Download

Unregulated power supplies
Contents
Unregulated power supplies
Unregulated power supplies
Overview
D.2
compactPower
D.4
D
2003670000
D.1
Unregulated power supplies
Unregulated power supplies – Overview
Unregulated power supplies – compactPower
Compact power supply units are important links in the
power supplies for controllers. They are used where
processes or control voltages are required that vary from the
mains voltage. Transformers provide the electrical isolation
between the input circuit and the output circuit.
The minimum requirement (to VDE 0550) is 2,000 V.
Screw terminals secure the input-side connection to the
mains. The single-phase devices are rated for a nominal
voltage of ∼230 ± ∼15 V, or ∼400 V ± ∼15 V, 50/60 Hz,
the 3-phase devices for 3 x 400 V ± 5 %. The secondary
DC voltage from the transformer is conducted to a bridge
rectifier where it is rectified.
D
Single-phase unregulated power supplies
D.2
The pulsating DC voltage is then fed from the rectifier and
filtered to a low residual ripple by means of an electrolytic
capacitor.
This DC voltage is then fed to the output terminal. These
are designed as pluggable screw terminals. A varistor is
integrated in the output circuitry to attenuate voltage peaks.
The operating status is indicated by means of a green LED
via the output circuit. Devices with 600 W and higher are
equipped with a fan.
Three-phase unregulated power supplies
2003670000
Unregulated power supplies
Unregulated power supplies – Overview
Well-balanced spectrum for optimum economy
Block diagram for single-phase devices CP NT
The output currents of these practical products are defined
by way of two ambient temperatures.
Size selection is based on the maximum effectiveness of the
components.
INPUT
+15 V
0V
–15 V
230 V
400 V
PE
Adapted to standard voltages in accordance
with IEC 38
By choosing the appropriate terminals, the ± 15 V tapping
capability allows the single-phase devices to be connected
to six different nominal AC voltages: 215, 230, 245, 385,
400, 415 V.
The ± 5 % tapping capability allows the 3-phase devices to
be connected to three different nominal voltages: 380, 400,
415 V.
Reliable short-circuit and overload protection
Integrated on the secondary side in device sizes up to
CP NT 192 W, the FKS fuse protects against overloads
and shortcircuits. For the devices CP NT 264 W and
CP NT 432 W, this protection is achieved by means of a
thermostatic switch built into the transformer.
.
.
.
.
.
D
Block diagram for 3-phase devices
CP NT3 250 / 400 / 500 W
INPUT
+5% 400 V –5% +5% 400 V –5% +5% 400 V –5%
3x
OUTPUT
+
+
24V DC
=
130°
PE
-
~
Block diagram for 3-phase devices
CP NT3 600 / 750 / 1.000 W
Easy mounting
Keyhole assembly simplifies mounting and saves time. A
snap-on fixing attachment for 35 mm DIN rails is available as
an accessory for single-phase devices up to 144 W.
Simply plugged into the device and secured with two
screws, it ensures easiest possible mounting!
OUTPUT
+
+
24V DC
INPUT
+5% 400 V –5% +5% 400 V –5% +5% 400 V –5%
3x
=
130°
M
PE
~
OUTPUT
+
+
24V DC
0V
Fail
Transformers, vacuum-impregnated, painted black
•
•
•
•
•
No humming
Moisture cannot ingress into the windings
Windings mechanically secured
Improved heat dissipation from the windings
Good heat dissipation
Unregulated power supplies
single-phase
Unregulated power supplies
3-phase
2003670000
D.3
Unregulated power supplies
compactPower
compactPower single-phase
CP NT 36
CP NT 72
INPUT
OUTPUT
+15V
0V
-15V
230V
400V
PE
D
.
.
.
.
INPUT
+
+
24VDC
+15V
0V
-15V
-
230V
400V
PE
.
OUTPUT
+
+
24VDC
.
.
.
.
.
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C
Output current at 55°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Mounting position, installation notice
Installation advice
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
230 V/ 400 V ±15 V
0.35 A/ 0.2 A
50/ 60 Hz
0.1 A / 0.06 A
0.63 A / 0.315 A time-lag
230 V/ 400 V ±15 V
0.56 A/ 0.32 A
50/ 60 Hz
0.13 A / 0.08 A
0.1 A / 0.63 A time-lag
24 V SELV
1.5 A
1A
36 W
<5%
3 A time-lag flat cable-lug fuse
Varistor
24 V SELV
3A
2.5 A
72 W
<5%
7.5 A time-lag flat cable-lug fuse
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...55 °C
-20 °C...80 °C
80%
Arbitrary, horizontally, on terminal rail TS 35
Direct mounting, TS 35 with clip-on plate
Green LED
1.5 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
-20 °C...55 °C
-20 °C...80 °C
83%
Arbitrary, horizontally, on terminal rail TS 35
Direct mounting, TS 35 with clip-on plate
Green LED
2.1 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
Input
2.5 / 0.13 / 2.5
68 / 78 / 123
Input
2.5 / 0.13 / 2.5
85 / 84 / 125
Type
CP NT 36W 24V 1.5A
Output
2.5 / 0.5 / 4
68 / 78 / 123
Qty.
