AC Power For Business-Critical Continuity Liebert NX UPS User Manual–10-30kVA, 400V, 50/60Hz TABLE OF CONTENTS 1.0 SINGLE MODULE UPS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3.1 1.3.2 1.3.3 1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4.1 1.4.2 1.4.3 1.4.4 1.4.5 1.4.6 1.4.7 1.4.8 1.5 Rectifier and Bypass Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 External Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Cable Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Control Cables and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1.7.1 1.8 5 5 5 6 6 6 6 6 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.6.1 1.7 System Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 to 30kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Moving the Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Floor Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.5.1 1.5.2 1.5.3 1.6 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 External Battery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Monitor Board Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.8.1 1.8.2 1.8.3 1.8.4 1.8.5 1.8.6 1.8.7 Input Dry Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance Bypass Cabinet Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Circuit-Breaker Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Emergency Power Off Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Bypass Switch Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Start Facility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 12 13 14 15 16 16 2.0 BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.3 Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 2.3.7 2.3.8 2.3.9 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit Isolator Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Temperature Sensor (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Moving the Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Arrangement Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i 19 19 19 19 19 20 20 20 21 2.4 Battery Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 2.4.1 2.4.2 2.4.3 2.4.4 Connection Principles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fitting the Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Room Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 25 25 25 2.5 Battery Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.0 UPS MULTI-MODULE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 3.2 Paralleled UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 3.2.1 3.2.2 3.2.3 3.2.4 3.3 27 28 28 29 Hot-Standby UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3.3.1 3.3.2 3.3.3 3.4 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 External Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Dual Bus System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Extended Dual Bus Synchronization Option (DBS Interface Box) . . . . . . . . . . . . . . . . . . . . . 31 31 31 32 32 4.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.2 Features of NX Multi-Module UPS Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Requirements for Paralleling of UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 5.3.6 5.3.7 5.3.8 5.3.9 5.4 39 40 40 41 41 Multi Module UPS—1+N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 5.2.1 5.2.2 5.3 Split-Bypass Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Static Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Temperature Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Redundant Control Power Supply Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Socket Outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Mode (Stored Energy Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auto-Restart Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance Mode (Manual Bypass) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ECO Mode (Single UPS Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parallel Redundancy Mode (System Expansion) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hot-Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 42 42 43 43 43 43 43 43 Battery Management—Set During Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 5.4.1 5.4.2 Normal Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Advanced Functions (Software Settings Performed by the Commissioning Engineer) . . . . . 44 ii 5.5 Battery Protection (settings by commissioning engineer) . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 6.0 OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 6.1.1 6.2 Power Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 6.2.1 6.2.2 Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Verify Switching Between Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 6.3 Switching the UPS from Normal to Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 6.4 Powering Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 6.5 Powering Down the UPS and Maintaining Power to Load . . . . . . . . . . . . . . . . . . . . . . . . . . 49 6.6 Emergency Shutdown With EPO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 6.7 Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 6.8 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions . . . . . . . . . . 50 6.9 Language Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 6.10 Changing the Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 6.11 Command Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 6.12 Isolating One Module in a Multi-Module System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 6.13 Inserting One Module into a Multi-Module System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 7.0 OPERATOR CONTROL PANEL AND DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 Mimic Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Audible Alarm (Buzzer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Direct Access Push Buttons (Keys) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LCD Monitor and Menu keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Detailed Description of Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 55 56 56 58 7.2 All Status and Event Messages Displayed on the UPS Front Panel. . . . . . . . . . . . . . . . . . . 60 7.3 Prompt (Pop-Up) Windows. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 7.4 Dynamic Energy Flow Chart and UPS Help Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 7.5 Default Screen Saver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 8.0 OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 8.1 Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 8.1.1 8.1.2 8.1.3 8.1.4 8.1.5 8.2 Battery Ground Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Redundant Fan for Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OC Web Card - SNMP/HTTP Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Multiport-4 Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 67 68 69 69 OC485 Web Card – Modbus, Jbus, IGM Net . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 8.2.1 8.2.2 Remote Alarm Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Dust Filter for 10-30kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 9.0 TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 9.1 Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 iii FIGURES Figure i Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi Residual current circuit breakers (RCCB) symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Auxiliary terminal block detail monitoring board (U2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Jumper connection for BCB interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Output dry contacts and EPO wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Battery start for UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Single temperature sensor and monitor board-U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Battery cabinet bottom cable entry location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Battery cabinet with fuse or optional circuit breaker locations . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Battery cabinet internal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Battery cabinet, bottom entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Battery room design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Emergency power off connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Typical 1+N system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Dry contacts, multiple UPS modules with distribution panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Connection of 1+N system parallel control cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Hot standby configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Typical dual bus system configuration with static transfer switch and Load Bus Synch . . . . . . 31 Connections of a typical dual bus system utilising Load Bus Synch . . . . . . . . . . . . . . . . . . . . . . . 32 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 General arrangement—10-30kVA UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 10-30kVA NX front view with doors open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Location of parallel logic board M3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Internal battery layout and connecting—GP12120 F2 (12AH/12V) . . . . . . . . . . . . . . . . . . . . . . . 37 Internal battery layout and connecting—LC-R127R2PG1 (7.2AH/12V) . . . . . . . . . . . . . . . . . . . . 37 Internal battery layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Single unit block diagram with split-bypass input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Multiple battery temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 1+N multi-module UPS with external maintenance bypass switch . . . . . . . . . . . . . . . . . . . . . . . 41 Example of configuration for single UPS with external maintenance bypass cabinet. . . . . . . . . 49 UPS control and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Graphic LCD monitor windows and keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Help screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Battery ground fault detection set connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Redundant power module fan set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Communication bays and cable location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 OC Web Card data summary window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 OC Web Card battery data summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 SiteNet MultiPort4 Intellislot pin configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 OC485 Web card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Dust filter replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 iv TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Table 10 Table 11 Table 12 Table 13 Table 14 Table 15 Table 16 Table 17 Table 18 Table 19 Table 20 Table 21 Table 22 Table 23 Table 24 Table 25 Table 26 Table 27 Table 28 Table 29 Table 30 Table 31 Table 32 Table 33 Table 34 Table 35 Table 36 Maximum steady state AC and DC currents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Distance from floor to connection point on the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Input dry contacts at X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Maintenance bypass cabinet interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 External circuit-breaker interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Output dry contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 EPO input contact relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Dimensions and weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 UPS operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Rotary switch configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 UPS control and display panel components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Rectifier indicator—1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Battery indicator—2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Bypass indicator—3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Inverter indicator—4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Load indicator—5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Status (Alarm) indicator—6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Audible alarm key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Menu key Icons and their meaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 UPS system window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Descriptions of UPS menus and data window items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 UPS messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Prompt windows, meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Dry contact fault alarm signal is available for remote monitoring . . . . . . . . . . . . . . . . . . . . . . . . 66 Relay Card pin configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Relay card jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 SiteNet MultiPort4 Intellislot pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 NX communication options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Compliance with European, international standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Environmental characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Overall efficiency, heat losses and air exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Mechanical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Rectifier AC input (mains) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Inverter output to critical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Bypass mains input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 v Figure i Model number nomenclature NXe 0 A0 010 U Feature Set for Region Input & Output Voltage A0 - EMEA B0 - Aust/NZ 50/60Hz Voltage Output kVA C0 - Japan Revision to Base Unit D0 - China 010 E0 - Latin Amer 015 F0 - Other 020 Code 220/380 F 230/400 U 240/415 G NX Product Line UPS Single Module Liebert NXe UPS module ratings: 10, 15, 20, 30kVA (with internal battery) Example: NXE0A0010U = 10kVA module for Europe and Middle East, 400V/230V output Options Battery cabinet Model Identification NXE0NBCS Battery Ground Fault detection kit NXA0UFXBGF Battery temperature probe (for external battery) NXA0UFXBTS Maintenance bypass cabinet (separate bypass input) NXE0NMBX Fan Redundancy kit NXE0UFXRF Seismic Anchor kit NXA0UFXSAN Dual bus control cable 05-10-15 metres NXA0UFXD Parallel control cable kit 05-10-15 metres NXA0UFXP Relay Card (On Bat, Bat Low, On Byp, Sum, UPS Fail) MultiPort4 (4 sets On Bat, bat Low) Web browser/TCPIP/SNMP Card Jbus/Modbus Card RELAYCARD-INT MULTIPORT 4 OCWEB-LB OC485CARD RAM - Remote Alarm Monitor NXA0CFXRAM Modem card NXA0CFXMOD Extended LBS box NXA0UFXLBS Air Filter NXA0UFXARF Dual Bus Extension Kit 50-150 Meters Individual Battery Monitoring Note NXXXXMLBSKIT BDS 40 or BDS 256 vi Specify total system kVA Specify UPS kVA rating Specify length in metres These are Intellislot plug-in cards (3 slots available). Requires RELAYCARD-INT One filter (XXX: 050 or 150) - Specify length in meters. Used for extension in length or dual bus arrangement between Nx and non-Nx sources' Specify number of blocks. Consult Emerson Network Power representatives for complete configuration SAFETY PRECAUTIONS This manual contains information concerning the installation and operation of this Emerson Network Power Liebert NX™ Uninterruptible Power System (UPS). This manual should be read before commencing installation. The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or agent). Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty. The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for use in life support applications. This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential environment, this product may nevertheless cause radio interference, in which case, the user may be required to take additional measures. Conformity and Standards This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Australia and New Zealand EMC Framework (C-Tick) and with the following product standards for Uninterruptible Power System (UPS). • EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area • EN / IEC / AS 62040-2—EMC requirements; Class A compliant • EN / IEC / AS 62040-3—Performance requirements and test methods For more details, see 9.0 - Technical Specifications Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only. ! WARNING High Leakage Current EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY. Earth leakage current exceeds 3.5 mA and is less than 860 mA. Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (class A) and insensitive to transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice. ! WARNING Back-Feed Protection Notice This UPS is fitted with a voltage-free contact closure signal for use with an external automatic disconnect device (supplied by others) to protect against back-feeding voltage into the bypass input. If this signal is not used by the installer, a label must be added at the external bypass input disconnect device to warn service personnel that the circuit is connected to a UPS. The text to use is the following or equivalent: ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT. 1 User-Serviceable Parts All equipment maintenance and servicing procedures involving internal access requires the use of a tool and should be carried out only by trained personnel. There are no user-serviceable parts behind covers requiring a tool for removal. This UPS is fully compliant with safety regulations for equipment located in an operator accessible area. Hazardous voltage is present within the UPS and battery enclosure but out of reach of non-service personnel. Contact with hazardous voltage is minimized by housing live parts behind safety panels that require a tool for their removal. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures. Battery Voltage Exceeds 400VDC All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel. ! WARNING Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal. Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities. 2 Single Module UPS Installation 1.0 SINGLE MODULE UPS INSTALLATION 1.1 Introduction This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NX uninterruptible power supply and related equipment. This chapter is a guide as to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures. ! WARNING Professional Installation Required Do not apply electrical power to the UPS equipment before being authorised to do so by the commissioning engineer. The UPS equipment shall be installed by a qualified electrical tradesperson in accordance with the information contained in this manual. All equipment not referred to this manual is shipped with details of its own mechanical and electrical installation. NOTE Three-phase, 4-wire input supply required. The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on the input and refer to the relative IT Systems’ standard ! WARNING Battery Hazards Special care should be taken when working with the batteries associated with this equipment. When connected together, the battery terminal voltage will exceed 400VDC and is hazardous. Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all other metal objects. Use only tools with insulated handles. Wear rubber gloves. If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations. If electrolyte comes into contact with the skin, the affected area should be washed immediately with water. 1.2 Preliminary Checks Before installing the UPS, please carry out the following preliminary checks: 1. Visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any damage to the shipper immediately. 2. Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the UPS. 3 Single Module UPS Installation 1.3 Location 1.3.1 UPS Room The UPS and its internal battery is intended for indoor installation and should be located in an environment with clean air and with adequate ventilation to keep the ambient temperature within the specified operating range (see Table 30). All models in the Liebert NX UPS range are air-cooled with the aid of internal fans. Cold air enters through ventilation grilles at the front of the cabinet and hot air is released through the grilles at the back. Do not cover the ventilation openings. If necessary to avoid room temperature build-up, install a system of room extractor fans. Optional air filters are available if the UPS is to operate in a dusty environment. The UPS heat dissipation detailed in Table 31 can be used as a guide for air conditioning sizing, depending on the selected mode of operation: • Normal Mode (VFI SS 111 Double Conversion UPS) • ECO Mode (VFD SS 311 Stand By UPS) If in doubt use Normal Mode figures. NOTE The UPS is suitable for mounting on concrete or other non-combustible surface only. 1.3.2 External Battery Room Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical battery manufacturer performance data are quoted for an operating temperature between 20 and 25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this range will reduce the battery capacity. In a normal installation the battery temperature is maintained between 15°C and 25°C (59 and 77°F). Keep batteries away from main heat sources or main air inlets etc. Where the batteries are located externally to the main UPS cabinet, a battery protection device (e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible. 1.3.3 Storage Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Table 30). ! CAUTION An unused battery must be recharged periodically per battery manufacturer recommendation. Temporarily connecting the UPS to a suitable AC supply mains and activating it for the time required for recharging the batteries can achieve this. 4 Single Module UPS Installation 1.4 Positioning The cabinet is mounted on four castor-wheels for ease of positioning and for short distance movement. Jacking feet are provided to prevent the UPS from moving once it has been wheeled to its final position. For optimal design life, the place chosen must offer: • • • • • • • • Easy connection Enough space to easily work on the UPS Sufficient air exchange of enough to dispel heat produced by UPS Protection against atmospheric agents Protection against excessive humidity and very high heat sources Protection against dust Compliance with the current fire prevention requirements Operating environment temperature between 20°C and 25°C (68 and 77°F). The batteries are at maximum efficiency in this temperature range (see Table 30). The UPS cabinet is constructed around a steel chassis with removable panels. The top and side panels are secured to the chassis by screws. Access to the power terminals, auxiliary terminals blocks and power switches is from the front. Operational status and alarm information is provided through the front door operator control panel. Models 30kVA and below house both the power components and an internal battery. Cooling air enters the front of the NX and is exhausted out the rear. 1.4.1 System Cabinets A UPS may comprise a number of cabinets, depending on the design requirements (e.g., UPS cabinet, external battery cabinet, external bypass cabinet). In general, all the Liebert cabinets used in a particular installation are of the same height and designed to be positioned side-by-side to form a matching array. Refer to 4.0 - Installation Drawings for assistance on positioning the cabinets described below. 1.4.2 10 to 30kVA UPS The UPS consist of a single cabinet, which uses typically forty (40) 12V battery blocks, fitted internally and connected in series to provide a nominal battery voltage. The UPS may be shipped without the batteries fitted. An extended battery option is available. This comprises a separate cabinet containing additional batteries that can be connected to the UPS to increase its battery run time. 1.4.3 Moving the Cabinets ! WARNING Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity. The UPS is fitted with casters. Take care to prevent the NX from moving when unbolting the unit from its shipping pallet. Ensure that adequate personnel and lifting aids are available when removing the shipping pallet. Ensure that the UPS weight is within the designated surface weight loading of any handling equipment. See Table 32. UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means of a forklift or similar equipment. The UPS cabinet also can be moved short distances by its casters. NOTE Care must be taken when maneuvering units fitted with batteries. Keep such moves to a minimum. 5 Single Module UPS Installation 1.4.4 Clearances The Liebert NX has no ventilation grilles at either side of the UPS. To enable routine tightening of power terminations within the UPS, in addition to meeting any local regulations, Liebert recommends providing adequate clearance in the front of the equipment for unimpeded passage of personnel with the doors fully opened. It is important to leave of 150mm (5.9") clearance behind the UPS to permit adequate circulation of air coming out of the unit. 1.4.5 Access The component layout of the UPS supports front and top access while servicing, diagnosing and repairing the UPS, thus reducing the space requirement for side and rear access. 1.4.6 Final Positioning The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning. ! WARNING Casters are strong enough for movement across even surfaces only. Caster failure could occur if they are subjected to shock loading. When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS will remain stationary and stable. 1.4.7 Floor Anchoring Diagrams in 4.0 - Installation Drawings show the location of the holes in the base plate through which the equipment may be bolted to the floor. If the equipment is to be installed on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view Figure 21 to design this pedestal. 1.4.8 Cable Entry Cables can enter the Liebert NX UPS and battery cabinet from below. Cable entry is made possible by removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole. 1.5 External Protective Devices Circuit breakers or other protective devices must be installed in the AC supply, external to the UPS. This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed. 1.5.1 Rectifier and Bypass Input Overcurrent protection must be installed at the distribution panel of the incoming main supply. The protection must discriminate with the power cables current capacity and with the overload capacity of the system (see Table 35). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2 trip curve C (normal) for 125% of the current listed in Table 1 is suitable. Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for the bypass in the incoming mains distribution panel. NOTE Rectifier and bypass input sources must be referenced to the same neutral potential. NOTE For IT power systems, four-pole protective devices must be used, external to the UPS, both upstream of the input distribution panel and downstream (toward the load). 6 Single Module UPS Installation Earth Leakage (RCD): Any residual current detector (RCD) installed upstream of the UPS input supply must be: • sensitive to DC unidirectional pulses (Class A) • insensitive to transient current pulses, and • must have an average sensitivity, adjustable between 0.3 and 1A. Figure 1 Residual current circuit breakers (RCCB) symbols To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input or when used in paralleled UPS configurations, must be located upstream of the common neutral sinking point. Alternatively, the device must monitor the combined four-wire rectifier and splitbypass input currents. The residual earth current introduced by the RFI suppression filter inside the UPS is greater than 3.5mA and less than 860mA. Liebert recommends verifying the selectivity with all other differential devices both upstream of the input distribution board and downstream (toward the load). 1.5.2 External Battery The UPS and its associated batteries are protected against overcurrents through a DC compatible disconnect device. 1.5.3 UPS Output Any external distribution board used for load distribution shall be fitted with protective devices that discriminate with those used at the bypass input to the UPS and with the UPS overload characteristics (see Table 35). 7 Single Module UPS Installation 1.6 Power Cables The cable design must comply with the voltages and currents provided in this section, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media). For cable entry terminal, refer to Figure 22. ! WARNING Before starting the UPS, ensure that you are aware of the location and operation of the external isolators that connect the ups input/bypass supply to the mains distribution panel. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. ! Table 1 WARNING Failure to follow adequate earthing procedures may result in electromagnetic interference or in hazards involving electric shock and fire. Maximum steady state AC and DC currents Nominal Current, Amps Input Mains Current With Full Battery Recharge 3ph + N Busbar Stud Size 1,2 Output Current2 at Full Load 3ph + N Input/Output/ Bypass Cables UPS Rating (kVA) 380V 400V 415V 380V 400V 415V Battery at End of Discharge 10 22 21 20 15 14 13 22 15 33 32 31 22 21 20 33 20 44 43 42 30 29 28 44 30 63 62 61 45 44 42 66 Bolt Hole Dia. (mm) External battery Cables (Bolts) Torque Load (Nm) M6 6 M6 5 1. Input mains current listed for common rectifier and bypass AC input. For split input the rectifier current is 94% of the currents listed. 2. Non-linear loads (switch mode power supplies) affect the design of the output and bypass neutral cables. The current circulating in the neutral cable may exceed the nominal phase current. A typical value is 1.5 In. 3. Protective earth cable: Connect each cabinet to the main ground system must follow the most direct route possible. The earth conductor shall be sized in accordance with the AC supply fault rating, cable lengths and type of protection. Typical cross sectional areas are 2.5mm2 (10kVA), 6mm2 (15kVA), 10mm2 (20kVA), 16mm2 (30kVA), as per AS / IEC 60950-1 4. When sizing battery cables, a maximum volt drop of 4 VDC is permissible at the current ratings given in Table 1. The load equipment is generally connected to a distribution board containing individually protected busbars rather than connected directly to the UPS output. The output cables from paralleled units to the parallel distribution bus should be of same length so as to optimise the sharing of current. Do not form coils, so as to minimise the formation of electromagnetic interference. 5. For terminal location – refer to 4.0 - Installation Drawings) Table 2 Distance from floor to connection point on the equipment UPS Minimum Distance mm (in.) Rectifier A.C. Input supply 284 (11-1/5) Bypass A.C. Input supply 284 (11-1/5) UPS Output A.C. 369 (14-1/2) Battery Power 369 (14-1/2) Auxiliary cables: Monitor board (U2) 1104 (43-1/2) 8 Single Module UPS Installation 1.6.1 Cable Termination NOTE The operations described in this section must be performed by authorised electricians or qualified technical personnel. If you have any difficulties, do not hesitate to contact our Customer Service and Support Department. See the back page of this manual for contact information. Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure. Refer to the appropriate cable connection drawing in 4.0 - Installation Drawings. 1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. 2. Open the door to the UPS cabinet and remove the front protective cover to gain access to the connections bars. 3. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar located on the floor of the equipment below the power connections. All cabinets in the UPS must be connected to the user’s ground connection. NOTE The earthing and neutral bonding arrangement must be in accordance with local and national codes of practice. Identify and make power connections for incoming cables according to one of the two procedures below, depending on the type of installation. Common Input Connections 4. For common bypass and rectifier inputs, connect the AC input supply cables between the mains distribution panel and the UPS input (mA-mB-mC-N terminals) and tighten the connections to 5Nm (M6 Bolt). Ensure correct phase rotation. Split-Bypass Connections 5. If a split-bypass configuration is used, connect the AC input supply cables to the rectifier input busbars (mA-mB-mC-N terminals) and the AC bypass supply cables to the bypass input (bA-bB-bC-N terminals) and tighten the connections to 5 Nm (M6 Bolt). Ensure correct phase rotation. NOTE For split-bypass operation, ensure that the linking busbars between bypass and rectifier input are removed. The AC input and the AC bypass supplies must be referenced to the same neutral point. Frequency Converter Mode If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars (U1-V1-W1-N terminals) to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm (M10 bolt). Ensure correct phase rotation and tighten the connections. There will not be any AC bypass supply cables to the bypass input (U3-V3-W3-N terminals). NOTE For frequency converter operation, ensure that the linking busbars between bypass and rectifier input are removed. 