PROeco power supplies

Switch-mode power supplies
connectPower PROeco
PROeco power supplies with basic functionality
and a high level of reliability
•Single- and three-phase switched-mode power supply units
•Slim design
•Large temperature range from –25 °C to 70 °C
•The output voltage can be precisely adjusted via the
potentiometer on the front
•Remote monitoring via integrated status relay
•Three-coloured LED indicators for simple error detection
•Advanced visual warning at 90 % rated output current
•International approvals
A
%
Derating curves
Technical data
≤ 480 Watt
120
Ioutput (% IN)
100
80
60
40
20
0
–25
0
20
30
40
50
Ambient temperature (°C)
60
70
Ioutput (% IN)
100
80
60
40
20
0
–25
A.4
General technical data
Ambient temp. operating / storage temperature
Max. perm. air humidity (operation)
Degree of protection
Class of protection
Pollution degree
Insulation voltage input/output
MTBF
Parallel connection option
Housing version
Mounting position, installation notice
Short-circuit protection
Overload protection
Overtemperature protection
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
960 Watt
120
0
\
20
30
40
50
Ambient temperature (°C)
60
70
Limiting of mains voltage harmonic currents
Resistance against vibration and shock
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switched-mode power units
Machinery with electronic equipment
Safety extra-low voltage
Protective separation / protection against electrical shock
Protection against dangerous shock currents
–25 °C…+70 °C / –40 °C…+85 °C
5 %…95 % RH
IP 20
I, with PE connection
2
3 kV E/A / 2 kV E/earth / 0.5 kV A/earth
> 500.000 h acc. to IEC 1709 (SN29500)
yes, max. 5 without diode module
metal, corrosion resistant
horizontal on mounting rail TS 35, 50 mm spacing
top and bottom for free air circulation
Yes, automatic restart
Yes, IU characteristic curve
Yes, automatic restart
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN61000-4-6 (conducted), EN61000-4-11 (Dips)
Acc. to EN61000-3-2
1 g acc. to EN50178, shock: 15 g in all directions
Acc. to EN60204
Acc. to EN61558-2-17
Acc. to EN50178 / VDE0160
SELV acc. to EN60950-1, PELV acc. to EN60204-1
VDE0100-410 / acc. to DIN57100-410
Acc. to VDE0106-101
1460790000 – 2014/2015
PRO ECO 72W 24V 3A
PROeco
Switch-mode power supplies
connectPower PROeco
PRO ECO 120W 24V 5A
A
L (+)
N (–)
AC
PE
DC
+
L (+)
–
–
13
14
N (–)
Pay attention to polarity of DC connection
AC
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering data
Note
1460790000 – 2014/2015
mm²
mm²
min/max
Nm
mm
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
0.55 A @ 230 V AC / 1.04 A @ 110 V AC
0.22 A @ 370 V DC / 0.68 A @ 120 V DC
Yes / max. 40
2 A / DI, Safety fuse
6 A, Char. B, Circuit breaker
2...4 A, Char. C, Circuit breaker
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
1.26 A @ 230 V AC / 2.24 A @ 110 V AC
0.39 A @ 370 V DC / 1.16 A @ 120 V DC
Yes / max. 40
4 A / DI, Safety fuse
6 A, Char. B, Circuit breaker
3...5 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
3 A up to 55 °C
3 A @ 55 °C, 2.25 A @ 70 °C
3.6 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
5 A up to 55 °C
5 A @ 55 °C, 3.75 A @ 70 °C
6 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
> 87 % @ 230 V AC & 3 A
4 W / 9.5 W
< 1 mA
> 0.42 @ 230 V AC / > 0.45 @ 115 V AC
> 100 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 34 / 100 mm / 0.5 kg
> 87 % @ 230 V AC & 5 A
4 W / 15 W
< 1 mA
> 0.47 @ 230 V AC / > 0.56 @ 115 V AC
> 80 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 40 / 100 mm / 0.6 kg
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
3 for L/N/PE
5 (13,14,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0.6
6
6
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
3 for L/N/PE
6 (13,14,+,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0.6
6
6
Type
PRO ECO 72W 24V 3A
Type
PRO ECO 120W 24V 5A
Qty.
1
Order No.
1469470000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
Qty.
1
Order No.
