Switched-mode and uninterruptible power supplies, and electronic fuses Catalogue 2015/2016 Let’s connect. Power supply Switch-Mode and Uninterruptible Power Supplies, Electronic Fuses Contents Switch-Mode and Uninterruptible Power Supplies, Electronic Fuses Catalogue 4.3 A Switch-mode power supplies B Uninterruptible power supplies (UPS) C Fuse protection for 24 V DC circuits D Unregulated power supplies Appendix Electrical cabinet socket outlet E Glossary/Technical appendix W Index 2003670000 X Index Type / Index Order No. Addresses worldwide I Product overview Power supplies – Overview II connectPower 1ph PROeco connectPower 3ph PROeco connectPower PROeco diode modules • Single-phase switched-mode power supply modules • Slim design • Large temperature range from –25 °C to 70 °C • Three-coloured LED indicators for simple error detection • Advanced visual warning at 90 % rated output current • International approvals • 3-phase switched-mode power supply modules • Slim design • Large temperature range from –25 °C to 70 °C • Three-coloured LED indicators for simple error detection • Advanced visual warning at 90 % rated output current • International approvals • Diode module for 100 % decoupling of switched-mode power supply modules • Optimum doubling of output power • Redundancy operation • Up to 40 A output current can be set • International approvals connectPower 1ph PROmax connectPower 3ph PROmax connectPower PRO-M Extension modules • Single-phase switched-mode power supply modules • Very slim design • High degree of efficiency • Power category 70...1,000 W • Up to five devices can be connected in parallel without a diode module • International approvals • 3-phase switched-mode power supply modules • Very slim design • High degree of efficiency • Power category 120...1,000 W • Up to five devices can be connected in parallel without a diode module • International approvals • Capacity module for increasing the peak current • Diode modules for redundant construction • Relay module for monitoring the output voltage connectPower PRO-M Application solutions connectPower 1ph PRO-H connectPower PRO-H Multi-phase • Wide-range input 85...264 V AC 80...430 V DC • Alarm relay • Metal snap-on foot • International approvals • Single-phase switched-mode power supplies • High MTBF values • Cl. I Div. 2 + ATEX • Performance class: 70 to 600 W • Output: 12, 24, 36 and 48 V DC • Multi-phase switched-mode power supplies • 85...132 / 187...550 V AC • UL approval • Performance class: 180 to 600 W 2003670000 Product overview connectPower PRO-H Redundancy modules connectPower PRO-E connectPower 1ph INSTAPOWER • 15 A or 25 A • 100 % load sharing • Remote On/Off • International approvals • Cl. I Div. 2 + ATEX • Wall mounting • Flat design • Metal housing • Performance classes from 25 W to 350 W • Universal input and output voltages • Single-phase switched-mode power supply modules for the distribution board • Compact form • Power category 24 and 48 W • Universal input and output voltage 5…48 V • International approvals connectPower 1ph WAVEPOWER connectPower DC/DC converters connectPower UPS control unit • Single-phase switched-mode power supply unit • Slim design 22.5 mm • Power category 12 W • International approvals • Compact form • Metal housing • Universal input and output voltage of 5 V to 48 V • International approvals • Two 24 V models in 10 A/20 A and 40 A • Temperature-compensated charging feature, for a long battery life • Integrated battery diagnostics including continuous availability test • Status relay and additional transistor outputs for remote monitoring • Convenient LED displays for easy error analysis connectPower battery module connectPower buffer module compactPower 1ph unregulated power supplies • Maintenance-free, lead-acid batteries from 1.3 Ah to 17 Ah • Integrated temperature sensor for optimal battery charging • Integrated fuse for reliable activation • Support capacity up to 40 A / 30 min or 10 A / 90 min • Robust metal housing for wall mounting • Maintenance-free UPS on a capacitor basis, with a capacity to support 20 A / 200 ms • Parallel switching to increase the output current or support time • Status notification via LED and relay contact • Single-phase unregulated power supplies • Compact form • Standard voltage ~230/400 V to IEC 38 +/– 15 V tap • Reliable short-circuit and overload protection 2003670000 III Product overview Power supplies – Overview IV compactPower 3ph unregulated power supplies WAVEGUARD Electrical cabinet socket outlet • 3-phase unregulated power supplies • Compact form • Nominal voltage to IEC 38 +/- 5 V tap • Reliable short-circuit and overload protection • Electronic fusing • Visual fault indication and potential-free contact • Reset input • Compact form • Simple installation in electrical cabinet • TS 35 module can be rail mounted • VDE mark of conformity • Two-pole with earthing contact 2003670000 2003670000 V Product overview Find the perfect product to meet your requirement Our extensive portfolio of power supplies at a glance 85–264 85–264 85–264 85–264 85–264 340–575 340–575 340–575 340–575 85–264 85–264 85–264 85–264 85–277 85–277 85–277 85–277 85–277 85–277 3 x 320–3 x 575 3 x 320–3 x 575 3 x 320–3 x 575 3 x 320–3 x 575 85–277 85–277 85–277 85–277 85–277 85–277 85–264 85–132/187–264 85–264 85–264 85–132/187–264 85–132/187–264 85–132/187–264 85–264 85–132/187–264 85–132/187–264 85–132/187–264 85–132/187–550 85–132/187–550 85–132/187–550 80–370 80–370 80–370 80–370 80–370 450–870 450–870 450–870 450–870 80–370 80–370 80–370 80–370 80–370 80–370 80–370 80–370 80–370 80–370 450–800 450–800 450–800 450–800 80–370 80–370 80–370 80–370 80–370 80–370 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a NO 24 3 72 NO 24 5 120 NO 24 10 240 NO 24 20 480 NO 24 40 960 NO 24 5 120 NO 24 10 240 > 55 NO 24 20 480 NO 24 40 960 NO 12 6 72 NO 12 10 120 NO 48 5 240 NO 48 10 480 CO 24 3 72 CO 24 5 120 CO 24 7.5 180 CO 24 10 240 CO 24 20 480 CO 24 40 960 24 5 120 120% CO CO 24 10 240 > 60 300% CO 24 20 480 @ 1 s CO 24 40 960 CO 5 14 70 CO 12 6 72 CO 12 10 120 CO 48 5 240 CO 48 10 480 CO 48 20 960 NO 12 6 70 NO 12 12 140 NO 24 3.8 90 NO 24 3.8 90 NO 24 7.5 180 NO 24 15 360 NO 24 25 600 > 40 NO 48 2 96 NO 48 4 192 NO 48 7.5 360 NO 48 12.5 600 NO 24 7.5 180 NO 24 15 360 NO 24 25 600 ● 87 ● 87 ● 90 ● 91 ● 93 ● 87 –25 ● 88 > 0.5 II to ● +70 89 ● 90 ● 90 ● 90 ● 90 ● 90 ● 90 ● 90 ● 91 ● 91 ● –25 91.5 ● to 92.5 ● 90 +70 ● 91 > 0.5 III ● 91.5 SEMI F47 ● Start-up 92.5 @ ● 86 ● –40°C 89 ● 89 Cl1Div2 ● 91 ● 91.5 Some not yet awarded ● 92.5 (status July 2014) 82 85 85 85 88 87 –25 89 to > 1.8 II 87 +70 90 89 91 88 Cl1Div2 88 88 % % u % Order No. Field cabinets Small and series machine construction Machine construction and plant manufacture Simple process applications Process industry Energy technology Power distribution Marine engineering Approvals Recommendation for application Surge category MTBF time [Mh] Efficiency [%] Temperature range [°C] Side-by-side connectability Status relay Additional functions Power boost [60 s] Derating at [°C] Power rating [V] Rated current [A] Rated voltage [V] 1 1 1 1 1 3 3 3 3 1 1 1 1 1 1 1 1 1 1 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1.2 1.2 1.2 Output side DC input voltage [V] PRO ECO 72 W 24 V 3 A PRO ECO 120 W 24 V 5 A PRO ECO 240 W 24 V 10 A PRO ECO 480 W 24 V 20 A PRO ECO 960 W 24 V 40 A PRO ECO3 120 W 24 V 5 A PRO ECO3 240 W 24 V 10 A PRO ECO3 480 W 24 V 20 A PRO ECO3 960 W 24 V 40 A PRO ECO 72 W 12 V 6 A PRO ECO 120 W 12 V 10 A PRO ECO 240 W 48 V 5 A PRO ECO 480 W 48 V 10 A PRO MAX 72 W 24 V 3 A PRO MAX 120 W 24 V 5 A PRO MAX 180 W 24 V 7,5 A PRO MAX 240 W 24 V 10 A PRO MAX 480 W 24 V 20 A PRO MAX 960 W 24 V 40 A PRO MAX3 120 W 24 V 5 A PRO MAX3 240 W 24 V 10 A PRO MAX3 480 W 24 V 20 A PRO MAX3 960 W 24 V 40 A PRO MAX 70 W 5 V 14 A PRO MAX 72 W 12 V 6 A PRO MAX 120 W 12 V 10 A PRO MAX 240 W 48 V 5 A PRO MAX 480 W 48 V 10 A PRO MAX 960 W 48 V 20 A CP T SNT 70 W 12 V 6 A CP T SNT 140 W 12 V 12 A CP T SNT 90 W 24 V 3.8 A CP T SNT 90 W 24 V 3.8 A CL2 CP T SNT 180 W 24 V 7.5 A CP T SNT 360 W 24 V 15 A CP T SNT 600 W 24 V 25 A CP T SNT 90 W 48 V 2 A CP T SNT 180 W 48 V 4 A CP T SNT 360 W 48 V 7.5 A CP T SNT 600 W 48 V 12.5 A CP T SNT2 180 W 24 V 7.5 A CP T SNT2 360 W 24 V 15 A CP T SNT2 600 W 24 V 25 A AC input voltage [V] Phases Input side Description A.30 PRO-H A.14 PROmax A.4 PROeco Page Series / family ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● 1469470000 1469480000 1469490000 1469510000 1469520000 1469530000 1469540000 1469550000 1469560000 1469570000 1469580000 1469590000 1469610000 1478100000 1478110000 1478120000 1478130000 1478140000 1478150000 1478170000 1478180000 1478190000 1478200000 1478210000 1478220000 1478230000 1478240000 1478250000 1478270000 1105430000 1105440000 1105790000 1194410000 1105810000 1105820000 1105840000 1194420000 1105850000 1105860000 1105870000 1194480000 1194490000 1194310000 NO = NO contact CO = CO contact Start-up @ –40°C = In the range of –40 to –25°C the device starts, but some technical parameter may differ (i. e., ripple-voltage). VI 2003670000 Product overview B.4 USV A.39 A.12 Status relay Parallel connection option Side-by-side connectability 22.5–29.5 10 240 ● ≤5 ● 1313320010 –25 to +70 24 20 480 ● ● CP DC UPS 24 V 20 A/10 A 20–30 Uin–0.3 V 20/10 480/240 ● ● 1370050010 CP DC UPS 24 V 40 A 20–30 Uin–0.3 V 40 960 ● ● 1370040010 24 24 24 24 24 10 A / 11.3 min. 10 A / 11.3 min. 10 A / 26.5 min. 10 A / 51 min. 10 A / 81 min. 1.3 Ah 3.4 Ah 7.2 Ah 12 Ah 17 Ah CP A BATTERY 24 V DC 1,3 Ah CP A BATTERY 24 V DC 3,4 Ah CP A BATTERY 24 V DC 7,2 Ah CP A BATTERY 24 V DC 12 Ah CP A BATTERY 24 V DC 17 Ah ≤2 ≤2 ≤2 ≤2 ≤2 ● ● ● ● ● CP T RM 10 (PRO-H redundancy module) 24 24 24–27 15 ● CP T RM 20 (PRO-H redundancy module) 24 24 24–27 25 ● CP DM 10 (diode module) 10–40 UIN–0.7 10 CP DM 20 (diode module) 10–40 UIN–0.7 20 CP M DM 20 (diode module) 18–30 UIN–0.7 20 ● ≤5 ● CP M DM 40 (diode module) 18–30 UIN–0.7 40 ● ≤5 ● CP M CAP (capacity module) 18–30 UIN 40 A/1 ms ● ≤5 ● 1 1 1.5 1.5 2 28 24 22.5 18 10 –10 to +55 ● ● ● ● ● CP SNT 24 W 28 V 1 A CP SNT 24 W 24 V 1 A CP SNT 24 W 15 V 1,5 A CP SNT 24 W 12 V 1,5 A CP SNT 24 W 5 V 2 A 85–265 85–265 85–265 85–265 85–265 120–300 120–300 120–300 120–300 120–300 28 24 15 12 5 CP SNT 25 W 5 V 5 A 85–264 110–370 5 4–8 5 25 ≤3 ● CP SNT 48 W 12 V 4 A 85–264 110–370 12 9–15 4 48 ≤3 ● CP SNT 48 W 24 V 2 A 85–264 110–370 24 15–28 2 48 ≤3 ● CP SNT 48 W 48 V 1A 85–264 110–370 48 46–55 1 48 ≤3 ● 2003670000 0 to +40 –25 to +70 A.23 A.24 A.60 INSTAPOWER Approvals (all CE) Power rating [W] 24 Temperature range [°C] Rated current [A] 18–31.2 Order No. 22.5–30 CP DC BUFFER 24 V 20 A Ergänzungsmodule Additional functions Adjustable range [V] CP DCDC 250 W 24 V 10 A Output Rated voltage [V] AC input voltage [V] Input DC input voltage [V] A.68 DC/DC Page Description Series / family 1251220000 1406930000 1251070000 1251080000 1251090000 1251110000 1105880000 1105890000 8710620000 8768650000 1222210000 –25 to +70 1222220000 1222240000 –20 to +50 9928890028 9928890024 9928890015 9928890012 9928890005 8754960000 –10 to +70 8754970000 8739140000 8879230000 VII VIII 2003670000 Switch-mode power supplies Contents Switch-mode power supplies Switch-mode power supplies 2003670000 Overview A.2 connectPower PROeco A.4 connectPower PROmax A.14 connectPower PRO-H A.30 connectPower PRO-E A.44 connectPower INSTAPOWER A.60 connectPower WAVEPOWER A.67 connectPower DC/DC converter A.68 A A.1 Switch-mode power supplies Switch-mode power supplies – Overview Switch-mode power supplies A The switch-mode power supplies feature a high degree of efficiency, compact dimensions and minimal heat generation. switch-mode power supplies can be depended upon for all applications because of their high efficiency and their resistance to both short circuits and overloads. They are an excellent, reliable solution for providing power in all automation applications – safely providing 24 V DC voltage. Weidmüller offers a system of one- and three-phase swtichmode power supplies especially for the PROmax family. These can be expanded with additional modules to create whole system solutions. The appropriate system can be assembled for any type of application: with redundancy circuits containing decoupled outputs, monitoring of the output voltage or triggering of circuit breakers. The different product series are optimised for the automation industry: they feature Ex approvals for the processing industry, a flat shape perfect for distribution tasks within buildings, or provide decentralised control voltages. All-purpose usage: with a wide range of AC/DC inputs, single-, double- or three-phase versions, and a wide temperature range. Additional performance increases are possible using simple parallel circuitry. Weidmüller A.2 2003670000 Switch-mode power supplies Switch-mode power supplies – Overview AC / DC International use Parallel connection from 3 3 mm A A wide-range input (both DC as well as AC voltages can be used; no switching required) and extensive approvals (UL/CSA and GL (EMC 1 – bridge)). connectPower Module power can be increased by connecting upto five power supplies in parallel without diode module. connectPower PROeco Narrow connectPower PROmax Space-saving configuration in the switching cabinet through very narrow housing construction and side-by-side connectability. connectPower PRO-H Robust Wide temperature range from –25 °C … +70 °C. connectPower PRO-E Wide choice The right power supply for every application: 1-phase 3 A, 5 A, 7.5 A, 10 A, 20 A, 40 A and 3-phase 5 A, 10 A, 20 A, 40 A. connectPower INSTAPOWER connectPower WAVEPOWER connectPower DC/DC converters 2003670000 A.3 Switch-mode power supplies connectPower PROeco PROeco power supplies with basic functionality and a high level of reliability • Single- and three-phase switched-mode power supply units • Slim design •Largetemperaturerangefrom–25 °Cto70 °C • The output voltage can be precisely adjusted via the potentiometer on the front • Remote monitoring via integrated status relay • Three-coloured LED indicators for simple error detection •Advancedvisualwarningat90 %ratedoutputcurrent • International approvals A % Derating curves Technical data ≤ 480 Watt 120 Ioutput (% IN) 100 80 60 40 20 0 –25 0 20 30 40 50 Ambient temperature (°C) 60 70 Ioutput (% IN) 100 80 60 40 20 0 –25 A.4 General technical data Ambient temp. operating / storage temperature Max. perm. air humidity (operation) Degree of protection Class of protection Pollution degree Insulation voltage input/output MTBF Parallel connection option Housing version Mounting position, installation notice Short-circuit protection Overload protection Overtemperature protection EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to 960 Watt 120 0 \Ž 20 30 40 50 Ambient temperature (°C) 60 70 Limiting of mains voltage harmonic currents Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock Protection against dangerous shock currents –25 °C…+70 °C / –40 °C…+85 °C 5 %…95 % RH IP 20 I, with PE connection 2 3 kV E/A / 2 kV E/earth / 0.5 kV A/earth > 500.000 h acc. to IEC 1709 (SN29500) yes, max. 5 without diode module metal, corrosion resistant horizontal on mounting rail TS35, 50 mm spacing top and bottom for free air circulation Yes, automatic restart Yes, IU characteristic curve Yes, automatic restart Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN61000-4-6 (conducted), EN61000-4-11 (Dips) Acc. to EN61000-3-2 1 g acc. to EN50178, shock: 15 g in all directions Acc. to EN60204 Acc. to EN61558-2-17 Acc. to EN50178 / VDE0160 SELV acc. to EN60950-1, PELV acc. to EN60204-1 VDE0100-410 / acc. to DIN57100-410 Acc. to VDE0106-101 2003670000 connectPower PROeco Switch-mode power supplies connectPower PROeco PRO ECO 120W 24V 5A PRO ECO 72W 24V 3A / 1² $& '& 3( / ² ² 1² 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ A Similar to illustration Similar to illustration $& ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note 2003670000 mm² mm² Nm 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 0,55 A @ 230 V AC / 1,04 A @ 110 V AC 0,22 A @ 370 V DC / 0,68 A @ 120 V DC Yes / max. 40 A 2 A / DI, safety fuse 6 A, Char. B, circuit breaker 2...4 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 1,26 A @ 230 V AC / 2,24 A @ 110 V AC 0,39 A @ 370 V DC / 1,16 A @ 120 V DC Yes / max. 40 A 4 A / DI, safety fuse 6 A, Char. B, circuit breaker 3...5 A, Char. C, circuit breaker 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 3 A at 55 °C 3 A @ 55 °C, 2,25 A @ 70 °C unrestricted Yes 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 5 A at 55 °C 5 A @ 55 °C, 3,75 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 87 % 4 W / 9.5 W 1 mA > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 34 / 125 mm / 578 g 87 % 4 W / 15 W 1 mA > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 80 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 40 / 125 mm / 680 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO 72W 24V 3A Output Screw connection 5 (+,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469470000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO 120W 24V 5A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469480000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. A.5 Switch-mode power supplies connectPower PROeco connectPower PROeco PRO ECO 480W 24V 20A PRO ECO 240W 24V 10A A Similar to illustration Similar to illustration / 1² $& ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note A.6 mm² mm² Nm 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 1,23 A @ 230 V AC / 2,47 A @ 110 V AC 1,18 A @ 370 V DC / 2,4 A @ 120 V DC Yes / max. 15 A 4 A / DI, safety fuse 10 A, Char. B, circuit breaker 3...4 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 2,37 A @ 230 V AC / 5,2 A @ 110 V AC 1,55 A @ 370 V DC / 4,65 A @ 120 V DC Yes / max. 5 A 6 A / DI, safety fuse 16 A, Char. B, circuit breaker 6...8 A, Char. C, circuit breaker 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 10 A @ 55 °C 10 A @ 55 °C, 7.5 A @ 70 °C unrestricted Yes 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 20 A @ 55 °C 20 A @ 55 °C, 15 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 90% 3 W / 24 W 1 mA > 0.94 @ 230 V AC / > 0.99 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 60 / 125 mm / 1026 g 91% 5 W / 43 W 1 mA > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 3 120 / 100 / 125 mm / 1557 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO 240W 24V 10A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469490000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO 480W 24V 20A Output Screw connection 7 (++,---,13,14) 0.5 / 6 0.5 / 2.5 26 / 10 0.5 / 0.6 Qty. 1 Order No. 1469510000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. 2003670000 connectPower PROeco Switch-mode power supplies connectPower PROeco PRO ECO 960W 24V 40A A Similar to illustration / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 4,6 A @ 230 V AC / 9,9 A @ 110 V AC 2,9 A @ 370 V DC / 9 A @ 120 V DC Yes / max. 5 A 16 A / DI, safety fuse 20 A, Char. B, circuit breaker 16 A, Char. C, circuit breaker Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 40 A @ 50 °C 40 A @ 50 °C, 24 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note 2003670000 93% 6 W / 76 W 1 mA > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 3 120 / 160 / 125 mm / 3019 g CE; TUEV (EN/IEC 60950-1); cULus; RCM mm² mm² Nm Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO 960W 24V 40A Output Screw connection 7 (++,---,13,14) 0.5 / 16 2.5 / 10 22 / 8 0.5 / 0.6 Qty. 1 Order No. 1469520000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. A.7 Switch-mode power supplies connectPower PROeco connectPower PROeco PRO ECO 120W 12V 10A PRO ECO 72W 12V 6A A Similar to illustration Similar to illustration / 1² $& '& 3( / ² ² 1² 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ $& ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note A.8 mm² mm² Nm 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 0.6 A @ 230 V AC / 1.1 A @ 115 V AC 0.25 A @ 370 V DC / 0.7 A @ 120 V DC Yes / max. 40 A 2 A / DI, safety fuse 6 A, Char. B, circuit breaker 2...4 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 1.25 A @ 230 V AC / 2.25 A @ 110 V AC 0.4 A @ 370 V DC / 1.2 A @ 120 V DC Yes / max. 40 A 4 A / DI, safety fuse 6 A, Char. B, circuit breaker 3...5 A, Char. C, circuit breaker 12 V DC ± 1 % 10...16 V (adjustable via potentiometer) ≤ 100 ms / < 50 mV ss @ 12 V DC, I Nenn 6 A @ 55 °C 6 A @ 55 °C, 4.5 A @ 70 °C unrestricted Yes 12 V DC ± 1 % 10...16 V (adjustable via potentiometer) ≤ 100 ms / < 50 mV ss @ 12 V DC, I Nenn 10 A @ 55 °C 10 A @ 55 °C, 7.5 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 85 % 4 W / 15 W 1 mA > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 100 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 34 / 125 mm / 644 g 87 % 4 W / 20 W 1 mA > 0.5 @ 230 V AC / > 0.53 @ 115 V AC > 80 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 40 / 125 mm / 698 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO 72W 12V 6A Output Screw connection 5 (+,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469570000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO 120W 12V 10A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469580000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. 2003670000 connectPower PROeco Switch-mode power supplies connectPower PROeco PRO ECO 480W 48V 10A PRO ECO 240W 48V 5A / 1² $& ² ² '& 3( A Similar to illustration Similar to illustration / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 1.2 A @ 230 V AC / 2.4 A @ 115 V AC 1.2 A @ 370 V DC / 2.4 A @ 120 V DC Yes / Max. 10 A 4 A / DI, safety fuse 10 A, Char. B, circuit breaker 3...4 A, Char. C, circuit breaker 100...240 V AC (wide-range input) 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…370 V DC (Derating @ 120 V DC) 2.4 A @ 230 V AC / 5.2 A @ 110 V AC 1.5 A @ 370 V DC / 4.6 A @ 120 V DC Yes / max. 3 A 6 A / DI, safety fuse 16 A, Char. B, circuit breaker 6...8 A, Char. C, circuit breaker 48 V DC ± 1 % 42...56 V (adjustable via potentiometer) ≤ 100 ms / < 100 mV ss @ 48 V DC, I Nenn 5 A at 55 °C 5 A @ 55 °C, 3,75 A @ 70 °C unrestricted Yes 48 V DC ± 1 % 42...56 V (adjustable via potentiometer) ≤ 100 ms / < 100 mV ss @ 48 V DC, I Nenn 10 A @ 55 °C 10 A @ 55 °C, 7.5 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 92 % 5 W / 50 W 1 mA > 0.94 @ 230 V AC / > 0.99 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 5 100 / 60 / 125 mm / 1076 g 93% 3 W / 23 W 1 mA > 0.98 @ 230 V AC / > 0.98 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC yes, max. 3 120 / 100 / 125 mm / 1570 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note 2003670000 mm² mm² Nm Type PRO ECO 240W 48V 5A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469590000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO 480W 48V 10A Output Screw connection 7 (++,---,13,14) 0.5 / 6 0.22 / 4 26 / 10 0.5 / 0.6 Qty. 1 Order No. 1469610000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. A.9 Switch-mode power supplies connectPower PROeco connectPower PROeco PRO ECO3 240W 24V 10A PRO ECO3 120W 24V 5A A Similar to illustration Similar to illustration / /² / $& ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / /² / $& ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note A.10 mm² mm² Nm 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.3 A @ 3 x 500 V AC / 0.4 A @ 3 x 400 V AC 0.2 A @ 800 V DC / 0.4 A @ 450 V DC Yes / max. 40 A 2 A / DI, safety fuse 2...3 A, Char. C, circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0.6 A @ 3 x 500 V AC / 0.8 A @ 3 x 400 V AC 0.4 A @ 800 V DC / 0.7 A @ 450 V DC Yes / max. 50 A 2 A / DI, safety fuse 2...3 A, Char. C, circuit breaker 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 5 A at 55 °C 5 A @ 55 °C, 3,75 A @ 70 °C unrestricted Yes 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 10 A @ 55 °C 10 A @ 55 °C, 7.5 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 87 % 6 W / 13 W 1 mA > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC > 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes, max. 5 100 / 40 / 125 mm / 710 g 88% 6 W / 24 W 1 mA > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC > 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes, max. 5 100 / 60 / 125 mm / 971 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO3 120W 24V 5A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469530000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO3 240W 24V 10A Output Screw connection 6 (++,--,13,14) 0.5 / 6 0.5 / 2.5 26 / 12 0.5 / 0.6 Qty. 1 Order No. 1469540000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. 