9 Single Module UPS Installation Output System Connections 6. Connect the system output cables between the UPS output (oA-oB-oC-N terminals) and the critical load and tighten the connections to 5 Nm (M6 Bolt). Ensure correct phase rotation. ! WARNING If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their ends. Internal UPS Battery Connection 7. The battery consists of a series string connection of 5 x 8 (or 10) x 12V 6-cell battery blocks. a. Ensure that the 8 (or 10) battery blocks in each tier (tray) are interconnected. b. Connect the positive, neutral and negative cables to the UPS terminals. c. Plug in the cables between the tiers. d. Ensure correct polarity battery string series connections (i.e., intertier and interblock connections are from positive to negative terminals. ! WARNING Hazardous Battery Terminal Voltage 480VDC Ensure correct polarity of string end connections to the UPS terminals, i.e., positive to positive, negative to negative and neutral to neutral, but leave these UPS terminal cables disconnected until connection is authorised by the commissioning engineer. Ensure correct polarity of string end connections to the battery circuit breaker and from the battery circuit breaker to the UPS terminals, i.e., positive to positive and negative to negative, but disconnect one or more battery cell links in each tier. Do not reconnect these links and do not close the battery circuit breaker before authorised by the commissioning engineer. 8. Refit all protective covers removed for cable installation. 10 Single Module UPS Installation 1.7 Control Cables and Communication 1.7.1 Monitor Board Features Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. The main features are: • • • • • • • Figure 2 Input and Output dry contacts signal (one pair of contacts of relay) Emergency Power Off control (EPO) Environmental parameter input interface User communication (for data setting and user background monitor) Intellislot™ interface Modem interface Temperature detect interface Auxiliary terminal block detail monitoring board (U2) J8 J3 J1 LCD J22 X7 J23 X6 J12 J9 J2 J15 PWR Modem SNMP Card J16 J17 Intellislot 2 J13 J21 J25 J28 J4 J26 J30 J10 Intellislot 1 X4 J24 Intellislot 3 BFP INV X1 ACF EPO X2 Dry In MBC BCB X3 11 The black square ( ) on each slot indicates Pin 1. X4 X5 Single Module UPS Installation 1.8 Dry Contacts The UPS provides input dry contacts and output dry contacts. 1.8.1 Input Dry Contacts There are several input dry contacts at the X3 slot. Figure 3 Input dry contacts 12V 12V 12V 12V X3 DRV FB GND OL FUSE F_FAN J10 T_OT AUX_O T_IT AUX_I J30 12V GND ENV BtG J26 GEN 12V J4 X3 Ancillary Control and Alarms X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, push-in terminal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS when connection between the relevant terminal and the +12V terminal is altered. Cables connected to X3 IN DRY must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5 to 1mm2 cross-section area for maximum runs between 25 and 50 meters (82-164 ft), respectively. Table 3 Input dry contacts at X3 Position Name J4.1 ENV3 J4.2 BtG J4.3 GEN1,2 J4.4 +12V Description Battery Room Alarm (NC) Battery Ground Fault Detection (NC) On Generator (NO) +12V Power 1 - Must be configured by configuration software before becoming active. 2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off. 1.8.2 Maintenance Bypass Cabinet Interface J26 and J30 are the MBC interface. Table 4 Maintenance bypass cabinet interface Position Name Description J26.1 T_IT1 Input transformer overtemperature (NC) J26.2 AUX_I Reserved J26.3 +12V +12V Power J26.4 GND Power Ground J30.1 FUSE Reserved J30.2 F_FAN Fan Fail Alarm (NC) J30.3 T_OT1 Output Transformer Overtemperature (NC) J30.4 AUX_O Reserved 1 - Must be configured by software before becoming active NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively. 12 Single Module UPS Installation 1.8.3 External Circuit-Breaker Interface J10 is the interface to any external battery circuit breaker (BCB). External circuit-breaker interface Table 5 Position Name Description J10.1 DRV BCB Driver Signal - (reserved) J10.2 FB BCB Contact State -(reserved) J10.3 GND J10.4 OL Power Ground BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.) NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively. Jumper connection for BCB interface UPS Monitoring Board OL J10 GND FB DRV Figure 4 Aux – N.O. Aux – N.O. Battery Circuit Breaker 13 Single Module UPS Installation 1.8.4 Output Dry Contacts There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6) Figure 5 Output dry contacts and EPO wiring +12V Table 6 X2 ACF_O J28 ACF_S ACF_C J25 INV_O INV_C BFP_O J21 BFP_S BFP_C J13 INV_S X1 EPO - NO EPO - NC Output dry contact relays Position Name Description J13.2 BFP_O Bypass feedback protection relay; normally open; closed when bypass SCR is shorted J13.3 BFP_S Bypass feedback protection relay center J13.4 BFP_C Bypass feedback protection relay; normally closed; open when bypass SCR is shorted J21.2 INV_O Inverter mode relay; normally open; closed when UPS is in inverter mode J21.3 INV_S Inverter mode relay center J21.4 INV_C Inverter mode relay; normally closed. Opened when UPS is in inverter mode J25.2 ACF_O Main input fault relay; normally open. Closed when main input is in fault J25.3 ACF_S Main input fault relay center J25.4 ACF_C Main input fault relay; normally closed. Open when main input is in fault NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively. 14 Single Module UPS Installation 1.8.5 Emergency Power Off Input The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield. The X2 slot, shown in Figure 5, is the remote EPO input interface. The EPO has an NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1 If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable (see Figure 5 and Table 7). If this function is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed. Table 7 EPO input contact relays Position Name Description J28.1 EPO_NC EPO activated when opened to J28.2 J28.2 EPO_NC EPO activated when opened to J28.1 J28.3 EPO_NO EPO activated when shorted to J28.4 J28.4 EPO_NO EPO activated when shorted to J28.3 NOTE The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated. NOTE Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor board and must remain installed if using NC contacts. NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2 (16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively. X5: Auxiliary DC Power Output Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA. X6: Analog Input Interface Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%. • • • • X6 pin 1: Not used X6 pin 2: +12V X6 pin 3: ENV-T – environment temperature detection X6 pin 4: GND X7: External Battery Temperature Detector Interface Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see Figure 7). Pin reference: • • • • X7 pin 1: Not used X7 pin 2: +12V (Power supply for Temperature Monitoring Probe) X7 pin 3: BAT-T (Battery Temperature signal) X7 pin 4: GND 15 Single Module UPS Installation Serial Ports RS232-1 and RS232-2 RS232-1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and server shutdown software. RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel. These serial ports are shared with the optional Web browser, SNMP, ModBus and relay cards. Refer to Table 28 regarding compatibility of simultaneous use. Intellislot Web Browser, SNMP, ModBus and Relay Cards Interface There are three interface slots available for optional Web browser, SNMP, ModBus and Relay cards as illustrated in 8.0 - Options—For Assembly Inside the UPS Cabinet. 1.8.6 External Bypass Switch Interlock EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used) Provides external maintenance bypass interlock protection for the UPS. Short circuit means external bypass closed. EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Provides external output interlock protection for paralleled UPS modules. Short circuit means external output switch closed. NOTE UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS front door – removal of this barrier requires the use of a tool and is restricted to service personnel. NOTE Jumper JP1 (located next to X3) needs to be removed for X3:3&4 to work properly. 1.8.7 Battery Start Facility 1. Rotate the switch to Normal Mode. 2. Verify that the batteries are connected. 3. Press Battery Start Button. The LCD begins to show startup screens. The rectifier indicator flashes green while the rectifier is starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters the normal operation state. 4. After UPS has initialized, press Inverter On Figure 6 Battery start for UPS Battery Start Button 16 Battery Installation 2.0 BATTERY INSTALLATION 2.1 Introduction The UPS battery bank consists of battery blocks connected in series to provide a D.C. string voltage as required by the UPS converter. The 'AUTONOMY TIME' (the time during which the battery can maintain supply to the load in the event of a mains failure) is limited by the ampere-hour capacity of the battery blocks and in some cases this results in several strings being connected in parallel. The NX usually has internal batteries, but longer run time is available by using an external battery cabinet. The battery cabinet will be supplied in one of the following forms: 1. 2. Complete installation, comprising the battery cabinet, batteries and protective device. Battery cabinets and protective device only—batteries supplied by others NOTE 10kVA to 30kVA UPS models contain an internal battery compartment that can accommodate up to 44 blocks of batteries for 12Ah/12V; 80 blocks of batteries for 7.2Ah/12V The battery bank may be disconnected from the UPS for maintenance or service. 17 Battery Installation 2.2 Safety Special care should be taken when working with the batteries associated with the Liebert NX UPS system. When all the cells are connected together, the battery terminal voltage is potentially hazardous. The battery installation must be segregated from all but appropriately qualified maintenance personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery room. When the batteries require maintenance, these precautions must be taken: • The rotary switch must be turned to Maint. position. • The input circuit breaker (CB1) must be opened. • The ANDERSON connector must be disconnected.. NOTE The fuse on the battery EMI board (UHA241A2-10kkVA, UHK241A2-15/20kVA, UHS242A2-30kVA) is 600VDC/30A, High Speed Fuse. NOTE Full safety instructions concerning the use and maintenance of UPS batteries are provided in the appropriate battery manufacturers manuals. The battery safety information contained in this section relates to key considerations that must be taken into account during the installation design process and might affect the design outcome depending on localised conditions. ! WARNING Hazardous battery voltage present behind covers No user-serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. When using internal batteries in 10 to 30kVA units, the batteries are always connected through power fuses to the UPS and to the segregated terminal bars available for connection to an external battery. Isolate any internal battery connections before attempting to access the segregated terminal bars available for connection to an external battery. The following general battery safety precautions and warnings should be observed at all times: • A battery can present risk of electric shock or burn from high- short-circuit currents. • The full nominal string voltage, when the battery blocks are interconnected, is 480VDC, which is hazardous • Only qualified personnel should install or service batteries. • Eye protection should be worn to prevent injury from electrical arcs. • Remove rings, watches, necklaces, bracelets and all other metal objects. • Use only tools with insulated handles. • Wear rubber gloves and a rubber apron when handling batteries. • If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container resistant to sulfuric acid and disposed of in accordance with local regulations. • If electrolyte comes into contact with the skin the affected area should be washed immediately with plenty of clean water. • Batteries must always be disposed of according to local environmental laws. • When replacing batteries, use the same number and type that were originally fitted. • Disconnect charging source before connecting or disconnecting battery terminals. • Determine whether the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. 18 Battery Installation 2.3 Battery Cabinet 2.3.1 Introduction This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommodation required by the larger cells associated with system’s having a long autonomy time. Where two (or more) cabinets are used they are positioned alongside each other and secured and bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two units are bolted together. 2.3.2 Temperature Considerations Valve-regulated, lead acid battery cells are sensitive to ambient temperature and should be operated between 15°C and 25°C (59-77°F). Battery capacity is increased by 1% for every 1°C (2°F) increase in temperature up to 25°C (77°F). Battery life is reduced at temperatures above 25°C (77°F). When batteries are mounted in the same room as the UPS unit, it is the battery that dictates the designed maximum ambient temperature, not the UPS. — i.e. in the case of valve-regulated cells, the ambient room temperature should be kept between 15°C and 25°C (59-77°F), and not between 0°C and 40°C (32-104°F) (which is the specified main equipment operating temperature range). Temperature deviations are permissible for short periods, provided the average temperature does not exceed 25°C (77°F). 2.3.3 Dimensions The external dimensions are shown in Table 8. These are the same height and depth as the UPS module and provide a matching appearance when bolted together. All cabinets are fitted with doors, which must be fully opened in order to fit or remove the batteries. The door swing must therefore be taken into consideration when planning the positioning of the cabinets. 2.3.4 Weight The unladen weight is shown below in Table 8. When designing the battery installation the weight of the batteries and cables must be added to the unladen weight. This is particularly important when placing the NX on a raised floor. Table 8 Dimensions and weight Model Optional Circuit Breaker Amperes Maximum Discharge Current (at EOD) External Cabinet WxDxH mm (in) 50A 10kVA 22A 15kVA 33A 20kVA 44A 820x700x1400 (32-1/4x27-5/8x55) Battery Cabinet 80A 2.3.5 Cabinet Weight Without Batteries kg (lb) 170 (375) 30kVA 66A Circuit Isolator Features The UPS is fitted with Anderson connectors and fuses for connection and disconnection of internal batteries. External battery banks require battery fuses or circuit breaker (with optional status contacts). Refer to 1.8.3 - External Circuit-Breaker Interface for details. 19 Battery Installation 2.3.6 Battery Temperature Sensor (Optional) The optional external battery temperature sensor kit contains one probe and one temperature transport board as illustrated in Figure 7. It is connected to the UPS Monitor Board. Figure 7 Single temperature sensor and monitor board-U2 Name: W2 L=5m Temperature Sensor Name: W1 L=30m X7 NC 12V OUT GND + IN TMP-2 Monitor Board – U2 -12V BAT-T GND UPS Cable W2 is packed with the temperature sensor. 2.3.7 Moving the Battery Cabinets ! WARNING Ensure any lifting equipment used in moving the cabinet has sufficient lifting capacity. Ensure that the weight is within the designated surface weight loading of any handling equipment. See Table 8 for weight details. Battery cabinets can be handled by means of a fork lift or similar equipment. NOTE Care must be taken when maneuvering units fitted with batteries. Keep such moves to a minimum. When the equipment has been finally positioned ensure the adjustable feet are set so that the battery cabinet will remain stationary and stable. Seismic anchors option is available for anchoring the unit to a concrete floor. 2.3.8 Cable Entry Cables enter the battery cabinet from the bottom. Cable entry is made possible by removing a blanking piece fitted at the bottom to reveal the cable entry hole. 20 Battery Installation 2.3.9 General Arrangement Drawings Refer to Figures 8 and 10 for general arrangement of battery cabinet models. Figure 8 Battery cabinet bottom cable entry location Bottom View 700 250 82,5 100 83 1400 620 828 All dimensions are expressed in millimeters. 