1
Order No.
8575260000
Type
CP NT 72W 24V 3A
Output
2.5 / 0.5 / 4
85 / 84 / 125
Qty.
1
Order No.
8575270000
Note
Accessories
Note
D.4
Clip-in plate for TS 35: 8588920000
Clip-in plate for TS 35: 8588920000
2003670000
compactPower single-phase
CP NT 144
CP NT 192
INPUT
OUTPUT
+15V
0V
-15V
230V
400V
PE
Unregulated power supplies
compactPower
.
.
.
.
INPUT
+
+
24VDC
+15V
0V
-15V
-
230V
400V
PE
.
OUTPUT
+
+
24VDC
.
.
.
.
.
D
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C
Output current at 55°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Mounting position, installation notice
Installation advice
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
230 V/ 400 V ±15 V
0.95 A/ 0.55 A
50/ 60 Hz
0.33 A / 0.19 A
1.6 A / 1.0 A time-lag
230 V/ 400 V ±15 V
1.3 A/ 0.7 A
50/ 60 Hz
0.3 A / 0.16 A
2.0 A / 1.25 A time-lag
24 V SELV
6A
5A
144 W
<5%
10 A time-lag flat cable-lug fuse
Varistor
24 V SELV
8A
7A
192 W
<5%
15 A time-lag flat cable-lug fuse
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...55 °C
-20 °C...80 °C
88%
Arbitrary, horizontally, on terminal rail TS 35
Direct mounting, TS 35 with clip-on plate
Green LED
3.1 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
-20 °C...55 °C
-20 °C...80 °C
90%
Input
2.5 / 0.13 / 2.5
92 / 96 / 135
Input
2.5 / 0.13 / 2.5
105 / 105 / 145
Type
CP NT 144W 24V 6A
Direct mounting
Green LED
4.3 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
Output
2.5 / 0.5 / 4
92 / 96 / 135
Qty.
1
Order No.
8575280000
Type
CP NT 192W 24V 8A
Output
2.5 / 0.5 / 4
105 / 105 / 145
Qty.
1
Order No.
8575300000
Note
Accessories
Note
2003670000
Clip-in plate for TS 35: 8588920000
D.5
Unregulated power supplies
compactPower
compactPower single-phase
CP NT 264
CP NT 432
INPUT
OUTPUT
+15V
0V
-15V
230V
400V
PE
D
.
.
.
.
INPUT
+
+
24VDC
+15V
0V
-15V
-
230V
400V
PE
.
OUTPUT
+
+
24VDC
.
.
.
.
.
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C
Output current at 55°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Installation advice
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
230 V/ 400 V ±15 V
1.8 A/ 1 A
50/ 60 Hz
0.5 A / 0.28 A
3.15 A / 1.6 A time-lag
230 V/ 400 V ±15 V
2.5 A/ 1.3 A
50/ 60 Hz
0.54 A / 0.31 A
4.0 A / 2.0 A time-lag
24 V SELV
11 A
10 A
264 W
<5%
Thermostatic switch
Varistor
24 V SELV
18 A
15 A
432 W
<5%
Thermostatic switch
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...55 °C
-20 °C...80 °C
93%
Direct mounting
Green LED
6.1 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
-20 °C...55 °C
-20 °C...80 °C
95%
Direct mounting
Green LED
9.1 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
CE; cULus; EAC
Input
2.5 / 0.13 / 2.5
113 / 120 / 165
Input
2.5 / 0.13 / 2.5
135 / 135 / 185
Type
CP NT 264W 24V 11A
Output
2.5 / 0.5 / 4
113 / 120 / 165
Qty.
1
Order No.
8575310000
Type
CP NT 432W 24V 18A
Output
2.5 / 0.5 / 4
135 / 135 / 185
Qty.
1
Order No.
8575320000
Note
Accessories
Note
D.6
2003670000
compactPower 3-phase
CP NT3 250
Unregulated power supplies
compactPower
CP NT3 400
INPUT
+5% 400V -5% +5% 400V - 5% +5% 400V -5%
OUTPUT
3x
=
130°
PE
~
INPUT
+
+
24VDC
-
+5% 400V -5% +5% 400V - 5% +5% 400V -5%
OUTPUT
3x
=
130°
PE
~
+
+
24VDC
-
D
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Input fuse
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C / 60°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Installation advice
Fan signal
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
3 x 400 V ±5 %
0.5 A
50/ 60 Hz
0.1 A
3 x primary thermostatic switch
3 x 1.0 A time-lag
3 x 400 V ±5 %
0.75 A
50/ 60 Hz
0.11 A
3 x primary thermostatic switch
3 x 1.2 A time-lag
24 V SELV
11 A / 10 A
250 W
<2%
External 10 A time-lag
Varistor
24 V SELV
18 A / 16 A
400 W
<2%
External 16 / 18 A slo-blo
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...60 °C
-20 °C...80 °C
76%
Direct mounting
No integrated fan
Green LED
4.7 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; EAC
-20 °C...60 °C
-20 °C...80 °C
77%
Direct mounting
No integrated fan
Green LED
6.9 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; EAC
Input
2.5 / 0.5 / 2.5
185 / 84 / 192
Input
2.5 / 0.5 / 2.5
220 / 88 / 213
Condensation not allowed
Type
CP NT3 250W 24V 10A
Output
6 / 0.5 / 6
185 / 84 / 192
Qty.