2003670000 connectPower PROeco Switch-mode power supplies connectPower PROeco PRO ECO3 960W 24V 40A PRO ECO3 480W 24V 20A Similar to illustration Similar to illustration / /² / $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / /² / $& ² ² ² '& 3( A 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Ramp-up time / Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Capacitive load Protection against inverse voltage Signalling Indication Floating contact / Contact load Relay on/off General data Degree of efficiency Power loss, idling / Power loss, nominal load Earth leakage current, max. Power factor (approx.) AC failure bridging time @ INom Parallel connection option Depth x width x height / Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque range Note Ordering data Note 2003670000 mm² mm² Nm 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 1.2 A @ 3 x 500 V AC / 1.5 A @ 3 x 400 V AC 0.7 A @ 800 V DC / 1.2 A @ 450 V DC Yes / max. 50 A 4 A / DI, safety fuse 3...5 A, Char. C, circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 47...63 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 2,15 A @ 3 x 500 V AC / 2,68 A @ 3 x 400 V AC 1,37 A @ 800 V DC / 2,37 A @ 450 V DC Yes / max. 40 A 6 A / DI, safety fuse 10 A, Char. B, circuit breaker 6...8 A, Char, C, circuit breaker 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 20 A @ 55 °C 20 A @ 55 °C, 15 A @ 70 °C unrestricted Yes 24 V DC ± 1 % 22...28 V (adjustable via potentiometer) ≤ 100 ms / < 50 mVSS @ 24 V DC, IN 40 A @ 50 °C 40 A @ 50 °C, 24 A @ 70 °C unrestricted Yes LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload LED green (Uoutput > 21.6 V DC), LED yellow (Ioutput > 90% IRated typ. ), LED red (overload, overtemperature, short-circuit, Uoutput < 20.4 V DC) Yes / max. 30 V DC / 1 A Output voltage > 21.6 V / < 20.4 V, overload 89% 8 W / 48 W 1 mA > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC > 30 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC yes, max. 3 120 / 100 / 125 mm / 1495 g 90% 5 W / 95 W 1 mA > 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC > 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V AC yes, max. 3 120 / 160 / 125 mm / 2899 g CE; TUEV (EN/IEC 60950-1); cULus; RCM CE; TUEV (EN/IEC 60950-1); cULus; RCM Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 4 for L1/L2/L3/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type PRO ECO3 480W 24V 20A Output Screw connection 7 (++,---,13,14) 0.5 / 6 0.5 / 2.5 26 / 10 0.5 / 0.6 Qty. 1 Order No. 1469550000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO ECO3 960W 24V 40A Output Screw connection 7 (++,---,13,14) 0.5 / 16 2.5 / 10 22 / 8 0.5 / 0.6 Qty. 1 Order No. 1469560000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. A.11 Switch-mode power supplies connectPower PROeco connectPower PROeco diode module CP DM 10 CP DM 20 A +V E1 E2 –V –V DC E1 E2 –V -V +V -V + +V –V DC – E1 E2 -V E1 E2 -V Technical data Input Input voltage Input current Output Output voltage Output current General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Mounting position, installation notice Installation advice Weight Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 40 V DC max. 2 x 0...10 A max. 40 V DC max. 2 x 0...20 A max. Uin - 0.5 V typical 0...20 A max. or 10 A max. for redundancy operation Uin - 0.5 V typical 0...40 A max. or 20 A max. for redundant operations -10 °C...55 °C -20 °C...85 °C 95.5% horizontally, on terminal rail TS 35 Clearance: side ≥ 2 cm; above/below ≥ 10 cm 399 g CE; cULus; cURus; EAC -10 °C...55 °C -20 °C...85 °C 97.5% horizontally, on terminal rail TS 35 Clearance: side ≥ 2 cm; above/below ≥ 10 cm 411 g CE; cULus; cURus; EAC Input 4 / 0.13 / 6 110 / 55.5 / 125 Input 4 / 0.13 / 6 110 / 55.5 / 125 Type CP DM 10 Output 4 / 0.13 / 6 110 / 55.5 / 125 Qty. 1 Order No. 8710620000 Type CP DM 20 Output 10 / 0.32 / 16 110 / 55.5 / 125 Qty. 1 Order No. 8768650000 Note Accessories Note A.12 2003670000 Small metal foot Type MTA 30 MF Large metal foot Order No. 1251320000 Small wall mounting Type CP A WALLADAPTER 30 MM Small plastic foot Type MTA 45 MF Order No. 1251310000 Type MTA 30 BK Switch-mode power supplies connectPower PROeco - Accessories Large plastic foot Order No. 1168970000 Type MTA 45 BK Order No. 1962250000 A Large wall mounting Order No. 1461870000 Type CP A WALLADAPTER 45 MM Order No. 1461850000 Small screwdriver Type SDIK PH1 SDIS 0.5X3.0X100 Blade type Size/AF 1.00 B a b 0.5 3 c 80 100 Order No. 9008570000 9008380000 End bracket Markers For DIN rail TS 35 Type SM 18/9.5 K MC NE WS 2003670000 Colour white Qty. 200 Order No. 1248580000 Polyamide with fibre glass, screwable WEW 35/1 SW Colour black Torque 1.2 Nm Qty. 50 Order No. 1162600000 A.13 Switch-mode power supplies connectPower PROmax connectPower PROmax A Derating curve Technical data /RDG 7HPS& Max. limiting average on state current [A] Typ\Temp. 45 °C 50 °C 55 °C 60 °C 65 °C 70 °C 1ph 24 V / 3 A 3,6 3,3 3,2 3 2,6 2,2 1ph 24 V / 5 A 6 5,7 5,4 5 4,4 3,8 1ph 24 V / 7,5 A 9 8,5 8 7,5 6,6 5,6 1ph 24 V / 10 A 12 11,3 10,7 10 8,8 7,5 1ph 24 V / 20 A 24 22,6 21,4 20 17,6 15 1ph 24 V / 40 A 48 45,2 42,8 40 35,2 30 1ph 5 V / 14 A 16,8 15,8 15 14 12,3 10,5 1ph 12 V / 6 A 7,2 6,8 6,4 6 5,3 4,5 1ph 12 V / 10 A 12 11,3 10,7 10 8,8 7,5 1ph 48 V / 5 A 6 5,7 5,4 5 4,4 3,8 1ph 48 V / 10 A 12 11,3 10,7 10 8,8 7,5 1ph 48 V / 20 A 24 22,6 21,4 20 17,6 15 3ph 24 V / 5 A 6 5,7 5,4 5 4,4 3,8 3ph 24 V / 10 A 12 11,3 10,7 10 8,8 7,5 3ph 24 V / 20 A 24 22,6 21,4 20 17,6 15 3ph 24 V / 40 A 48 45,2 42,8 40 35,2 30 A.14 General technical data Current limiting Insulation voltage input earth Insulation voltage output earth Insulation voltage input/output Earth leakage current Series switching capability Ambient temp. operating / storage temperature / Start up Humidity at operating temperature Class of protection / Pollution degree MTBF Housing version Status indication Mounting position, installation notice EMC / shock / vibration Noise immunity tests acc. to Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock Protection against dangerous shock currents > 120 % IN 3.5 kV 0.5 kV 4 kV 3.5 mA Yes -25 °C...+70 °C / -40 °C...+85 °C / ≥ -40 °C 5...95 %, no condensation I/2 >500,000h (25°C, IEC 61709) Metal, corrosion resistant LED red/green and relay (≥21.6 V DC LED green, relay on/ ≤20.6 LED red, relay off) Horizontal on TS35 mounting rail, with 50 mm of clearance at top and bottom for air circulation. Can be mounted side by side with no space in between. EN55024; EN55022; IEC61000-3-2,-3; IEC61000-4-2,-3,-4,-5,-6,-8,-11 2.3 g / 30 g in all directions Acc. to EN60204 Acc. to EN61558-2-16 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204, IEC61204 VDE0100-410 / acc. to DIN57100-410 Acc. to VDE0106-101 2003670000 connectPower PROmax PRO MAX 72W 24V 3A Switch-mode power supplies connectPower PROmax PRO MAX 120W 24V 5A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1 A @ 230 V AC / 1.5 A @ 115 V AC 1A @ 370 VDC / 1,5A @ 120 VDC Yes / max. 15 A 6 A, Char. B, circuit breaker, 3 - 5 A Char. C, circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1A @ 230 VAC / 2,5A @ 115 VAC 1,5A @ 370 VDC / 2,5A @ 120 VDC Yes / max. 15 A 6 A, Char. B, circuit breaker, 6 A, char. C circuit breaker 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 3 A @ 60 °C 3,6 A @ 45°C, 2,25 A @ 70°C 3.6 A (1 min), 4.5 A (4s) 9 A (2ms) 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 5 A @ 60 °C 6.0 A @ 45 °C, 3,75 A @ 70 °C 6 A (1 min), 7.5 A (4s) 15 A (2ms) 89% > 0.90 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 32 / 130 mm 650 g 89% > 0.90 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 40 / 130 mm 859 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 72W 24V 3A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478100000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 120W 24V 5A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478110000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note 2003670000 A.15 Switch-mode power supplies connectPower PROmax connectPower PROmax PRO MAX 180W 24V 7,5A PRO MAX 240W 24V 10A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1 A @ 230 V AC / 2 A @ 115 V AC 1A @ 370 VDC / 2A @ 120 VDC Yes / max. 15 A 10 A, char. B circuit breaker, 6…8 A, char. C circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1.5 A @ 230 V AC / 3 A @ 115 V AC 1,5A @ 370 VDC / 3A @ 120 VDC Yes / max. 15 A 10 A, char. B circuit breaker, 6…8 A, char. C circuit breaker 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 7,5 A @ 60 °C 9 A @ 45°C, 5,6 A @ 70°C 9 A (1 min), 11.25 A (4s) 22,5 A (2ms) 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 10 A @ 60 °C 12 A @ 45°C, 7,5 A @ 70°C 12 A (1 min), 15 A (4s) 30 A (2ms) 91.5% > 0.95 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 50 / 130 mm 950 g 91.5% > 0.95 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 60 / 130 mm 1050 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 180W 24V 7,5A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478120000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 240W 24V 10A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478130000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note A.16 2003670000 connectPower PROmax PRO MAX 480W 24V 20A Switch-mode power supplies connectPower PROmax PRO MAX 960W 24V 40A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 2,3A @ 230 VAC / 4,8A @ 115 VAC 1,5A @ 370 VDC / 4.8A @ 120 VDC Yes / max. 15 A 16 A, Char. B circuit breaker, 10 A, char. C circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 4,52A @ 230 VAC / 10A @ 115 VAC 2,8A @ 370 VDC / 10A @ 120 VDC Yes / max. 15 A 20 A, char. B circuit breaker, 16 A, Char. C circuit breaker 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 20 A @ 60 °C 24 A @ 45°C, 15 A @ 70°C 24 A (1 min), 30 A (4s), 100…240 V AC 60 A (2ms) 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 40 A @ 60 °C 48 A @ 45°C, 30 A @ 70°C 48 A (1 min), 60 A (4s), 100…240 V AC 120 A (2ms) 92 % > 0.95 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 3 150 / 90 / 130 mm 2000 g 93% > 0.95 @ 230 V AC min. 20 ms 30…35 V DC yes, max. 3 150 / 140 / 130 mm 3900 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 480W 24V 20A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478140000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 960W 24V 40A Output Screw connection 8 (++,---,11,13,14) 0.5 / 16 0.5 / 16 22 / 8 1.0 x 5.5 Qty. 1 Order No. 1478150000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note 2003670000 A.17 Switch-mode power supplies connectPower PROmax connectPower PROmax PRO MAX 70W 5V 14A PRO MAX 72W 12V 6A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1 A @ 230 V AC / 1.5 A @ 115 V AC 1A @ 370 VDC / 1,5A @ 120 VDC Yes / max. 15 A 6 A, Char. B, circuit breaker, 3 - 5 A Char. C, circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1 A @ 230 V AC / 1.5 A @ 115 V AC 1A @ 370 VDC / 1,5A @ 120 VDC Yes / max. 15 A 6 A, Char. B, circuit breaker, 3 - 5 A Char. C, circuit breaker 5 V DC 4.5...7 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 14 A @ 60°C 16,8 A @ 45°C, 10,5 A @ 70°C 16.8 A (1 min), 21 A (4s) 42 A (2ms) 12 V DC ± 1 % 10...15 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 6 A @ 60°C 7.2 A @ 45°C, 4.5 A @ 70°C 7.2 A (1 min), 9 A (4s) 18 A (2ms) 86% > 0.90 @ 230 V AC min. 20 ms > 7.5 V DC yes, max. 5 125 / 32 / 130 mm 650 g 89% > 0.90 @ 230 V AC min. 20 ms > 18 V DC yes, max. 5 125 / 32 / 130 mm 650 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 70W 5V 14A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478210000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 72W 12V 6A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478220000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note A.18 2003670000 connectPower PROmax PRO MAX 120W 12V 10A Switch-mode power supplies connectPower PROmax PRO MAX 240W 48V 5A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1A @ 230 VAC / 2,5A @ 115 VAC 1,5A @ 370 VDC / 2,5A @ 120 VDC Yes / max. 15 A 6 A, Char. B, circuit breaker, 6 A, char. C circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 1.5 A @ 230 V AC / 3 A @ 115 V AC 1,5A @ 370 VDC / 3A @ 120 VDC Yes / max. 15 A 10 A, char. B circuit breaker, 6…8 A, char. C circuit breaker 12 V DC ± 1 % 10...15 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 10 A @ 60 °C 12 A @ 45°C, 7,5 A @ 70°C 12 A (1 min), 15 A (4s) 30 A (2ms) 48 V DC ± 1 % 30...56 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 5 A @ 60 °C 6.0 A @ 45 °C, 3,75 A @ 70 °C 5 A (1 min), 7.5 A (4s) 15 A (2ms) 89% > 0.90 @ 230 V AC min. 20 ms > 18 V DC yes, max. 5 125 / 40 / 130 mm 850 g 92.5% > 0.95 @ 230 V AC min. 20 ms 58 … 65 V DC yes, max. 5 125 / 60 / 130 mm 1050 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 120W 12V 10A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478230000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 240W 48V 5A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478240000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note 2003670000 A.19 Switch-mode power supplies connectPower PROmax connectPower PROmax PRO MAX 480W 48V 10A PRO MAX 960W 48V 20A A / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / 1² $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 2,3A @ 230 VAC / 4,8A @ 115 VAC 1,5A @ 370 VDC / 4.8A @ 120 VDC Yes / max. 15 A 16 A, Char. B circuit breaker, 10 A, char. C circuit breaker 100...240 V AC (wide-range input) 85…277 V AC 45…65 Hz 80...370 V DC 4,52A @ 230 VAC / 10A @ 115 VAC 2,8A @ 370 VDC / 10A @ 120 VDC Yes / max. 15 A 20 A, char. B circuit breaker, 16 A, Char. C circuit breaker 48 V DC ± 1 % 30...56 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 10 A @ 60 °C 12 A @ 45°C, 7,5 A @ 70°C 12 A (1 min), 15 A (4s), 100…240 V AC 60 A (2ms) 48 V DC ± 1 % 30...56 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 20 A @ 60 °C 24 A @ 45°C, 15 A @ 70°C 24 A (1 min), 30 A (4s), 100…240 V AC 60 A (2ms) 93% > 0.95 @ 230 V AC min. 20 ms 58 … 65 V DC yes, max. 5 150 / 90 / 130 mm 2000 g 94% > 0.95 @ 230 V AC min. 20 ms 58 … 65 V DC yes, max. 5 150 / 140 / 130 mm 1350 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 3 for L/N/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX 480W 48V 10A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478250000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX 960W 48V 20A Output Screw connection 8 (++,---,11,13,14) 0.5 / 16 0.5 / 16 22 / 8 1.0 x 5.5 Qty. 1 Order No. 1478270000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note A.20 2003670000 connectPower PROmax PRO MAX3 120W 24V 5A Switch-mode power supplies connectPower PROmax PRO MAX3 240W 24V 10A A / /² / $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / /² / $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 45…65 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0,28A @ 3*500 VAC / 0,3A @ 3*400 VAC 0.18 A @ 800 V DC / 0.3 A @ 450 V DC Yes / max. 15 A 2…3 A, char. C circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 45…65 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0,35A @ 3*500 VAC / 0,4A @ 3*400 VAC 0.35 A @ 800 V DC / 0.6 A @ 450 V DC Yes / max. 15 A 3 - 5 A Char. C, circuit breaker 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 5 A @ 60 °C 6.0 A @ 45 °C, 3,75 A @ 70 °C 6 A (1 min), 7.5 A (4s), 400…500 V AC 15 A (2ms) 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 10 A @ 60 °C 12 A @ 45°C, 7,5 A @ 70°C 12 A (1 min), 15 A (4s) 30 A (2ms) 90% > 0.50 @ 3*400 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 40 / 130 mm 850 g 91.5% > 0.85 @ 3*400 V AC min. 20 ms 30…35 V DC yes, max. 5 125 / 60 / 130 mm 1350 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 4 for L1/L2/L3/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 4 for L1/L2/L3/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX3 120W 24V 5A Output Screw connection 8 (++,---,11,13,14) 0.5 / 6 0.5 / 4 26 / 12 0.6 x 3.5 Qty. 1 Order No. 1478170000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX3 240W 24V 10A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478180000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note 2003670000 A.21 Switch-mode power supplies connectPower PROmax connectPower PROmax PRO MAX3 480W 24V 20A PRO MAX3 960W 24V 40A A / /² / $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ / /² / $& ² ² ² '& 3( 3D\DWWHQWLRQWRSRODULW\RI'&FRQQHFWLRQ Technical data Input Rated input voltage Input voltage range AC Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom Continuous output current @ URated Power boost @ URated Pulsed current capacity @ URated General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Protection against reverse voltages from the load Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Connection system Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Screwdriver blade Note Ordering data Note mm² mm² 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 45…65 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 0,7A @ 3*500 VAC / 0,85 @ 3*400 VAC 0.7 A @ 800 V DC / 1.2 A @ 450 V DC Yes / max. 15 A 3 - 5 A Char. C, circuit breaker 3 x 400...3 x 500 V AC (wide-range input) 3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC 45…65 Hz 450...800 V DC (max. 500 V DC acc. to UL508) 1,3A @ 3*500 VAC / 1,6A @ 3*400 VAC 1.4 A @ 800 V DC / 2.4 A @ 450 V DC Yes / max. 15 A 6…8 A, char. C circuit breaker 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 20 A @ 60 °C 24 A @ 45°C, 15 A @ 70°C 24 A (1 min), 30 A (4s) 60 A (2ms) 24 V DC ± 1 % 22.5...29.5 V (adjustable via potentiometer) < 50 mVss @ UNenn, Full Load 40 A @ 60 °C 48 A @ 45°C, 30 A @ 70°C 48 A (1 min), 60 A (4s), 400…500 V AC 120 A (2ms) 91.5% > 0.85 @ 3*400 V AC min. 20 ms 30…35 V DC yes, max. 3 150 / 70 / 130 mm 1600 g 93.5% > 0.75 @ 3*400 V AC min. 20 ms 30…35 V DC yes, max. 3 150 / 140 / 130 mm 3400 g CE; cULus; cULusEX; cURus; EAC; TUEV CE; cULus; cULusEX; cURus; EAC; TUEV Input Screw connection 4 for L1/L2/L3/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Input Screw connection 4 for L1/L2/L3/PE 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Type PRO MAX3 480W 24V 20A Output Screw connection 8 (++,---,11,13,14) 0.18 / 6 0.22 / 4 26 / 10 0.8 x 4.0, PZ 1 Qty. 1 Order No. 1478190000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type PRO MAX3 960W 24V 40A Output Screw connection 8 (++,---,11,13,14) 0.5 / 16 0.5 / 16 22 / 8 1.0 x 5.5 Qty. 1 Order No. 1478200000 The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Accessories Note A.22 2003670000 PRO-M: diode, capacity and relay modules CP M DM20 CP M DM40 1+ 12- Switch-mode power supplies connectPower PROmax 3+ 4+ 11 12 14 34- 21 22 24 2+ 1+ 12- 3+ 4+ 11 12 14 A 34- 21 22 24 2+ Technical data Input Rated input voltage / DC input voltage range Input current Output Rated output voltage / Output voltage Rated (nominal) output current @ UNom continous output current @ 24 V DC Voltage monitoring / Floating contact Switching thresholds 24 V DC / 18…30 V DC 2 x 10 A or 1 x 20 A 24 V DC / 18…30 V DC 2 x 20 A or 1 x 40 A 24 V DC ± 1 % / Input voltage - 0.7 V 20 A @ 60 °C 24 A @ 45 °C, 22.5 A @ 55 °C, 15 A @ 70 °C Yes, In both inputs / Yes 21.6 V DC, relay is on for Power Good, 20.4 V DC, relay is off for Power Fail 24 V DC ± 1 % / Input voltage - 0.7 V 40 A @ 60 °C 48 A @ 45 °C, 45 A @ 55 °C, 30 A @ 70 °C Yes, In both inputs / Yes 21.6 V DC, relay is on for Power Good, 20.4 V DC, relay is off for Power Fail > 97% @ 24 V input voltage 150 / 34 / 130 mm / 0.3 kg -25 °C...70 °C / -40 °C...85 °C 5...95 %, no condensation IP 20 / III, with no ground connection, for SELV / 2 0.5 kV Input/output housing > 500,000 h acc. to IEC 1709 (SN29500 Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. > 97% @ 24 V input voltage 150 / 60 / 130 mm / 0.6 kg -25 °C...70 °C / -40 °C...85 °C 5...95 %, no condensation IP 20 / III, with no ground connection, for SELV / 2 0.5 kV Input/output housing > 500,000 h acc. to IEC 1709 (SN29500 Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. Class B EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)|EN 61000-4-4 (burst)|EN 61000-4-5 (surge)|EN 61000-4-6 (conducted) Class B EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)|EN 61000-4-4 (burst)|EN 61000-4-5 (surge)|EN 61000-4-6 (conducted) Resistance to vibration / Shock Electrical safety (applied standards) Electrical machine equipment For use with electronic equipment Safety extra-low voltage Approvals Approvals 1 g according to EN50178 / 15 g In all directions 1 g according to EN50178 / 15 g In all directions Acc. to EN60204 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204 Acc. to EN60204 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204 cCSAus; CE; cULus; EAC; GL; GOSTME25 cCSAus; CE; cULus; EAC; GL; GOSTME25 Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Input Screw connection 4 (1+, 2+, 1-, 2-) 0.5 / 6 0.5 / 2.5 26 / 12 Input Screw connection 4 (1+, 2+, 1-, 2-) 0.5 / 16 2.5 / 10 22 / 6 General data Degree of efficiency Depth x width x height / Weight Ambient temperature (operational) / Storage temperature Humidity Protection degree / Class of protection / Pollution degree Insulation voltage MTBF Mounting position, installation notice EMC / shock / vibration Noise emission acc. to EN55022 Interference immunity test acc. to mm² mm² Ordering data Plastic clip-on foot Metal clip-on foot Type CP M DM20 CP M DM20 Output Screw connection 4 (3 +, 4 +, 3 -, 4 -) 0.5 / 6 0.5 / 2.5 26 / 12 Qty. 1 1 Order No. 1222210000 1222210010 Type CP M DM40 CP M DM40 Output Screw connection 4 (3 +, 4 +, 3 -, 4 -) 0.5 / 16 2.5 / 10 22 / 6 Qty. 1 1 Order No. 1222220000 1222220010 Note Accessories Note 2003670000 A.23 Switch-mode power supplies connectPower PROmax PRO-M: diode, capacity and relay modules CP M CAP Pulse triggering for circuit breakers: with the Weidmüller capacitance module The following conditions apply to the table entries: • Ambient temperature of 20 °C • Inner resistance of the circuit breakers is taken into account • Half of the rated current flows to a neighbouring circuit before the short circuit is formed • DC-compatible circuit breakers: Siemens 5SY series + 11 12 14 12- Distance in m Technical data Fuse tripping Input Rated input voltage / DC input voltage range Output Peak current output / Recovery time for the capacitor Switching thresholds 24 V DC / 18…30 V DC Depending on the load (typically 40 A for 1 ms) / Approx. 1 sec. 21.6 V DC, relay is on for Power Good, 20.4 V DC, relay is off for Power Fail Yes Floating contact General data Depth x width x height / Weight Ambient temperature (operational) / Storage temperature Humidity Protection degree Class of protection Pollution degree Insulation voltage MTBF Mounting position, installation notice 150 / 34 / 130 mm / 0.4 kg -25 °C...70 °C / -40 °C...85 °C 5...95 %, no condensation IP 20 III, with no ground connection, for SELV 2 0.5 kV Input/output housing > 500,000 h acc. to IEC 1709 (SN29500 Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between. EMC / shock / vibration Noise emission acc. to EN55022 Interference immunity test acc. to Class B EN 61000-4-2 (ESD)|EN 61000-4-3 and EN 61000-4-8 (fields)|EN 61000-4-4 (burst)|EN 61000-4-5 (surge)|EN 61000-4-6 (conducted)|EN 61000-4-11 (dips) 1 g according to EN50178 / 15 g In all directions Resistance to vibration / Shock Electrical safety (applied standards) Electrical machine equipment For use with electronic equipment Safety extra-low voltage Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Load 1+ 2+ Power supply + CAP module A Acc. to EN60204 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PELV acc. to EN60204 Conductor cross section 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 0.75 mm2 1.0 mm2 1.5 mm2 2.5 mm2 4 mm2 6 mm2 B6 10 m 14 m 20 m 30 m 50 m B10 6 m 9 m 15 m 24 m B16 4m 6m 10 m 16 m C2 11 m 14 m 21 m 34 m C6 3m 3.5 m 5.5 m 9m 14 m C4 6 m 8 m 12 m 19 m 32 m C10 2 m 3 m 5 m 8 m 12 m CE; cULus; EAC; GL mm² mm² Input Screw connection 4 (++--) 0.5 / 6 0.5 / 4 26 / 12 Output Screw connection 3 (CO contacts) 0.5 / 6 0.5 / 2.5 26 / 12 For low-impedance connections we recommend 2.5 mm². Ordering data Plastic clip-on foot Metal clip-on foot Type CP M CAP CP M CAP Qty. 1 1 Order No. 1222240000 1222240010 Note Accessories Note A.24 2003670000 A 2003670000 A.25 Switch-mode power supplies Switch-mode power supplies connectPower PROmax A PRO-M: Application solution for wind power Switched-mode power supply with wide-range input Application solution for wind power: • 80 ... 