21 Battery Installation Figure 9 Battery cabinet with fuse or optional circuit breaker locations Bottom cable entry 22 Battery Installation Figure 10 Battery cabinet internal layout Positions of captive nuts for grille mounting 292 328,4 102 Minimum service space 65mm B 65 29 280 280 280 280 65 Captive nut M6 43 215 1. 3 Layers: Largest battery dimensions: 201x170x190 (LxWxH) 170 10 170 5 218 201 10 201 5 15 635 201 10 201 10 201 1 Layer: Largest battery dimensions: 201x170x190 (LxWxH) 368 7 635 170 10 170 10 170 10 170 308,6 218,5 437,8 280 65 15 738 All measurements are in millimeters. AMNXE0NBCSL4BT 23 Detail B Hex flange screw M6x16 Battery Installation Figure 11 Battery cabinet, bottom entry 12 11 13 4 6 1 7 8 4 6 13 12 8 9 5 AMNXE0NBCSL4BT 2 Item # Item Name 1 Grille steel 2 Grille steel 3 Middle pillar 10 3 4 Cover module BC Small NXe 5 Ground bus 6 Captive nut M4 7 Captive nut M6 8 Screw flange M6x16 9 Nut flange M6 10 Screw M6x16 countersink 11 Spring washer M4 12 Flat washer M4 13 Screw mushroom head cross M4x12 2.4 Battery Power Cables 2.4.1 Connection Principles The following notes, in conjunction with the diagrams, illustrate the broad principles to be followed when fitting and connecting the majority of battery installations. 24 Battery Installation 2.4.2 Fitting the Batteries 1. In general, at least 10mm (3/8") must be left unobstructed on all vertical sides of the battery blocks to permit free air movement around the cells. 2. Clearance should be allowed between the top of the cells and the underside of the shelf above (this is necessary for monitoring and servicing the cells). 3. When installing the batteries on racks always work from the bottom shelf upwards to prevent raising the centre of gravity. 2.4.3 Connecting the Battery 1. When the battery cabinet is installed on a raised floor the battery power cables and optional circuit breaker control cables can be routed to the UPS cabinet via the floor of the cabinet. If the UPS and battery cabinet are located adjacent to each other and located on a solid floor these cables can be passed between the cabinets via the lifting apertures located in the lower sides of the cabinets. 2. In general it is recommended that the inter-connecting cables be fitted to the batteries within their particular level before fitting the inter-level connecting cables, followed finally by the cables to the circuit breaker. 3. An insulating shroud should be fitted to each terminal after its connection has been made. 4. When connecting the cables between the battery string ends to the optional circuit breaker always connect the circuit breaker end of the cable first. 2.4.4 Battery Room Design Whatever the type of mounting system selected, the following conditions should be noted: • Cell Layout—1 Whichever battery mounting system is used, the batteries should be arranged to prevent the possibility of simultaneous contact with two exposed live parts having a potential greater an 150V. Where this is not possible, insulated terminal shields must be installed and insulated cables must be used for connections. • Service Platform—2 The service platform (or duckboard) must be slip-proof, insulated from the floor and at least one metre (39 in.) wide. • Connections—3 All connections must be as short as possible. • Battery Protection Fuses/Circuit Breaker—4 The battery circuit breaker is generally installed at the front of the battery room. See 2.5 - Battery Control for details on connecting the circuit breaker box available for the Liebert NX. Figure 12 Battery room design 4 1 3 2 2.5 Battery Control Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB, the Battery Temperature sensor and the battery as shown in Figure 7. Cables connected to X3 BCB must contain a protective earth wire or a shield, be segregated from power circuits, double insulated and of a typical 0.5 to 1mm2 cross section area for maximum runs between 25 and 50 meters respectively. The shield should be connected to the protective earth of the battery cabinet or battery breaker, not at the UPS 25 UPS Multi-Module Installation 3.0 UPS MULTI-MODULE INSTALLATION 3.1 General The installation of a multi-module UPS configuration must follow the installation procedure for a single UPS module with the additional requirements detailed in this chapter. In addition to the local EPO push button on the front panel of the UPS module (that stops operation of that module), the UPS supports also a remote emergency stop to permit simultaneous multi-module shutdown. NOTES 1. The remote emergency power off switch must be voltage-free and Normally Open or Normally Closed. 2. The open voltage supplied is 12VDC, < 20mA 3. This external emergency stop may be supplied with a second set of contacts that can be used to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with remote trip units. 4. Normally Closed EPO - X2: 1&2, these terminals are supplied factory-linked on the monitor board. Figure 13 Emergency power off connections UPS2 X2:3 X2:4 X2:3 X2:4 Monitor Board Monitor Board UPS1 EPO UPS2 X2:1 X2:2 X2:1 X2:2 Monitor Board UPS1 EPO 26 Monitor Board UPS Multi-Module Installation 3.2 Paralleled UPS Modules The basic installation procedure of a parallel system comprising two or more UPS modules is the same as that of single module system. The following sections only introduce the installation procedures specific to the parallel system. 3.2.1 Cabinet Installation Place the UPS modules side by side and interconnect as shown in Figure 14. The distribution panel (external bypass cabinet) is optional but recommended for ease of maintenance and system testing. Figure 14 Typical 1+N system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel SUPPLIED BY OTHERS INPUT MAINS INPUT MAINS SUPPLY L1, L2, L3, N UPS1 SUPPLY L1, L2, L3, N CB1 UPS2 RECTIFER CB1 RECTIFER SW1-C FUSES SW1-C FUSES STATIC SWITCH STATIC SWITCH CHARGER CHARGER BATTERY 2 BATTERY 1 INVERTER INVERTER SW1-D SW1-A SW1-A L1, L2, L3, N L1, L2, L3, N Q2EXT Q1EXT QUPS Distribution Cabinet TO LOAD 27 QBYP UPS Multi-Module Installation Figure 15 Dry contacts, multiple UPS modules with distribution panel Input Distribution UPS 1 UPS 2 UPS N M3 Board X3 M3 Board X3 M3 Board X3 Ext. Maint. Ext. Out Ext. Maint. Ext. Out Ext. Maint. Ext. Out 1 2 3 4 1 2 3 4 1 2 3 4 Q1Ext Q2Ext Distribution Panel QUPS QnExt QByp To Load 3.2.2 External Protective Devices Refer to the instructions in 1.0 - Single Module UPS Installation. 3.2.3 Power Cables The wiring of power cables is similar to that of single module system. The Bypass and the Main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Module UPS Installation. NOTE The length and specification of power cables including the bypass input cables and UPS output cables should be the same. This facilitates load sharing when operating in bypass mode. 28 UPS Multi-Module Installation 3.2.4 Control Cables Intermodule Control Shielded and double insulated control cables available in lengths of 5, 10 and 15 meters must be must be interconnected in a ring configuration between UPS modules as shown below. The parallel control board is mounted on the top, behind protective cover of each UPS module (refer to Figure 23). The ring configuration ensures high reliability of the control. Refer to Figure 16. Figure 16 Connection of 1+N system parallel control cables 3.3 Hot-Standby UPS Modules 3.3.1 Cabinet Installation X1-2 X1-2 X1-1 X2-1 P1 X2-2 P2 P1 P2 X1-1 X2-1 X1-2 P4 X1-1 X2-2 X4 P3 X1-2 X2-1 P1 P2 P2 X1-1 X2-2 Parallel Board X3 P5 X4 P4 X1-2 X4 X2-1 6 Parallel Board X3 P5 P3 X1-1 X2-2 5 Parallel Board X3 P5 P3 X1-2 X2-1 4 X4 P3 P2 P1 X2-2 P3 P3 X1-1 X2-1 P4 P2 X2-2 X4 P1 X4 Parallel Board X3 P5 P1 Parallel Board X3 P5 P4 Parallel Board X3 P5 UPS 3 P4 2 P4 1 Place the UPS modules side by side and interconnect as shown below. The hot standby mode comprises two series connected UPS modules of the same rating. One module is designated as the hot standby master (downstream), and the other module is designated as the hot standby slave (upstream). Their roles are determined by power connection and configuration software. In normal operation, both slave and master operate in normal mode and the output from one upstream (slave) UPS feeds the bypass input to the other (downstream/master) UPS. The output of the downstream (master) UPS is connected to the critical load and is always synchronised to the output of the upstream (slave) UPS. If the inverter of the UPS connected to the load fails, the inverter of the upstream (slave) UPS supplies the load through the downstream (master) UPS bypass circuit. The system can be programmed to cycle the downstream (master) UPS between normal mode and bypass mode so that both ups are equally exercised. NOTE If it is a hot-standby system, the master (downstream) must be turned on first. 3.3.2 External Protective Devices Refer to the instructions in 1.0 - Single Module UPS Installation. 29 UPS Multi-Module Installation 3.3.3 Power Cables The wiring of power cables is similar to that of single module system except that the output of the upstream UPS is fed into the bypass input of the downstream UPS, and the load is fed by the downstream UPS through its inverter or bypass. The bypass and the main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Module UPS Installation. No control wires other than those specified for the single module configuration are required. Figure 17 Hot standby configuration INPUT DISTRIBUTION UPSTREAM DOWNSTREAM Bypass L1, L2, L3, N Mains L1, L2, L3, N Bypass L1, L2, L3, N Mains L1, L2, L3, N CB1 CB1 RECTIFIER STATIC SWITCH INVERTER L1, L2, L3, N L1, L2, L3, N UPS1 OUTPUT TO LOAD 30 UPS Multi-Module Installation 3.4 Dual Bus System 3.4.1 Cabinet Installation The Dual Bus System consists of two independent UPS configurations each consisting of one or more UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple input terminals. For single input loads an optional Static Transfer Switch may be added and the standard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate installation instructions for each system. Place the UPS modules side by side and interconnect as shown below. The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS systems (or parallel systems) in synchronization. One system is designated as the master; the other is designated as the slave. The operating modes covered comprise master and or slave operating inverter or bypass mode. Figure 18 Typical dual bus system configuration with static transfer switch and Load Bus Synch Bypass supply Bypass supply Input Rectifier UPS 6 Input Rectifier UPS1 Intermodule control cable Input Rectifier LBS Input Rectifier UPS 6 UPS1 Intermodule control cable STS Load 3.4.2 External Protective Devices Refer to the instructions supplied in 1.0 - Single Module UPS Installation. 3.4.3 Power Cables The wiring of power cables is similar to that of single module system. The Bypass and the Main input sources must be referenced to the same neutral potential and input earth leakage monitoring devices, if installed, must be located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Module UPS Installation 31 UPS Multi-Module Installation 3.4.4 Control Wires For Liebert NX to NX dual bus configuration, interconnect the optional DBS cable between any DBS ports of two parallel systems as illustrated in Figure 19. Figure 19 Connections of a typical dual bus system utilising Load Bus Synch UPS 8 X1-2 X2-1 P1 X2-2 X1-1 X1-2 P4 X1-1 X1-2 X2-1 P2 P2 P1 X2-2 X4 P3 DBS Cable P4 X1-1 P3 P4 X1-2 X2-1 Parallel Board X3 P5 X4 P1 X2-2 P2 X2-1 P1 P2 P3 X1-1 X4 P4 X4 X2-2 Parallel Board X3 P5 Parallel Board X3 P5 P3 Parallel Board X3 P5 UPS 8 Parallel System I A Parallel System II B NOTE Example shown with ring control cables ("8") for DSB applied to two 1+1 paralleled systems. 3.4.5 Extended Dual Bus Synchronization Option (DBS Interface Box) For Liebert NX to non- NX (whether another Liebert UPS range or not) dual bus configuration, one DBS interface box shall be mounted on the non- Liebert NX UPS. In this situation, the other UPS system is always treated as a master and the following conditions are covered: • Master and slave are both on inverter • Master on bypass, slave on inverter NOTE Extended DBS interface box is also used for extending DBS cable length up to 150 meters (490ft) for DBS configuration between two groups of NX UPS systems. 32 Installation Drawings 4.0 INSTALLATION DRAWINGS Figure 20 Electrical connections Earth UPS To Customer’s Safety Earth A X3 Ext. Maint. B Parallel Board C Ext. Out To Critical Load N Power Cables A B X5 X4 ModemSNMP Main/Bypass Input Supply N RS-485 J4 Gen J13 BPS J21 AFC J25 X2 Ext EPO Input X3 J26 MBC J28-1 J28-2 J28-3 J28-4 BCB J30 X3 External Battery X7 J10-1 J10-2 J10-4 J10-3 J22-2 J22-3 J22-4 X1 C Monitor Board + N Batt 33 Installation Drawings Figure 21 General arrangement—10-30kVA UPS module 600 700 10mm dia threaded mounting holes 2 7 86.5 1400 1 Leve Detail A, rear of unit shown without side panel Leveling feet 90 LEFT SIDE VIEW FRONT VIEW 420 180 3 5 4 867.5 708 572 6 1380 166 210 236 346 520 625 BOTTOM VIEW TOP VIEW All dimensions are in mm. 34 1) Air inlet grille 2) Air outlet grille 3) Adjustable fixing feet 4) Castors for maneuvering 5) Seismic anchors (option) 6) Cable entry 7) Operator control and display panel Installation Drawings Figure 22 10-30kVA NX front view with doors open 1) Main/Bypass Input terminal (T1) 2) Battery /Output terminal (T2) 3) Input circuit breaker (CB1) 4) Rotary switch (SW1) 5) Monitor board (U2) 5 4 3 2 1 T2 External Battery Input Output T1 Main Input Bypass Input 35 Installation Drawings Figure 23 Location of parallel logic board M3 Battery Start Interface Parallel Logic Board NXe 10-30kVA Top View 36 Installation Drawings Figure 24 Internal battery layout and connecting—GP12120 F2 (12AH/12V) BOTTOM LAYER Layer 5 Layer 4 43 W501 4pcs Layer 3 TOP LAYER Layer 1 Layer 2 41 44 42 W500 34Pcs 77 55 33 1 1 W503 BLK W502 W511 BLK W510 W515 BLK W514 W513 BLK W512 W506 W506 BLU W504 A A BLK W508 RED W508 W509 W505 J2 J4 J6 NIN +BATT IN BATTERY INTERCONNECT WIRING DIAGRAM W507 NOTE -BATT IN 1. TYPICAL USED FOR:GP 12120 F2 (12AH/12V) 2. REMOVE 43&44 WHEN 42 JARS ARE USED. REMOVE 41~44 WHEN 40 JARS ARE USED. A2 BOARD UPS MODULE Figure 25 Internal battery layout and connecting—LC-R127R2PG1 (7.2AH/12V) BOTTOM LAYER Layer 5 Layer 4 Layer 3 W520 W501 4Pcs TOP LAYER Layer 1 Layer 2 W517 W500 68Pcs W514 W513 BLK W512 W506 BLU W506 BLK A A W504 RED W508 W508 W509 W505 J2 +BATT IN W507 J4 J6 NIN BATTERY INTERCONNECT WIRING DIAGRAM -BATT IN A2 BOARD UPS MODULE NOTE 37 1 TYPICAL USED FOR: LC-R127R2PG1 (7.2AH/12V) RED BLK W521 11 M M W515 K K W510 E E BLK BLU I W511 I W502 W519 33 RED BLK BLK W503 5 5 BLK W518 77 C C BLU G G W516 Installation Drawings Figure 26 Internal battery layout 347mm 151mm 562mm 160mm 160mm 160mm 160mm Battery 136mm 38 Operation 5.0 OPERATION ! WARNING Hazardous Mains and / or Battery Voltage present behind covers. No user-serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. 5.1 Introduction Liebert’s NX™ Uninterruptible Power System system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The NX UPS supplies power that is free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags. The NX utilizes the latest in high frequency, double-conversion pulse width modulation (PWM) technology and fully digital controls to enhance its reliability and increase the ease of use. The standard NX consists of the UPS and internal batteries in a compact, single cabinet. As shown in Figure 27, the AC utility source is input at CB1 and the rectifier converts the AC utility into DC power. The inverter converts that DC power from the utility—or DC power from the batteries —into AC power for the load. The batteries power the load through the inverter in the event of a power failure. The utility source can also power the load through the static bypass. If maintenance or repair of the UPS is necessary, the load can be switched without interruption in service to the maintenance bypass. Figure 27 Single unit block diagram with split-bypass input SW1/D Maintenance Bypass Static Swich Bypass Input SW1/C UPS Output AC Utility Input SW1/A CB1 Rectifier Neutral Wire Discharge Inverter Static Swich SW1/B Battery Charger Neutral Wire Battery 5.1.1 Split-Bypass Input Figure 27 illustrates the Liebert NX UPS in what is known as the split-bypass configuration wherein a separate power switch to a dedicated bypass power source that also feeds the maintenance bypass line connects the static bypass line. Where a separate power source is not available, the bypass and rectifier input supply connections are linked. 