1
Condensation not allowed
Order No.
8628620000
Type
CP NT3 400W 24V 15A
Output
6 / 0.5 / 6
220 / 88 / 213
Qty.
1
Order No.
8628630000
Note
Accessories
Note
2003670000
D.7
Unregulated power supplies
compactPower
compactPower 3-phase
CP NT3 500
CP NT3 600
INPUT
+5% 400V -5% +5% 400V - 5% +5% 400V -5%
OUTPUT
3x
=
130°
PE
~
D
INPUT
+
+
24VDC
-
+5% 400V -5% +5% 400V -5% +5% 400V -5%
OUTPUT
3x
=
130°
M
PE
+
+
24VDC
0V
Fail
~
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Input fuse
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C / 60°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Installation advice
Fan signal
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
3 x 400 V ±5 %
0.9 A
50/ 60 Hz
0.13 A
3 x primary thermostatic switch
3 x 1.6 A time-lag
3 x 400 V ±5 %
1.2 A
50/ 60 Hz
0.15 A
3 x primary thermostatic switch
3 x 2 A time-lag
24 V SELV
22 A / 20 A
500 W
<2%
External 20 / 22 A slo-blo
Varistor
24 V SELV
26 A / 25 A
600 W
<2%
External 25 / 26 A slo-blo
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...60 °C
-20 °C...80 °C
78%
Direct mounting
No integrated fan
Green LED
10 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; cULus; EAC
-20 °C...60 °C
-20 °C...80 °C
78%
Direct mounting
Open collector <30 V/ <5 mA during interference
Green LED
11 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; EAC
Input
2.5 / 0.5 / 2.5
220 / 108 / 215
Input
2.5 / 0.5 / 2.5
230 / 108 / 212
Condensation not allowed
Type
CP NT3 500W 24V 20A
Output
6 / 0.5 / 6
220 / 108 / 215
Qty.
1
Condensation not allowed
Order No.
8628650000
Type
CP NT3 600W 24V 25A
Output
6 / 0.5 / 6
230 / 108 / 212
Qty.
1
Order No.
8628660000
Note
Accessories
Note
D.8
2003670000
compactPower 3-phase
CP NT3 750
Unregulated power supplies
compactPower
CP NT3 1000
INPUT
+5% 400V -5% +5% 400V -5% +5% 400V -5%
OUTPUT
3x
=
130°
M
PE
0V
Fail
~
INPUT
+
+
24VDC
+5% 400V -5% +5% 400V -5% +5% 400V -5%
OUTPUT
3x
=
130°
M
PE
+
+
24VDC
0V
Fail
~
D
Technical data
Input
Input voltage
Input current
Input frequency
No-load input current
Input fuse
Ext. Back-up fuse
Output
Output voltage
Output current at 40°C / 60°C
Output power
Max. residual ripple
Fuse, max.
Protective circuit, load side
Insulation coordination (EN 50178)
Electric shock protection
Insulation strength
Insulation class
Protection degree
Class of protection
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Installation advice
Fan signal
Status indication
Weight
Standards
EMC standards
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
Ordering data
Screw connection
3 x 400 V ±5 %
1.4 A
50/ 60 Hz
0.16 A
3 x primary thermostatic switch
3 x 2.5 A time-lag
3 x 400 V ±5 %
1.8 A
50/ 60 Hz
0.14 A
3 x primary thermostatic switch
3 x 3.15 A time-lag
24 V SELV
32 A / 30 A
750 W
<2%
External 30 / 32 A slo-blo
Varistor
24 V SELV
42 A / 40 A
1000 W
<2%
External 40 / 42 A slo-blo
Varistor
acc. to BGV A3
4 kV
B
IP 20
I
acc. to BGV A3
4 kV
B
IP 20
I
-20 °C...60 °C
-20 °C...80 °C
77%
Direct mounting
Open collector <30 V/ <5 mA during interference
Green LED
14 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; EAC
-20 °C...60 °C
-20 °C...80 °C
77%
Direct mounting
Open collector <30 V/ <5 mA during interference
Green LED
18 kg
DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG
EN 61000-6 /-2, -3
cCSAus; CE; EAC
Input
2.5 / 0.5 / 2.5
270 / 121 / 255
Input
2.5 / 0.5 / 2.5
280 / 122 / 275
Condensation not allowed
Type
CP NT3 750W 24V 30A
Output
6 / 0.5 / 6
270 / 121 / 255
Qty.
1
Condensation not allowed
Order No.
8628670000
Type
CP NT3 1000W 24V 40A
Output
10 / 0.5 / 10
280 / 122 / 275
Qty.
1
Order No.
8628680000
Note
Accessories
Note
2003670000
D.9
D
D.10
2003670000
Unregulated power supplies