430 V DC input • Alarm contact • Metal snap-on foot % { \u Technical data General technical data Output characteristic curve / current limit Earth discharge current Ambient temperature (operational) / Storage temperature / Start-up Max. permitted humidity (operational) Degree of protection Class of protection Pollution degree Insulation voltage MTBF Protection against reverse voltages from the load Can be connected in parallel Housing version Signal indication Mounting position, installation notice Voltage derating 110 Pout [% Pn] 190 90 80 70 60 50 40 80 120 160 200 240 280 320 360 400 440 DC Input [V] Temperature derating 130 120 EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to Pout [% Pn] 110 100 90 80 70 60 20 30 40 50 60 Ambient temperature [°C] A.26 70 80 Limiting of mains voltage harmonic currents Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Safety transformers for switched-mode power units Safety extra low voltage Protective separation / protection against electrical shock Protection against dangerous shock currents IU / > 120 % IR < 3.5 mA –25 °C…+70 °C / –40 °C…+85 °C / ≥ –40 °C 5 %…95 % RH IP 20 I, with PE connection 2 3 kV AC 1 min. / 2 kV AC 1 min. / 0.5 kV AC 1 min. > 500,000 h according to IEC 1709 (SN29500) 30…35 V DC Yes, without diode module Metal, corrosion resistant Operations, green/red LED Horizontal on TS 35 mounting rail, with 50 mm of clearance at top and bottom for air circulation. Can be mounted side by side with no space in between. Suitable for installation in rotating systems. Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) according to EN61000-3-2 according to EN50178, Shock: 5 g in all directions according to EN60204 according to EN61558-2-17 according to EN50178 / VDE0160 SELV according to EN60950, PELV according to EN60204 VDE0100-410 / according to DIN57100-410 according to VDE0106-101 2003670000 PRO-M: application solutions for wind power Switch-mode power supplies connectPower PROmax CP M SNT 250W 24V 10A UW A / 1² $& ² ² '& 3( 8 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Rated input voltage / Input voltage range AC 100...240 V AC (wide-range input) / 85…264 V AC (Derating @ 100 V AC) 47...63 Hz 80…430 V DC 1.2 A @ 230 V AC / 2.4 A @ 115 V AC 0.8 A @ 370 V DC / 2.3 A @ 120 V DC Yes 4 A / DI, safety fuse 10 A, Char. B, circuit breaker 3...4 A, Char. C, circuit breaker Frequency range AC DC input voltage range AC current consumption DC current consumption Input fuse (internal) Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency Power factor (approx.) AC failure bridging time @ INom Depth x width x height / Weight Additional equipment Status indicator Relay on/off Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note 24 V DC ± 1 % 22.5...29.5 V DC (adjustable via potentiometer on front) < 50 mVSS @ 24 V DC, IN, < 2,4 VSS @ 24 V DC, IN @ -40°C 10 A @ 60 °C 12 A @ 45 °C, 10.7 A @ 55 °C, 7.5 A @ 70 °C 90 % @ 230 V AC / 87 % @ 115 V AC > 0.99 @ 230 V AC / > 0.97 @ 115 V AC > 20 ms @ 230 V AC / > 20 ms @ 115 V AC 155 / 60 / 130 mm / 1.2 Kg Green LED, red LED Output voltage > 21.6 V / < 20.4 V CE; cULus; EAC; GL; GOSTME25; TUEV mm² mm² Input Screw connection 3 for L/N/PE 0.5 / 6 0.5 / 2.5 26 / 12 Type CP M SNT 250W 24V 10AUW Output Screw connection 6 (+,+,-,-,COM,NO) 0.5 / 6 0.5 / 2.5 26 / 12 Qty. 1 Order No. 1165480010 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.27 Switch-mode power supplies connectPower PROmax - Accessories A Small metal foot Type MTA 30 MF Large metal foot Order No. 1251320000 Small wall mounting Type CP A WALLADAPTER 30 MM Small plastic foot Type MTA 45 MF Order No. 1251310000 Order No. 1168970000 Type MTA 45 BK Order No. 1962250000 Large wall mounting Order No. 1461870000 Type CP A WALLADAPTER 45 MM Order No. 1461850000 Large screwdriver Small screwdriver Type SDIK PH1 SDIS 0.5X3.0X100 Type MTA 30 BK Large plastic foot Blade type Size/AF 1.00 B a b 0.5 3 c 80 100 Order No. 9008570000 9008380000 Type SDIS 1.0X5.5X125 Blade type B Size/AF a 1 b 5.5 c 125 Order No. 9008410000 Qty. 50 Order No. 1162600000 Endwinkel Markers For DIN rail TS 35 Type SM 18/9.5 K MC NE WS A.28 Colour white Qty. 200 Order No. 1248580000 Polyamide with fibre glass, screwable WEW 35/1 SW Colour black Torque 1.2 Nm 2003670000 A 2003670000 A.29 Switch-mode power supplies Switch-mode power supplies connectPower PRO-H connectPower PRO-H A % { \ | CB Scheme Technical data L (+) N (–) AC DC PE General technical data Current limiting Ambient temp. operating / storage temperature Max. perm. air humidity (operation) Degree of protection / Class of protection Pollution degree Insulation voltage input/output MTBF according to IEC 61709 + + – – 13 14 DC OK Data Link > 100 % Irated -25…+70 °C -25 °C…+85 °C 95 % RH IP 20 / I, with PE connection 2 4 kV I/O 2 kV I/earth 0.5 kV O/earth CP T … 70/90 W > 1.8 Mio. h CP T … 140 W > 1.2 Mio. h CP T … 180/360/600 W > 0.9 Mio. h 16 V DC / 35 V DC / 63 V DC yes, without diode module metal, corrosion resistant Thermal protection, autom. restart Unlimited, autom. restart Dual LED Operational: Green LED; Error: Red LED Horizontal on TS 35 mounting rail, with 80 mm space at top and bottom. Side by side mounting with 50 mm clearance. 7 mm Protection against reverse voltages from the load Parallel connection option Housing version Overload protection Short circuit protection Indication Mounting position, installation notice Stripping length (rated connection) Signal indication Power Good Signal Trigger point 12 V Version 9…11 V DC 24 V Version 18...22 V DC 48 V Version 36...44 V DC NO contact 30 V DC / 1.0 A max. for 12/24 V DC modules 48 V DC/ 0.5 A max. for 36/48 V DC modules 70 W 11 V DC ± 1 V DC / 20 mA max. 140 W 11 V DC ± 1 V DC / 40 mA max. 90 W 22 V DC ± 2 V DC / 10 mA max. 180/360/600 W 24 V DC 22 V DC± 2 V DC / 20 mA max. 180/360/600 W 48 V DC 44 V DC± 4 V DC / 15 mA max. Potential free, floating signal contact Active output signal Max. limiting average on state current [A] Type\Temp. 1 ph 12 V / 6 A 1 ph 12 V / 12 A 1 ph 24 V / 3.8 A 1 ph 24 V / 7.5 A 1 ph 24 V / 15 A 1 ph 24 V / 25 A 1 ph 36 V / 16.5 A 1 ph 48 V / 2 A 1 ph 48 V / 4 A 1 ph 48 V / 7.5 A 1 ph 48 V / 12.5 A 1-2 ph 24 V / 7.5 A 1-2 ph 24 V / 15 A 1-2 ph 24 V / 25 A 40 °C 6.0 12.0 3.8 7.5 15.0 25.0 16.5 2.0 4.0 7.5 12.5 7.5 15.0 25.0 50 °C 5.7 9.5 3.1 6.3 12.5 22.5 15.0 1.6 3.3 6.3 11.3 6.3 12.5 22.5 60 °C 5.4 7.0 2.5 5.0 10.0 20.0 13.3 1.3 2.5 5.0 10.0 5.0 10.0 20.0 70 °C 4.5 3.7 1.7 3.3 6.7 13.3 9.0 0.8 1.7 3.3 7.5 3.3 6.7 13.3 EMC / shock / vibration Noise emission acc. to EN55022 Noise immunity tests acc. to Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) according to EN61000-3-2 3 axes, Sinus, 10…55 Hz, 1 g, 1 oct./min 3 axes, 15 g, half sinus, 11 ms Limiting of mains voltage harmonic currents Vibration IEC 60068-2-6 Shock IEC 60068-2-27 Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra low voltage according to EN60204 according to EN61558-2-4 according to EN50178 SELV according to EN60950 CP T SNT... 100 100 90 600 W 80 70 90 W 180 W 360 W 60 50 40 -25 40 50 Temperature [°C] A.30 70 W 140 W 60 70 Output Power [% Pmax] Output Power [% Pmax] 90 80 70 60 50 40 85 90 100 110 115 132 187 230 264 Input Voltage [V AC] 2003670000 connectPower PRO-H CP T SNT 70W 12V 6A Switch-mode power supplies connectPower PRO-H CP T SNT 140W 12V 12A A L (+) N (–) + – AC PE DC 13 14 DC OK Data Link L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 1 A @ 230 V AC, 2 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 1.4 A @ 230 V AC, 2.5 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 12 V DC ± 1 % 12...14 V DC (adjustable via potentiometer on front) 100 mVSS @ 12 V DC, Inom 6 A @ 40 °C 6 A @ 40 °C, 5.4 A @ 60 °C, 4.5 A @ 70 °C 12 V DC ± 1 % 12...14 V DC (adjustable via potentiometer on front) 100 mVSS @ 12 V DC, Inom 12 A @ 40 °C 12 A @ 40 °C, 7 A @ 60 °C, 3.7 A @ 70 °C typ. 82 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 35 / 110 mm 0.5 kg typ. 85 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 54 / 110 mm 0.7 kg BVATEX; CE; CSA; cURus; EAC; UL BVATEX; CE; CSA; cURus; EAC; UL Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 70W 12V 6A Output Screw connection 2 (+ / -) 1 / 2.5 1 / 2.5 18 / 12 Qty. 1 Order No. 1105430000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 140W 12V 12A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 1 / 2.5 18 / 12 Qty. 1 Order No. 1105440000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.31 Switch-mode power supplies connectPower PRO-H connectPower PRO-H CP T SNT 90W 24V 3.8A CP T SNT 90W 24V 3.8A CL2 Class 2, UL 1310 A L (+) N (–) + – AC PE DC 13 14 DC OK Data Link L (+) N (–) + – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 1 A @ 230 V AC, 2.1 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 1 A @ 230 V AC, 2.1 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 3.8 A @ 40 °C 3.8 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 3.8 A @ 40 °C 3.8 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C typ. 85 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 35 / 110 mm 0.5 kg typ. 85 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 35 / 110 mm 0.5 kg BVATEX; CE; CSA; cURus; EAC; UL CE; EAC; UL Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 90W 24V 3,8A Output Screw connection 2 (+ / -) 1 / 2.5 0.5 / 2.5 24 / 12 Qty. 1 Order No. 1105790000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 90W 24V3,8ACL2 Output Screw connection 2 (+ / -) 1 / 2.5 0.5 / 2.5 24 / 12 Qty. 1 Order No. 1194410000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note A.32 2003670000 connectPower PRO-H CP T SNT 180W 24V 7.5A Switch-mode power supplies connectPower PRO-H CP T SNT 360W 24V 15A A L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note mm² mm² 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 1.4 A @ 230 V AC, 2.5 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 2.5 A @ 230 V AC, 5 A @ 115 V AC 6.3 A / < 25 A (230 V AC) 10…16 A, char. B, circuit breaker 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 7.5 A @ 40 °C 7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 15 A @ 40 °C 15 A @ 40 °C, 10 A @ 60 °C, 6.7 A @ 70 °C typ. 88 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 54 / 110 mm 0.7 kg typ. 87 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 80 / 110 mm 1.1 kg BVATEX; CE; CSA; cURus; EAC; UL BVATEX; CE; CSA; cURus; EAC; UL Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 180W 24V 7,5A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 0.5 / 2.5 24 / 12 Qty. 1 Order No. 1105810000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 360W 24V 15A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 1 / 2.5 18 / 12 Qty. 1 Order No. 1105820000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.33 Switch-mode power supplies connectPower PRO-H connectPower PRO-H CP T SNT 600W 24V 25A A L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 5 A @ 230 V AC, 10 A @ 115 V AC 12 A / < 30 A (230 V AC) 16…25 A, char. B, circuit breaker 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 25 A @ 40 °C 25 A @ 40 °C, 20 A @ 60 °C, 13.3 A @ 70 °C typ. 89 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 125 / 165 / 125 mm 2.8 kg BVATEX; CE; CSA; cURus; EAC; UL mm² mm² Input Screw connection 3 for L/N/PE 1/4 1/4 18 / 10 Type CP T SNT 600W 24V 25A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 2.5 / 4 12 / 10 Qty. 1 Order No. 1105840000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note A.34 2003670000 connectPower PRO-H CP T SNT 90W 48V 2A Switch-mode power supplies connectPower PRO-H CP T SNT 180W 48V 4A A L (+) N (–) PE + – AC DC 13 14 DC OK Data Link L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note mm² mm² 100...240 V AC (wide-range input) 85...264 V AC 47...63 Hz 1 A @ 230 V AC, 2.1 A @ 115 V AC 4 A / < 20 A (230 V AC) 6…16 A, char. B, circuit breaker 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 1.4 A @ 230 V AC, 2.5 A @ 115 V AC 4 A / < 25 A (230 V AC) 6…16 A, char. B, circuit breaker 48 V DC ± 1 % 48...56 V DC (adjustable via potentiometer on front) 100 mVSS @ 48 V DC, INenn 2 A @ 40 °C 2 A @ 40 °C, 1.3 A @ 60 °C, 0.8 A @ 70 °C 48 V DC ± 1 % 48...56 V DC (adjustable via potentiometer on front) 100 mVSS @ 48 V DC, INenn 4 A @ 40 °C 4 A @ 40 °C, 2.5 A @ 60 °C, 1.7 A @ 70 °C typ. 87 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 35 / 110 mm 0.5 kg typ. 90 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 110 / 54 / 110 mm 0.7 kg BVATEX; CE; EAC; UL BVATEX; CE; CSA; cURus; EAC; UL Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 90W 48V 2A Output Screw connection 2 (+ / -) 1 / 2.5 0.5 / 2.5 24 / 12 Qty. 1 Order No. 1194420000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 180W 48V 4A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 0.5 / 2.5 24 / 12 Qty. 1 Order No. 1105850000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.35 Switch-mode power supplies connectPower PRO-H connectPower PRO-H CP T SNT 360W 48V 7.5A CP T SNT 600W 48V 12.5A A L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note mm² mm² 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 2.5 A @ 230 V AC, 5 A @ 115 V AC 6.3 A / < 25 A (230 V AC) 10…16 A, char. B, circuit breaker 100…240 V AC (auto-select) 85…132 V AC, 187…264 V AC 47...63 Hz 5 A @ 230 V AC, 10 A @ 115 V AC 12 A / < 30 A (230 V AC) 16…25 A, char. B, circuit breaker 48 V DC ± 1 % 48...56 V DC (adjustable via potentiometer on front) 100 mVSS @ 48 V DC, INenn 7.5 A @ 40 °C 7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C 48 V DC ± 1 % 48...56 V DC (adjustable via potentiometer on front) 100 mVSS @ 48 V DC, INenn 12.5 A @ 40 °C 12.5 A @ 40 °C, 10 A @ 60 °C, 7.5 A @ 70 °C typ. 89 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 125 / 80 / 125 mm 1.1 kg typ. 91 % @ 230 V AC min. 20 ms @ 230 V AC, min. 10 ms @ 115 V AC yes, max. 5 125 / 165 / 125 mm 2.8 kg BVATEX; CE; CSA; cURus; EAC; UL BVATEX; CE; CSA; cURus; EAC; UL Input Screw connection 3 for L/N/PE 0.5 / 2.5 0.5 / 2.5 24 / 12 Type CP T SNT 360W 48V 7,5A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 1 / 2.5 18 / 12 Qty. 1 Order No. 1105860000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Input Screw connection 3 for L/N/PE 1/4 1/4 18 / 10 Type CP T SNT 600W 48V 12,5A Output Screw connection 7 (+ / - / Signal) 1 / 2.5 2.5 / 4 12 / 10 Qty. 1 Order No. 1105870000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note A.36 2003670000 connectPower PRO-H CP T SNT2 180W 24V 7.5A Switch-mode power supplies connectPower PRO-H CP T SNT2 360W 24V 15A A L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note 100…500 V AC (switchable) 85…132 V AC, 187…550 V AC 50 / 60 Hz 100…500 V AC (switchable) 85…132 V AC, 187…550 V AC 50 / 60 Hz / < 23 A @ 230 V AC mm² mm² / < 23 A @ 230 V AC 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 7.5 A @ 40 °C 7.5 A @ 40 °C, 5 A @ 60 °C, 3.3 A @ 70 °C 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 15 A @ 40 °C 15 A @ 40 °C, 6.7 A @ 70 °C, 10 A @ 60 °C typ. 88 % min. 20 ms Yes 110 / 54 / 110 mm 0.7 kg typ. 88 % min. 20 ms Yes 125 / 80 / 125 mm 1.1 kg CE; EAC CE; EAC Input Screw connection 3 for L/N/PE 1/4 1/4 18 / 10 Output Screw connection 4 (++ / --) 2.5 / 4 2.5 / 4 12 / 10 Input Screw connection 3 for L/N/PE 1/4 1/4 18 / 10 Output Screw connection 4 (++ / --) 2.5 / 4 2.5 / 4 12 / 10 The device is suitable for single-phase and two-phase operation. The device is suitable for single-phase and two-phase operation. Type CP T SNT2 180 W 24 V 7,5 A Type CP T SNT2 360 W 24 V 15 A Qty. 1 Order No. 1194480000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Qty. 1 Order No. 1194490000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.37 Switch-mode power supplies connectPower PRO-H connectPower PRO-H CP T SNT2 600W 24V 25A A L (+) N (–) + + – – AC PE DC 13 14 DC OK Data Link Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data Note 100…500 V AC (switchable) 85…132 V AC, 187…550 V AC 50 / 60 Hz / < 50 A @ 230 V AC 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 25 A @ 40 °C 25 A @ 40 °C, 20 A @ 40 °C, 13.3 A @ 70 °C typ. 88 % min. 20 ms Yes 125 / 190 / 125 mm 3 kg CE; EAC mm² mm² Input Screw connection 3 for L/N/PE 1/4 1/4 18 / 10 Output Screw connection 5 (++ / ---) 2.5 / 4 2.5 / 4 12 / 10 The device is suitable for single-phase and two-phase operation. Type CP T SNT2 600 W 24 V 25 A Qty. 1 Order No. 1194310000 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Accessories Note A.38 2003670000 connectPower PRO-H CP T RM 10 Switch-mode power supplies connectPower PRO-H CP T RM 20 A Input 1 Data Link PS1 Data Link PS2 Input 1 Output Control Input 2 Remote ON/OFF Data Link PS1 Data Link PS2 Output Control Input 2 DC OK Remote ON/OFF DC OK Technical data Input Rated input voltage Input voltage range AC Frequency range AC AC current consumption Input fuse (internal) / Inrush current Recommended back-up fuse Output Rated output voltage Output voltage Residual ripple, breaking spikes Rated (nominal) output current @ UNom continous output current @ 24 V DC General data Degree of efficiency AC failure bridging time @ INom Parallel connection option Depth x width x height Weight Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data mm² mm² 24 V DC 24 V DC 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 15 A @ 40 °C 24 V DC ± 1 % 24...28 V DC (adjustable via potentiometer on front) 100 mVPP @ 24 V DC, Inenn 25 A @ 40 °C 110 / 35 / 110 mm 0.4 kg 110 / 54 / 110 mm 0.45 kg CE; CSA; cURus; EAC; GOSTME25 CE; CSA; cURus; EAC; GOSTME25 Input Output Input Output 4 (++--) 1/4 1/4 18 / 10 4 (++ / --) 2.5 / 4 2.5 / 4 12 / 10 4 (++--) 1/4 1/4 18 / 10 4 (++ / --) 2.5 / 4 2.5 / 4 12 / 10 Type CP T RM 10 Qty. 1 Order No. 1105880000 Type CP T RM 20 Qty. 1 Order No. 1105890000 Note Accessories Note 2003670000 A.39 Switch-mode power supplies connectPower PRO H - Accessories A Large screwdriver Small screwdriver Type SDIK PH1 SDIS 0.5X3.0X100 Blade type Size/AF 1.00 B a b 0.5 3 c 80 100 Order No. 9008570000 9008380000 Type SDIK PH2 SDIS 1.0X5.5X125 Blade type Size/AF 2.00 B a b 1 5.5 c 100 125 Order No. 9008580000 9008410000 Qty. 50 Order No. 1162600000 End bracket Markers For DIN rail TS 35 Type SM 18/9.5 K MC NE WS A.40 Colour white Qty. 200 Order No. 1248580000 Polyamide with fibre glass, screwable WEW 35/1 SW Colour black Torque 1.2 Nm 2003670000 PRO-H Dimensional drawings CP T RM 10 CP T RM 20 35.0 (1.38) DC 24 V / 25 A Inputs ON - + - + 25.0 110.0 DC IN 1 5.0 (0.20) (0.98) 5.0 CP T SNT 70 W / 90 W DC IN 2 25.0 (0.20) 5.0 (0.20) 80.0 (3.15) DC IN 1 DC IN 2 14.5 (0.57) CP T SNT 180 W / 140 W 110.0 54.0 (4.33) 110.0 (4.33) (2.13) 38.5 (1.52) (1.38) DC OK DC ON A 24 ² 27 V 80.0 (3.15) 110.0 (4.33) (4.33) 24 ² 27 V 38.5 (1.52) Output Inputs ON (0.98) 110.0 (4.33) (2.13) 38.5 (1.52) 38.5 - - + + 35.0 54.0 (4.33) (1.52) 110.0 Switch-mode power supplies connectPower PRO-H DC ON DC OK O/P ADJ . 5.0 (0.20) 5.0 (0.20) L 25.0 (0.98) 14.5 (0.57) S P 25.0 (0.98) PE N L 5.0 N (0.20) PE 80.0 (3.15) 110.0 80.0 (3.15) 110.0 (4.33) (4.33) O/P ADJ . P/ S P S Remote P/ S Remote 2003670000 A.41 CP T SNT 360 W / 480 W CP T SNT 600 W / 960 W 80.0 (3.15) 125.0 (4.92) P/ S Remote 45.0 (1.77) P S DC OK DC ON O/P ADJ . 86.5 (3.41) A PRO-H Dimensional drawings 125.0 (4.92) Switch-mode power supplies connectPower PRO-H 25.0 25.0 (0.98) PE N (0.98) 21.0 123.0 L (4.84) (0.83) 165.0 (6.50) 45.0 (1.77) (0.98) 17.0 (0.67) 25.0 (0.98) 125.0 (4.92) 5.0 (0.20) (1.81) PE N L DC OK DC ON O/P A DJ. 86.5 (3.41) 46.0 25.0 125.0 (4.92) Remote P S P/ S A.42 2003670000 A 2003670000 A.43 Switch-mode power supplies Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 25W 5V 5A CP E SNT 25W 12V 2.1A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 0.3 A @ 230 V AC / 0.6 A @ 120 V AC 47...63 Hz yes / max. 20A 1 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 0.3 A @ 230 V AC / 0.6 A @ 120 V AC 47...63 Hz yes / max. 20A 1 A at 230 V AC, characteristic curve C 5 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 5 A@5 V DC 25 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 5.6...6.8 V @ 5 V DC 20 ms 0.5% Recommended with diode module 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 2.1 A@12 V DC 25 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 77 % @ 5 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 240 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 79 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 240 g CE; cURus; EAC 0.34 / 4 mm² 91 / 51 / 28 mm 0.34 / 4 mm² 91 / 51 / 28 mm Note Ordering data Note Type CP E SNT 25W 5V 5A Qty. 1 Order No. 1202640000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 25W 12V 2.1A Qty. 1 Order No. 1202630000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.44 2003670000 connectPower PRO-E CP E SNT 25W 24V 1.1A Switch-mode power supplies connectPower PRO-E CP E SNT 25W 48V 0.57A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 0.3 A @ 230 V AC / 0.6 A @ 120 V AC 47...63 Hz yes / max. 20A 1 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 0.3 A @ 230 V AC / 0.6 A @ 120 V AC 47...63 Hz yes / max. 20A 1 A at 230 V AC, characteristic curve C 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 1.1 A@24 V DC 25 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 0.57 A@48 V DC 25 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 84 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 240 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 83 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 240 g CE; cURus; EAC 0.34 / 4 mm² 91 / 51 / 28 mm 0.34 / 4 mm² 91 / 51 / 28 mm Note Ordering data Note Type CP E SNT 25W 24V 1.1A Qty. 1 Order No. 1202620000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 25W 48V 0.57A Qty. 1 Order No. 1202610000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.45 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 50W 5V 10A CP E SNT 50 W 12V 4.2A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 0.6 A @ 230 V AC / 1.2 A @ 120 V AC 47...63 Hz yes / max. 20A 2 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 0.6 A @ 230 V AC / 1.2 A @ 120 V AC 47...63 Hz yes / max. 20A 2 A at 230 V AC, characteristic curve C 5 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 10 A@5 V DC 50 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 5.6...6.8 V @ 5 V DC 20 ms 0.5% Recommended with diode module 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 4.2 A@12 V DC 50 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 78 % @ 5 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 310 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 81 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 310 g CE; cURus; EAC 0.34 / 4 mm² 105 / 100 / 35 mm 0.34 / 4 mm² 105 / 100 / 35 mm Note Ordering data Note Type CP E SNT 50W 5V 10A Qty. 1 Order No. 1202590000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 50W 12V 4.2A Qty. 1 Order No. 1202580000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.46 2003670000 connectPower PRO-E CP E SNT 50W 24V 2.2A Switch-mode power supplies connectPower PRO-E CP E SNT 50W 48V 1.1A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 0.6 A @ 230 V AC / 1.2 A @ 120 V AC 47...63 Hz yes / max. 20A 2 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 0.6 A @ 230 V AC / 1.2 A @ 120 V AC 47...63 Hz yes / max. 20A 2 A at 230 V AC, characteristic curve C 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 2.2 A@24 V DC 50 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 1.1 A@48 V DC 50 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 84 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 310 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 86 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 310 g CE; cURus; EAC 0.34 / 4 mm² 105 / 100 / 35 mm 0.34 / 4 mm² 105 / 100 / 35 mm Note Ordering data Note Type CP E SNT 50W 24V 2.2A Qty. 1 Order No. 1202450000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 50W 48V 1.1A Qty. 1 Order No. 1202460000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.47 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 75W 5V 12A CP E SNT 75W 12V 6A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 1 A @ 230 V AC / 2 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 1 A @ 230 V AC / 2 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 5 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 12 A@5 V DC 75 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 5.6...6.8 V @ 5 V DC 20 ms 0.5% Recommended with diode module 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 6 A@12 V DC 75 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 