39 Operation 5.1.2 Static Transfer Switch The circuit blocks labeled Static Switch in Figure 27 contain electronically controlled switching circuits that enable the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. During normal system operation the load is connected to the inverter; but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static bypass line. To provide a clean (no-break) load transfer between the inverter output and static bypass line, the static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window. A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance. NOTE When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is not protected from power failures or surges and sags. 5.1.3 Battery Temperature Compensation For 10-30kVA UPS with internal batteries, a standard temperature probe is installed to measure the internal battery temperature to optimize battery management. The measured temperature can be displayed from the UPS front panel. For UPS with external batteries, an optional battery temperature interface equally optimises the external battery management by connecting up to four external temperature sensors from the battery cabinet(s) to a control unit inside the UPS. Figure 28 Multiple battery temperature sensors Temperature Sensor X103 NC 12V OUT GND + IN TMP-2 Temperature Sensor X104 NC 12V OUT GND + IN TMP-2 X108 +12V OUT GND Temperature Sensor X105 NC 12V OUT GND + IN - BCB Control Board – C2 X106 NC 12V OUT GND + IN TMP-2 BCB Box 40 Monitor Board – U2 -12V BAT-T GND UPS TMP-2 Temperature Sensor X7 Operation 5.1.4 Redundant Control Power Supply Board The UPS is equipped with two identical and fully redundant control power supply boards. Each of them takes inputs from the AC and DC sources. When one of the sources or even if one of the control power boards fails, the UPS system can still operate normally. This feature further enhances the reliability of the system. 5.1.5 Socket Outlet One single-phase Shuko-type universal outlet of 3A current handling capability provides nominal UPS output voltage of up to 3A current capacity for the ease of testing, commissioning & servicing of the UPS. 5.2 Multi Module UPS—1+N Multi-module UPS are formed by several “single unit” UPS modules to constitute “1+N”system where groups of one or more, up to six, single units operate together for the purpose of providing additional power or reliability or both. The load is equally shared between any paralleled UPS. Figure 29 1+N multi-module UPS with external maintenance bypass switch Qin UPS1 Qin UPS2 Qin UPS3 Qin Ext Byp Supplied by Others Input Mains Supply Input Mains Supply L1,L2,L3,N CB1 L1,L2,L3,N Input Mains Supply Bypass Mains Supply L1,L2,L3,N L1,L2,L3,N Bypass Mains Supply L1,L2,L3,N L1,L2,L3,N L1,L2,L3,N CB1 CB1 RECTIFIER RECTIFIER RECTIFIER STATIC SWITCH STATIC SWITCH STATIC SWITCH INVERTER INVERTER INVERTER UPS1 OUTPUT Qout UPS1 Qout all UPS L1,L2,L3,N UPS2 OUTPUT Qout UPS2 Distribution Cabinet UPS3 OUTPUT L1,L2,L3,N Qout UPS3 Qout Byp Further, single unit or 1+N groups may be configured as “distributed redundant” systems with independent outputs that nevertheless are synchronised through a Load Bus Synchroniser (LBS) so that critical loads can be seamlessly transferred from one system to another. See 5.3 - Modes of Operation for more information. 41 Operation 5.2.1 Features of NX Multi-Module UPS Configurations 1. The hardware and firmware of single module UPS units is completely compatible with the requirements of a multi-module system. Multi-module configuration is achieved merely through settings in configuration software. 2. Parallel control cables are connected in a ring, providing both performance and redundancy. Dual-bus control cables are connected between any two UPS modules of each bus. The intelligent paralleling logic provides the user with maximum flexibility. For example, shutting down or starting up UPS modules in a parallel system can be done in any sequence. Transfers between Normal and Bypass modes of operation are synchronised and self –recovering e.g. following overloads and their clearance. 3. The total load of the multi-module system can be queried from each module’s LCD display. 5.2.2 Requirements for Paralleling of UPS Modules A group of paralleled modules behave as if it were one large UPS with the advantage of presenting higher reliability. In order to assure that all modules are equally utilised and to comply with relevant wiring rules, the following requirements apply: 1. All UPS modules must be of the same rating and must be connected to the same bypass source. 2. The bypass and the main input sources must be referenced to the same neutral potential. 3. Any RCD, Residual Current monitoring device, if installed, must be of an appropriate setting and located upstream of the common neutral bonding point. Alternatively, the device must monitor the combined 4-wire rectifier and split-bypass input currents of the system. Refer to the High Leakage Current Warning on page 1. 4. The outputs of all UPS modules must be connected to a common output bus. NOTE Optional isolation transformers are available for applications where sources do not share the same neutral reference or where the neutral is not available. 5.3 Modes of Operation The NX UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these modes: • • • • • • • • • 5.3.1 Normal Mode Battery Mode (Stored Energy Mode) Auto-Restart Mode Bypass Mode Maintenance Mode (Manual Bypass) ECO Mode Parallel Redundancy Mode Hot-Standby Mode Frequency Converter Mode Normal Mode The UPS inverter continuously supplies the critical AC load. The rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or BOOST charging its associated backup battery. 5.3.2 Battery Mode (Stored Energy Mode) Upon failure of the AC mains input power; the inverter, which obtains power from the battery, supplies the critical AC load. There is no interruption in power to the critical load upon failure or restoration of the AC mains input power after which the “Normal Mode” operation will continue without the necessity of user intervention. 5.3.3 Auto-Restart Mode The battery may become exhausted following an extended AC mains failure. The inverter shuts down when the battery reaches the End Of Discharge voltage (EOD). The UPS may be programmed to “Auto Recovery after EOD” after a delay time. This mode and any delay time are programmed by the commissioning engineer. 42 Operation 5.3.4 Bypass Mode If the inverter overload capacity is exceeded, or if the inverter becomes unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter to the bypass source, with no interruption in power to the critical AC load. Should the inverter be asynchronous with the bypass, the static switch will perform a transfer of the load from the inverter to the bypass with interruption in power to critical AC load. This is to avoid paralleling of unsynchronised AC sources. This interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms (60Hz). 5.3.5 Maintenance Mode (Manual Bypass) A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable e.g. during a maintenance procedure. This manual bypass switch is fitted in all UPS modules and rated for full load of one module. 5.3.6 ECO Mode (Single UPS Only) IF ECO mode is selected, the double-conversion UPS operation is inhibited at most times for the purpose of saving energy. In this mode of operation, not unlike UPS of line-interactive or stand-by technology, the bypass is the preferred source and only when the voltage and / or frequency of the bypass supply are beyond pre-defined and adjustable limits the critical AC load is transferred to the inverter. This transfer takes place with an interruption of less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms (60Hz). 5.3.7 Parallel Redundancy Mode (System Expansion) For higher capacity or higher reliability or both, the outputs of up to six UPS modules can programmed for directly paralleling while a built-in parallel controller in each UPS ensures automatic load sharing. 5.3.8 Hot-Standby Mode This is an alternative 1+1 redundancy application that ensures higher availability or better usage control or both. Two UPS are connected in Hot Stand By mode as follows: UPS 1connects to the critical load, and UPS 2 connects to the bypass of UPS 1. The remaining AC inputs are connected to the incoming AC mains supply. UPS 1 synchronises to the output of the UPS 2 ensuring uninterrupted load transfer from UPS 1 to UPS 2 or vice versa. This ensures that any specified load is supplied by a UPS while still providing a bypass path to cater for overloads. Further, the system can also be programmed to reverse UPS1 between Normal and Bypass Modes so that each UPS is equally utilised. This interval is programmable from 1 to 4,320 hours (180 days). 5.3.9 Frequency Converter Mode The NX UPS can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 40Hz to 70Hz. In this mode the static bypass operation is disabled, and the battery becomes optional depending on any requirement to operate in battery mode (stored energy mode). 43 Operation 5.4 Battery Management—Set During Commissioning 5.4.1 Normal Function • Constant charging current—Current can be set up to limit charging power. • Constant boost voltage boost (if applicable)—Voltage of boost charging can be set as required by the type of battery. For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not exceed 2.4V / cell. • Float Charge—Voltage of float charging can be set as required by the type of battery. For VRLA, float charge voltage should be between 2.2V to 2.3V. • Float Charge Temperature Compensation (optional)—A coefficient of temperature compensation can be as required by the type of battery. • End of discharge protection (EOD)—If the battery voltage is lower than the EOD, the battery converter will shut down and the battery is isolated to avoid further battery discharge. EOD is settable from 1.6V to 1.75V per cell (VRLA) or 0.9 to 1.1 V per cell (NiCd). • Battery Low Warning Time—Settable between 3 and 60 minutes. The default is 5 minutes. 5.4.2 Advanced Functions (Software Settings Performed by the Commissioning Engineer) Battery Self-Test and Self-Service At periodic intervals 20% of the rated capacity of the battery will be discharged automatically. The minimum amount of load must exceed 20% of the nominal rating of the UPS module. If the load is less than 20%, auto-discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The periodic testing can also be inhibited. • Conditions—Battery float charge for at least 5 hours, load 20~100% of rated UPS capacity • Trigger—Manually through through the command of Battery Maintenance Test in the LCD panel or automatically • Battery Self-Test Interval—30-360 days (default setting is 60 days) 5.5 Battery Protection (settings by commissioning engineer) Battery Undervoltage Pre-warning The battery undervoltage pre-warning occurs before the end of discharge. After this pre-warning, the battery should have the capacity for 3 remaining minutes discharging with full load. The time is user configured from 3 to 60 minutes. Battery End of Discharging (EOD) Protection If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is settable from 1.6V to 1.75V per VRLA cell (or 1.0 to 1.1V per NiCd cell). Battery Isolator Open Warning If the battery isolator is open, this warning will occur. The external battery to the UPS through an external battery isolator, which is manually closed and electronically tripped via the UPS control circuits. 44 Operating Procedures 6.0 OPERATING PROCEDURES ! WARNING Hazardous mains and / or battery voltage present behind covers. No user-serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. 6.1 Introduction The NX can operate in any of four modes, as shown in Table 9. This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations. Table 9 UPS operating modes Rotary Switch Position NORMAL Operating Mode Normal Operation On Static Bypass BYPASS or NORMAL On Test TEST On Maintenance Bypass MAINT Description The UPS is powering the load. The load power is supplied through the static bypass line. This may be considered as a temporary mode during load transfers between inverter and maintenance bypass or supply under abnormal operating conditions. No load power is supplied by the UPS. The load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode. The UPS is shut down but the load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode. NOTE 1. The user controls and indicators mentioned in these procedures are identified in 7.0 Operator Control Panel and Display. 2. The audible alarm may sound at various points during these procedures. It can be canceled at any time by pressing the SILENCE ON/OFF push button. NOTE This unit refers to some modes and conditions that are set or adjusted using proprietary service software. To take advantage of all the available features for the NX, the unit must be commissioned by a Liebert factory-trained service engineer. 6.1.1 Power Switches The UPS unit power switches are CB1 and SW1. • CB1-Input Current Breaker. Connects the utility supply to the UPS input. • SW1 - Rotary switch. Has four positions—NORMAL, BYPASS, TEST and MAINT—that correspond to different positions of the SW1-A/B/C/D. The positions of the rotary switch (SW1) are: • SW1-A—Output Isolator. Connects the output of the UPS to the load. • SW1-B—Neutral Isolator. Connects neutral to the UPS. • SW1-C—Bypass Isolator. Connects the UPS with the bypass supply. • SW1-D—Maintenance Bypass Isolator. Permits supply of the load directly by the bypass line for maintenance of the UPS unit. The functions of the rotary switch are shown in Table 10. Table 10 Rotary switch configurations Rotary Switch Position NORMAL BYPASS TEST MAINT OUTPUT (SW1-A) BYPASS (SW1-C) ✔ ✔ ✔ ✔ ✔ MAINT (SW1-D) ✔ ✔ 45 NEUTRAL (SW1-B) ✔ ✔ ✔ Operating Procedures 6.2 UPS Startup The NX must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started. 6.2.1 Start-Up Procedure To start the UPS from a fully powered-down condition: 1. Open the UPS door to gain access to the main power switches. ! WARNING During this procedure the output terminals will become live. If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the UPS output terminals. ! CAUTION Do not operate the rotary switch too fast. Always wait at least 30 seconds when rotating the switch from one position to another 2. Close CB1. 3. Turn the rotary switch to TEST. The bypass static SCR (M2) closes automatically and the LCD begins to show start-up screens. The rectifier indicator flashes green while the rectifier is starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters the normal operation state. After initialization, the bypass static switch closes. Because output switch SW1-A is still open, the UPS channels power through Maintenance Bypass Supply line (SW1-D). The bypass indicator extinguishes, provided that the bypass is normal. The UPS mimic display indicators will be: Indicator Rectifier indicator State Off Battery indicator Off Bypass indicator Off Inverter indicator Off Load indicator Off Status indicator Off ! WARNING Do NOT turn the rotary switch until the rectifier indicator stops flashing green. 4. Turn the rotary switch to BYPASS. Indicator State Rectifier indicator Green Battery indicator Off Bypass indicator Green Inverter indicator Off Load indicator Green Status indicator Amber The maintenance switch SW1-D opens and output switch SW1-A closes. The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the rotary switch ensures uninterrupted output. 46 Operating Procedures 5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds. The inverter will start and the inverter indicator will flash green. After the inverter is ready, the UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load indicators turn on. The UPS is operating normally. The UPS mimic display indicators will: 6.2.2 Indicator State Rectifier indicator Green Battery indicator Off Bypass indicator Off Inverter indicator Green Output indicator Green Status indicator Green Verify Switching Between Operation Modes Switch from normal mode to battery mode • Open CB1 to enter battery mode. This breaks the utility connection to the NX. To return to normal mode, wait a few seconds and close CB1. The rectifier will restart automatically after 10 seconds and resume feeding power to the inverter. Switch from Normal Mode to Bypass Mode • Press INVERTER OFF button to switch to bypass mode. NOTE In bypass mode, the load is being powered by the utility and is not receiving conditioned power through the inverter. Switch from Bypass Mode to Normal Mode • Turn the rotary switch to NORMAL. • In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will switch to normal mode. 47 Operating Procedures 6.3 Switching the UPS from Normal to Maintenance Bypass Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS. ! CAUTION Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load. This procedure assumes that UPS is operating normally. 