1469480000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
A.5
Switch-mode power supplies
connectPower PROeco
PRO ECO 240W 24V 10A
PROeco
PRO ECO 480W 24V 20A
A
L (+)
N (–)
AC
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
L (+)
N (–)
AC
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering data
Note
A.6
mm²
mm²
min/max
Nm
mm
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
1.23 A @ 230 V AC / 2.47 A @ 110 V AC
1.18 A @ 370 V DC / 2.4 A @ 120 V DC
Yes / max. 15 A
4 A / DI, Safety fuse
10 A, Char. B, Circuit breaker
3...4 A, Char. C, Circuit breaker
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
2.37 A @ 230 V AC / 5.2 A @ 110 V AC
1.55 A @ 370 V DC / 4.65 A @ 120 V DC
Yes / max. 3 A
6 A / DI, Safety fuse
16 A, Char. B, Circuit breaker
6…8 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
10 A up to 55 °C
10 A @ 55 °C, 7.5 A @ 70 °C
12 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
20 A up to 55 °C
20 A @ 55 °C, 15 A @ 70 °C
24 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
> 90 % @ 230 V AC & 10 A
3 W / 24 W
< 1 mA
> 0.93 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 5
125 / 60 / 100 mm / 1 kg
> 91 % @ 230 V AC & 20 A
5 W / 43 W
< 1 mA
> 0.97 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 3
125 / 100 / 120 mm / 1.6 kg
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
3 for L/N/PE
6 (13,14,+,+, - -)
0.5/6
0.5/6
0.5/2.5
0.5/2.5
26/12
26/12
0.5/0.6
0.5/0..6
6
6
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
3 for L/N/PE
7 (13,14,+,+, - ,-,-)
0.5/6
0.18/6
0.5/2.5
0.5/2.5
26/12
26/10
0.5/0.6
0.5/0.6
6
7
Type
PRO ECO 240W 24V 10A
Type
PRO ECO 480W 24V 20A
Qty.
1
Order No.
1469490000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
Qty.
1
Order No.
1469510000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
1460790000 – 2014/2015
Switch-mode power supplies
connectPower PROeco
PRO ECO 960W 24V 40A
PROeco
A
L (+)
N (–)
AC
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering data
Note
1460790000 – 2014/2015
100 … 240 V AC
85 … 264 V AC (Derating @ 100 V AC)
47 … 63 Hz
80 … 370 DC (Derating @ 120 V DC)
4.6 A @ 230 V AC / 9.9 A @ 110 V AC
2.9 A @ 370 V DC / 9 A @ 120 V DC
Yes / max. 3 A
16 A / DI, Safety fuse
20 A, Char. B, Circuit breaker
16 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
40 A up to 50 °C
40 A @ 50 °C, 24 A @ 70 °C
48 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
> 93 % @ 230 V AC & 40 A
6 W / 76 W
< 1 mA
> 0.97 @ 230 V AC / > 0.99 @ 115 V AC
> 20 ms @ 230 V AC / > 20 ms @ 115 V AC
yes, max. 3
125 / 160 / 120 mm / 2.9 kg
mm²
mm²
min/max
Nm
mm
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
3 for L/N/PE
7 (13,14,+,+,+, - -)
0.18/6
0.5/16
0.5/2.5
2.5/10
26/10
22/8
0.5/0.6
1.2/1.5
7
12
Type
PRO ECO 960W 24V 40A
Qty.
1
Order No.