76 % @ 5 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 440 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 81 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 440 g CE; cURus; EAC 0.34 / 4 mm² 135 / 98.5 / 40 mm 0.34 / 4 mm² 135 / 98.5 / 40 mm Note Ordering data Note Type CP E SNT 75W 5V 12A Qty. 1 Order No. 1202470000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 75W 12V 6A Qty. 1 Order No. 1202480000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.48 2003670000 connectPower PRO-E CP E SNT 75W 24V 3.2A Switch-mode power supplies connectPower PRO-E CP E SNT 75W 48V 1.6A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 1 A @ 230 V AC / 2 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 1 A @ 230 V AC / 2 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 3.2 A@24 V DC 75 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 1.6 A@48 V DC 75 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 85 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 440 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 86 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 440 g CE; cURus; EAC 0.34 / 4 mm² 135 / 98.5 / 40 mm 0.34 / 4 mm² 135 / 98.5 / 40 mm Note Ordering data Note Type CP E SNT 75W 24V 3.2A Qty. 1 Order No. 1202490000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 75W 48V 1.6A Qty. 1 Order No. 1202510000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.49 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 100W 5V 16A CP E SNT 100W 12V 8.5A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 1.5 A @ 230 V AC / 3 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 88…132 V AC / 176…264 V AC optional / 250...370 V DC 1.5 A @ 230 V AC / 3 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 5 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 16 A@5 V DC 100 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 5.6...6.8 V @ 5 V DC 20 ms 0.5% Recommended with diode module 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 8.5 A@12 V DC 100 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 77 % @ 5 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 590 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 81 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 590 g CE; cURus; EAC 0.34 / 4 mm² 164 / 97.5 / 40 mm 0.34 / 4 mm² 164 / 97.5 / 40 mm Note Ordering data Note Type CP E SNT 100W 5V 16A Qty. 1 Order No. 1165820000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 100W 12V 8.5A Qty. 1 Order No. 1165830000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.50 2003670000 connectPower PRO-E CP E SNT 100W 24V 4.5A Switch-mode power supplies connectPower PRO-E CP E SNT 100W 48V 2.3A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 1.5 A @ 230 V AC / 3 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 88…132 V AC / 176…264 V AC optional / 250...370 V DC 1.5 A @ 230 V AC / 3 A @ 120 V AC 47...63 Hz yes / max. 20A 4 A at 230 V AC, characteristic curve C 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 4.5 A@24 V DC 100 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 2.3 A@48 V DC 100 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 85 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 590 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 86 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 590 g CE; cURus; EAC 0.34 / 4 mm² 164 / 97.5 / 40 mm 0.34 / 4 mm² 164 / 97.5 / 40 mm Note Ordering data Note Type CP E SNT 100W 24V 4.5A Qty. 1 Order No. 1165840000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 100W 48V 2.3A Qty. 1 Order No. 1165850000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.51 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 150W 12V 12.5A CP E SNT 150W 24V 6.5A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2 A @ 230 V AC / 3.5 A @ 120 V AC 47...63 Hz yes / max. 35A 4 A at 230 V AC, characteristic curve C 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2 A @ 230 V AC / 3.5 A @ 120 V AC 47...63 Hz yes / max. 35A 4 A at 230 V AC, characteristic curve C 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 12.5 A@12 V DC 150 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 6.5 A@24 V DC 150 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 82 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 820 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 86 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 820 g CE; cURus; EAC 0.34 / 4 mm² 205 / 99 / 40 mm 0.34 / 4 mm² 205 / 99 / 40 mm Note Ordering data Note Type CP E SNT 150W 12V 12.5A Qty. 1 Order No. 1165870000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 150W 24V 6.5A Qty. 1 Order No. 1165880000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.52 2003670000 connectPower PRO-E Switch-mode power supplies connectPower PRO-E CP E SNT 150W 48V 3.3A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2 A @ 230 V AC / 3.5 A @ 120 V AC 47...63 Hz yes / max. 35A 4 A at 230 V AC, characteristic curve C 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 3.3 A@48 V DC 150 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 87 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 820 g CE; cURus; EAC 0.34 / 4 mm² 205 / 99 / 40 mm Note Ordering data Note Type CP E SNT 150W 48V 3.3A Qty. 1 Order No. 1165890000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.53 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 250W 12V 21A CP E SNT 250W 24V 10.5A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2.5 A @ 230 V AC / 4.7 A @ 120 V AC 47...63 Hz yes / max. 35A 6 A at 230 V AC, characteristic curve C 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2.5 A @ 230 V AC / 4.7 A @ 120 V AC 47...63 Hz yes / max. 35A 6 A at 230 V AC, characteristic curve C 12 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 21 A@12 V DC 250 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 13.5...16.2 V @ 12 V DC 20 ms 0.5% Recommended with diode module 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 10.5 A @ 24 V DC 250 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 80 % @ 12 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 1080 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 81 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 1080 g CE; cURus; EAC 0.34 / 4 mm² 231 / 115 / 49.5 mm 0.34 / 4 mm² 231 / 115 / 49.5 mm Note Ordering data Note Type CP E SNT 250W 12V 21A Qty. 1 Order No. 1202520000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 250W 24V 10.5A Qty. 1 Order No. 1202530000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.54 2003670000 connectPower PRO-E Switch-mode power supplies connectPower PRO-E CP E SNT 250W 48V 5.2A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 88…132 V AC / 176…264 V AC optional / 250...370 V DC 2.5 A @ 230 V AC / 4.7 A @ 120 V AC 47...63 Hz yes / max. 35A 6 A at 230 V AC, characteristic curve C 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 5.2 A@48 V DC 250 W < 100 mVPP 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 83 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 1080 g CE; cURus; EAC 0.34 / 4 mm² 231 / 115 / 49.5 mm Note Ordering data Note Type CP E SNT 250W 48V 5.2A Qty. 1 Order No. 1202540000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.55 Switch-mode power supplies connectPower PRO-E connectPower PRO-E CP E SNT 350W 24V 14.6A CP E SNT 350W 48V 7.3A A / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ / 1² $& 3( '& ² 1RWHSRODULW\IRU'&FRQQHFWLRQ Technical data Input Input voltage Input current Input frequency Input fuse (internal) Recommended back-up fuse Output Output voltage Output voltage adjustment Output current Output power Residual ripple, breaking spikes Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output General data Ambient temperature (operational) Storage temperature Max. perm. air humidity (operational) Degree of efficiency Status indicator Standards EMC standards Mounting position, installation notice Weight Approvals Screw connection Connection cross-section, solid, min. / max. Depth x width x height 85...264 V AC / 110…370 V DC 3 A @ 230 V AC / 5.6 A @ 120 V AC 47...63 Hz yes / max. 35A 6 A at 230 V AC, characteristic curve C 85...264 V AC / 110…370 V DC 3 A @ 230 V AC / 5.6 A @ 120 V AC 47...63 Hz yes / max. 35A 6 A at 230 V AC, characteristic curve C 24 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 14.6 A@24 V DC 350 W 48 V DC ± 10% nominal output voltage tolerance, adjustable with potentiometer 7.3 A@48 V DC 350 W 120~150% Ikonst. of max. output power, automatic restart 28...32 V @ 24 V DC 20 ms 0.5% Recommended with diode module 120~150% Ikonst. of max. output power, automatic restart 55...62 V @ 48 V DC 20 ms 0.5% Recommended with diode module 0.5 kV 1.5 kV 3 kV 0.5 kV 1.5 kV 3 kV -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 83 % @ 24 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 1250 g CE; cURus; EAC -20°C…70°C (>50°C derating,refer derated curve); 70% rated load@70°C -20 °C...85 °C 5 %…95 % RH 85 % @ 48 V DC Operation, green LED EN 60950 EN 55011, EN 55022, EN 55024, EN 61000-6 /-2, -3 Panel mount, screw fix 1250 g CE; cURus; EAC 0.34 / 4 mm² 230 / 115 / 49.5 mm 0.34 / 4 mm² 230 / 115 / 49.5 mm Note Ordering data Note Type CP E SNT 350W 24V 14.6A Qty. 1 Order No. 1202550000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Type CP E SNT 350W 48V 7.3A Qty. 1 Order No. 1202560000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.56 2003670000 A 2003670000 A.57 Switch-mode power supplies Installation drawing CP E SNT 25W CP E SNT 50W 78 55 11 105 99.5 6.5 Ø 3.5 52.5 32 93 100 A 34 25.5 2-M3 2-M3 3 Ø4 Ø 3.5 3.25 Ø 3.5 3.25 14 30 28 66 12 12 15 13.5 35 Switch-mode power supplies connectPower PRO-E 15 93 100 2-M3 CP E SNT 75W 3-M3 CP E SNT 100W 135 124.5 78 4.4 Ø 3.5 164 57 6 6.5 52 32 90.5 97.5 32 91.5 98.5 32.5 34 Ø 3.5 2-M3 2.25 Ø 3.5 Ø 3.5 2.25 117 152.5 3-M3 3.25 Ø 3.5 18 28.5 40 31 19.8 3-M3 28.4 18.6 22 Ø 3.5 4-M3 11 18 29.5 40 Ø 3.5 2.75 20 10 Ø 3.5 124.5 78 120 18.5 80.5 92 99 6.5 205 195.5 9.25 CP E SNT 150W Ø 3.5 Ø 3.5 4-M3 18.5 31 40 157 205 A.58 4.75 3.5 157 193 20.5 11 28 18 Ø 3.5 3-M3 2003670000 Switch-mode power supplies connectPower PRO-E Installation drawing CP E SNT 250W and CP E SNT 350W 150 32.5 230 25 49.5 20 12.5 5-M3 CP E SNT 250W and CP E SNT 350W (with mounting clip) 57 150 230 150.5 32.5 32.5 26 14 26 150 4.5 3-Ø 26 32.5 8 15 Ø4 .5 115 A 15 8 50 115 5-M3 150 14 26 32.5 150 26 3-Ø4.514 8 15 15 8 26 49.5 26 Ø4.5 230 Ø4.5 115 131 145 32.5 115 118 12.5 32 145 131 25 Ø4.5 6-M3 4.5 3-Ø 49.5 68 .5 Ø4 230 25 14 26 CP-E-SNT derating curve / ambient temperature CP E SNT 25W up to CP E SNT 350W 100% Load (%) 80% 60% 40% 20% 0 10 20 30 40 50 60 70 80 Ambient temperature (°C) 2003670000 A.59 Switch-mode power supplies connectPower INSTAPOWER connectPower Single-phase CP SNT 24W 24V 1A CP SNT 24W 15V 1.5A A L AC/DC N PWM L + FUSE N DC + L − N FUSE + − – Technical data Input Input voltage Input current Input frequency Turn-on current limit Input fuse Surge protection Output Output voltage Output current Output power Max. residual ripple Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection Note 85...265 V AC, 120...300 V DC 460 mA @ 115 V AC; 250 mA @ 230 V AC 50/ 60 Hz Thermistor 2 A time-lag fuse (internal) Varistor 85...265 V AC, 120...300 V DC 460 mA @ 115 V AC; 250 mA @ 230 V AC 50/ 60 Hz Thermistor 2 A time-lag fuse (internal) Varistor 24 V DC 1A 24 W <2% Surge current / thermal cut-out Varistor 35 ms @ 115 V AC / 160 ms @ 230 V AC 0.5% 8000 µF 15 V DC 1.5 A 22.5 W <2% Surge current / thermal cut-out Varistor 35 ms @ 115 V AC / 160 ms @ 230 V AC 0.5% 8000 µF 0.5 kV 1.5 kV 3 kV 4 kV 0.5 kV 1.5 kV 3 kV 4 kV -20 °C...50 °C -40 °C...85 °C 78% DIN EN 50178, DIN EN 60950, IEC950 CE; CSA; CSAEX; cULus; EAC; GOSTME25 EN 61000-6 /-2, -3 yes, max 2. -20 °C...50 °C -40 °C...85 °C 78% DIN EN 50178, DIN EN 60950, IEC950 CE; CSA; cULus; EAC; GOSTME25 EN 61000-6 /-2, -3 yes, max 2. Input/Output 4 / 0.08 / 4 62.5 / 52 / 90.5 Input/Output 4 / 0.08 / 4 62.5 / 52 / 90.5 Derating loss: 33 % @ 60 °C The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Derating loss: 33 % @ 60 °C The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type CP SNT 24W 24V 1A Type CP SNT 24W 15V 1.5A Qty. 1 Order No. 9928890024 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Qty. 1 Order No. 9928890015 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.60 2003670000 connectPower Single-phase CP SNT 24W 12V 1.5A Switch-mode power supplies connectPower INSTAPOWER CP SNT 24W 5V 2A A L AC/DC N PWM L + FUSE N DC + L − N FUSE + − – Technical data Input Input voltage Input current Input frequency Turn-on current limit Input fuse Surge protection Output Output voltage Output current Output power Max. residual ripple Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection Note 85...265 V AC, 120...300 V DC 460 mA @ 115 V AC; 250 mA @ 230 V AC 50/ 60 Hz Thermistor 2 A time-lag fuse (internal) Varistor 85...265 V AC, 120...300 V DC 460 mA @ 115 V AC; 250 mA @ 230 V AC 50/ 60 Hz Thermistor 2 A time-lag fuse (internal) Varistor 12 V DC 1.5 A 18 W <2% Surge current / thermal cut-out Varistor 35 ms @ 115 V AC / 160 ms @ 230 V AC 0.5% 8000 µF 5 V DC 2A 10 W <2% Surge current / thermal cut-out Varistor 35 ms @ 115 V AC / 160 ms @ 230 V AC 0.5% 8000 µF 0.5 kV 1.5 kV 3 kV 4 kV 0.5 kV 1.5 kV 3 kV 4 kV -20 °C...50 °C -40 °C...85 °C 78% DIN EN 50178, DIN EN 60950, IEC950 CE; CSA; cULus; EAC; GOSTME25 EN 61000-6 /-2, -3 yes, max 2. -20 °C...50 °C -40 °C...85 °C 78% DIN EN 50178, DIN EN 60950, IEC950 CE; CSA; cULus; EAC; GOSTME25 EN 61000-6 /-2, -3 yes, max 2. Input/Output 4 / 0.08 / 4 62.5 / 52 / 90.5 Input/Output 4 / 0.08 / 4 62.5 / 52 / 90.5 Derating loss: 33 % @ 60 °C The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Derating loss: 33 % @ 60 °C The internal varistor found in a switch-mode power supply does not replace the need for surge protection within a system. Type CP SNT 24W 12V 1.5A Type CP SNT 24W 5V 2A Qty. 1 Order No. 9928890012 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Qty. 1 Order No. 9928890005 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.61 Switch-mode power supplies connectPower INSTAPOWER connectPower Single-phase CP SNT 25W 5V 5A A PWM L + FUSE + − N DC – Technical data Derating curve Input Input voltage Input current Input frequency Turn-on current limit Input fuse Output Output voltage Output current Output power Max. residual ripple Overload protection 85...264 V AC / 110...370 V DC 500 mA at rated load @ 230 V AC 50/ 60 Hz Yes Fusible link 2.5 A (T) / 250 V 5 4...8 V DC (adjustable via potentiometer) 5A 25 W 120 mVSS 105 %...150 % Iconst of max. output load; automatic reset 4 3 2 1 0 0 10 20 30 40 50 60 Ambient temperature (°C) 70 80 Varistor 11 ms @ 115 V AC / 50 ms @ 230 V AC 1% 10000 µF Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height 6 Current (A) L AC/DC N 0.5 kV 1.5 kV 3 kV 4 kV -10...70 °C (Derating ab 55 °C) -20 °C...85 °C 70% DIN EN 50178 (PELV), DIN EN 60950 (SELV) cCSAus; cURus; EAC; GOSTME25; UL EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4 Max. 3 devices (rated voltages are to be calibrated at ±20 mV) mm² mm Input/Output 2.5 / 0.5 / 4 62.5 / 70 / 90.5 Note Ordering data Screw connection Note Type CP SNT 25W 5V 5A Qty. 1 Order No. 8754960000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.62 2003670000 connectPower Single-phase Switch-mode power supplies connectPower INSTAPOWER CP SNT 48W 12V 4A A PWM L + FUSE + − N DC – Technical data Derating curve Input Input voltage Input current Input frequency Turn-on current limit Input fuse Output Output voltage Output current Output power Max. residual ripple Overload protection 85...264 V AC / 110...370 V DC 500 mA at rated load @ 230 V AC 50/ 60 Hz Yes Fusible link 2.5 A (T) / 250 V 5 9...15 V DC (adjustable via potentiometer) 4A 48 W 120 mVSS 105 %...150 % Iconst of max. output load; automatic reset 4 3 2 1 0 0 10 20 30 40 50 60 Ambient temperature (°C) 70 80 Varistor 11 ms @ 115 V AC / 50 ms @ 230 V AC 1% 10000 µF Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height 6 Current (A) L AC/DC N 0.5 kV 1.5 kV 3 kV 4 kV -10...70 °C (Derating ab 55 °C) -20 °C...85 °C 75% DIN EN 50178 (PELV), DIN EN 60950 (SELV) cCSAus; CE; cURus; EAC; GOSTME25; UL EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4 Max. 3 devices (rated voltages are to be calibrated at ±20 mV) mm² mm Input/Output 2.5 / 0.5 / 4 62.5 / 70 / 90.5 Note Ordering data Screw connection Note Type CP SNT 48W 12V 4A Qty. 1 Order No. 8754970000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.63 Switch-mode power supplies connectPower INSTAPOWER connectPower Single-phase CP SNT 48W 24V 2A A PWM L + FUSE + − N DC – Technical data Derating curve Input Input voltage Input current Input frequency Turn-on current limit Input fuse Output Output voltage Output current Output power Max. residual ripple Overload protection 85...264 V AC / 110...370 V DC 500 mA at rated load @ 230 V AC 50/ 60 Hz Yes Fusible link 2.5 A (T) / 250 V 15...28 V DC (adjustable via potentiometer) 2A 48 W 120 mVSS 105 %...150 % Iconst of max. output load; automatic reset 2 1.5 1 0.5 0 0 10 20 30 40 50 60 Ambient temperature (°C) 70 80 Varistor 11 ms @ 115 V AC / 50 ms @ 230 V AC 1% 10000 µF Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height 3 2.5 Current (A) L AC/DC N 0.5 kV 1.5 kV 3 kV 4 kV -10...70 °C (Derating ab 55 °C) -20 °C...85 °C 78% DIN EN 50178 (PELV), DIN EN 60950 (SELV) cCSAus; cURus; EAC; GOSTME25; UL EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4 Max. 3 devices (rated voltages are to be calibrated at ±20 mV) mm² mm Input/Output 2.5 / 0.5 / 4 62.5 / 70 / 90.5 Note Ordering data Screw connection Note Type CP SNT 48W 24V 2A Qty. 1 Order No. 8739140000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note A.64 2003670000 connectPower Single-phase Switch-mode power supplies connectPower INSTAPOWER CP SNT 48W 48V 1A A PWM L + FUSE + − N DC – Technical data Derating curve Input Input voltage Input current Input frequency Turn-on current limit Input fuse Output Output voltage Output current Output power Max. residual ripple Overload protection 85...264 V AC / 110...370 V DC 500 mA at rated load @ 230 V AC 50/ 60 Hz Yes Fusible link 2.5 A (T) / 250 V 46...55 V DC (adjustable via potentiometer) 1A 48 W 120 mVSS 105 %...150 % Iconst of max. output load; automatic reset 1.5 1 0.5 0 0 10 20 30 40 50 60 Ambient temperature (°C) 70 80 Varistor 11 ms @ 115 V AC / 50 ms @ 230 V AC 1% 10000 µF Surge protection Mains failure bridge-over time Control at 10...100% load Max. capacitance at output Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Standards Approvals EMC standards Parallel connection option Dimensions Clamping range (nominal / min. / max.) Depth x width x height 2 Current (A) L AC/DC N 0.5 kV 1.5 kV 3 kV 4 kV -10...70 °C (Derating ab 55 °C) -20 °C...85 °C 80% DIN EN 50178 (PELV), DIN EN 60950 (SELV) cCSAus; cURus; EAC; GOSTME25; UL EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4 Max. 3 devices (rated voltages are to be calibrated at ±20 mV) mm² mm Input/Output 2.5 / 0.5 / 4 62.5 / 70 / 90.5 Note Ordering data Screw connection Note Type CP SNT 48W 48V 1A Qty. 1 Order No. 8879230000 The internal varistor found in a switch-mode power supply does not replace the necessary surge protection in a system. Accessories Note 2003670000 A.65 Switch-mode power supplies connectPower INSTAPOWER - Accessories A Small screwdriver Type SDIK PH1 SDIS 0.5X3.0X100 Blade type Size/AF 1.00 B a b 0.5 3 c 80 100 Order No. 9008570000 9008380000 End bracket Markers For DIN rail TS 35 Type SM 18/9.5 K MC NE WS A.66 Colour white Qty. 200 Order No. 1248580000 Polyamide with fibre glass, screwable WEW 35/1 SW Colour black Torque 1.2 Nm Qty. 50 Order No. 1162600000 2003670000 connectPower Single-phase Switch-mode power supplies connectPower WAVEPOWER CP SNT 12W 24V 0.5A A L AC/DC N PWM + DC – Technical data Input Input voltage Input current Input frequency Input fuse Surge protection Output Output voltage Output current Output power Max. residual ripple Overload protection Surge protection Mains failure bridge-over time Control at 10...100% load Parallel connection option Insulation coordination (EN 50178) electrical isolation, output-earth electrical isolation, input-earth electrical isolation, input-output electrical isolation, I/O rail General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Status indication Standards EMC standards Power factor correction Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note 85...265 V AC, 120...300 V DC 260 mA @ 115 V AC; 180 mA @ 230 V AC 50/ 60 Hz 2 A time-lag fuse (internal) Varistor 24 V DC 0.5 A 12 W 0.1 % Surge current / thermal cut-out Varistor 30 ms @ 115 V AC / 80 ms @ 230 V AC 0.6% No 0.5 kV 1.5 kV 3 kV 4 kV -20...50 °C -40 °C...85 °C 80% Green LED DIN EN 50178, DIN EN 60950, IEC950 IEC 61000-6 /-2, -3 No CE; CSA; cULus; EAC; GOSTME25 mm² mm Ordering data Screw connection Note Accessories Note 2003670000 Input/Output 2.5 / 0.5 / 2.5 112.4 / 22.5 / 92.4 Type CP SNT 12W 24V 0.5A Qty. 1 Order No. 9918840024 The internal varistor found in a switch-mode power unit does not replace the necessary surge protection in a system. Supply voltage 24 V and 0 V can be cross-connected with ZQV 2.5N/2 A.67 Switch-mode power supplies connectPower DC/DC converter connectPower CP DCDC 50W 22-24V 2A CP DCDC 50W 20-24V 2A A '& ² Chopper Transformer Rectifier and filtering Chopper Transformer Rectifier and filtering '& Technical data Input Input voltage Input fuse Output Output voltage Output current Overload protection General data Ambient temperature (operational) Storage temperature Status indication Switching frequency Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 18...30 V DC, typ. 24 V DC, ± 15% internal 10…14 V DC, typ. 12V DC, ± 15% internal 22...24 V DC 2A Surge current cut-out with self-reset 20.5...29.5 V DC 2A Surge current cut-out with self-reset -10...60 °C (Derating ab 50 °C) -40 °C...85 °C Green LED 200 kHz CE; CSA; CSAEX; cULus; EAC -10...60 °C (Derating ab 50 °C) -40 °C...85 °C Green LED 200 kHz CE; CSA; CSAEX; cULus; EAC Input/Output 4 / 0.1 / 4 131 / 57 / 98 Input/Output 4 / 0.1 / 4 131 / 57 / 98 Type CP DCDC 50W 22-24V 2A Qty. 1 Order No. 9919372424 Type CP DCDC 50W 22-24V 2A Qty. 1 Order No. 9919371224 Note Accessories Note A.68 Bracket for wall mounting: 7920560000 Bracket for wall mounting: 7920560000 2003670000 Switch-mode power supplies connectPower DC/DC converter CP DCDC 50W 12V 3A A Chopper Transformer Rectifier and filtering 18...30 V DC, typ. 24 V DC, ± 15% internal 10.5...14.5 V DC 3A Surge current cut-out with self-reset -10...60 °C (Derating ab 50 °C) -40 °C...85 °C Green LED 200 kHz CE; CSA; CSAEX; cULus; EAC Input/Output 4 / 0.1 / 4 131 / 57 / 98 Type CP DCDC 50W 12V 3A Qty. 1 Order No. 9919372412 Bracket for wall mounting: 7920560000 2003670000 A.69 Switch-mode power supplies connectPower DC/DC converter connectPower CP DCDC 50W 15V 3A CP DCDC 50W 5V 8A A '& ² Chopper Transformer Rectifier and filtering Chopper Transformer Rectifier and filtering '& Technical data Input Input voltage Input fuse Output Output voltage Output current Overload protection General data Ambient temperature (operational) Storage temperature Status indication Switching frequency Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 18...30 V DC, typ. 24 V DC, ± 15% internal 18...30 V DC, typ. 24 V DC, ± 15% internal 15 V DC 3A Surge current cut-out with self-reset 5 V DC 8A Surge current cut-out with self-reset -10...60 °C (Derating ab 50 °C) -40 °C...85 °C Green LED 200 kHz CE; CSA; CSAEX; cULus; EAC -10...60 °C (Derating ab 50 °C) -40 °C...85 °C Green LED 200 kHz CE; CSA; CSAEX; cULus; EAC Input/Output 4 / 0.1 / 4 131 / 57 / 98 Input/Output 4 / 0.1 / 4 131 / 57 / 98 Type CP DCDC 50W 15V 3A Qty. 1 Order No. 9919372415 Type CP DCDC 50W 5V 8A Qty. 1 Order No. 9919372405 Note Accessories Note A.70 Bracket for wall mounting: 7920560000 Bracket for wall mounting: 7920560000 2003670000 A 2003670000 A.71 Switch-mode power supplies Switch-mode power supplies connectPower DC/DC converter connectPower DC/DC converter DC voltage converter for preparation and potential isolation in 24 V DC systems •OvervoltagecategoryIII •ClassIIIprotection •Statusofrelaycontact •DCOKtransistoroutput A % { \u Technical data Temperature derating 130 Pout [% Pn] 120 110 100 90 80 70 60 20 30 40 50 60 Ambient temperature [°C] 70 80 General technical specifications Output characteristic curve / current limit Earth discharge current Ambient temp. Operating / storage temperature Max. permitted humidity (operational) Protection degree Class of protection Contamination degree Insulation voltage Overvoltage category MTBF Protection against load reverse voltages Parallel capability (without diode module) Mountable side-by-side without gaps Housing version, metal Signal operations Mounting position, installation notice Metal clip-on foot EMC / shock / vibration Noise emission according to EN55022 Interference immunity tests, according to Limiting of mains voltage harmonic currents Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switched-mode power units Machinery with electronic equipment Safety extra-low voltage Protective separation / protection against electrical shock Protection against dangerous shock currents Accessories Diode module (for redundant power supply) Capacity module (for pulse triggering of circuit breakers) A.72 IU / > 120 % IR < 0.005 mA –25 °C … +70 °C / –40 °C … +85 °C 5 %…95 % RH IP 20 III 2 2.5 kV AC 1 min. / 1.5 kV AC 1 min. / 0.5 kV AC 1 min. III > 500,000 hrs. according to IEC 1709 (SN29500) 33…34 V DC Yes, max. 5 Yes Resistant to corrosion LED green / red Horizontal on TS 35 DIN rail, above and below 50 mm Clearance for air circulation, suitable for aligning without clearance gap For installation in rotating systems Yes Class B EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields), EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted), EN61000-4-11 (Dips) According to EN 61000-3-2 According to EN50178, shock: 5 g in all directions According to EN60204 According to EN61558-2-17 According to EN50178 / VDE0160 SELV according to EN60950, PLEV according to EN60204 VDE0100-410 / according to DIN57100-410 According to VDE0106-101 Type CP M DM 20 CP M CAP Qty. 1 1 Order No. 1222210000 1222240000 2003670000 connectPower DC/DC converter Switch-mode power supplies connectPower DC/DC converter CP DCDC 250W 24V 10A A + + DC – – DC OK 14 13 DC Technical data Input Rated input voltage / DC input voltage range DC current consumption Inrush current Input fuse (internal) Recommended back-up fuse 24 V DC / 18 ... 