1. Press the INVERTER OFF button on the right side of the operator control panel for longer than 2 seconds. The Inverter indicator will turn off and the status indicator (6) will turn amber and an audible alarm will sound. The load will transfer to static bypass and the inverter will shut off. NOTE Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified. 2. Open the UPS door to gain access to the main power switches, SW1 and CB1. 3. Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to load. 4. Turn the rotary switch to TEST. The load is now on maintenance bypass. 5. Turn the rotary switch to MAINT. 6. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual maintenance bypass. ! WARNING ! WARNING ! 6.4 Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers. Even with the UPS rotary switch in maintenance bypass position portions of the unit are still energized. Service is to be performed by qualified personnel only. CAUTION The load equipment is not protected from normal supply aberrations when operating in the maintenance bypass mode. Powering Down the UPS To power down the UPS completely, follow the procedures in 6.3 - Switching the UPS from Normal to Maintenance Bypass. To completely isolate the UPS from the AC supplies, the main external power input isolator (both isolators, where separate supplies are provided for rectifier and bypass) should be opened (see Figure 30). ! WARNING To prevent injury to personnel, lockout or tagout the service supplies. 48 Operating Procedures 6.5 Powering Down the UPS and Maintaining Power to Load NOTE An external Maintenance Bypass Cabinet must be installed before attempting to perform the following procedure If the UPS needs to be shut down completely while maintaining power to the load, follow these steps: 1. Perform Steps 1 through 5 in 6.3 - Switching the UPS from Normal to Maintenance Bypass. 2. Close the external maintenance bypass rotary switch to Maint position. ! WARNING ! WARNING On the primary input distribution panel, which is often located distant from the UPS area, a label should be posted advising service personnel that the UPS circuit is under maintenance. Wait 5 minutes for the internal DC busbar capacitors to discharge. The UPS is now completely powered down. NOTE The maintenance bypass power switch may be operated at any time while the UPS is powered down to connect the load to the maintenance bypass supply if required The procedure can be performed only after the installation has been completed (which includes the maintenance bypass cabinet), after the system has been placed in operation by authorized personnel. See Figure 30 for more information. Figure 30 Example of configuration for single UPS with external maintenance bypass cabinet. CB1 SW CB2 3P 49 Operating Procedures 6.6 Emergency Shutdown With EPO This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If the input utility is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, the external feeder breaker should be opened. 6.7 Auto Restart When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down. The UPS will automatically restart and enable output power: • After utility power is restored • If “Auto Recovery after EOD Enabling” is enabled • After the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes). If the “Auto Recovery after EOD Enabling” feature is disabled, the user may restart the system manually by pressing “Fault Clear” button. 6.8 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions Once all appropriate measures have been taken to correct the problem indicated by the alarm message appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature, Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc. When the user confirms that the fault is cleared: 1. Press the FAULT CLEAR button to let the system exit the Emergency Off state. 2. Press the INVERTER ON button on the right side of the operator control panel for longer than 2 seconds. NOTE The rectifier will start again, and the bypass will begin to power the load (for units with internal battery contactor installed, the battery contactor will close). The Rectifier indicator flashes while the rectifier is starting up. When the rectifier enters the normal operation state (about 30 seconds), the rectifier indicator turns green. NOTE The rectifier will be turned On automatically when the overtemperature fault disappears at 5 minutes after the disappearance of overtemperature signals. After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely. When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position, the UPS will start up on Bypass. There will be power at the output terminals of the UPS. ! WARNING If the rotary switch is in the Maint. position and input utility is present, there will be power at the output terminals of the UPS. 50 Operating Procedures 6.9 Language Selection The LCD menus and data display are available in 12 languages: Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish.To select a different language than the one being displayed: 1. From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen. 2. Press F2 and F3 (left and right arrows) as needed to select the Language menu. 3. Press F1 (shift) to move the cursor to the data and settings area of the LCD. 4. Use F2 and F3 (up and down) to select the required language. 5. Press the F4 (enter) key to accept the language selection. 6. Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now be displayed in the selected language. 6.10 Changing the Current Date and Time To change the system date and time: 1. From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen. 2. Press F2 and F3 (left and right arrows) as needed to select the Settings menu. 3. Press F1 (shift) to move the cursor to the data and settings area of the LCD. 4. Use F2 and F3 (up and down) to select the Date & Time option, then press F4 (enter). 5. Position the cursor on the row in which the date and time are displayed, then press F4 (enter). 6. Using the F2 and F3 (up and down) keys, enter the current time and date information. 7. Press F4 (enter) to save the settings, then press F1 (ESC) to return to the main menu. 6.11 Command Password Password protection is used to limit the control functions accessible to the operator. The default password is 12345. This password provides access to UPS and battery test functions. 51 Operating Procedures 6.12 Isolating One Module in a Multi-Module System NOTE The Multi-Module system must have at least one UPS module redundant in the system and have an external output breaker installed with interlocking cables connected to the UPS module. The inverter firmware in each UPS in the system must be I140 or greater. 1. With all UPS modules in the system in Normal mode, open the external output isolator. NOTE Opening the external output isolator under these condtions puts the UPS module into Standby mode. This is indicated by a flashing inverter LED and the message “Check UPS output.” An “Inverter asynchronous” alarm is also normal. The remaining UPS modules will remain on line and “Parallel comm fail” will annunciate. 2. Press the UPS EPO to isolate the batteries. 3. Open the UPS door to gain access to the main power switches SW1 and CB1. 4. Turn the rotary switch (SW1) to the Bypass position then continue to rotate to Test. NOTE With the UPS external output breaker open and auxiliary switches closed the UPS control will enable the UPS switch to be rotated through “Bypass” without initiating the remaining on line UPS modules to transfer to Bypass. 5. Open rectifier input breaker CB1. ! WARNING Hazardous Battery Voltage No operator serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. The UPS battery and connecting terminals remains energized at hazardous voltage levels at all times. The battery is located behind protective covers that require a tool for their removal: inside the UPS cabinet, inside a free-standing battery cabinet or on open racks inside a dedicated battery room that may be locked. 52 Operating Procedures 6.13 Inserting One Module into a Multi-Module System This procedure is indicated to reintegrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are open. WARNING ! Mains voltage will be applied to UPS output terminals. No operator serviceable parts are located behind covers that require a tool for their removal. Only qualified service personnel are authorised to remove such covers. 1. Open the UPS door to gain access to the main power switches. 2. Rotate the switch to Test position. The LCD display becomes active. 3. Close the Input breaker CB1 The Rectifier indicator flashes on the UPS mimic panel during the startup of rectifier and becomes steady green once the rectifier reaches normal operation state after about 30s. 4. Close external battery circuit breaker QF1 (where an external battery is used). This breaker is located inside the battery cabinet (if used) or is otherwise adjacent to the battery racks 5. Following battery availability being detected by the UPS, the red battery indicator extinguishes moments after when the battery charger starts operation. 6. Rotate switch to Bypass position 7. Turn the rotary switch to NORMAL. 8. Close external output power isolators. 9. Press the INVERTER ON control button for 2 seconds. The inverter will startup and the inverter indicator will flash while it synchronizes to the load voltage and frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator becomes steady green and the output indicator becomes green. 10. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and the status of the indicators as follows: # LED LED Function Status 1 Rectifier indicator green 2 Battery indicator off 3 Bypass indicator off 4 Inverter indicator green 5 Output indicator green 6 Alarm indicator off The UPS is now operating in NORMAL mode. 53 Operator Control Panel and Display 7.0 OPERATOR CONTROL PANEL AND DISPLAY 7.1 Introduction The operator control panel and display is located on the front door of the UPS. The panel is the access point for operator control and monitoring of all measured parameters, UPS and battery status and of event and alarm logs. Figure 31 UPS control and display panel The operator control panel is divided into three functional areas Mimic Power Flow Chart Graphic LCD monitor with menu keys Direct Access keys 6 3 Status 1 4 Liebert NX 020kVA 3X3 2005-10-22 Single 17:32:20 Normal 8 5 Bypass 2 7 Output L1-N/L2 L1-N/L2 voltage (V) 229.5 L-N current (A) 24.5 Frequency (Hz) 49.97 L-L voltage (V) 397.5 Power Factor 0.99 Rotary SW. normal pos. Manual turn on Normal mode Load L2-N/L3 229.5 24.5 49.97 397.5 1.00 07-07 07-07 07-07 L3-N/L1 229.5 24.5 49.97 397.5 0.99 EPO INVERTER ON INVERTER OFF FAULT CLEAR SILENCE ON /OFF 17:24 17:29 17:30 ? F1 Table 11 F2 F3 F4 HELP UPS control and display panel components Component # Button Function Function 1 Rectifier (Input AC to DC) EPO Emergency Power Off button 2 Battery (DC Back-up) Inverter ON Inverter start button 3 Bypass Input Inverter OFF Inverter shutdown button 4 Inverter (DC to AC) Fault Clear Reset button 5 Load (AC Output) Silence On/Off Audible Alarm Mute 6 UPS Status and Alarm indicator 7 Audible Alarm (Buzzer)_ 8 Emergency Power Off Button cover — F1-F4, Help 54 — — LCD Menu keys — Operator Control Panel and Display 7.1.1 Mimic Power Flow The LEDs mounted on the mimic flow chart represent the various power paths and current UPS operational status. Table 12 Green Rectifier in Normal Operation Flashing Green Input AC Normal, but rectifier not operating Red Rectifier Failed Off Rectifier Not operating, Input AC Not Available or out of normal range Table 13 Battery indicator—2 Green Battery Normal, but discharging and powering the load Flashing Green Battery End of Discharge pre-warning Red Battery abnormal (Failed, Absent or Polarity Reversed) or Battery Converter abnormal (Failed, overcurrent, overtemperature) Off Battery and Converter Normal, Battery charging. Table 14 Bypass indicator—3 Green Load on Bypass power Red Bypass not available, out of normal range or Static bypass switch fault. Off Bypass Normal, load not on bypass Table 15 Inverter indicator—4 Green Inverter Normal and powering the load Flashing Green Inverter ON, starting up, synchronising, or standing by (ECO mode) Red Inverter failed Off Inverter not operating Table 16 Load indicator—5 Green UPS output ON and Normal Red UPS output ON and Overloaded Off UPS output OFF. Table 17 7.1.2 Rectifier indicator—1 Status (Alarm) indicator—6 Green Normal Operation Yellow UPS Warning e.g. AC Input Failure Red UPS fault e.g. Fuse or Hardware failure Audible Alarm (Buzzer) UPS activity is accompanied by the following sounds Table 18 Audible alarm key Single beep Direct Access key acknowledgement One beep per second UPS Warning e.g. AC Input Failure Continuous beep Fault e.g. Fuse or Hardware failure 55 Operator Control Panel and Display 7.1.3 Direct Access Push Buttons (Keys) Emergency Power Off (EPO) Disconnects Power to the Load. Disables rectifier, inverter, static bypass and battery operation. Inverter ON Enables Inverter Operation Inverter OFF Disables Inverter Operation Fault clear Resets blocked UPS functions (subject to any fault being cleared) Silence ON/OFF Toggle type buzzer mute. Any new fault re-enables the buzzer. Press and hold Direct Access key briefly until acknowledged by a single beep. 7.1.4 LCD Monitor and Menu keys The user-friendly and menu-driven 320 x 240 dot graphic LCD monitor displays real time data and at the same time stores 512 historical records that can retrieve for reference and diagnosis. The user can perform commands or easily browse through the input, output, load and battery parameters. For quick reference, the UPS status and any warnings are always highlighted without the need of navigating through the menu. The versions of converter firmware, inverter firmware and internal monitor firmware can also be displayed on the LCD. Menu keys F1 to F4 are used to navigate within the graphic LCD monitor windows. Table 19 Menu key Icons and their meaning Key F1 F2 F3 F4 Help ? Window Type 1 LEFT RIGHT ENTER Next Data Window HELP ESC Window Type 2 Escape UP DOWN Figure 32 Graphic LCD monitor windows and keypad Liebert NX 20kVA 3X3 2005-10-22 Unit #1 Bypass Main A(AB) 220 20.5 50.1 380 0.99 Vphase V Iphase A Freq. Hz Vline V P.F. Input breaker closed Manual turn on UPS in normal mode 17:32:20 Normal Output B(BC) 220 20.5 50.1 380 0.99 C(CA) 220 20.5 50.1 380 0.99 01-12 12:28:16 01-12 12:30:06 01-22 12:30:16 ? F1 F2 F3 56 F4 HELP 1 - UPS System Window 2 - UPS Menu Window 3 - UPS Data Window 4 - Current Record Window 5 - Keypad Window Operator Control Panel and Display The function of keys F1 to F4 is shown by a self-explanatory icon as appropriate for the particular window. As shown in Figure 32 above, pressing F1 moves the cursor (resting in “OUTPUT”) from the UPS Menu Window (2) to current record window (4) where it would first rest in “Input breaker closed’. In a similar manner, pressing F2 would move the cursor from the Output data window to the Bypass data window. The summary menu tree is shown below. Refer to 7.2 - All Status and Event Messages Displayed on the UPS Front Panel for a detailed description of each menu item. Figure 33 Menu tree Mains (input) TX Input * Bypass Output TX Output ** L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor L-N voltage (V) L-L voltage (V) L-N voltage (V) Frequency (Hz) L-L voltage (V) L-N voltage (V) L-N current (A) Frequency (Hz) L-L voltage (V) Power factor L-N voltage (V) L-L voltage (V) Load System Battery Records Sout (kVA) Pout (kW) Qout (kVAR) Loadlevel % Crest factor Sout (kVA) Pout (kW) Qout (kVAR) Single unit, no parallel data Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min. Battery capacity (%) Battery boost charging Battery float charging Battery disconnected (history log) Language Settings Command Version (Choices for display) Display contrast Date format set Date & time Comm1 baud rate Comm2 baud rate Comm3 baud rate Communication address Communication mode Callback times Phone No.1 Phone No.2 Phone No.3 Command password Battery maintenance test Battery capacity test System test Stop testing UPS version UPS model Freshening Charge Stop Freshening Charge * When configured, input transformer voltages are displayed on the front LCD. When not activated, the values are hidden. ** When configured, output transformer voltages are displayed on the front LCD. When not activated, the values are hidden. 