direct or from CT
Control Voltage ................................ See Part Number Selection
Trip Point .......................................... Screwdriver adjustable. Adjustment range in
accordance with ordering information.
Pick-Up to Drop-Out Differential ..... Approximately 0.1 amp.
Overcurrent Allowance .................... Maximum of 500% for 0.25 seconds
Surge Withstand Capabiliy .............. In compliance with C37.90B ANSI/IEEE
Operating Temperature .................... -40oC to +70oC
Temperature Drift ............................. ± .05%
Burden .............................................. Current input: 1.2 VA, Control voltage: 2.5 VA
Contact Ratings ................................ One set, N.O., One set N.C.
5 amp resistive at 120 VAC or 28 VDC
Notes:
1. Remove black screws for access to the current pick-up and the time delay adjustment.
2. Clockwise rotation of the pick-up adjustment will raise the current trip point.
3. Clockwise rotation of the time delay adjustment, (Type WCT1 only) will increase the time delay.
0
0.1
0.2
0.3
0.4
Pick-Up Time Delay
PART NUMBER SELECTION
Sample Part No.
WCT1-48DC-5-B
Type:
WC1 = Per Time Curves
WCT1 = Adjustable Time Delay
Control Voltage (+/- 15%)
26 DC
48 DC
125 DC
120 AC
230 AC
380 AC
460 AC
Trip Adjustment Range
1 = .2 amp - 1 amp
5 = 1 amp to 5 amp
10 = 2 amp to 10 amp
Other Options
A = Two normally open contacts
B = Two normally closed contacts
See next pages for 3-phase types and consult factory for
additional models.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
33
Current Sensitive Relays
WILMAR™ Protective Relays – WC3 & WCT3 Series, Overcurrent
Function: 50/51
• ANSI/IEEE C37.90-1978
TERMINAL STRIPS
#6 - 32 SCREWS
4.0
3.0
• UL file No. E58048
• CSA file No. LR61158
Current sensitive relays are available for single and
three phase applications. Voltage controlled
overcurrent relays protect generators against fault
currents below the full rated value, when the fault
produces a voltage drop as in the case of short
circuits or grounds. Phase balance relays are
available to sense and control unbalanced current
flow in three phase systems. Current differential
relays operate when the differential between two
currents exceeds preset values. Over/under current
phase-band relays are also available.
4.0
1 /2
4 7 /8
4
3
7 /8
4
21 /
32
See previous page for WC can
dimensions
Typical Curves (WC3 Series)
8
6
11/ 64 " DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Time Delay
Standard Time Delay (WC3 Series)
A fixed inverse time delay is incorporated in all
overcurrent relays and is represented by the typical
curves shown.
Adjustable Time Delay (WCT3 Series)
The time delay is field adjustable. The standard time
delay can be increased by any value between 0.5 and 20 seconds.
PRODUCT SPECIFICATIONS
Part Number
WC3 & WCT3
Line Current ..................................... Three Phase, AC current, 50-400 Hz Direct or from CT
Control Voltage ................................ See Part Number Selection
Trip Point .......................................... Screwdriver adjustable. Adjustment range in
accordance with ordering information.
Pick-Up to Drop-Out Differential ..... Approximately 0.1 amp
Overcurrent Allowance .................... Maximum of 500% for 0.25 seconds
Surge Withstand Capabiliy .............. In compliance with the requirements of ANSI/IEEE
Operating Temperature .................... -40oC to +70oC
Temperature Drift ............................. ± 0.05%/oC
Burden .............................................. Current input: 1.2 VA, Control voltage: 2.5 VA
Contact Ratings ................................ One set, N.O., One set N.C.
5 amp resistive at 120 VAC or 28VDC
Notes:
1. Remove black screws for access to the current pick-up and the time delay adjustment.
2. Clockwise rotation of the pick-up adjustment will raise the current trip point.
3. Clockwise rotation of the time delay adjustment, (Type WCT3 only) will increase the time delay.
34
4
2
PART NUMBER SELECTION
0
0
0.1
0.2
0.3
0.4
Pick-Up Time Delay
PART NUMBER SELECTION
Sample Part No.
WCT3-48DC-5A
Type:
WC3 = Per Time Curves
WCT3 = Adjustable Time Delay
Control Voltage (+/- 15%)
26 DC
48 DC
125 DC
120 AC
230 AC
380 AC
460 AC
Trip Adjustment Range
1 = .2 amp to 1 amp
5 = 1 amp to 5 amp
10 = 2 amp to 10 amp
Other Options
A = Two normally open contacts
B = Two normally closed contacts
See previous page for 1-phase models and consult factory
for additional models.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)