31.2 V DC Typ.: 11 A, Max.: 15.5 A Max. 10 A Yes 16 A / DI/II safety fuse, 16 A, Char. B circuit breaker, 16 A, Char. C circuit breaker Output Rated output voltage Output voltage Ramp-up time Residual ripple, breaking spikes Rated (nominal) output current @ UNom Short-circuit protection / Overload protection Powerboost @ 24 V DC, 60 °C General data Degree of efficiency Power loss AC failure bridging time @ INom Tightening torque Reverse polarity protection Depth x width x height / Weight Signalling Status indicator 24 V DC ± 1 % ≤ 100 ms < 50 mVSS @ 24 V DC, IN 10 A @ 60 °C Yes / Yes 12 A for 1 min, ED = 5 % typ. 91% Idle: max. 2 W, Nominal load: 24 W > 7 ms @ 24 V DC 0.5...0.6 Nm Yes 150 / 60 / 130 mm / 1250 g LED green (DC OK): output voltage ≥ 21.6 V, LED red (fault): output voltage ≤ 20.4 V Output voltage ≥ 21.6 V ( max. 250 mA) Output voltage ≤ 20.4 V / Yes Yes max. 30 V DC / 0.5 A Output voltage > 21.6 V / < 20.4 V DC OK transistor output „1“ (max. load) DC OK transistor output „0“ / DC OK short circuit resistant Floating contact Contact load Relay on/off Approvals Approvals Connection data Wire connection method Number of terminals Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Note Ordering data cULus; EAC; GL; TUEV mm² mm² Input Screw connection 2 for (+ -) 0.5 / 6 0.5 / 2.5 26 / 12 Type CP DCDC 250W 24V 10A Output Screw connection 7 for (DCOK, 13,14, + + --) 0.5 / 6 0.5 / 2.5 26 / 12 Qty. 1 Order No. 1313320010 Note Accessories Note 2003670000 A.73 A A.74 2003670000 Uninterruptible power supplies (UPS) Contents Uninterruptible power supplies (UPS) Uninterruptible power supplies (UPS) 2003670000 Overview B.2 UPS control unit B.4 Battery modules B.6 Buffer modules B.8 B B.1 Uninterruptible power supplies (UPS) Uninterruptible power supplies (UPS) – Overview Uninterruptible power supplies Weidmüller‘s uninterruptible power supplies reliably protect 24 V DC consumers from voltage drop-outs and dips, such as those that could occur as a result of mains faults. These products therefore play a key role in increasing systems availability. B The buffer module is the perfect solution for bridging short-term power supply failures or dips of up to 100 ms. The capacitor-based technology enables maintenance-free operation, depending on the application, of up to 10 years. The UPS control unit, together with the accompanying battery module and the power supply, form a complete DC UPS system with support times in minutes or hours. The modular construction allows for the overall load to be distributed into non-safe and safe load circuits, such that often a smaller UPS can be designed. A huge variety of operating types are available to suit the particular application precisely. A remote input to block battery operation, as well as multiple signal outputs, enable remote operation of the UPS. UPS with battery module 0DLQV 5HPRWHGLVFRQQHFWLRQ ,QWHUORFN 3520 $& '& 9'& ² 5HOD\DQG WUDQVLVWRURXWSXWV &3'&8369 836FRQWUROXQLW 9'& ² 6DIH ORDG %DWWHU\PRGXOH &3$%DWWHU\9'& 1RQVDIH ORDG UPS with buffer module Relay and transistor ouput Mains PRO-M AC DC +24 V DC + – CP DC BUFFER 24V 20A + Buffer module +24 V DC Safe load – Non-safe load B.2 2003670000 Can your facility afford to experience a power failure? Allow us to connect you so that you are safe from failure and downtime. Let’s connect. Uninterruptible power supplies (UPS) Uninterruptible power supplies (UPS) – Overview B It is critical to safeguard a facility‘s power supply in the event of an outage. You cannot do without the important signals from the field, which serve to control the entire process. In addition, you also need to monitor a whole range of functions and performance parameters for your facility. Our highly modular power supply concept will support you in the practical fulfilment of all your requirements. At the same time, we will also familiarise ourselves with your future requirements and provide you with an individual, tailor-made solution, with components that are precisely aligned to work with one another. For a continual, lasting power supply and clean control voltage, we use redundant circuits, selective short-circuit solutions, battery reservoirs and DC/DC converters. And because lightning and power surges can put an uninterrupted power supply in a production facility at risk, we also provide lightning and overvoltage protection. The VPU series provides unrestricted operation of power supplies and automation devices such as sensors, actuators and control units. The subsequent availability of the power supply means that all devices will restart in a controlled manner. Let’s connect. 2003670000 PRO-M • • • • • Used to save space in automation technology Individual modulation of the output power Up to 5 devices can be switched directly, in parallel Optional diode modules with fault signalling Expanded temperature range –25 °C to 70 °C UPS control unit • Different status relays for status monitoring • Direct switchover to battery operation in the event of malfunction • Automatic reconnection to load when power recovers • Long battery life due to integrated deep discharge protection • Optimised charging feature B.3 Uninterruptible power supplies (UPS) UPS control unit • Two 24 V models in 10 A/20 A and 40 A • Temperature-compensated charging feature for long battery life • Integrated battery diagnostics including continuous availability test • Status relay and additional transistor outputs for remote monitoring • Convenient LED displays for easy error analysis B { \u % Technical data Indication Status relay ( max.load 30 V AC/DC 0.1 A) Transistor outputs (24 to 27 V DC max. load 150 mA) LED status indicator General technical data Ambient temperature (operational) Storage temperature Max. perm. air humidity Protection degree Class of protection Pollution severity level Overvoltage category Insulation voltage input/output to housing/ground MTBF Protection against reverse voltages from the load Parallel connection option Housing version Mounting position, installation notice Overload protection Short-circuit protection EMC / shock / vibration Interference emission Interference immunity tests Resistance against vibration and shock Electrical safety (applied standards) Electrical equipment of machines Safety transformers for switch-mode power supplies Machinery with electronic equipment Extra-low voltage protection Block diagram Interlock – 1 Interlock + 2 Temperature 6 Sensor 7 –25 °C…+70 °C –40 °C…+85 °C 5…95 % IP 20 3 2 III 1300 V DC 1 min (typetest) > 500,000 hours acc. to IEC 1709 32…34 V DC Yes, only with diode module for redundancy Metal, corrosion resistant Horizontal on mounting rail TS 35, 50 mm above and below Space for free movement of air Yes Yes Acc. to EN55022 Class B Acc.to EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (fields), EN61000-4-4 (burst), EN61000-4-5 (surge), EN610004-6 (conducted), EN61000-4-11 (dips) Acc.to IEC60954 Vibration: 2.3 g, Acc.to IEC60068-2-31 shock: 30 g in all directions Acc. to EN60204 Acc. to EN61558-2-17 Acc. to EN50178 / VDE0160 SELV acc. to EN60950, PLEV acc. to EN60204 Cabling 3 Alarm Battery Capacity Normal / Buffering Alarm Cut-off / Bat.Failure Selector switches – Buffer time – Battery size – DIP switch – 10/20A (only1370050010) 4 Buffering 5 Charging 11 14 Alarm 12 21 24 Buffering 22 31 34 Charging 32 + µC + 24V DC Input Charger – 24V DC Output – Bat – B.4 Fault (alarm), battery operation (buff.), charging (charg.) Fault (alarm), battery operation (buff.), charging (charg.) Three-colour LED: battery capacities > 85 % green, > 40 % yellow, > 20 % red, < 20 % red (flashing) Green/yellow LED: normal / buffering Yellow/red LED: temperature alarm / alarm Yellow/red LED: switch-off / battery fault + + Unbuffered DC Load – + – + + – 24V DC Output Buffered DC Load – + – + – + – + Input Battery Output + – Power Supply DC UPS Battery Module PRO–M Series CP DC UPS 24V DC 20A/10A CP DC UPS 24V DC 40A CP A BATTERY 24V DC .. Ah 1 2 3 4 5 11 21 31 6 7 12 14 22 24 32 34 7 6 Temperature Sensor 2003670000 UPS control unit CP DC UPS 24V 20A/10A Uninterruptible power supplies (UPS) UPS control unit CP DC UPS 24V 40A B Technical data Input Rated input voltage DC input voltage range Input current Input fuse (internal) DC current consumption Reverse polarity protection Output Rated output voltage Output voltage Rated (nominal) output current @ UNom continous output current @ 24 V DC Powerboost @ 24 V DC, 60 °C Integrated battery charger Charging feature Charging voltage (temperature compensated) Temperature coefficient Charging current Battery availability test Battery module Rated voltage Storage medium Parallel connection option [battery] Operating elements and control inputs Output current selector switch Selector switch battery Selector switch buffer times DIP switch Remote disconnection (Interlock) Temperature probe General data Buffer times Degree of efficiency Power loss Depth x width x height / Weight Approvals Approvals Connection data Wire connection method Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque Note Ordering data mm² mm² Nm 24 V DC 20...30 V DC ≤ 13A (for 10A), ≤ 23A (for 20A) Yes max. 200 mA (without battery), max. 0.5 A (with fully charged battery) Yes 20...30 V DC ≤ 43 A Yes max. 200 mA (without battery), max. 0.5 A (with fully charged battery) Yes 24 V DC ± 1 % Vo = Vin - 0.2 V normal operation (Imax), Vo = Vin - 0.3 V battery operation (Imax) 20 A @ 60 °C 24 A @ 45 °C, 20 A @ 60 °C, 15 A @ 70 °C 24 A for 1 min, ED = 5 % 24 V DC ± 1 % Vo = Vin - 0.2 V normal operation (Imax), Vo = Vin - 0.3 V battery operation (Imax) 40 A @ 60 °C 48 A @ 45 °C, 24 A @ 70 °C, 40 A @ 60 °C 48 A for 1 min, ED = 5 % IU characteristic curve 27, 48 V @ 20°C - 48 mV / °C 0.15 CA every minute IU characteristic curve 27, 48 V @ 20°C - 48 mV / °C 0.15 CA every minute 24 V 1.3 Ah, 3.4 Ah, 7.2 Ah, 12 Ah, 17 Ah, Selectable with rotary switch yes, max 2. 24 V 3.4 Ah, 7.2 Ah, 12 Ah, 17 Ah, Selectable with rotary switch yes, max 2. 20 A, 10 A 1.3 Ah, 3.4 Ah, 7.2 Ah, 12 Ah, 17 Ah, No Battery, Service 0.5 min, 1 min, 3 min, 5 min, 10 min, 20 min, 30 min, 45 min, ∞, ∞ w/0 Inversion of transistor outputs, Operation without temperature probe Yes NTC 100 kΩ 3.4 Ah, 7.2 Ah, 12 Ah, 17 Ah, No Battery, Service 0.5 min, 1 min, 3 min, 5 min, 10 min, 20 min, 30 min, 45 min, ∞, ∞ w/0 Inversion of transistor outputs, Operation without temperature probe Yes NTC 100 kΩ Depending on the connected battery ≥ 96% normal mode, battery is being charged, ≥ 98% normal mode, battery is charged, ≥ 98% buffer mode < 10 W 150 / 66 / 130 mm / 980 g Depending on the connected battery ≥ 96% normal mode, battery is being charged, ≥ 98% normal mode, battery is charged, ≥ 98% buffer mode < 10 W 150 / 66 / 130 mm / 1000 g CE; EAC; GL; GOSTME25 CE; EAC; GL; GOSTME25 Input/output/battery Screw connection 0.5 / 16 0.5 / 16 26 / 6 1.2...1.5 Type CP DC UPS 24V 20A/10A Signal Screw connection 0.5 / 16 0.5 / 16 26 / 12 Qty. 1 Order No. 1370050010 Input/output/battery Screw connection 0.5 / 16 0.5 / 16 26 / 6 1.2...1.5 Type CP DC UPS 24V 40A Signal Screw connection 0.5 / 16 0.5 / 16 26 / 12 Qty. 1 Order No. 1370040010 Note 2003670000 B.5 Uninterruptible power supplies (UPS) Battery modules Battery modules CP A BATTERY 24V DC1.3AH CP A BATTERY 24V DC3.4AH • Maintenence-free lead-acid batteries from 3.4 Ah to 17 Ah • Integrated temperature sensor for optimal battery charging • Capacity up to 40 A / 30 min or 1 A / 30 hrs • Robust metal housing for wall mounting B 6HQVRU %XIIHUWLPHVQ>PLQ@ %XIIHUWLPHVRXWSXWFXUUHQWFXUYH &3$%DWWHU\9'&$K &3$%DWWHU\9'&$K 6HQVRU &3$%DWWHU\9'&$K 17& &3$%DWWHU\9'&$K 17& &3$%DWWHU\9'&$K 3( 2XWSXWFXUUHQW>$@ 3( Technical data Rated input voltage Nominal capacity Charging current, max. Overload and short circuit protection Buffer time 10A Buffer time 20A Output current, max. Parallel connection option Series switching capability Temperature probe General data Battery type Operating life Ambient temperature Storage temperature Latest commissioning Max. perm. air humidity (operational) Class of protection Protection degree Vibration DIN rail/wall in accordance with IEC 68-2-6 Shock wall acc. to IEC 68227 Depth x width x height / Weight Approvals 24 V DC 1.3 Ah 0.2 A 15 A fuse 3 min min 15 A Yes No NTC 100 kΩ 24 V DC 3.4 Ah 0.51 A 25 A fuse 11.3 min 5 min 25 A Yes No NTC 100 kΩ Maintenance-free AGM lead-acid battery 6…9 years @ 20°C 0°...+40°C (Charging); -15°…+50°C (Discharging) -15 °C...40 °C 9 months 5 %…95 % RH III, with no ground connection, for SELV IP 20 0.7 / 0.7 g 30 g 124 / 52 / 148 mm / 1500 g cULus; EAC; GL Maintenance-free AGM lead-acid battery 6…9 years @ 20°C 0°...+40°C (Charging); -15°…+50°C (Discharging) -15 °C...40 °C 9 months 5 %…95 % RH III, with no ground connection, for SELV IP 20 0.7 / 0.7 g 30 g 137 / 108 / 144 mm / 3600 g cULus; EAC; GL Connection data Wire connection method Wire cross-section, rigid min/max Wire cross-section, flexible min/max Wire cross-section, AWG/kcmil min/max Tightening torque Note Input/output/battery Input/output/battery Ordering data mm² mm² Nm 0.2 / 4 0.2 / 4 30 / 12 0.5...0.5 Type CP A BATTERY 24V DC1.3AH Signal Pluggable screw connection 0.2 / 4 0.2 / 4 30 / 12 Qty. 1 Order No. 1406930000 0.2 / 6 0.5 / 6 22 / 10 0.5...0.6 Type CP A BATTERY 24V DC3.4AH Signal Pluggable screw connection 0.2 / 1.5 0.2 / 1.5 28 / 16 Qty. 1 Order No. 1251070000 Note Accessories Note B.6 2003670000 CP A BATTERY 24V DC7.2AH CP A BATTERY 24V DC12AH 6HQVRU CP A BATTERY 24V DC17AH 6HQVRU 17& 17& 3( 3( 24 V DC 7.2 Ah 1.08 A 2x25 A fuse 26.5 min 11.5 min 50 A Yes No NTC 100 kΩ 24 V DC 12 Ah 1.8 A 2x25 A fuse 51 min 22.7 min 50 A Yes No NTC 100 kΩ 24 V DC 17 Ah 2.55 A 2x25 A fuse 81 min 34.2 min 50 A Yes No NTC 100 kΩ Maintenance-free AGM lead-acid battery 9…12 years @ 20°C 0°...+40°C (Charging); -15°…+50°C (Discharging) -15 °C...40 °C 9 months 5 %…95 % RH III, with no ground connection, for SELV IP 20 - / 0.7 g 30 g 134 / 162 / 155 mm / 5900 g cULus; EAC; GL Maintenance-free AGM lead-acid battery 6…9 years @ 20°C 0°...+40°C (Charging); -15°…+50°C (Discharging) -15 °C...40 °C 9 months 5 %…95 % RH III, with no ground connection, for SELV IP 20 - / 0.7 g 30 g 134 / 229 / 155 mm / 9220 g cULus; EAC; GL Maintenance-free AGM lead-acid battery 6…9 years @ 20°C 0°...+40°C (Charging); -15°…+50°C (Discharging) -15 °C...40 °C 9 months 5 %…95 % RH III, with no ground connection, for SELV IP 20 - / 0.7 g 30 g 160 / 242 / 178 mm / 13400 g cULus; EAC Input/output/battery Input/output/battery Input/output/battery 0.2 / 16 0.5 / 16 22 / 6 1.2...1.5 Type CP A BATTERY 24V DC7.2AH 2003670000 Signal Pluggable screw connection 0.2 / 1.5 0.2 / 1.5 28 / 16 Qty. 1 Order No. 1251080000 B 6HQVRU 17& 3( Uninterruptible power supplies (UPS) Battery modules 0.2 / 16 0.5 / 16 22 / 6 1.2...1.5 Type CP A BATTERY 24V DC12AH Signal Pluggable screw connection 0.2 / 1.5 0.2 / 1.5 28 / 16 Qty. 1 Order No. 1251090000 0.2 / 16 0.5 / 16 22 / 6 1.2...1.5 Type CP A BATTERY 24V DC17AH Signal Pluggable screw connection 0.2 / 1.5 0.2 / 1.5 28 / 16 Qty. 1 Order No. 1251110000 B.7 Uninterruptible power supplies (UPS) Buffer modules Buffer modules CP DC BUFFER 24V 20A • Maintenance-free UPS on capacitor basis with a capacity to support 20 A / 260 ms • Parallel switching to increase the output current or support time • Status notification via LED and relay contact B %ORFNGLDJUDP ,QSXW ² 2XWSXW ² 5HDG\ ² )DLO Technical data Input Rated input voltage Input current Max. approved input current Surge protection Output Output voltage Output current Output current, max. Parallel connection option Overload protection Surge protection Status relay (max. load) 24 V DC 0…22 A 22 A 31 ... 34 V (only at discharge) 24 V 20 A 22 A Yes, without diode module ≥ 22 A (only at discharge) 31 ... 34 V (only at discharge) Input voltage OK (30 V AC/DC 2A), Ready for operation (24 V AC/ DC 300 mA) Display Status indicator General data Degree of efficiency Insulation voltage, input/output Storage medium Buffer times MTBF Ambient temperature (operational) Storage temperature Humidity Depth x width x height / Weight For use with electronic equipment EMC standards Approvals Connection data Wire connection method Wire cross-section, rigid min/max Note Ordering data Green LED 95 % 1 kV Internal condenser 250 ms at 20 A, 6 s at 1 A > 500,000 h acc. to IEC 1709 (SN29500 -25 °C...70 °C -40 °C...85 °C 5...95 %, no condensation 150 / 66 / 130 mm / 1150 g Acc. to EN50178 / VDE0160 CE; TUEV; cULus; cURus mm² Input Screw connection Output Type CP DC BUFFER 24V 20A Signal Qty. 1 Order No. 1251220000 Note Accessories Note B.8 2003670000 Small metal foot Type MTA 30 MF Large metal foot Order No. 1251320000 Small wall mounting Type CP A WALLADAPTER 30 MM Small plastic foot Type MTA 45 MF Order No. 1251310000 Large wall mounting Order No. 1461870000 Type CP A WALLADAPTER 45 MM Order No. 1461850000 2003670000 Order No. 1168970000 Type MTA 45 BK Order No. 1962250000 B Type CP DC UPS TF25 CP DC UPS TF05 Cable length 2.5 m 0.5 m Order No. 1444540000 1444480000 Large screwdriver Blade type B Size/AF a 0.5 b 3 c 100 Order No. 9008380000 Type SDIS 1.0X5.5X125 Blade type B Size/AF a 1 b 5.5 c 125 Order No. 9008410000 Qty. 50 Order No. 1162600000 End bracket Markers Type SM 18/9.5 K MC NE WS Large plastic foot Temperature probe Small screwdriver Type SDIS 0.5X3.0X100 Type MTA 30 BK Uninterruptible power supplies (UPS) UPS control unit - Accessories For DIN rail TS 35 Colour white Qty. 200 Order No. 1248580000 Polyamide with fibre glass, screwable WEW 35/1 SW Colour black Torque 1.2 Nm B.9 B B.10 2003670000 Uninterruptible power supplies (UPS) Fuse protection for 24 V DC circuits Contents Fuse protection for 24 V DC circuits Fuse protection for 24 V DC circuits Overview C.2 WAVEGUARD C.4 C 2003670000 C.1 Fuse protection for 24 V DC circuits Fuse protection for 24 V DC circuits – Overview Fuse protection A 24 V DC control voltage has become the standard in the automation industry. Selective fuse protection is often used when the power is being supplied by PLC-guided controllers. It divides the total load into separate, logically connected safety circuits. For example, the CPU, actuators and sensors can be separated in the load circuits. This selective load protection helps to decrease facility downtime and also to simplify troubleshooting. When a disruption (short circuit) occurs on a standard protective system, the entire power supply is interrupted. In a system using selective fuse protection, only the fuse in the one disrupted load circuit is triggered. If the fuse is triggered quick enough so that other loads (and particularly the CPU) can continue functioning properly, then various control algorithms can be used to deal with the disruption. It is then possible to shut down the facility in an orderly and controlled fashion. C A fundamental problem when using ordinary fuses is that they take a relatively long time to trigger. Usually, a C.2 switched-mode power supply is already well over the surgecurrent limit (typically 120 % of Inom) before its fuse triggers. Ordinary fuses are therefore not suitable for constructing a selective fuse protective system. Such systems present DC fuses with special challenges. They must be able to switch off quickly enough but they must also be able to tolerate the start-up surge currents from consumer loads. Weidmüller‘s electronic fuses, from our established WAVEGUARD line, are the answer to both of these challenges: they are quick acting but can also tolerate start-up currents. You can easily implement selective load protection using our WAVEGUARD models. In addition, Weidmüller‘s electronic fuses feature a floating alarm contact and a reset input. This allows a PLC controller to query the status of the fuse or to perform an automated reset after troubleshooting. This provides you with a convenient method for remotely maintaining a complex facility. As a result, you save both time and money. 