57 Operator Control Panel and Display 7.1.5 Detailed Description of Menu Items The description that follows refers to the graphic LCD monitor window shown on Figure 32. UPS System Window: This fixed-pane window displays current time and date and identifies the UPS, its configuration and its status. Table 20 UPS system window Description Explanation Liebert NX UPS family name 2005-10-22 YYYY-MM-DD (see Settings menu for other date formats) 12:30:36 Current Time (24 hr HH:MM:SS format) 30kVA-3x3 30kVA = UPS rated output, 3 x 3 = 3-phase input and output (Configuration) Single = single double-conversion unit ECO = single stand-by unit with double-conversion fall-back Master = master in a 1+1 Hot Stand By system Slave = slave in a 1+1 Hot Stand By system Unit # 1 = of max 6 double-conversion units in a parallel system Single, ECO, Master, Slave or Unit # 1 (Status) Normal, Warning or Fault Normal = UPS operating Normal Warning = System attention required, e.g. AC Input Failure Fault = UPS Fuse or Hardware Failure Menu and Data Window Use the horizontal arrow keys to navigate between any of the selectable menu and data windows. Table 21 Menu Type Mains (input) TX Input Bypass Output TX Output Load Descriptions of UPS menus and data window items Item Type Explanation L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (v Line-line voltage Power factor Power factor L-N voltage (V) Phase voltage L-L voltage (V) Line-line voltage L-N voltage (V) Phase voltage Frequency (Hz) Bypass frequency L-L voltage (A) Line-line voltage L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (V) Line-line voltage Power factor Power factor L-N voltage (V) Phase voltage L-L voltage (V) Line-line voltage Sout (kVA) Sout: Apparent power Pout (kW) Pout: Active power Qout (kVAR) Qout: Reactive power Loadlevel % The percent of the UPS rating load Crest factor Output current Crest Factor 58 Operator Control Panel and Display Table 21 Menu Type System Battery Records Language Settings Command (start/stop battery & system tests) Version Descriptions of UPS menus and data window items (continued) Item Type Explanation Sout (kVA) Sout: Apparent power Pout (kW) Pout: Active power Qout (kVAR) Qout: Reactive power Single unit, no parallel data When configured as a single unit, UPS has only native load, no system load. Battery voltage (V) Battery bus voltage Battery current (A) Battery bus current Battery temperature (°C) Internal battery temperature °C Remain Time Min. Battery run time remaining Battery boost charging Battery is boost charging Battery float charging Battery is float charging Battery disconnected Battery is not connected (history log) Displays all records in the history log (choices for text displayed) User may select any of 12 languages for LCD text. Display contrast Adjust the LCD display contrast Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D Date & time Set the date and time Comm1 baud rate Communication baud rate setting for Intellislot 1 Comm2 baud rate Communication baud rate setting for Intellislot 2 Comm3 baud rate Communication baud rate setting for Intellislot 3 Communication address This setting is applicable to RS485 communication mode Communication mode Communication Mode Setting Callback times When Intellislot 1 Communication mode is Modem, this parameter sets the number of times a number is redialed to send an alarm notification. Phone No.1 When Intellislot 1 Communication mode is Modem, this is the first phone number to be dialed (to send an alarm notification). Phone No.2 When Intellislot 1 Communication mode is Modem, this is the second phone number to be dialed (to send an alarm notification). Phone No.3 When Intellislot 1 Communication mode is Modem, this is the third phone number to be dialed (to send an alarm notification). Command password User can modify the command password. Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate of the battery capacity. Load must be between 20% and 100%. Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of the battery capacity. Load must be between 20% and 100%. System test This is a self-test of the UPS. When the user activates this function, a popup window appears about 5 seconds later to show the results. Stop testing Manually stops a battery maintenance test, battery capacity test or system test. Freshening Charge This command will allow a temporary Equalize charge for the batteries. This charge is configurable for 1 to 36 hours Stop Freshening Charge Manually stop a Freshening Charge UPS version Provides UPS firmware version numbers for the inverter, rectifier and software display board. UPS model Provides UPS model information—for example, 400V-50Hz. 59 Operator Control Panel and Display Current Record Window Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions that have been resolved. Use “page” (F1) and up / down arrow to read the events. For a complete history log, refer to the Records tab of the Menu and Data Window. Refer to Table 22 for a complete list of supported status messages. 7.2 All Status and Event Messages Displayed on the UPS Front Panel This is the complete list of UPS events and status messages supported for display in either the Record window (Historic data) or in the Current window (Prevailing data) as described in 7.1.4 - LCD Monitor and Menu keys. Table 22 UPS messages Message Description / Suggested Action (if any) Inverter Comm. Fail Internal RS485 communication failure between monitor and inverter Rectifier Comm. Fail Internal RS485 communication failure between monitor and rectifier Parallel Comm. Fail The CAN communication between different UPSs within a parallel system fails. 1.Check if there are some UPSs not powered on in the parallel system. If so, power on these UPSs and check if the alarm disappears. 2. Press Fault Clear push button. Battery Overtemp. The Battery temperature is over limit. Check the battery temperature and ventilation Ambient Overtemp. The Ambient temperature is over limit. Check the ventilation of UPS room. Battery Fault Battery detected faulty (Reserved) Replace Battery Battery test failed, Battery should be replaced. Battery Low Pre-warning Before the end of discharge, battery undervoltage pre-warning should occur. After this prewarning, battery should have the capacity for 3 minutes discharging with full load. The time is user-configured from 3 to 60 minutes. Shut down the load in time. Battery End of Discharge Inverter turned off due to low battery voltage. Check the utility failure and try to recover it. Mains Volt. Abnormal Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input line-to-neutral voltage amplitude of rectifier. Mains Undervoltage Mains Voltage is undervoltage with derated load. Check the input line-to-line voltage amplitude of rectifier Mains Freq. Abnormal Mains frequency is out of limit range and results in rectifier shutdown. Check the rectifier’s input voltage frequency Rectifier Fault Rectifier detected faulty. Rectifier shuts down. Battery discharges. Rectifier Overtemp. The temperature of heat sink is too high to keep the rectifier running. The UPS can recover automatically. Check the environment and ventilation. Batt. Contactor Fail Battery contactor or circuit breaker not responding to control signals. Batt. Charger Fault The voltage of the battery charger is too high. Control Power 1 Fail UPS operates but Redundant Control Power is not available. Mains Phase Reversed AC Input phase sequence is reversed. Rectifier Overcurrent Rectifier is overloaded. Soft Start Fail Rectifier could not start due to low DC bus voltage Bypass Unable to Trace This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% rating. This alarm automatically resets once the bypass voltage goes normal. 1. First verify that the bypass voltage and frequency displayed on the panel is within the selected range. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to be faulty. 60 Operator Control Panel and Display Table 22 UPS messages (continued) Message Description / Suggested Action (if any) Bypass Abnormal This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal. First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase reverse” and “Mains neutral lost”. If they appear, solve them first. 1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass limit. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger through the configuration software according to the customer’s agreement. Inverter Asynchronous This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition is no longer true. 1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first. 2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek any possible measurements. Inverter Fault Inverter output voltage beyond limits. Load transfers to bypass. Inverter Overtemp. The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true, then check for and verify: 1. high ambient air temperature. 2. blocked cooling airway. 3. any fan failure. 4. prolonged inverter overload Fan Fault At least one of the cooling fans has failed Inverter STS Fail At least one of the static switches of inverter side is open or short circuit. This fault is locked until power off. Bypass STS Fail At least one of the static switches of bypass side is open or short circuit. This fault is locked until power off Operation Invalid This record is registered following an incorrect operation: Output Fuse Fail At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass. Control Power 2 Fail UPS operates but Redundant Control Power is not available. Unit Over load The UPS is confirmed to be overload when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm. System Over load The UPS parallel system is confirmed to overload when the total load arises above 105% nominal rating for the set basic number of UPSs. The alarm automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by checking the system load percent indicated on the LCD panel to determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm. 61 Operator Control Panel and Display Table 22 UPS messages (continued) Message Description / Suggested Action (if any) Unit Over load Timeout The UPS is confirmed to overload and the overload times out. Note 1: the highest loaded phase will indicate overload timing-out first. Note 2: When the timer is active then alarm “unit overload” should also be active as the load is above nominal. Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred to bypass. The inverter shutdown and will restart after 10 seconds. Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to inverter mode. Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an overload is indicated then check the load, and investigate any additional load connected prior to the alarm (if applicable). Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption Inverter Over Current Inverter Pulse Width Modulation module overloaded. Bypass Phase Reversed The phase sequence direction of bypass voltage is reversed. Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C lags 120 degrees behind phase B. Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it is found to be in error Load Impact Transfer A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverter. Transfer Time-out The load is on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour. Load Sharing Fault UPS modules within a parallel system are not sharing the load current equally. DC Bus Abnormal DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass. System Transfer The whole paralleled UPS system transferred to bypass at the same time. This message will appear on the UPS which passive transfer to bypass Parallel Board Fault Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer” to bypass. DC Bus Over Voltage Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high. Check whether there is a fault in rectifier side. If no, then check whether overload occurs. Restart the inverter after resetting the fault Parallel Connect Fault The parallel cables are not connected correctly in a parallel system. Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the “inverter on” button. Bypass Over Current Bypass current is over limit above 135% rating. The UPS just alarms and does nothing. LBS Active Load Bus Synchronisation is active. The UPS is acting as an LBS master or slave in a dual bus configuration. Setting Save Error History records not saved. (Reserved) Mains Neutral Lost AC Input mains reference neutral not detected. Protocol version clash Firmware incompatibility between Monitor Board and Digital Signal Processor Board. Battery ground fault Battery leakage to ground detected (option) Inv. Turned On Manually Manual Turn On via front panel Inv. Turned Off Manually Manual Turn Off via front panel EPO Emergency Power Off direct access key pressed or external command received Transfer Confirm Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will happen. Transfer Cancel Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen. Unit Off Confirm Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other paralleled UPS modules. System Off Confirm Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected from the load. 62 Operator Control Panel and Display Table 22 UPS messages (continued) Message Description / Suggested Action (if any) Fault Reset Fault clear direct access key pressed Alarm Silence Silence On/Off direct access key pressed Turn On Fail Inverter failed to turn on when Inverter On direct access key was pressed. This may be as a result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready. Alarm Reset Fault clear or Silence On/Off direct access key pressed Bypass Mode Load supplied from AC input bypass supply. Normal Mode Load supplied from Inverter output through double conversion of the AC mains input supply. Battery Mode Load supplied from Inverter output through double conversion of the Battery supply. Source share mode Load supplied from Inverter output through shared double conversion of the AC mains input supply and of the Battery supply. UPS Shutdown UPS Shutdown, output power-down Check UPS Output Inverter off during normal startup (diagnostics information only) Generator Connected Generator active signal received. Source share mode may be activated pending UPS settings. BCB open Battery Circuit Breaker status (open) BCB closed Battery Circuit Breaker status (closed) Battery Float Charging Battery status (Float charge mode) Battery Boost Charging Battery status (Boost charge mode) Battery Discharging Battery status (discharge mode) Battery Period Testing Automatic periodic battery maintenance discharge test (20% capacity discharge) Batt. Capacity Testing User initiated battery capacity discharge test (100% capacity discharge) Batt. Maint. Testing User initiated maintenance discharge test (20% capacity discharge) UPS System Testing User initiated UPS self test Inverter in Setting Inverter starting up and synchronising Rectifier in Setting Rectifier starting up and synchronising MBP-T cabinet Fan Fault Maintenance bypass cabinet fans fault. Ext Input TX Overtemp External Input Isolation Transformer Over Temperature Ext Output TX Overtemp External Output Isolation Transformer Over Temperature Battery Room Alarm Environment in Battery Room Needs Attention Rotary Sw. Test Pos. Rotary switch is in test position. Rotary Sw. Normal Pos. Rotary switch is in normal position. Rotary Sw. Bypass Pos. Rotary switch is in bypass position. Rotary Sw. Maint. Pos. Rotary switch is in maintenance position. Battery Contactor Open Battery Contactor Open Battery Contactor Close Battery Contactor Closed Battery Reverse Connect the battery again and check the wiring of batteries No Battery Check the battery and the wiring of batteries Auto start After UPS was shutdown at EOD, inverter auto starts when utility restore Rec. Flash Update Rectifier firmware is being update Inv. Flash Update Inverter firmware is being update Monitor Flash Update Monitor firmware is being update Input contactor fault Input contactor is in fault Contactor P.S. 1 fault Contactor Power Supply board 1 Fault Contactor P.S. 2 fault Contactor Power Supply board 2 Fault LBS abnormal LBS is abnormal DSP firmware error The inverter firmware does not match with the rectifier firmware. 