1469520000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
A.7
Switch-mode power supplies
connectPower PROeco
PRO ECO3 120W 24V 5A
PROeco
PRO ECO3 240W 24V 10A
A
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering data
Note
A.8
mm²
mm²
min/max
Nm
mm
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance with UL 508)
0.3 A @ 3 x 500 V AC / 0.4 A @ 3 x 400 V AC
0.2 A @ 800 V DC / 0.4 A @ 450 V DC
Yes / max. 40 A
2 A / DI, Safety fuse
2...3 A, Char. C, Circuit breaker
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance with UL 508)
0.6 A @ 3 x 500 V AC / 0.8 A @ 3 x 400 V AC
0.4 A @ 800 V DC / 0.7 A @ 450 V DC
Yes / max. 50 A
2 A / DI, Safety fuse
2...3 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
5 A up to 55 °C
5 A @ 55 °C, 3.75 A @ 70 °C
6 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
10 A up to 55 °C
10 A @ 55 °C, 7.5 A @ 70 °C
12 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
87 % @ 3 x 500 V AC / 88 % @ 3 x 400 V AC
6 W / 13 W
< 1 mA
> 0.4 @ 3 x 500 V AC / > 0.45 @ 3 x 400 V AC
> 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 5
125 / 40 / 100 mm / 0.6 kg
88 % @ 3 x 500 V AC / 89 % @ 3 x 400 V AC
8 W / 26 W
< 0.5 mA
> 0.45 @ 3 x 500 V AC / > 0.5 @ 3 x 400 V AC
> 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 5
125 / 60 / 100 mm / 1 kg
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
6 (13,14,+,+, - -)
0.18/6
0.5/6
0.5/2.5
0.5/2.5
26/10
26/12
0.5/0.6
0.5/0.6
8
6
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
6 (13,14,+,+, - -)
0.18/6
0.5/6
0.5/2.5
0.5/2.5
26/10
26/12
0.5/0.6
0.5/0.6
7
6
Type
PRO ECO3 120W 24V 5A
Type
PRO ECO3 240W 24V 10A
Qty.
1
Order No.
1469530000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
Qty.
1
Order No.
1469540000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
1460790000 – 2014/2015
PRO ECO3 480W 24V 20A
PROeco
Switch-mode power supplies
connectPower PROeco
PRO ECO3 960W 24V 40A
A
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
L1 (+)
L2 (–)
AC
L3
PE
+
+
–
–
–
13
14
DC
Pay attention to polarity of DC connection
Technical data
Input
Rated input voltage
AC input voltage range
AC frequency range
DC input voltage range
AC current consumption
DC current consumption
Input fuse (internal) / inrush current
Recommended back-up fuse
Output
Rated output voltage
Output voltage
Ramp-up time / residual ripple, switching peaks
Rated output current @ Urated
Continuous output current @ 24 V DC
Power boost @ 24 V DC, 60 °C
Capacitive load
Protection against reverse voltages from the load
Protection against internal surge voltage
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
On/Off relay
General data
Efficiency
Power loss @ idling / nominal load
Earth discharge current
Power factor (approx.)
Mains buffering @ Irated
Parallel connection option
Height x width x depth / weight
Approvals
Approvals
Connection data
Conductor connection system
Number of terminals
Wire cross-section, rigid min/max
Wire cross-section, flexible min/max
Wire cross-section, AWG/kcmil
Min./max. tightening torque range
Stripping length
Note
Ordering data
Note
1460790000 – 2014/2015
mm²
mm²
min/max
Nm
mm
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance with UL 508)
1.2 A @ 3 x 500 V AC / 1.5 A @ 3 x 400 V AC
0.7 A @ 800 V DC / 1.2 A @ 450 V DC
Yes / max. 50 A
4 A / DI, Safety fuse
3...5 A, Char. C, Circuit breaker
3 x 400...3 x 500 V AC (Wide-range input)
3 x 340...3 x 575 V AC / 2 x 360...2 x 575 V AC
47...63 Hz
450...800 V DC (max. 500 V DC in accordance with UL 508)
2.15 A @ 3 x 500 V AC / 2.68 A @ 3 x 400 V AC
1.37 A @ 800 V DC / 2.37 A @ 450 V DC
Yes / max. 40 A
6 A / DI, Safety fuse
10 A, Char. B, Circuit breaker
6...8 A, Char. C, Circuit breaker
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
20 A up to 55 °C
20 A @ 55 °C, 15 A @ 70 °C
24 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
24 V DC ± 1 %
22...28 V DC (adjustable via potentiometer on front)
< 100 ms / < 50 mVSS @ 24 V DC, IR
40 A up to 50 °C
40 A @ 50 °C, 24 A @ 70 °C
48 A for 1 min, ED = 5 %
Unrestricted
30…35 V DC
35 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
LED Green (Uoutput > 21.6 V DC)
LED Yellow (Ioutput > 90 % IR )
LED Red (Overload, overtemperature, short-circuit, Uoutput < 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC
8 W / 48 W
< 0.5 mA
> 0.41 @ 3 x 500 V AC / > 0.43 @ 3 x 400 V AC
> 30 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 3
125 / 100 / 120 mm / 1.3 kg
90 % @ 3 x 500 V AC / 91 % @ 3 x 400 V AC
5 W / 95 W
< 1 mA
> 0.56 @ 3 x 500 V AC / > 0.56 @ 3 x 400 V AC
> 25 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V AC
yes, max. 3
125 / 160 / 120 mm / 2.5 kg
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
7 (13,14,+,+, - ,-,-)
0.18/6
0.18/6
0.5/2.5
0.5/2.5
26/10
26/10
0.5/0.6
0.5/0.6
7
7
CE, TÜV (EN/IEC 60950-1), cULus (Pending)
Input
Output
Screw connection
Screw connection
4 for L1/L2/L3/PE
7 (13,14,+,+, - ,-,-)
0.18/6
0.5/16
0.5/2.5
2.5/10
26/10
22/8
0.5/0.6
1.2/1.5
7
12
Type
PRO ECO3 480W 24V 20A
Type
PRO ECO3 960W 24V 40A
Qty.