2003670000 Fuse protection for 24 V DC circuits Fuse protection for 24 V DC circuits – Overview Resetting The WAVEGUARD family can be reset manually or by using an external signal. They can be reset remotely by simply applying a 24 V signal pulse on the reset input. The reset occurs on the falling edge of the signal. Note: A cyclical automatic reset is not permitted and can lead to a malfunction. BLOCK DIAGRAM WAVEGUARD INPUT 24 V Reset (8) (1) (9) gn 24 V fail C re (2) 0V OUTPUT (7) (3) NC contact 50 Vuc/0.05A Signalling A red LED displays when the electronic fuse has been triggered. An alert is also sent out over a floating alarm contact. A green LED signals that the unit is switched on. The alarm contact uses an NC contact. WAVEGUARD 2003670000 C.3 Fuse protection for 24 V DC circuits WAVEGUARD INPUT 24 V Reset C 24 V DC 3.15 A 24 V DC 1.6 A 0V (8) (1 ) (9 ) gn rt OUTPUT 24 V fail (7 ) (2 ) (3 ) NC contact 50 V uc /0.05 A Current (A ) Current (A ) 20 18 16 14 12 10 8 6 4 2 0 24 22 20 18 16 14 12 10 8 6 4 2 0 Time ( m s ) 0 20 40 60 80 10 0 12 0 14 0 T i m e ( m s) 0 10 15 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 16 0 Technical data Input Rated control voltage Rated current Reset Output Status relay / CO contact Signalling delay General data Ambient temperature (operational) Storage temperature Status indication Standards EMC standards Sliding switch Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection Tension-clamp connection 24 V DC 1.6 A Impulse > 100 ms +24 V, falling edge ON 24 V DC 3.15 A Impulse > 100 ms +24 V, falling edge ON NC contact, max. 50 V / 0.05 A; for low voltage only! 3.5 ms typ. NC contact, max. 50 V / 0.05 A; for low voltage only! 3.5 ms typ. 0 °C...55 °C -20 °C...85 °C LED green: OK, LED red: tripped DIN EN 50178 EN 55011, EN 61000-6-1, 2, 4 OFF - wait 10 s - ON; on / off cCSAus; CE; cURus; EAC; GOSTME25 0 °C...55 °C -20 °C...85 °C LED green: OK, LED red: tripped DIN EN 50178 EN 55011, EN 61000-6-1, 2, 4 OFF - wait 10 s - ON; on / off cCSAus; CE; cURus; EAC; GOSTME25 2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5 92.4 / 22.5 / 72 92.4 / 22.5 / 72 Periodic auto-reset not permitted; Tu=23 °C,Tension single module Screw connection clamp connection 2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5 92.4 / 22.5 / 72 92.4 / 22.5 / 72 Periodic auto-reset not permitted; Tu=23 °C,Tension single module Screw connection clamp connection Type WGS 24Vdc 1,6A WGZ 24Vdc 1,6A Type WGS 24Vdc 3,15A WGZ 24Vdc 3,15A Qty. 1 1 Order No. 8618890000 8621040000 Qty. 1 1 Order No. 8618910000 8621030000 Note Accessories Note C.4 Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5 N/2 Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5 N/2 2003670000 24 V DC 6.3 A INPUT 24 V Reset 0V (8) (1 ) (9 ) gn rt 24 V fail (7 ) (2 ) (3 ) 24 V DC 8 A Current (A ) Current (A ) OUTPUT NC contact 50 V uc /0.05 A 26 24 22 20 18 16 14 12 10 8 6 4 Time (ms) 0 10 Fuse protection for 24 V DC circuits WAVEGUARD 15 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 65 60 55 50 45 40 35 30 25 20 15 10 5 C Time (ms) 0 5 10 15 20 25 30 35 40 45 50 Technical data Input Rated control voltage Rated current Reset Output Status relay / CO contact Signalling delay General data Ambient temperature (operational) Storage temperature Status indication Standards EMC standards Sliding switch Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection Tension-clamp connection 24 V DC 6.3 A Impulse > 100 ms +24 V, falling edge ON 24 V DC 8A Impulse > 100 ms +24 V, falling edge ON NC contact, max. 50 V / 0.05 A; for low voltage only! 3.5 ms typ. NC contact, max. 50 V / 0.05 A; for low voltage only! 3.5 ms typ. 0 °C...55 °C -20 °C...85 °C LED green: OK, LED red: tripped DIN EN 50178 EN 55011, EN 61000-6-1, 2, 4 OFF - wait 10 s - ON; on / off cCSAus; CE; cURus; EAC; GOSTME25 0 °C...55 °C -20 °C...85 °C LED green: OK, LED red: tripped DIN EN 50178 EN 55011, EN 61000-6-1, 2, 4 OFF - wait 10 s - ON; on / off cCSAus; CE; cURus; EAC; GOSTME25 2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5 92.4 / 22.5 / 72 92.4 / 22.5 / 72 Periodic auto-reset not permitted; Tu=23 °C,Tension single module Screw connection clamp connection 2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5 92.4 / 22.5 / 72 92.4 / 22.5 / 72 Periodic auto-reset not permitted; Tu=23 °C,Tension single module Screw connection clamp connection Type WGS 24Vdc 6,3A WGZ 24Vdc 6,3A Type WGS 24Vdc 8,0A WGZ 24Vdc 8,0A Qty. 1 1 Order No. 8618930000 8621020000 Qty. 1 1 Order No. 8618940000 8621010000 Note Accessories Note 2003670000 Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5 N/2 Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5 N/2 C.5 Fuse protection for 24 V DC circuits WAVEGUARD 24 V DC 0.5...5 A INPUT 24 V Reset C 0V (8) (1 ) (9 ) gn rt OUTPUT 24 V fail (7 ) (2 ) (3 ) NC contact 50 V uc /0.05 A Technical data Derating curve Input Rated control voltage Rated current Reset Output Status relay / CO contact Signalling delay General data Ambient temperature (operational) Storage temperature Status indication Standards EMC standards Sliding switch Approvals Dynamic tripping characteristic 24 V DC 0.5...5 A adjustable Impulse > 100 ms +24 V, falling edge ON Tripping current: 0.5 A Tripping current (A) 25 20 15 10 5 0 0 20 40 NC contact, max. 50 V / 0.05 A; for low voltage only! 3.5 ms typ. 0 °C...55 °C -20 °C...85 °C LED green: OK, LED red: tripped DIN EN 50178 EN 55011, EN 61000-6-1, 2, 4 OFF - wait 10 s - ON; on / off cCSAus; CE; cURus; EAC; GOSTME25 mm² mm Ordering data Screw connection Tension-clamp connection 80 100 120 140 60 80 100 120 140 Time (ms) Tripping current: 5.0 A Tripping current (A) 25 20 15 10 5 0 0 20 40 Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note 60 Time (ms) 2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5 92.4 / 22.5 / 72 92.4 / 22.5 / 72 Periodic auto-reset not permitted; Tu=23 °C,Tension single module Screw connection clamp connection Type WGS 24Vdc 0.5...5A WGZ 24Vdc 0.5...5A Qty. 1 1 Order No. 8710270000 8727630000 Note Accessories Note C.6 Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5 N/2 2003670000 Unregulated power supplies Contents Unregulated power supplies Unregulated power supplies Overview D.2 compactPower D.4 D 2003670000 D.1 Unregulated power supplies Unregulated power supplies – Overview Unregulated power supplies – compactPower Compact power supply units are important links in the power supplies for controllers. They are used where processes or control voltages are required that vary from the mains voltage. Transformers provide the electrical isolation between the input circuit and the output circuit. The minimum requirement (to VDE 0550) is 2,000 V. Screw terminals secure the input-side connection to the mains. The single-phase devices are rated for a nominal voltage of ∼230 ± ∼15 V, or ∼400 V ± ∼15 V, 50/60 Hz, the 3-phase devices for 3 x 400 V ± 5 %. The secondary DC voltage from the transformer is conducted to a bridge rectifier where it is rectified. D Single-phase unregulated power supplies D.2 The pulsating DC voltage is then fed from the rectifier and filtered to a low residual ripple by means of an electrolytic capacitor. This DC voltage is then fed to the output terminal. These are designed as pluggable screw terminals. A varistor is integrated in the output circuitry to attenuate voltage peaks. The operating status is indicated by means of a green LED via the output circuit. Devices with 600 W and higher are equipped with a fan. Three-phase unregulated power supplies 2003670000 Unregulated power supplies Unregulated power supplies – Overview Well-balanced spectrum for optimum economy Block diagram for single-phase devices CP NT The output currents of these practical products are defined by way of two ambient temperatures. Size selection is based on the maximum effectiveness of the components. INPUT +15 V 0V –15 V 230 V 400 V PE Adapted to standard voltages in accordance with IEC 38 By choosing the appropriate terminals, the ± 15 V tapping capability allows the single-phase devices to be connected to six different nominal AC voltages: 215, 230, 245, 385, 400, 415 V. The ± 5 % tapping capability allows the 3-phase devices to be connected to three different nominal voltages: 380, 400, 415 V. Reliable short-circuit and overload protection Integrated on the secondary side in device sizes up to CP NT 192 W, the FKS fuse protects against overloads and shortcircuits. For the devices CP NT 264 W and CP NT 432 W, this protection is achieved by means of a thermostatic switch built into the transformer. . . . . . D Block diagram for 3-phase devices CP NT3 250 / 400 / 500 W INPUT +5% 400 V –5% +5% 400 V –5% +5% 400 V –5% 3x OUTPUT + + 24V DC = 130° PE - ~ Block diagram for 3-phase devices CP NT3 600 / 750 / 1.000 W Easy mounting Keyhole assembly simplifies mounting and saves time. A snap-on fixing attachment for 35 mm DIN rails is available as an accessory for single-phase devices up to 144 W. Simply plugged into the device and secured with two screws, it ensures easiest possible mounting! OUTPUT + + 24V DC INPUT +5% 400 V –5% +5% 400 V –5% +5% 400 V –5% 3x = 130° M PE ~ OUTPUT + + 24V DC 0V Fail Transformers, vacuum-impregnated, painted black • • • • • No humming Moisture cannot ingress into the windings Windings mechanically secured Improved heat dissipation from the windings Good heat dissipation Unregulated power supplies single-phase Unregulated power supplies 3-phase 2003670000 D.3 Unregulated power supplies compactPower compactPower single-phase CP NT 36 CP NT 72 INPUT OUTPUT +15V 0V -15V 230V 400V PE D . . . . INPUT + + 24VDC +15V 0V -15V - 230V 400V PE . OUTPUT + + 24VDC . . . . . Technical data Input Input voltage Input current Input frequency No-load input current Ext. Back-up fuse Output Output voltage Output current at 40°C Output current at 55°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Mounting position, installation notice Installation advice Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 230 V/ 400 V ±15 V 0.35 A/ 0.2 A 50/ 60 Hz 0.1 A / 0.06 A 0.63 A / 0.315 A time-lag 230 V/ 400 V ±15 V 0.56 A/ 0.32 A 50/ 60 Hz 0.13 A / 0.08 A 0.1 A / 0.63 A time-lag 24 V SELV 1.5 A 1A 36 W <5% 3 A time-lag flat cable-lug fuse Varistor 24 V SELV 3A 2.5 A 72 W <5% 7.5 A time-lag flat cable-lug fuse Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...55 °C -20 °C...80 °C 80% Arbitrary, horizontally, on terminal rail TS 35 Direct mounting, TS 35 with clip-on plate Green LED 1.5 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC -20 °C...55 °C -20 °C...80 °C 83% Arbitrary, horizontally, on terminal rail TS 35 Direct mounting, TS 35 with clip-on plate Green LED 2.1 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC Input 2.5 / 0.13 / 2.5 68 / 78 / 123 Input 2.5 / 0.13 / 2.5 85 / 84 / 125 Type CP NT 36W 24V 1.5A Output 2.5 / 0.5 / 4 68 / 78 / 123 Qty. 1 Order No. 8575260000 Type CP NT 72W 24V 3A Output 2.5 / 0.5 / 4 85 / 84 / 125 Qty. 1 Order No. 8575270000 Note Accessories Note D.4 Clip-in plate for TS 35: 8588920000 Clip-in plate for TS 35: 8588920000 2003670000 compactPower single-phase CP NT 144 CP NT 192 INPUT OUTPUT +15V 0V -15V 230V 400V PE Unregulated power supplies compactPower . . . . INPUT + + 24VDC +15V 0V -15V - 230V 400V PE . OUTPUT + + 24VDC . . . . . D Technical data Input Input voltage Input current Input frequency No-load input current Ext. Back-up fuse Output Output voltage Output current at 40°C Output current at 55°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Mounting position, installation notice Installation advice Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 230 V/ 400 V ±15 V 0.95 A/ 0.55 A 50/ 60 Hz 0.33 A / 0.19 A 1.6 A / 1.0 A time-lag 230 V/ 400 V ±15 V 1.3 A/ 0.7 A 50/ 60 Hz 0.3 A / 0.16 A 2.0 A / 1.25 A time-lag 24 V SELV 6A 5A 144 W <5% 10 A time-lag flat cable-lug fuse Varistor 24 V SELV 8A 7A 192 W <5% 15 A time-lag flat cable-lug fuse Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...55 °C -20 °C...80 °C 88% Arbitrary, horizontally, on terminal rail TS 35 Direct mounting, TS 35 with clip-on plate Green LED 3.1 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC -20 °C...55 °C -20 °C...80 °C 90% Input 2.5 / 0.13 / 2.5 92 / 96 / 135 Input 2.5 / 0.13 / 2.5 105 / 105 / 145 Type CP NT 144W 24V 6A Direct mounting Green LED 4.3 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC Output 2.5 / 0.5 / 4 92 / 96 / 135 Qty. 1 Order No. 8575280000 Type CP NT 192W 24V 8A Output 2.5 / 0.5 / 4 105 / 105 / 145 Qty. 1 Order No. 8575300000 Note Accessories Note 2003670000 Clip-in plate for TS 35: 8588920000 D.5 Unregulated power supplies compactPower compactPower single-phase CP NT 264 CP NT 432 INPUT OUTPUT +15V 0V -15V 230V 400V PE D . . . . INPUT + + 24VDC +15V 0V -15V - 230V 400V PE . OUTPUT + + 24VDC . . . . . Technical data Input Input voltage Input current Input frequency No-load input current Ext. Back-up fuse Output Output voltage Output current at 40°C Output current at 55°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Installation advice Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 230 V/ 400 V ±15 V 1.8 A/ 1 A 50/ 60 Hz 0.5 A / 0.28 A 3.15 A / 1.6 A time-lag 230 V/ 400 V ±15 V 2.5 A/ 1.3 A 50/ 60 Hz 0.54 A / 0.31 A 4.0 A / 2.0 A time-lag 24 V SELV 11 A 10 A 264 W <5% Thermostatic switch Varistor 24 V SELV 18 A 15 A 432 W <5% Thermostatic switch Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...55 °C -20 °C...80 °C 93% Direct mounting Green LED 6.1 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC -20 °C...55 °C -20 °C...80 °C 95% Direct mounting Green LED 9.1 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 CE; cULus; EAC Input 2.5 / 0.13 / 2.5 113 / 120 / 165 Input 2.5 / 0.13 / 2.5 135 / 135 / 185 Type CP NT 264W 24V 11A Output 2.5 / 0.5 / 4 113 / 120 / 165 Qty. 1 Order No. 8575310000 Type CP NT 432W 24V 18A Output 2.5 / 0.5 / 4 135 / 135 / 185 Qty. 1 Order No. 8575320000 Note Accessories Note D.6 2003670000 compactPower 3-phase CP NT3 250 Unregulated power supplies compactPower CP NT3 400 INPUT +5% 400V -5% +5% 400V - 5% +5% 400V -5% OUTPUT 3x = 130° PE ~ INPUT + + 24VDC - +5% 400V -5% +5% 400V - 5% +5% 400V -5% OUTPUT 3x = 130° PE ~ + + 24VDC - D Technical data Input Input voltage Input current Input frequency No-load input current Input fuse Ext. Back-up fuse Output Output voltage Output current at 40°C / 60°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Installation advice Fan signal Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 3 x 400 V ±5 % 0.5 A 50/ 60 Hz 0.1 A 3 x primary thermostatic switch 3 x 1.0 A time-lag 3 x 400 V ±5 % 0.75 A 50/ 60 Hz 0.11 A 3 x primary thermostatic switch 3 x 1.2 A time-lag 24 V SELV 11 A / 10 A 250 W <2% External 10 A time-lag Varistor 24 V SELV 18 A / 16 A 400 W <2% External 16 / 18 A slo-blo Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...60 °C -20 °C...80 °C 76% Direct mounting No integrated fan Green LED 4.7 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; EAC -20 °C...60 °C -20 °C...80 °C 77% Direct mounting No integrated fan Green LED 6.9 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; EAC Input 2.5 / 0.5 / 2.5 185 / 84 / 192 Input 2.5 / 0.5 / 2.5 220 / 88 / 213 Condensation not allowed Type CP NT3 250W 24V 10A Output 6 / 0.5 / 6 185 / 84 / 192 Qty. 1 Condensation not allowed Order No. 8628620000 Type CP NT3 400W 24V 15A Output 6 / 0.5 / 6 220 / 88 / 213 Qty. 1 Order No. 8628630000 Note Accessories Note 2003670000 D.7 Unregulated power supplies compactPower compactPower 3-phase CP NT3 500 CP NT3 600 INPUT +5% 400V -5% +5% 400V - 5% +5% 400V -5% OUTPUT 3x = 130° PE ~ D INPUT + + 24VDC - +5% 400V -5% +5% 400V -5% +5% 400V -5% OUTPUT 3x = 130° M PE + + 24VDC 0V Fail ~ Technical data Input Input voltage Input current Input frequency No-load input current Input fuse Ext. Back-up fuse Output Output voltage Output current at 40°C / 60°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Installation advice Fan signal Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 3 x 400 V ±5 % 0.9 A 50/ 60 Hz 0.13 A 3 x primary thermostatic switch 3 x 1.6 A time-lag 3 x 400 V ±5 % 1.2 A 50/ 60 Hz 0.15 A 3 x primary thermostatic switch 3 x 2 A time-lag 24 V SELV 22 A / 20 A 500 W <2% External 20 / 22 A slo-blo Varistor 24 V SELV 26 A / 25 A 600 W <2% External 25 / 26 A slo-blo Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...60 °C -20 °C...80 °C 78% Direct mounting No integrated fan Green LED 10 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; cULus; EAC -20 °C...60 °C -20 °C...80 °C 78% Direct mounting Open collector <30 V/ <5 mA during interference Green LED 11 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; EAC Input 2.5 / 0.5 / 2.5 220 / 108 / 215 Input 2.5 / 0.5 / 2.5 230 / 108 / 212 Condensation not allowed Type CP NT3 500W 24V 20A Output 6 / 0.5 / 6 220 / 108 / 215 Qty. 1 Condensation not allowed Order No. 8628650000 Type CP NT3 600W 24V 25A Output 6 / 0.5 / 6 230 / 108 / 212 Qty. 1 Order No. 8628660000 Note Accessories Note D.8 2003670000 compactPower 3-phase CP NT3 750 Unregulated power supplies compactPower CP NT3 1000 INPUT +5% 400V -5% +5% 400V -5% +5% 400V -5% OUTPUT 3x = 130° M PE 0V Fail ~ INPUT + + 24VDC +5% 400V -5% +5% 400V -5% +5% 400V -5% OUTPUT 3x = 130° M PE + + 24VDC 0V Fail ~ D Technical data Input Input voltage Input current Input frequency No-load input current Input fuse Ext. Back-up fuse Output Output voltage Output current at 40°C / 60°C Output power Max. residual ripple Fuse, max. Protective circuit, load side Insulation coordination (EN 50178) Electric shock protection Insulation strength Insulation class Protection degree Class of protection General data Ambient temperature (operational) Storage temperature Degree of efficiency at max. load Installation advice Fan signal Status indication Weight Standards EMC standards Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note mm² mm Ordering data Screw connection 3 x 400 V ±5 % 1.4 A 50/ 60 Hz 0.16 A 3 x primary thermostatic switch 3 x 2.5 A time-lag 3 x 400 V ±5 % 1.8 A 50/ 60 Hz 0.14 A 3 x primary thermostatic switch 3 x 3.15 A time-lag 24 V SELV 32 A / 30 A 750 W <2% External 30 / 32 A slo-blo Varistor 24 V SELV 42 A / 40 A 1000 W <2% External 40 / 42 A slo-blo Varistor acc. to BGV A3 4 kV B IP 20 I acc. to BGV A3 4 kV B IP 20 I -20 °C...60 °C -20 °C...80 °C 77% Direct mounting Open collector <30 V/ <5 mA during interference Green LED 14 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; EAC -20 °C...60 °C -20 °C...80 °C 77% Direct mounting Open collector <30 V/ <5 mA during interference Green LED 18 kg DIN EN 60950, DIN EN 61558-2-4, -6, 72/23/EWG EN 61000-6 /-2, -3 cCSAus; CE; EAC Input 2.5 / 0.5 / 2.5 270 / 121 / 255 Input 2.5 / 0.5 / 2.5 280 / 122 / 275 Condensation not allowed Type CP NT3 750W 24V 30A Output 6 / 0.5 / 6 270 / 121 / 255 Qty. 1 Condensation not allowed Order No. 8628670000 Type CP NT3 1000W 24V 40A Output 10 / 0.5 / 10 280 / 122 / 275 Qty. 1 Order No. 8628680000 Note Accessories Note 2003670000 D.9 D D.10 2003670000 Unregulated power supplies Electrical cabinet socket outlet Contents Electrical cabinet socket outlet Electrical cabinet socket outlet Electrical cabinet socket outlet E.2 E 2003670000 E.1 Electrical cabinet socket outlet Electrical cabinet socket outlet Electrical cabinet socket outlet Schuko TS35 • Simple installation in electrical cabinet • TS 35 module can be mounted on rail • VDE mark of conformity • Two-pole with earthing contact Technical data E Rated voltage Rated voltage, max. Rated current Clamping range, nom. Tightening torque Ambient temperature (operational) Overvoltage category Pollution degree Protection degree Approvals Dimensions Clamping range (nominal / min. / max.) Depth x width x height Note Ordering data 230 V 250 V 16 A 1 mm²-1.5 mm² 1.3 Nm -20...40 °C II 2 GOSTME25; VDE mm² mm 1.5 / 1 / 1.5 / 76 / 45 Type Schuko TS35 Qty. 10 Order No. 8734580000 Note Accessories Note E.2 2003670000 Glossary/Technical appendix Contents Glossary/Technical appendix Glossary/Technical appendix Power Supplies – Overview W.2 Standards and approvals W.4 Glossary W.6 W 2003670000 W.1 Glossary/Technical appendix Power Supplies – Overview Power Supplies – Overview Power supplies are important links in the energy supply chain of automation systems. Unregulated power supplies or regulated switched-mode power supplies are at the heart of every electrical cabinet. 24 V DC has emerged as the standard control voltage for the supply of electrical subassemblies and systems. But other control voltages are also required. The correct power supply is a critical factor for the reliable operation of the supplied components. Thus it must be chosen with particular attention. Power supplies from Weidmüller, whether regulated or unregulated, have proven themselves reliable over many years in the supply of electrical sub-assemblies and systems. They perform reliably and safely – even under harsh industrial conditions – in all sectors of machine construction, industrial automation, and the power and process industries. Weidmüller offers custom-fit solutions for practically all of your requirements: • • • • • • Unregulated transformer power supplies Primary switch-mode power supplies DC/DC converters Diode modules UPS control modules Electronic fusing How they work Unregulated power supply units consist of a mains power transformer that transforms the input voltage into a different AC voltage. The units then make use of a rectifier and a filter circuit to smooth out the DC output voltage. Mains (AC) Output Unregulated transformer power supply Regulated power supply units in the range up to 1,000 W are usually designed as primary switched-mode power units. The mains AC voltage is then rectified and transformed in high frequency to the secondary side using switching transistors and power transformers. This is followed by the rectifier and filter circuit in order to generate the DC output voltage. A control circuit compares the current and voltage on the output side to the specified target values and then generates a control signal for the switching transistors. This permits compensation for load changes and mains voltage fluctuations. As a result, the output voltage remains stable. These power supply units are increasingly being operated with DC input voltages (for example, Weidmüller‘s PRO-M line of switched-mode power supplies). Controller Mains (AC/DC) Output Switched-mode power supply W W.2 2003670000 Glossary/Technical appendix Power Supplies – Overview A DC/DC converter is a variation of the classic switched mode power supply. The switching strategy is similar but there is no input rectifier. Starting with a specified DC input voltage, DC/DC converters generate a different DC voltage at a similar or different level. They are used to adapt different voltage levels and also for isolating potentials. Controller Mains (DC) Output DC/DC converter In use around the globe Weidmüller‘s power supply units have been designed for use around the world. They can be used in practically all applications throughout the world because of their CE label and many other national and international approvals. Their wide input voltage ranges and compatibility with various mains power connections increases their global appeal. Temperature range During operation, power supply units generate power losses. In Weidmüller‘s switched-mode power supplies, the resulting heat is dispersed using natural air currents only. The design, which does not make use of a ventilation fan, is an example of our uncompromised durability standard. Weidmüller‘s power supply units, depending on the model, can be used in temperatures ranging from -25 °C to +70 °C. Compact and efficient design Weidmüller‘s switched-mode power supplies are extra small because they take advantage of the above-average degree of efficiency offered by the latest technologies. The power supplies from Weidmüller – whether they are book-shaped with minimised base surface, or variants with reduced height for use in distributor boxes – always provide the proper costsaving solution. 2003670000 W W.3 Glossary/Technical appendix Standards and approvals W W.4 Standards and approvals Standard/Approval Description DIN EN 50178 (VDE 0160) Electronic equipment for use in power installations DIN EN 60950-1 (VDE 0805-1) IT Equipment – Safety – Part 1: General requirements DIN EN 61558-1 (VDE 0570-1) Safety of transformers, power supply units, throttles and similar devices Part 1: General requirements and tests DIN EN 61558-2-17 (VDE 0570 Part 2-17) Safety of transformers, power supply units and similar devices Part 2-17: Special requirements for switch-mode power supply transformers DIN EN 60204-1 (VDE 0113-1) Safety of machinery – Electrical equipment of machinery – Part 1: General requirements DIN VDE 0100-410 Construction of power installations with rated voltages up to 1,000 V Part 4: Protective measures Chapter 41: Protection against electrical shock DIN EN 61204-1 Power supply units for low voltages, with direct-current-output – properties DIN EN 60947-1 Low-voltage switching devices – Part 1: General definitions DIN EN 61140 Protection against electrical shock - common requirements for facilities and operating equipment IEC 38 Supplementary notes relating to status of international standards and European harmonisation of mains voltages 230/400 V 73/23 EWG Electrical equipment for use within specific voltage limits (Low Voltage Directive) 2004/108/EG (89/336 EWG) Electromagnetic compatibility (EMC Directive) 2006/42/EG (98/37 EG) Safety of machines (directive covering mechanical equipment) UL Safety approval for the United States market CSA Safety approval for the Canadian market GL Test specifications for electrical/electronic devices and systems for use in marine technology UL1310 Class 2 power supplies (limited energy) UL1604 Electrical equipment for use in dangerous surroundings 2003670000 Glossary/Technical appendix Standards and approvals Standard/Approval Description SEMI F47 Resistance of electronic devices against voltage drops 2006/95/EG (72/23/EWG) Low Voltage Directive EN 60721-3-2 Classification of surrounding conditions EN 60664-1 (VDE0110-1) Insulation coordination for electrical equipment C22.2 No. 107.1 General standards for power supplies (Canadian standard) EN 61000-3-2 Limiting of mains voltage harmonic currents EN 61000-4-x Interference immunity tests W 2003670000 W.5 Glossary/Technical appendix Glossary Glossary A AC/DC converter Conventional switched-mode power supplies generate a DC voltage from an AC voltage. For this reason they are sometimes also called AC/DC converters. Such devices are increasingly compatible for use with DC input voltages. The primary and secondary sides are typically electrically isolated. Ambient temperature (operational) The ambient operating temperature (the min. and max. values) together with the output current and voltage ratings can be used to describe the power capabilities of a power supply unit. B Burst C W W.6 A burst is a quick low-power burst pulse which can, for example, simulate welding equipment phenomena. Similar phenomena can also result from switching operations on the mains supply. This test can be used to demonstrate immunity against quick transients. Class of protection Electrical equipment is classified according to varying classes of protection. These classes define the particular safety measures that are required to avoid an electrical shock. The most widely used power supplies correspond with protection class I. The basic requirement of protection class I is for a basic insulation and for the earthing of all conductive housing parts. If the basic insulation fails, then the earthed conductive housing serves to prevent an electrical shock. For this reason, devices in protection class I are equipped with an earth (PE) connection. Connecting power supply units in parallel Power supplies can only be connected in parallel when this is clearly permitted by the manufacturer. Parallel connections are then normally tied to certain conditions. This is a typical way to increase the output power (for example, when extending a facility). Power supplies are also wired in parallel in order to design in redundant power supply systems. The parallel circuit is not wired straight though but connects using decoupling diodes. ➝ Redundancy Cooling Cooling is used by components or devices to prevent them from overheating. A variety of cooling strategies are available – two of the most common are natural and forced-air cooling. Natural (convection-based) cooling takes advantage of the natural air currents. Manufacturers must then ensure that there is sufficient air flow by specifying the clearance gaps and mounting positions that are required above and below the ventilation openings. Forced-air cooling normally uses a fan to dissipate any heat that has been generated. When fans are used in a device, they have the effect of increasing the likelihood of device outages. For this reason, a power supply with natural cooling methods is generally preferred. 2003670000 D Glossary/Technical appendix Glossary DC/DC converter DC/DC converters are switched-mode power supplies that convert a specific DC voltage into another voltage. They are a variant of the AC/DC converter. DC/DC converters, in their simplest implementation, do not isolate voltage potentials. They are used only for adapting voltages. Improved DC/DC converters have isolated voltages. A safety isolating transformer in the power element ensures the required electrical isolation. Besides the voltage adaptation, the isolation of the voltage potentials is an important factor. Derating For power supply devices, derating generally refers to the reduction in power as influenced by the surrounding temperature and the input voltage. A temperature derating often occurs starting at a surrounding temperature of 50 °C. The rated power is guaranteed up to this temperature. The available power continually declines as the temperature heats up above this level. This is typically specified in %/K. A voltage-dependent specification is another form of derating For switched-mode power supplies, the derating begins below a specific input voltage. So a switched-mode power supply with a wide input range can typically work under full power with 115 V AC input voltage. However at 85 V AC it can only produce 60 % of the power rating. The coefficient is usually specified in %/V. Temperature derating 100 95 90 85 80 75 70 40 45 50 55 60 Temperature [°C] Diode modules E Efficiency 65 Voltage derating 120 Max. current [%IN] Max. current [%IN] 105 70 75 100 80 60 40 20 0 70 90 110 130 150 170 190 210 230 250 270 Main voltage [V] Diode modules are used to construct a redundant power supply system. They are important for decoupling the power supply unit. Thus, a short circuit that occurs on the output of a power supply unit will not influence the output voltage. The degree of efficiency is equal to the ratio of output power to input power and is expressed in percent. The degree of efficiency can be between 70 and 90 %, depending on the dimensions and type of technology in use. EMC (electromagnetic compatibility) Electromagnetic compatibility describes the interference emissions caused by an electronic device and the level of immunity against external electrical influences. Interference emissions can be caused by cabling and wires or by radiated emissions. Immunity measures the resistance against such wire-based emissions and against radiated emissions such as electrostatic fields and magnetic fields. Electric devices must also be protected against electrostatic discharges. 2003670000 W W.7 Glossary/Technical appendix Glossary F Foldback characteristic curve The foldback characteristic curve is a special type of output curve that protects the power supply unit from overloads. When a specific current limit is exceeded (for example, by 110 or 120 % of the nominal level), the current is limited electronically and lowered to a very low, safe value. This downward-sloping characteristic curve means that it is not sufficient to simply eliminate the overload. The load must be reduced significantly more so that the adjustment control can return to the normal voltage control. Thus this solution is not suitable for many applications and is becoming less popular. U UA INominal I Limit G Galvanic isolation H Hiccup mode I Galvanic (electrical) isolation ensures that no electrical connections can exist between the primary and the secondary sides. Opto modules and transformers are the typical components used. The hiccup mode is a special output characteristic curve that protects power supply units from overloads and short circuits. The unit switches off at a specified current limit (for example, 110 or 120 % on the nominal rating) and then switches back on after a certain delay. This leads to a pulsating mode of operations which can only revert to continual operations after the overload has been eliminated. The main disadvantage here is that the connected consumer load must be restarted after every pause. A restart may not be possible with motors or large capacitive loads since the restart current peak may once again exceed the defined limit. U UA W t I ILimit INominal t W.8 2003670000 Glossary/Technical appendix Glossary Hold-up time (mains-failure bridging time) The hold-up time (also known as the mains-failure bridging time) is the interval from the start of the mains outage to the point in time when the output voltage can no longer be maintained at its original level. The hold-up time indicates how long a mains outage may last before it influences the output voltage. For DC power supplies, EN 61204 requires a bridging time of at least 20 ms. U UA hold-up time Power failure (cutoff) I t Input voltage range This refers to the minimum and maximum input voltage at which the rated output specifications can be maintained. Inrush current The inrush current refers to the peak current that occurs when turning on a consumer load. Switched-mode power supplies have storage capacitors in the input which can cause significant current peaks while the mains power is being switched on. A variety of circuitry solutions can be used to attenuate these current peaks. In the simplest solution, an inrush limiter is used. Active switching can be used in other cases. The peak current specification indicates which upstream fuse should be used in the circuit. If a fuse is selected which is too sensitive, it can trigger when the mains power is switched on. W 2003670000 W.9 Glossary/Technical appendix Glossary IU characteristic curve The IU characteristic curve is a special output characteristic curve that protects power supply units from overloads and short circuits. It offers the best performance with regards to overload and short circuit capabilities. A current limit is activated at a specific current level (for example, 110 or 120 % on the nominal rating). As the load continues to increase, the output voltage is reduced according to the current limit curve until it reaches a level approaching zero volts. Thus a pulsating mode of operations is avoided for short-term overloads. Large capacitive loads or motors are brought back up along the slope of the current-limit characteristic curve. After a short circuit or overload is fixed, the IU characteristic curve offers the advantage of immediately returning to the normal voltage control mechanism. The full output voltage is then immediately available. The IU characteristic curve is becoming the established standard for modern power supplies. Additional variants are available which pertain to the peak current capacity and the slope of the current-limit characteristic curve. U UA INominal I Limit M Mains harmonics Power supplies can experience harmonics caused by mains rectification on the input side. These harmonics are multiples of the mains frequencies. Existing standards define specific limit values since such harmonics can significantly lower the mains quality. Mains system types This refers to the types of mains supply systems. Systems differ in their method of earthing and the implementation of the phase wire, PE wire and central-point wire. Common mains systems include the TN, IT and TT networks. The individual mains types can also differ in their voltage levels and frequencies. PRO-M PRO-M L N PE TN-S Mains L1 L2 L3 N PE W W.10 I MTBF (mean time between failure) PRO-M L N PE TN-C Mains L1 L2 L3 PEN PRO-M L N PE TT Mains L1 L2 L3 N L N PE IT Mains L1 L2 L3 N The MTBF is a statistical value that specifies the probability that a product will fail. It is typically specified in hours and normally assumes a temperature of 25 °C. The probability of failure depends largely on the ambient surroundings. The key variables are the type of load and the ambient temperature. 2003670000 O Glossary/Technical appendix Glossary Output characteristic curves The output characteristic curves of power supply devices are determined by current and voltage. Unregulated devices do not have a current limit. In the case of an overload or short circuit, fuses or temperature switches are used to protect the device. Regulated devices are protected against overload and short circuits by means of various output characteristic curves. In this case, the system attempts to prevent any activation of fuses or temperature switches. The mandatory manual reset which follows an overload or short circuit can then be avoided. Common output characteristic curves include the hiccup mode, the foldback characteristic curve or the IU characteristic curve. ➝ Hiccup mode, foldback characteristic curve, IU characteristic curve Overvoltage category Power supply units are classified into overvoltage categories according to the immunity against mains surges and transient voltages. P PELV (protective extra-low voltage) This is a functional DC voltage with secure isolation according to EN 50178. As with SELV, a reinforced or double insulation is used between the primary and secondary sides. However, the secondary side is earthed. PFC (power factor correction) The power factor correction can be either passive or active in relation to power supply devices. The reactive power resulting from the bridge rectification puts a significant strain on the power supply network. The relatively poor power efficiency factor that results can be improved by using passive components (such as filters) or an active electronic mechanism. For switched-mode power supplies, PFC usually refers to the active variant of the power factor correction. Power factors of almost 1 can be reached when using an active PFC. Practically no reactive power is drawn from the mains supply network; therefore the strain on the mains network is relatively low. Pollution severity Pollution severity describes the environment and ambient conditions that a device requires in order for it to function smoothly. Significant environmental variables include condensation or air containing dust and oil. Power-boost or boost The power-boost function is the surge current handling capacity in the seconds to minutes range. This function is often required for starting up DC motors. DC motors have a high start-up current and often require several seconds before they have achieved their rated rotational speed. The power-boost function helps to optimise this start-up phase. Power factor The power factor is the ratio of reactive power to apparent power. It is an indicator of the device performance with respect to the load on the mains power network. Depending on the technology in use, the power factor for power supplies can be between 0.45 and nearly 1. 2003670000 W W.11 Glossary/Technical appendix Glossary Power loss For power supply units, the power loss specification indicates the thermal output emitted during nominal (rated) operations. This is a key specification used by engineers when designing the climate control systems within electrical cabinets. It is calculated as the difference between the input and output power and can also take the degree of efficiency into account. Power rating The continual output permitted under the rated conditions. Power supply units connected in series Power supplies can only be connected in series when this is clearly permitted by the manufacturer. Such series connections are then normally tied to certain conditions. They can be used to increase the output voltage. This is not widely implemented. Protection degree According to DIN EN 60529, devices can be classified according to their protection degrees. The numeric code (for example, IP 20) defines two protection degrees: protection against touch or penetration by external objects (the first digit) and protection against water penetration (the second digit). Switched-mode power supplies intended for use in electrical cabinets or similar enclosures are often designed with IP 20 protection. The first digit (in this case, 2) ensures finger protection. The second digit (0) indicates that no protection against water is provided. Pulsed current capacity The pulsed current capacity describes the dynamic performance of a switchedmode power supply. Capacitive consumer loads, with their high inrush currents, put a particular strain on a switched-mode power supply. Peak values are reached (in the ms range) which amount to levels many times higher than the mains current. If the current control mechanism reacts too quickly, this can lead to voltage drops and can cause problems for loads which are connected in parallel. For this reason, power supplies are often equipped with a surge current limiting factor based on time. This allows a high current output for only a few ms which can be much higher than the rated current. R W W.12 Rated control voltage The nominal value of the sparkover voltage for the relay. Rated input voltage The input voltage required at which, under the normal mains voltage fluctuations, the output levels can be kept stable. It usually corresponds to the rated voltage for the electric utility‘s power grid. Rated output current The long-term current permitted under the rated conditions. Rated output voltage The nominal output voltage used for the rated specifications. It usually corresponds to the factory default output voltage. 2003670000 Glossary/Technical appendix Glossary Redundancy A power supply system is considered redundant if it is constructed so that it has partial power supplies which are independent of each other and each of these can individually deliver the output load. When a fault occurs, therefore, it is still possible to continue to supply the connected rated load. In reality, at least two power supplies are connected in parallel using decoupling diodes. In this way, a short circuit in the output of one power supply will not lead to the failure of the entire power supply system. ➝ Diode modules Regulated power supply units Switched-mode power supplies, as opposed to more common power supply units, have become established as the standard for the 10–1,000 W power range. They produce a stable output voltage with minimal residual ripple, even when influenced by fluctuations in the mains voltage, mains frequency or load. Their small size and weight is a result of their superior efficiency degree. The electronic control mechanism typically ensures a constant output voltage that varies ±1 %. Residual ripple The residual ripple describes the ratio of superimposed AC voltage to DC voltage on the output side of the power supplies. In addition to a percent specification, the superimposed ripple is often specified in mVSS for switched-mode power supplies. Resistance to shock Resistance to shock refers to mechanical immunity against impacts in any direction. This is a key factor while the product is being transported. Response time The response time is the time that a power supply unit needs to compensate for a disturbance (for example, a load fluctuation). S Switching frequency Switched-mode power supplies are normally operated with switching frequencies from 20 to 200 kHz. The HF or power transformer is switched on an off using transistors at this switching frequency. Small, compact units can be built with this method in comparison with the traditional 50/60 Hz transformers. W 2003670000 W.13 Glossary/Technical appendix Glossary Switched-mode power supply units The switching pulse can be either primary or secondary. Thus there are primary switched-mode and secondary switched-mode power supply units. Secondary switched-mode power supply units are no longer of much significance. The primary switched-mode power supplies are now the focus of attention. The pulse refers to the high-frequency on and off switching of the transformer or transmitter in order to transmit energy. The high frequency allows the use of extra small inductive and capacitive components, particularly for the transmitter. In comparison to transformer-based power supply units, the weight and volume required are much reduced. L + – N PE Selectivity When surge protection equipment is connected in series, selectivity refers to the ability of only one upstream fuse to trigger selectively in the event of an overload. The differentiation can take into account current or also time. With DC power supply systems, selectivity refers to the separate fusing of load circuits on the DC side. In this case as well, only the proper series fuse should trigger in the event of an overload. Fuses in DC circuits play a critical role since the power supplies must react to upcoming short circuits with a speedy cut-off or by limiting the current. Usually electronic fuses are used for this purpose. Mains Mains 63 A 25 A ˜ = Power Supplies 16 A Load Selectivity for fuses connected in series W W.14 Load Load Load Selectivity for DC systems SELV (safety extra low voltage) SELV refers to extra-low safety voltages according to IEC/EN 60950. Reinforced or doubled insulation between the primary and secondary sides is used to prevent electric shock. The output voltage here is sufficiently low so that it does not pose an injury risk if a person comes into direct contact. Earthing on the secondary side is possible but not required. Surge A surge is a high-power voltage pulse which can be caused by, for example, a lightning strike. The switching operations from large consumer loads can also generate such voltage surges on the mains network. The surge test is used to demonstrate the immunity against high-power voltage pulses. 2003670000 T Temperature range U Unregulated power supply units V Vibration resistance W Wide-range input Glossary/Technical appendix Glossary The temperature range specifies the minimum and maximum ambient temperatures for which a device can start up and run continuously. Unregulated power supplies consist mainly of a transformer, a rectifier and an Elkos filter. Since no controlling system is in place, mains voltage fluctuations influence the DC voltage side. Unregulated power supply units are very sturdy; they can be used in applications where a stabilised DC voltage is not necessary (for example, power supply to contactors). Vibration resistance describes the resistance against constant mechanical vibrations that occur during operations. Rail and ship applications place stricter demands for vibration resistance on the device. Modern switched-mode power supplies often feature a wide input range. They can be run under a wide range of voltages: from min. to max. rated voltages including the tolerance limits. They do not require any manual range switching. W 2003670000 W.15 W W.16 2003670000 Glossary/Technical appendix Contents Index Index Index Index Type X.2 Index Order No. X.3 Adresses worldwide X.4 X 2003670000 X.1 Type C Index / Type CP A BATTERY 24V DC1.3AH CP A BATTERY 24V DC12AH CP A BATTERY 24V DC17AH CP A BATTERY 24V DC3.4AH CP A BATTERY 24V DC7.2AH CP A WALLADAPTER 30 MM CP A WALLADAPTER 30 MM CP A WALLADAPTER 30 MM CP A WALLADAPTER 45MM CP A WALLADAPTER 45MM CP A WALLADAPTER 45MM CP DC BUFFER 24V 20A CP DC UPS 24V 20A/10A CP DC UPS 24V 40A CP DC UPS TF05 CP DC UPS TF25 CP DCDC 250W 24V 10A CP DCDC 50W 12V 3A CP DCDC 50W 15V 3A CP DCDC 50W 22-24V 2A CP DCDC 50W 22-24V 2A CP DCDC 50W 5V 8A CP DM 10 CP DM 20 CP E SNT 100W 12V 8.5A CP E SNT 100W 48V 2.3A CP E SNT 100W 5V 16A CP E SNT 100W 24V 4.5A CP E SNT 150W 12V 12.5A CP E SNT 150W 48V 3.3A CP E SNT 150W 24V 6.5A CP E SNT 250W 12V 21A CP E SNT 250W 24V 10.5A CP E SNT 250W 48V 5.2A CP E SNT 25W 12V 2.1A CP E SNT 25W 24V 1.1A CP E SNT 25W 48V 0.57A CP E SNT 25W 5V 5A CP E SNT 350W 24V 14.6A CP E SNT 350W 48V 7.3A CP E SNT 50W 12V 4.2A CP E SNT 50W 24V 2.2A CP E SNT 50W 48V 1.1A CP E SNT 50W 5V 10A CP E SNT 75W 12V 6A CP E SNT 75W 24V 3.2A CP E SNT 75W 48V 1.6A CP E SNT 75W 5V 12A CP M CAP CP M CAP CP M CAP CP M DM20 CP M DM20 CP M DM20 CP M DM40 CP M DM40 CP M SNT 250W 24V 10AUW CP NT 144W 24V 6A CP NT 192W 24V 8A CP NT 264W 24V 11A CP NT 36W 24V 1.5A CP NT 432W 24V 18A CP NT 72W 24V 3A CP NT3 1000W 24V 40A CP NT3 250W 24V 10A CP NT3 400W 24V 15A CP NT3 500W 24V 20A CP NT3 600W 24V 25A CP NT3 750W 24V 30A CP SNT 12W 24V 0.5A CP SNT 24W 12V 1.5A CP SNT 24W 15V 1.5A CP SNT 24W 24V 1A CP SNT 24W 5V 2A CP SNT 25W 5V 5A CP SNT 48W 12V 4A CP SNT 48W 24V 2A CP SNT 48W 48V 1A CP T RM 10 CP T RM 20 CP T SNT 140W 12V 12A CP T SNT 180W 24V 7,5A CP T SNT 180W 48V 4A CP T SNT 360W 24V 15A CP T SNT 360W 48V 7,5A CP T SNT 600W 24V 25A CP T SNT 600W 48V 12,5A CP T SNT 70W 12V 6A CP T SNT 90W 24V 3,8A CP T SNT 90W 24V3,8ACL2 CP T SNT 90W 48V 2A CP T SNT2 180 W 24 V 7,5 A CP T SNT2 360 W 24 V 15 A CP T SNT2 600 W 24 V 25 A X X.2 Order No. 1406930000 1251090000 1251110000 1251070000 1251080000 1461870000 1461870000 1461870000 1461850000 1461850000 1461850000 1251220000 1370050010 1370040010 1444480000 1444540000 1313320010 9919372412 9919372415 9919372424 9919371224 9919372405 8710620000 8768650000 1165830000 1165850000 1165820000 1165840000 1165870000 1165890000 1165880000 1202520000 1202530000 1202540000 1202630000 1202620000 1202610000 1202640000 1202550000 1202560000 1202580000 1202450000 1202460000 1202590000 1202480000 1202490000 1202510000 1202470000 1222240000 1222240010 1222240000 1222210000 1222210010 1222210000 1222220000 1222220010 1165480010 8575280000 8575300000 8575310000 8575260000 8575320000 8575270000 8628680000 8628620000 8628630000 8628650000 8628660000 8628670000 9918840024 9928890012 9928890015 9928890024 9928890005 8754960000 8754970000 8739140000 8879230000 1105880000 1105890000 1105440000 1105810000 1105850000 1105820000 1105860000 1105840000 1105870000 1105430000 1105790000 1194410000 1194420000 1194480000 1194490000 1194310000 Page B.6 B.6 B.7 B.7 B.7 A.13 A.28 B.9 A.13 A.28 B.9 B.8 B.5 B.5 B.9 B.9 A.73 A.69 A.70 A.68 A.68 A.70 A.12 A.12 A.50 A.51 A.50 A.51 A.52 A.53 A.52 A.54 A.54 A.55 A.44 A.45 A.45 A.44 A.56 A.56 A.46 A.47 A.47 A.46 A.48 A.49 A.49 A.48 A.24 A.24 A.72 A.23 A.23 A.72 A.23 A.23 A.27 D.5 D.5 D.6 D.4 D.6 D.4 D.9 D.7 D.7 D.8 D.8 D.9 A.67 A.61 A.60 A.60 A.61 A.62 A.63 A.64 A.65 A.39 A.39 A.31 A.33 A.35 A.33 A.36 A.34 A.36 A.31 A.32 A.32 A.35 A.37 A.37 A.38 Type M MTA 30 BK MTA 30 BK MTA 30 BK MTA 30 MF MTA 30 MF MTA 30 MF MTA 45 BK MTA 45 BK MTA 45 BK MTA 45 MF MTA 45 MF MTA 45 MF P PRO ECO 240W 48V 5A PRO ECO 480W 48V 10A PRO ECO 72W 12V 6A PRO ECO 120W 12V 10A PRO ECO 120W 24V 5A PRO ECO 240W 24V 10A PRO ECO 480W 24V 20A PRO ECO 72W 24V 3A PRO ECO 960W 24V 40A PRO ECO3 120W 24V 5A PRO ECO3 240W 24V 10A PRO ECO3 480W 24V 20A PRO ECO3 960W 24V 40A PRO MAX 120W 12V 10A PRO MAX 120W 24V 5A PRO MAX 180W 24V 7,5A PRO MAX 240W 24V 10A PRO MAX 240W 48V 5A PRO MAX 480W 24V 20A PRO MAX 480W 48V 10A PRO MAX 70W 5V 14A PRO MAX 72W 12V 6A PRO MAX 72W 24V 3A PRO MAX 960W 24V 40A PRO MAX 960W 48V 20A PRO MAX3 120W 24V 5A PRO MAX3 240W 24V 