1
Order No.
1469550000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
Qty.
1
Order No.
1469560000
The internal varistor found in a switch-mode power unit does not replace
the necessary surge protection in a system.
A.9
Switch-mode power supplies
connectPower PROeco
connectPower PROeco diode module
CP DM 10
CP DM 20
A
+V
E1
E2
–V
–V
DC
E1 E2 –V
-V
+V
-V
+
+V –V
DC
–
E1
E2
-V
E1
E2
-V
Technical data
Input
Input voltage
Input current
Output
Output voltage
Output current
General data
Ambient temperature (operational)
Storage temperature
Degree of efficiency at max. load
Mounting position, installation notice
Installation advice
Weight
Approvals
Dimensions
Clamping range (nominal / min. / max.)
Depth x width x height
Note
mm²
mm
40 V DC max.
2 x 0...10 A max.
40 V DC max.
2 x 0...20 A max.
Uin - 0.5 V typical
0...20 A max. or 10 A max. for redundancy operation
Uin - 0.5 V typical
0...40 A max. or 20 A max. for redundant operations
-10 °C...+55 °C
-20 °C...+85 °C
95.5%
horizontally, on terminal rail TS 35
Space: side ≥ 2 cm; above/below ≥ 10 cm
0.4 kg
CE; cULus; cURus
-10 °C...+55 °C
-20 °C...+85 °C
97.5%
horizontally, on terminal rail TS 35
Space: side ≥ 2 cm; above/below ≥ 10 cm
0.4 kg
CE; cULus; cURus
Input
4 / 0.13 / 6
110 / 55.5 / 125
Input
4 / 0.13 / 6
110 / 55.5 / 125
Output
4 / 0.13 / 6
110 / 55.5 / 125
Output
10 / 0.32 / 16
110 / 55.5 / 125
Ordering data
Screw connection
Type
CP DM 10
Qty.
1
Order No.
8710620000
Type
CP DM 20
Qty.
1
Order No.
8768650000
Note
Accessories
Note
A.10
1460790000 – 2014/2015
Small metal foot
Type
MTA 30 MF
Large metal foot
Order No.
1251320000
Small wall mounting
Type
CP A WALLADAPTER 30 MM
Small plastic foot
Type
MTA 45 MF
Order No.
1251310000
Type
MTA 30 BK
Switch-mode power supplies
PROeco - Accessories
Large plastic foot
Order No.
1168970000
Type
MTA 45 BK
Order No.
1962250000
A
Large wall mounting
Order No.
1461870000
Type
CP A WALLADAPTER 45 MM
Order No.
1461850000
Small screwdriver
Type
SDIK PH1
SDIS 0.5X3.0X100
Blade type
Size/AF
1.00
B
a
b
0.5
3
c
80
100
Order No.
9008570000
9008380000
End bracket
Markers
For DIN rail TS 35
Type
SM 18/9.5 K MC NE WS
1460790000 – 2014/2015
Colour
white
Qty.
200
Order No.
1248580000
Polyamide with fibre glass, screwable
WEW 35/1 SW
Colour
black
Torque
1.2 Nm
Qty.
50
Order No.
1162600000