10A PRO MAX3 480W 24V 20A PRO MAX3 960W 24V 40A S Schuko TS35 SDIK PH1 SDIK PH1 SDIK PH1 SDIK PH1 SDIK PH2 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 1.0X5.5X125 SDIS 1.0X5.5X125 SDIS 1.0X5.5X125 SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS W WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW WGS 24Vdc 0.5...5A WGS 24Vdc 1,6A WGS 24Vdc 3,15A WGS 24Vdc 6,3A WGS 24Vdc 8,0A WGZ 24Vdc 0.5...5A WGZ 24Vdc 1,6A WGZ 24Vdc 3,15A WGZ 24Vdc 6,3A WGZ 24Vdc 8,0A Order No. Page 1168970000 1168970000 1168970000 1251320000 1251320000 1251320000 1962250000 1962250000 1962250000 1251310000 1251310000 1251310000 A.13 A.28 B.9 A.13 A.28 B.9 A.13 A.28 B.9 A.13 A.28 B.9 1469590000 1469610000 1469570000 1469580000 1469480000 1469490000 1469510000 1469470000 1469520000 1469530000 1469540000 1469550000 1469560000 1478230000 1478110000 1478120000 1478130000 1478240000 1478140000 1478250000 1478210000 1478220000 1478100000 1478150000 1478270000 1478170000 1478180000 1478190000 1478200000 A.9 A.9 A.8 A.8 A.5 A.6 A.6 A.5 A.7 A.10 A.10 A.11 A.11 A.19 A.15 A.16 A.16 A.19 A.17 A.20 A.18 A.18 A.15 A.17 A.20 A.21 A.21 A.22 A.22 8734580000 9008570000 9008570000 9008570000 9008570000 9008580000 9008380000 9008380000 9008380000 9008380000 9008380000 9008410000 9008410000 9008410000 1248580000 1248580000 1248580000 1248580000 1248580000 E.2 A.13 A.28 A.40 A.66 A.40 A.13 A.28 A.40 A.66 B.9 A.28 A.40 B.9 A.13 A.28 A.40 A.66 B.9 1162600000 1162600000 1162600000 1162600000 1162600000 8710270000 8618890000 8618910000 8618930000 8618940000 8727630000 8621040000 8621030000 8621020000 8621010000 A.13 A.28 A.40 A.66 B.9 C.6 C.4 C.4 C.5 C.5 C.6 C.4 C.4 C.5 C.5 2003670000 Type 1100000000 1105430000 1105440000 1105790000 1105810000 1105820000 1105840000 1105850000 1105860000 1105870000 1105880000 1105890000 CP T SNT 70W 12V 6A CP T SNT 140W 12V 12A CP T SNT 90W 24V 3,8A CP T SNT 180W 24V 7,5A CP T SNT 360W 24V 15A CP T SNT 600W 24V 25A CP T SNT 180W 48V 4A CP T SNT 360W 48V 7,5A CP T SNT 600W 48V 12,5A CP T RM 10 CP T RM 20 1160000000 1162600000 1162600000 1162600000 1162600000 1162600000 1165480010 1165820000 1165830000 1165840000 1165850000 1165870000 1165880000 1165890000 1168970000 1168970000 1168970000 WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW WEW 35/1 SW CP M SNT 250W 24V 10AUW CP E SNT 100W 5V 16A CP E SNT 100W 12V 8.5A CP E SNT 100W 24V 4.5A CP E SNT 100W 48V 2.3A CP E SNT 150W 12V 12.5A CP E SNT 150W 24V 6.5A CP E SNT 150W 48V 3.3A MTA 30 BK MTA 30 BK MTA 30 BK 1190000000 1194310000 1194410000 1194420000 1194480000 1194490000 CP T SNT2 600 W 24 V 25 A CP T SNT 90W 24V3,8ACL2 CP T SNT 90W 48V 2A CP T SNT2 180 W 24 V 7,5 A CP T SNT2 360 W 24 V 15 A 1200000000 1202450000 1202460000 1202470000 1202480000 1202490000 1202510000 1202520000 1202530000 1202540000 1202550000 1202560000 1202580000 1202590000 1202610000 1202620000 1202630000 1202640000 CP E SNT 50W 24V 2.2A CP E SNT 50W 48V 1.1A CP E SNT 75W 5V 12A CP E SNT 75W 12V 6A CP E SNT 75W 24V 3.2A CP E SNT 75W 48V 1.6A CP E SNT 250W 12V 21A CP E SNT 250W 24V 10.5A CP E SNT 250W 48V 5.2A CP E SNT 350W 24V 14.6A CP E SNT 350W 48V 7.3A CP E SNT 50W 12V 4.2A CP E SNT 50W 5V 10A CP E SNT 25W 48V 0.57A CP E SNT 25W 24V 1.1A CP E SNT 25W 12V 2.1A CP E SNT 25W 5V 5A 1220000000 1222210000 1222210000 1222210010 1222220000 1222220010 1222240000 1222240000 1222240010 CP M DM20 CP M DM20 CP M DM20 CP M DM40 CP M DM40 CP M CAP CP M CAP CP M CAP 1240000000 1248580000 1248580000 1248580000 1248580000 1248580000 SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS SM 18/9.5 K MC NE WS 1250000000 1251070000 1251080000 1251090000 1251110000 1251220000 1251310000 1251310000 1251310000 1251320000 1251320000 1251320000 CP A BATTERY 24V DC3.4AH CP A BATTERY 24V DC7.2AH CP A BATTERY 24V DC12AH CP A BATTERY 24V DC17AH CP DC BUFFER 24V 20A MTA 45 MF MTA 45 MF MTA 45 MF MTA 30 MF MTA 30 MF MTA 30 MF 1310000000 1313320010 CP DCDC 250W 24V 10A 2003670000 Page A.31 A.31 A.32 A.33 A.33 A.34 A.35 A.36 A.36 A.39 A.39 A.13 A.28 A.40 A.66 B.9 A.27 A.50 A.50 A.51 A.51 A.52 A.52 A.53 A.13 A.28 B.9 A.38 A.32 A.35 A.37 A.37 A.47 A.47 A.48 A.48 A.49 A.49 A.54 A.54 A.55 A.56 A.56 A.46 A.46 A.45 A.45 A.44 A.44 A.23 A.72 A.23 A.23 A.23 A.24 A.72 A.24 A.13 A.28 A.40 A.66 B.9 B.7 B.7 B.6 B.7 B.8 A.13 A.28 B.9 A.13 A.28 B.9 A.73 Order No. Type 1370000000 1370040010 1370050010 CP DC UPS 24V 40A CP DC UPS 24V 20A/10A 1400000000 1406930000 CP A BATTERY 24V DC1.3AH 1440000000 1444480000 1444540000 CP DC UPS TF05 CP DC UPS TF25 1460000000 1461850000 1461850000 1461850000 1461870000 1461870000 1461870000 1469470000 1469480000 1469490000 1469510000 1469520000 1469530000 1469540000 1469550000 1469560000 1469570000 1469580000 1469590000 1469610000 CP A WALLADAPTER 45MM CP A WALLADAPTER 45MM CP A WALLADAPTER 45MM CP A WALLADAPTER 30 MM CP A WALLADAPTER 30 MM CP A WALLADAPTER 30 MM PRO ECO 72W 24V 3A PRO ECO 120W 24V 5A PRO ECO 240W 24V 10A PRO ECO 480W 24V 20A PRO ECO 960W 24V 40A PRO ECO3 120W 24V 5A PRO ECO3 240W 24V 10A PRO ECO3 480W 24V 20A PRO ECO3 960W 24V 40A PRO ECO 72W 12V 6A PRO ECO 120W 12V 10A PRO ECO 240W 48V 5A PRO ECO 480W 48V 10A 1470000000 1478100000 1478110000 1478120000 1478130000 1478140000 1478150000 1478170000 1478180000 1478190000 1478200000 1478210000 1478220000 1478230000 1478240000 1478250000 1478270000 PRO MAX 72W 24V 3A PRO MAX 120W 24V 5A PRO MAX 180W 24V 7,5A PRO MAX 240W 24V 10A PRO MAX 480W 24V 20A PRO MAX 960W 24V 40A PRO MAX3 120W 24V 5A PRO MAX3 240W 24V 10A PRO MAX3 480W 24V 20A PRO MAX3 960W 24V 40A PRO MAX 70W 5V 14A PRO MAX 72W 12V 6A PRO MAX 120W 12V 10A PRO MAX 240W 48V 5A PRO MAX 480W 48V 10A PRO MAX 960W 48V 20A 1960000000 1962250000 1962250000 1962250000 MTA 45 BK MTA 45 BK MTA 45 BK 8570000000 8575260000 8575270000 8575280000 8575300000 8575310000 8575320000 CP NT 36W 24V 1.5A CP NT 72W 24V 3A CP NT 144W 24V 6A CP NT 192W 24V 8A CP NT 264W 24V 11A CP NT 432W 24V 18A 8610000000 8618890000 8618910000 8618930000 8618940000 WGS 24Vdc 1,6A WGS 24Vdc 3,15A WGS 24Vdc 6,3A WGS 24Vdc 8,0A 8620000000 8621010000 8621020000 8621030000 8621040000 8628620000 8628630000 8628650000 8628660000 8628670000 8628680000 WGZ 24Vdc 8,0A WGZ 24Vdc 6,3A WGZ 24Vdc 3,15A WGZ 24Vdc 1,6A CP NT3 250W 24V 10A CP NT3 400W 24V 15A CP NT3 500W 24V 20A CP NT3 600W 24V 25A CP NT3 750W 24V 30A CP NT3 1000W 24V 40A 8710000000 8710270000 8710620000 WGS 24Vdc 0.5...5A CP DM 10 8720000000 8727630000 WGZ 24Vdc 0.5...5A Page B.5 B.5 B.6 B.9 B.9 A.13 A.28 B.9 A.13 A.28 B.9 A.5 A.5 A.6 A.6 A.7 A.10 A.10 A.11 A.11 A.8 A.8 A.9 A.9 A.15 A.15 A.16 A.16 A.17 A.17 A.21 A.21 A.22 A.22 A.18 A.18 A.19 A.19 A.20 A.20 Order No. Type 8730000000 8734580000 8739140000 Schuko TS35 CP SNT 48W 24V 2A 8750000000 8754960000 8754970000 CP SNT 25W 5V 5A CP SNT 48W 12V 4A 8760000000 8768650000 CP DM 20 8870000000 8879230000 CP SNT 48W 48V 1A 9000000000 9008380000 9008380000 9008380000 9008380000 9008380000 9008410000 9008410000 9008410000 9008570000 9008570000 9008570000 9008570000 9008580000 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 0.5X3.0X100 SDIS 1.0X5.5X125 SDIS 1.0X5.5X125 SDIS 1.0X5.5X125 SDIK PH1 SDIK PH1 SDIK PH1 SDIK PH1 SDIK PH2 9910000000 9918840024 9919371224 9919372405 9919372412 9919372415 9919372424 CP SNT 12W 24V 0.5A CP DCDC 50W 22-24V 2A CP DCDC 50W 5V 8A CP DCDC 50W 12V 3A CP DCDC 50W 15V 3A CP DCDC 50W 22-24V 2A 9920000000 9928890005 9928890012 9928890015 9928890024 CP SNT 24W 5V 2A CP SNT 24W 12V 1.5A CP SNT 24W 15V 1.5A CP SNT 24W 24V 1A Page E.2 A.64 Index / Order No. Order No. A.62 A.63 A.12 A.65 A.13 A.28 A.40 A.66 B.9 A.28 A.40 B.9 A.13 A.28 A.40 A.66 A.40 A.67 A.68 A.70 A.69 A.70 A.68 A.61 A.61 A.60 A.60 A.13 A.28 B.9 D.4 D.4 D.5 D.5 D.6 D.6 C.4 C.4 C.5 C.5 C.5 C.5 C.4 C.4 D.7 D.7 D.8 D.8 D.9 D.9 C.6 A.12 X C.6 X.3 Addresses worldwide Addresses worldwide Let’s connect. AE United Arab Emirates BR Weidmuller Middle East FZE Warehouse Q3-79 SAIF-Zone P.O. BOX 8591 Sharjah Tel. +971 65572723 Fax +971 65572724 [email protected] AO Angola Please contact Phambili Interface South Africa AR Argentina CPI SA Bauness 2660 C1431DOF Buenos Aires Tel. +54 11 4523 8008 Fax +54 11 4522 0546 [email protected] www.cpi.com.ar AT AU AZ BA Austria Weidmüller GmbH IZ NOE Süd Straße 2b, Obj M 59 2355 Wiener Neudorf Tel. +43 2236 67080 Fax +43 2236 6708-899 [email protected] www.weidmueller.com Australia Weidmüller Pty. Ltd. PO BOX 6944 Huntingwood 2148 Huntingwood Drive 43 Huntingwood NSW 2148 Tel. +61 2 9671 9999 Fax +61 2 9671 9911 [email protected] www.weidmuller.com.au Azerbaijan Representative Office Rashad Mahmudov Demirchi Tower, 4th floor 37, Khojali ave. AZ 1025 Baku Tel. +994 12 488 80 36 Fax +994 12 488 80 37 rashad.mahmudov@ weidmueller.com BW Botswana Please contact Phambili Interface South Africa BY Belarus TECHNIKON Ltd. Nezavisimosti pr. 177-9 220125 Minsk Tel. +375 17 393-11-77 Fax +375 17 3930080 [email protected] CA CG CH CL Bosnia and Herzegovina Please contact our Representative Office Weidmüller Interface GmbH & Co. KG Serbia BE Belgium Weidmüller Benelux B. V. Mechelsesteenweg 519 bus 6 en 7 1930 Nossegem Tel. +32 2 752 40 70 Fax +32 2 751 36 06 [email protected] www.weidmueller.be BG Bulgaria Weid-Bul EOOD Bul. „Kliment Ohridski“ 13 1756 Sofia Tel. +359 2 963 2560 Fax +359 2 963 1098 [email protected] www.weidbul.com BH X X.4 Bahrain Khayber Trading Company P.O Box 1976 Manama Tel. +973 720747 Fax +973 720331 [email protected] Canada W Interconnections Canada Inc. 10 Spy Court Markham Ontario L3R 5H6 Tel. +1 (905) 475-1507 Ext. 9836 Fax +1 (905) 475-2798 [email protected] www.weidmuller.ca Congo Please contact Phambili Interface South Africa CN CO CR CZ DE DK EC EE Switzerland Weidmüller Schweiz AG Rundbuckstraße 2 8212 Neuhausen am Rheinfall SH Tel. +41 52 674 07 07 Fax +41 52 674 07 08 [email protected] www.weidmueller.ch Chile ATS - INTECH María Luisa Santander 0475 Santiago Providencia 7500859 Tel. +56 2 341 1271 Fax +56 2 341 1275 [email protected] www.atsintech.com CPI CHILE LTDA Av. Presidente Frei Montalva 6001, 47 complejo el cortijo Santiago - Conchali Tel. +562 963 8440 Fax +562 963 8440 [email protected] www.cpichile.cl or BIG electric d.o.o Mladena Stojanovića 117A 78000 Banja Luka Tel. +387 51926277 Fax +387 51926277 [email protected] www.bigelectric.ba Brazil Weidmuller Conexel do Brasil Conexões Elétricas Ltda. Av. Presidente Juscelino, 642 - Piraporinha Diadema, São Paulo 09950-370 Tel. +55 (11) 4366-9600 Fax +55 (11) 4362-1677 [email protected] www.weidmueller.com.br China Weidmüller Interface (Shanghai) Co. Ltd. 100 Yutong Road 25 F, BM Intercontinental Business Center 200070 Shanghai Tel. +86 21-22195008 Fax +86 512-68417505 customer.hotline@ weidmueller.com.cn www.weidmueller.com.cn w Colombia Automatización Avanzada S. A. Carrera 97 No., 24 c - 23 Bodega 4 110911 Bogotá-D.C. Tel. +57 (1) 547-8510 Fax +57 (1) 422-3044 comercial@ automatizacionavanzada.com www. automatizacionavanzada.com Costa Rica ELVATRON S. A. la Uruca 400 Norte Banco Costa Rica San Jose Costa Rica Tel. +506 2961-060 Fax +506 5200-609 [email protected] www.elvatron.com Czech Republic Weidmüller s.r.o. Lomnického 5/1705 140 00 Praha 4 Tel. +420 244 001 400 Fax +420 244 001 499 [email protected] www.weidmueller.cz Germany Weidmüller GmbH & Co. KG Ohmstraße 9 32758 Detmold Postfach 30 54 32720 Detmold Tel. +49 5231 1428-0 Fax +49 5231 14-292083 [email protected] www.weidmueller.de Denmark Weidmüller Danmark Vallensbækvej 18A 2605 Brøndby Tel. +45 27747800 [email protected] www.weidmuller.dk Ecuador Elsystec S. A., Electricidad Sistemas y Tecnología Vasco de Contreras N35-251 y Mañosca Quito - Pichincha Tel. +593 22456510 Fax +593 22456755 [email protected] Estonia Please contact our Representative Office Weidmüller Interface GmbH & Co. KG Latvia GE Georgia Please contact our Representative Office Rashad Mahmudov Azerbaijan. GH Ghana Please contact Weidmüller Interface GmbH & Co. KG South Africa GR Greece G.A. Solutions Ippokratous 11 Metamorfosi 144 52 Athen Tel. +30 210 2823233 Fax +30 210 2823233 [email protected] www.weidmuller.gr GT Guatemala Prestelectro, Prestegard Electro, S.A. Avenida Petapa 44-22, Zona 12 Guatemala City Tel. +502 2442-3346 Fax +502 2476-8945 [email protected] HK HR or Soots Interface OÜ Pärnu mnt 142 11317 Tallinn Tel. +372 609 6933 Fax [email protected] www.sootsinterface.ee EG ES FI Egypt Standard Electric (OMEGA) 1, Abdelhamid Badawy Street Heliopolis Cairo Tel. +202 21805111 Fax +202 21805600 [email protected] Spain Weidmüller, S. A. Narcis Monturiol 11-13, Pol. Ind. Sudoeste 8960 Sant Just Desvern - Barcelona Tel. +34 934 803 386 Fax +34 933 718 055 [email protected] www.weidmuller.es Finland Weidmüller Suomi, Weidmüller Aktiebolagetin sivuliike Koy Plaza Vivace Äyritie 8C FI 1510 Vantaa Tel. +358 20 7351300 Fax +358 800 114 667 [email protected] www.weidmuller.fi FR France Weidmüller E. U. R. L. 12, Chaussée Jules César BP 263 Osny 95523 Cergy-Pontoise Cedex Tel. +33 1 34 24 55 00 Fax +33 1 34 24 55 01 [email protected] GB Great Britain Weidmüller Ltd. Klippon House Centurion Court Office Park, Meridian East, Meridian Business Park Leicester LE19 1TP Tel. +44 116 282 3470 Fax +44 116 289 3582 [email protected] www.weidmuller.co.uk Hong Kong Weidmuller (Hong Kong) Limited Co. Ltd. Unit 1617, Metropolis Tower No. 10 Metropolis Drive, Hunghom, Kowloon Tel. +852 3154 8088 Fax +852 31548099 [email protected] Croatia ElektroPARTNER d.o.o. Slavonska avenija 24/6 HR-10000 Zagreb Tel. +385 (1) 6184 793 Fax +385 (1) 6184 795 [email protected] www.elektropartner.hr HU Hungary Weidmüller Kereskedelmi Kft. Budapest Gubacsi út 6. 1097 Tel. +36 1 382 7700 Fax +36 1 382 7701 [email protected] www.weidmueller.hu ID Indonesia PT. Nego Electrindo Ruko Mega Grosir Cempaka Mas Blok I No. 20 – 22 Jakarta 10640 Tel. +62 21 42882255 Fax +62 21 42882266 [email protected] IE Ireland Please contact Weidmüller Ltd. Great Britain IL Israel A. U. Shay Ltd. 23/25, Embar Street 49222 Petach-Tikva P.O. Box 1 00 49 49222 Petach-Tikva Tel. +972 3-923-3601 Fax +972 3-923-4601 [email protected] www.uriel-shay.com ATEKA Ltd. 4, Ha Tavor lane Industrial area Segula 49691 Petach-Tikva P.O. Box 4710 Petach-Tikva Tel. +972 73-200-1311 Fax +972 3-924 4245 [email protected] www.ateka.co.il IN India Representative Office Weidmüller Electronics India Pvt. Ltd. 12th Lane North Avenue, Opp Joggers Park, Kalyani Nagar, Pune 411 006 Tel. +91 20-41290090 [email protected] www.weidmueller.com IS Iceland Samey Automation Center Lyngas 13 210 Garoabaer Tel. +354 510 5200 Fax +354 5 10 5201 [email protected] www.samey.is IT Italy Weidmüller S. r.l. Via Albert Einstein 4 20092 Cinisello Balsamo Milano Tel. +39 02 660681 Fax +39 02 6124945 [email protected] www.weidmuller.it JM Jamaica Please contact W Interconnections Inc. United States JO Jordan Trans Jordan for Electro PO Box 33 06 07 Amman Tel. +962 6 533 2020 Fax +962 6 533 5800 [email protected] JP Japan Nihon Weidmüller Co. Ltd. Sphere Tower Tennoz 2-2-8 Higashi-Shinagawa, Shinagawa-ku Tokyo 140-0002 Tel. +81 3 6711 5300 Fax +81 3 6711 5333 weidmullerjapan@weidmuller. co.jp www.weidmuller.co.jp KE Kenya Please contact Phambili Interface South Africa KR Korea Weidmuller Korea Co. Ltd. 9th floor, Wonbang B/D Samseong 2-Dong, GangnamGu Seoul 143-42 Tel. +82 2-516-0003 Fax +82 2-516-0090 [email protected] www.weidmuller.co.kr KZ Kazakhstan Please contact OOO Weidmüller Russia LT Lithuania Please contact our Representative Office Weidmüller Interface GmbH & Co. KG Latvia or ELEKTROS IRANGA Tinklu g. 29 a LT-5319 Panevezys Tel. +370 (45) 582 828 Fax [email protected] LU Luxembourg Please contact Weidmüller Benelux B. V. Netherlands LV Latvia SIA Abi4 Daugavgrivas 31b Riga, LV-1007 Tel. +371 674 70999 Fax +371 676 24562 [email protected] Representative Office Weidmüller Interface GmbH & Co. KG Udens str. 12-118 Riga, LV-1007 Tel. +371 29254766 Fax +371 674 65637 Ilgonis.rudaks@weidmueller. com www.weidmueller.com 2003670000 You can find all Weidmüller addresses and your local contact on the internet at: www. weidmueller.com/countries Addresses worldwide Sales company Representation abroad without representation abroad Let’s connect. MD ME MG MK Moldova BERHORD A & D srl 79/1, str. Milescu Spartaru MD-2075 Chisinau Moldova Tel. +373 (22) 815002 Fax +373 (22) 815007 [email protected] www.ad.berhord.com Montenegro Please contact our Representative Office Weidmüller Interface GmbH & Co. KG Serbia. NL NO Madagascar Please contact Phambili Interface South Africa Macedonia Please contact our Representative Office Weidmüller Interface GmbH & Co. KG Serbia NZ or ELEKTRO - SMK dooel UL. III Makedonska brigada b.b. 1000 Skopje Tel. +389 22460295 Fax [email protected] MT Malta E. S. S., Electrical Supplies & Services Ltd. San Gwakkin Road Mriehel Tel. +356 21255777 Fax +356 21255999 [email protected] MU MW MX MY Mauritius Mubelo Electrical Ltd. Office 26, Gateway building, St Jean Road Quatre Bornes Mauritius Tel. +230 4670989 Fax +230 4654051 [email protected] Malaysia Connect Plus Technology Sdn Bhd No. 43, Jalan PJS 11/22, Bandar Sunway 46150 Petaling Jaya Selangor Darul Ehsan Tel. +60 3 5633 7363 Fax +60 3 5633 6562 [email protected] www.cptech.com.my MZ Mozambique Please contact Phambili Interface South Africa NA Namibia Please contact Phambili Interface South Africa NG Nigeria Please contact Weidmüller Interface GmbH & Co. KG South Africa 2003670000 Norway Sivilingeniør J.F. Knudtzen AS Billlingstadsletta 97 1396 Billingstad PO Box 160 1378 Nesbru Tel. +47 66 98 33 50 Fax +47 66 98 09 55 [email protected] www.jfknudtzen.no New Zealand Cuthbert S. Steward Ltd. 27 Te Puni Street Petone PO Box 38496 Wellington Mail Centre 5054 Tel. (04) 568 6156 Fax (09) 489 1752 [email protected] Cuthbert S. Steward Ltd 4 Fred Thomas Drive Aon Building, Ground Floor, South Entry Takapuna PO Box 100 338 North Shore City 745 Tel. (09) 489 1751 Fax (04) 568 6056 [email protected] OM PE Malawi Please contact Phambili Interface South Africa Mexico W Interconnections S. A. DE C. V. Blvd. Hermanos Serdán 698, Col. San Rafael Oriente 72029 Puebla Tel. +52 (222) 268 6227 Fax +52 (222) 286 6242 [email protected] Netherlands Weidmüller Benelux B. V. Franciscusweg 221 1216 SE Hilversum P.O. Box 1505 1200 BM Hilversum Tel. +31 35 626 12 61 Fax +31 35 623 20 44 [email protected] www.weidmuller.nl Oman DAN INTERNATIONAL LLC. Ghala St. 111 BP 2901 Seeb Tel. +968 5036 77 Fax +968 5037 55 [email protected] Peru IMPEXINCA S.A.C. Calle Ortiz de Zevallos No. 105, Urb. San Antonio 18 Lima, Miraflores Tel. +51 1 447 5608 [email protected] www.impexinca.pe J & W CIA. S. A. Calle 6 Mz. D Lte. 23, Urb. Ind. Grimanesa 01 Callao Tel. +51 1 572 2539 Fax +51 1 572 0152 [email protected] www.jwcia.com PH PK PL Philippines Enclosure Systems Specialists Inc. 2276 Don Chino Roces Avenue Extension Room 103/105 Narra Building 1231 Makati City Tel. +63 2 813 8580 Fax +63 2 813 8596 [email protected] www.enclosuresystemsph. com Pakistan Automation Controls (Pak) Apartment No. 33 C III, Chenab Block, Allama Iqbal Town Lahore Tel. +92 42 37809948 Fax +92 42 37809950 [email protected] www.acpak.com.pk Poland Weidmüller Sp. z. o. o. ul. Ogrodowa 58 00-876 Warszawa Tel. +48 22 510 09 40 Fax +48 22 510 09 41 [email protected] www.weidmuller.pl PR Puerto Rico Please contact W Interconnections Inc. United States PT Portugal Weidmüller Sistemas de Interface S. A. Estrada Outeiro Polima, R. Augusto Dias da Silva, Lote B - Esct. 2 São Domingos de Rana 2785-515 Abóboda Tel. +351 214 459 191 Fax +351 214 455 871 [email protected] www.weidmuller.pt PY Paraguay Please contact CPI SA Argentina RO Romania Representative Office Weidmüller Interface GmbH & Co. KG Ionescu Crum Street, No. 1, 1st Tower, 1st Floor, Office 4 500446 Brasov - Brasov Business Park Tel. +40 (268) 446 222 Fax +40 (262) 205 410 claudiu.totea@weidmueller. com www.weidmueller.com RS RU Serbia Representative Office Weidmüller Interface GmbH & Co. KG Ustanicka 189, III sprat lokal 7a 11050 Beograd Tel. +381 112885274 Fax +381 112885274 zoran.rabrenovic@ weidmueller.com Russia OOO Weidmüller 7/10 Khlebozavodskiy Passage, Moskau 115230 Tel. +7 (495) 771-69-40 Fax +7 (495) 771-69-41 [email protected] www.weidmueller.ru SA Saudi Arabia Please contact Weidmuller Middle East FZE United Arab Emirates SE Sweden Weidmüller AB Axel Danielssons väg 271 BOX 31025 SE-200 49 Malmö Tel. +46 77-143 00 44 Fax +46 40-37 48 60 [email protected] www.weidmuller.se SG SI SK SV El Salvador Prestegard Electro 11 Avenida Norte No. 240 Edificio Salazar No. 2 San Salvador Tel. +503 2271 1690 Fax +503 2221 3851 [email protected] SY Syria Please contact Weidmuller Middle East FZE United Arab Emirates SZ Swaziland Please contact Phambili Interface South Africa TH Thailand Pisanu Engineering Co. Ltd. Kwang Dingaeng, Khet Dingaeng 800/2 Soi Trakulsuk, Asokedindaeng Road Dindaeng, Bangkok 10400 Tel. +66 2 248 2896 Fax +662 105 6301 [email protected] www.pisanu.co.th TN Tunisia Please contact Weidmüller E. U. R. L. France TR Turkey Weidmüller Elektronik Ticaret Ltd. Sirketi Kavacik Mah. Orhan Veli Kanik Caddesi 9/1 34810 Beykoz / Istanbul Tel. +90 (216) 537 10 70 Fax +90 (216) 537 10 77 [email protected] www.weidmuller.com.tr TW Taiwan Weidmuller (Hong Kong) Limited No. 3, Lane 89, ChaungYang N. Rd 24148 SanChuang City, Taipei Tel. +886 921 949 751 [email protected] TZ Tanzania Please contact Phambili Interface South Africa UA Ukraine LLC WM UKRAINE Levanevskogo str. 6 Kiev 3058 Tel. +38 044 490 32 48 Fax [email protected] wm-ua.com.ua/ Slovakia ELEKTRIS s.r.o. Elektrárenská 1 831 04 Bratislava Tel. +421 2/4920 0113 Fax +421 2/4920 0119 [email protected] Vietnam AUMI Industrial Equipment & Automation Company Limited E1, La Thanh Hotel 218 Doi Can Street Lieu Giai Ward, Ba Dinh District Hanoi City Tel. +84 4 37628601 Fax +84 4 62661391 [email protected] www.aumi.com.vn Representative Office Weidmüller Pte. Ltd. Level 16 Saigon Tower Building 29 Le Duan Street District 1 Ho Chi Minh Tel. +848 3520 7717 Fax +848 3520 7604 [email protected] ZA Representative Office Weidmüller Pte. Ltd. 37/F, Sathorn Square Building 98 North Sathorn Road Bangkok, Silom Bangrak 10500 Tel. +66 2 105 6300 Fax +66 2 642 9220 [email protected] Singapore Weidmüller Pte. Ltd. 70 Bendemeer Road # 04-03 Luzerne Building Singapore 339940 Tel. +65 6841 5311 Fax +65 6841 5377 [email protected] www.weidmuller.com.sg Slovenia Elektrospoji d. o. o. Stegne 27 SI- 1000 Ljubljana Osrednjeslovenska Tel. +386 1 511 3810 Fax +386 1 511 1604 [email protected] www.elektrospoji.si VN South Africa Phambili Interface PO Box 193 1609 Johannesburg, Edenvale 5 Bundo Road, Sebenza 1610 Johannesburg Tel. +27 (11) 4521930 Fax [email protected] www.weidmuller.co.za Representative Office Weidmüller Interface GmbH & Co. KG 210 Amarand Avenue, Pegasus Building 181 Pretoria, waterkloof Glen ext 2 - Tel. +27 12 003 2906 Fax +27 (11) 4526455 Jacques.Vosloo@weidmueller. com www.weidmueller.com ZM Zambia Please contact Phambili Interface South Africa ZW Zimbabwe Please contact Phambili Interface South Africa Representative Office Weidmueller Interface GmbH & Co. KG Z, office 303 7-D, Zdolbunivska str. Kiev, 2081 Mobile +38 050 440 25 24 [email protected] US UZ United States W Interconnections Inc. 821 Southlake Boulevard Richmond Virginia 23236 Tel. +1 (804) 794-2877 Fax +1 (804) 379-2593 [email protected] www.weidmuller.com X Republic of Uzbekistan Please contact OOO Weidmüller Russia X.5 Index We cannot guarantee that there are no mistakes in the publications or software provided by us to the customer for the purpose of making orders. We try our best to quickly correct errors in our printed media. All orders are based on our general terms of delivery, which can be reviewed on the websites of our group companies where you place your order. On demand we can also send the general terms of delivery to you. X X.6 2003670000 Weidmüller – Your partner in Industrial Connectivity As experienced experts we support our customers and partners around the world with products, solutions and services in the industrial environment of power, signal and data. We are at home in their industries and markets and know the technological challenges of tomorrow. We are therefore continuously developing innovative, sustainable and useful solutions for their individual needs. Together we set standards in Industrial Connectivity. Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 32758 Detmold, Germany T +49 5231 14-0 F +49 5231 14-292083 [email protected] www.weidmueller.com Made in Germany Your local Weidmüller partner can be found on our website: www.weidmueller.com/countries Order number: 2003670000/05/2015/SMKW