63 Operator Control Panel and Display 7.3 Prompt (Pop-Up) Windows The prompt window is displayed during the operation of the system to alert the user to certain conditions and / or to require user confirmation of a command. Table 23 7.4 Prompt windows, meanings Prompt Meaning Transfer with interrupt, please confirm or cancel Inverter and Bypass supplies are not synchronised and any load transfer between the supplies will cause a brief load interruption. The load is too high to be transferred with interrupt The total load must be less than the capacity of one unit to allow a parallel system to perform an interrupted transfer from bypass to inverter. This Operation Leads to Output Shutdown, Confirm or Cancel No alternative supply is available and any Inverter Off operation will cause the load to be de-energised. This operation leads to inverter overload, confirm or cancel The turn-off this inverter will lead to the overload of remaining inverter(s) in a parallel system. Turn on more UPS to carry current load The number of paralleled inverters already turned on is insufficient to carry the existing load. Battery will be depleted, confirm Battery Capacity test discharges the battery 100% System self test finished - everything is ok. No action required System self test finished - Please check the current warnings. Check “Current Records” window Enter control password Required for Battery or UPS test (default = 12345) Battery Self Test aborted, condition not met Battery self-test condition is not enough. User should check whether battery state is boost charging and whether load level is greater than 20 percent. Battery Refresh Charge aborted, condition not met Boost charging condition is not enough, such as (No battery, charger has failed, etc.). Dynamic Energy Flow Chart and UPS Help Screen This screen displays a mimic diagram of the UPS that includes energy flow and status of isolation and transfer switches. Press the “Help” key to activate this screen. Press again to toggle between this screen and the main screen. Figure 34 Help screen Help information Select the current record window Select the previous menu item Press help key back to main menu F1 F2 F3 64 F4 HELP Operator Control Panel and Display 7.5 Default Screen Saver This default screen is displayed following at least 2 minutes of operation with no new alarm. After another delay, the backlight turns off. Press any key (F1-F4 or Help) to reactivate the screen. Figure 35 Default screen Liebert NX 20 kVA-3x3 2005-05-22 UNIT #1 12:30:36 NORMAL Press any key, back to main menu F1 F2 F3 65 F4 HELP Options—For Assembly Inside the UPS Cabinet 8.0 OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET Several items of optional equipment are available for connection to the Liebert NX UPS. These are described in this section of the manual and should be fitted prior to installation. 8.1 Protection 8.1.1 Battery Ground Fault Detection In addition to any residual current device mounted externally and upstream the UPS or when optional isolation transformers are fitted to the UPS, an optional residual battery current device can be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current range monitored: 30~3000mA. Power supply voltage for the set: AC230V (L-N); When a battery ground fault is detected, an alarm will appear on the UPS display panel. An additional Dry contact fault Alarm signal is available for remote monitoring: Table 24 Terminal 21 Dry contact fault alarm signal is available for remote monitoring Name Definition Common Battery Ground Fault Detection – can be programmed as Alarm or Pre-Alarm 22 NC 24 NO The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive residual current monitor. The connection of this set for UPS is illustrated as follows. Figure 36 Battery ground fault detection set connections Current Transformer W1-A358 (installed externally only ) Battery BCB or Contactor Batt + Batt-N Batt - Socket X X K1 Output Phase K2 I2 Monitor Board -U2 I2 A1 11 4 +12V A2 14 2 IN DRY-X3 Output Neutral Battery Ground Fault Detection Resys B470 (AC230) 66 BtG UPS Options—For Assembly Inside the UPS Cabinet 8.1.2 Redundant Fan for Power Module In addition, to ensure sufficient cooling power at various operation modes with 100% rated load, a redundant power module fan set can be supplied, thus ensuring continuity of UPS operation even with the failure of some fans. No extra footprint is required. Figure 37 Redundant power module fan set Redundant AC Fan (AC Fan 1-1) (AC Fan 1-2) (AC Fan 1-3) Standard AC Fan (AC Fan 1-4) Fan120 Fan120 Fan120 Fan120 TOP VIEW Figure 38 Communication bays and cable location Location Preferred Device This Location RS-232-1 DB-9 (COM Port 1) - Serial MultiLink Software (Port Setting 2400 Baud) RS-232-2 DB-9 (COM Port 2 - Service Access Software (Port Setting 9600 Baud) DB-9 Monitor Board Location Preferred Device This Location Top Bay Mid Bay Bottom Bay Relay Card (no port setting required) Multiport4 (no port setting required) OCWeb LB / OC485 (port setting 2400 Baud) Top Mid Bottom Suggested routing of customer-supplied communication cables Gland plate for cable exit Notes: a) All Intellislot cards are supported in any bay. b) Port sharing is: - PERMITTED between RS232-x DB9 devices and Relay / Multiport4 Intellislot cards (i.e., Serial Multilink software will work from RS232-1 DB9 also when relay card is inserted in the top bay. - NOT PERMITTED between RS-232-x D-B9 devices and OCWeb / OC485 cards (i.e., Serial MultiLink software will not work from RS232-1 DB-9 when OCWeb card is inserted in the top bay. 67 Options—For Assembly Inside the UPS Cabinet 8.1.3 OC Web Card - SNMP/HTTP Network Interface Card This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet network and in addition the same card will also transmit the same status information and all measured parameters for display via a Web browser. This card is supported in the top, middle and bottom Intellislot bays. Figure 39 OC Web Card data summary window Figure 40 OC Web Card battery data summary 68 Options—For Assembly Inside the UPS Cabinet 8.1.4 Relay Card The Relay card provides voltage-free contact closures for remote monitoring of alarm conditions. Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems. The Relay card is rated for 24 VAC/VDC at 1A and supported in any of the three NX Intellislot bays. Table 25 Pin Relay Card pin configuration Function Operation Closed if no UPS failure 1 UPS Fault 2-3 Not Used 4 UPS Fault Closed if UPS fails 5 Summary Alarm** Closed if SUMMARY ALARM** occurs 6 Summary Alarm** Closed if no alarm conditions are present 7 Any Mode Shutdown return Not Supported– use External EPO terminal 8 Not Used 9 Common - Low Battery 10 Low Battery Closed if battery is OK Low Battery Closed if LOW BATTERY point occurs. 11 12-13 Not Used 14 UPS Any Mode Shutdown Not supported– use External EPO terminal 15 On UPS Closed if ON UPS (inverter) power 16 On Battery Closed if ON BATTERY power (Utility failure) 17 Common - UPS Fault, Summary Alarm, On UPS, On Battery, On Bypass 18 On Battery 19 ÷ 23 Closed if not ON Battery power (Utility OK) Not Used 24 On Bypass 25 Not Used Closed if ON BYPASS **A Summary Alarm occurs when any of the following conditions exist: • • • • Utility power is out of the acceptable range (voltage and/or frequency) UPS is in BYPASS MODE (load not on Inverter power) UPS Battery is LOW UPS fault has occurred Table 26 # 8.1.5 Relay card jumpers Connection Description JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together. JP02 Pin 7 to Pin 17 Irrelevant for NX - (Interconnects all relay COMMONS and the (not supported) ANY MODE SHUTDOWN Return. Multiport-4 Card The Multiport-4 card provides 4 sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical application is to allows a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure / low battery) of a single UPS. This card is supported in any of the three NX Intellislot bays. 69 Options—For Assembly Inside the UPS Cabinet Figure 41 SiteNet MultiPort4 Intellislot pin configuration CPU CPU UPS CPU CPU Table 27 Pin SiteNet MultiPort4 Intellislot pin assignment Assignment Description 1 Low Battery 2 Not Used 3 Not Used 4 Not Used 5 Not Used 6 Not Used 7 Low Battery Common 8 Utility Fail Common 9 Utility Fail 70 Options—For Assembly Inside the UPS Cabinet 8.2 OC485 Web Card – Modbus, Jbus, IGM Net The OpenComms 485 Card facilitates SiteScan Web or Building Management Systems monitoring. The RS232 port is used for connection to a personal computer for setting up. The RS-485 port supports IGM Net and Modbus/JBus protocols and maps the operation of the UPS including status, alarms and data (voltages, currents, frequency, power, power factor, temperatures etc.) Figure 42 OC485 Web card Table 28 NX communication options Physical description of port Top Intellislot Labeled ID Name of Port Intellislot 2 (On Monitor Board) On the UPS LCD screen, under Settings, controlled by: Comm 1 Monitoring Devices supported Multiport 4 any Relaycard-int any OCWEB-LB Modbus/Jbus Middle Intellislot Intellislot 1 (On Monitor Board) Comm 2 Relaycard-int any OCWEB-LB 8.2.1 Comm 3 Top DB9 port RS232-1 Comm 1 Bottom DB9 port RS232-2 Comm 2 2400 Not simultaneous with Multilink in RS232-2 any any OCWEB-LB 2400 Modbus/Jbus 2400 Service Software (Reserved) Not simultaneous with Multilink in RS232-1 2400 Relaycard-int Multilink Serial Comments 2400 any Multiport 4 Intellislot 3 (On Monitor Board) 2400 Multiport 4 Modbus/Jbus Bottom Intellislot Baud rate 9600 Not simultaneous with Web card in top Intellislot. 9600 Not simultaneous with Web card in middle Intellislot. Remote Alarm Monitor Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel that is driven by volt-free alarm status contacts from an optional relay alarm board. 71 Options—For Assembly Inside the UPS Cabinet 8.2.2 Dust Filter for 10-30kVA Installing the two dust filters in the Liebert NX requires only a Phillips screwdriver. Each filter is held in place by a bracket on either side of each filter. To install each filter: 1. Open the UPS door and locate the filters (on the back side of the front door; see Figure 43). 2. Remove one bracket and loosen the screw on the second bracket. The second bracket need not be removed (see Figure 43). 3. Remove the dust filter to be replaced. 4. Insert the clean filter. 5. Reinstall the bracket, tightening the screw securely. 6. Tighten the screw on the second bracket. Figure 43 Dust filter replacement Bracket Sems screw 72 Bracket Technical Specifications 9.0 TECHNICAL SPECIFICATIONS 9.1 Conformity and Standards The UPS has been designed to conform to the following European and international standards: Table 29 Compliance with European, international standards Description Normative reference General and safety requirements for UPS used in operator access areas EN 50091-1-1 /IEC 62040-1-1 / AS 62040-1-1 Electromagnetic compatibility (EMC) requirements for UPS EN 50091-2 / IEC 62040-2 / AS 62040-2 (Class A) Method of specifying the performance and test requirements of UPS EN 50091-3 / IEC 62040-3 / AS 62040-3 (VFI SS 111) The product standards in Table 29 incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529). Table 30 Environmental characteristics Unit of Measurement 10 15 20 30 Acoustic Noise Level at 1 Meter (39 in) dBa 51.0 51.5 51.6 56 Altitude of Operation m (ft) ≤1000m (3280 ft) above sea level de-rate power by 1% per 100m(328 ft) between 1000 and 2000 m (3280 and 6560 ft) - 0 to 95% non condensing Operating Temperature °C (°F) 0 to 40 (32-104°) Battery life is halved for every 10° (18°) increase above 20° (68°) Storage-Transport Temperature for UPS °C (°F) -20 to 70 (-4 to 158) Recommended Battery Storage Temperature °C (°F) -20 to 30 (-4 to 86)°F) (20°C [68°F] for optimum battery storage) Rated power, kVA Relative Humidity Table 31 Overall efficiency, heat losses and air exchange Unit of Measurement 10 15 20 30 Normal Mode (dual conversion) % 90.4 91.2 91.3 91.9 ECO Mode % 93.2 94.2 94.7 96.6 Rated Power, kVA 10 15 20 30 Battery Mode % 91.3 91.7 92.0 92.5 Rated Power kVA 10 15 20 30 Normal Mode kW 1.6 1.8 2.2 2.6 ECO Mode kW 1.3 1.4 1.4 1.5 No Load kW 1.3 1.3 1.3 1.3 L/sec (m3/hr) 119 (428) Rated Power, kVA Inverter Efficiency (DC/AC) (battery at nominal voltage 480VDC and full-rated linear load) Heat Loss & Air Exchange (Ventilation) Maximum Forced Air Cooling (front intake, back exhaust) Input and output voltage 400VAC, battery charged, full rated linear load 73 239 (860) Technical Specifications Table 32 Mechanical characteristics Rated Power, kVA Dimensions, WxDxH Unit of Measurement 10 15 20 30 600x700x1400 (23-9/16x27-5/8x55) mm (in) Mass Mass without batteries kg (lb) 180 (397) 204 (450) 204 (450) 210 (463) Finish N/A Pantone 877 (Silver grey) equivalent Becker Silver epoxy polyester powder 041-37-2 Protection Degree, IEC (60529) N/A IP20 (finger-proof with front doors open or closed) Table 33 Rectifier AC input (mains) Rated Power, kVA Unit of Measurement 10 15 20 30 Rated AC Input Voltage 1 VAC 380/400/415 (3-phase and sharing neutral with the bypass input) Input Voltage Tolerance 2 VAC 305V to 477V 304V to 208V (output derated below 70%) Hz 50/60Hz (tolerance 40Hz to 70Hz) Power Factor kW/kVA, full load (half load) 0.99 (0.98) Input Power kVA rated 3 (maximum 4) 8.9 (11.7) 13.3 (18.9) 17.8 (23.3) 26.6 (35.0) Input Current A rated 3 (maximum 4) 12.9 (16.9) 19.3 (27.4) 25.8 (33.8) 38.6 (50.7) THDI % FL 3 3 3 3 Frequency 2 Harmonic Current Distortion Duration of Progressive Power Walk-In 10 seconds to reach full rated current (selectable 5 through 30 seconds in 5-second intervals) sec 1. Rectifier operates at any of the rated supply voltages and frequencies without further adjustment. 2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged battery 3. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged 4. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power. 74 Technical Specifications Table 34 Battery Intermediate DC Circuit Rated Power, Unit of kVA Measurement Battery Bus VDC Voltage Number of Lead-Acid Cells Nominal Maximum Float Voltage 10 15 20 Nominal: 480V (VRLA Float charge is 540V) Range: 400V - 616V 30 240 = [40 x 6-cell (12V) blocks] 264 = [44 x 6-cell (12V) blocks] 2.25 V/cell (selectable from 2.2 –2.3V/cell) Constant current and constant voltage (IU) charge mode V/cell (VRLA) Temperature Compensation Ripple Voltage Ripple Current mV/°C/cl - 3.0 (selectable 0 to – 5.0 around 25°C or 30°C. or inhibit) % V float % C10 Boost Voltage V/cell (VRLA) ≤1 ≤5 2.35 V/cell (selectable from 2.30-2.40V/cell) Constant current and constant voltage (IU) charge mode - float-boost current trigger 0.050 C10 (selectable 0.030-0.070) - boost-float current trigger 0.010 C10 (selectable 0.005-0.025) with 24 hr safety timeout (selectable 8-30 hr) - boost mode inhibit also selectable 1.63 V/cell (selectable from 1.60~1.75 V/cell Auto Inverse EOD voltage x discharge current mode (The end of discharge voltage increases at low discharge currents). 2.4 V/cell (selectable from 2.3-2.4V/cell) Constant current and constant voltage (IU) charge mode Programmable auto trigger or inhibit of boost mode Boost Control End Of Discharge V/cell (VRLA) Battery Charge Battery Charging Power* max current (adjustable) 1 V/cell kW 2.5 5 5 7.5 A 3.75 7.5 7.5 12 * At low input voltage the UPS recharge capability increases with load decrease (up to the maximum capacity indicated) 1. Max currents listed are for EOD voltage of 1.67 V/cell for 240 cells. Table 35 Inverter output to critical load Rated Power, kVA (kW) Unit of Measurement Overload % Rated Fault Current Non linear load capability 3 Neutral current capability Steady state voltage stability Transient voltage response 4 Total Harmonic Voltage Distortion (THDV) Synchronisation - Window % Rated % Rated % Rated % % 10 (8) 15 (12) 20 (16) 30 (24) 380/400/415 V (three-phase, four-wire with neutral referenced to the bypass neutral) 50 / 60 110% for 60 min 125% for 10 min 150% for 1 min >150% for 200 msec 340% current limitation for 200 msec 100% 170% ±1 (balanced load), ±2 (100% unbalanced load), ±5 % < 1 (linear load), < 4 (non linear load 3) Hz sec Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz) 1 Hz/sec selectable 0.1 to 3Hz/s (single UPS) 0.2Hz/sec (paralleled UPS) ±5 Rated AC Voltage 1 Frequency 2 Slew Rate (Max change rate of synch frequency) Inverter Voltage Tolerance 1. 2. 3. 4. VAC Hz %V (AC) Factory set to 400V – 380 or 415V selectable by commissioning engineer. Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable. EN 50091-3 (1.4.58) crest factor 3:1 IEC 62040-3 / EN 50091-3 also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage within half a cycle. 75 Technical Specifications Table 36 Bypass mains input Rated power, kVA Unit of Measurement Rated AC Voltage 1 VAC 10 15 20 30 380/400/415 V three-phase four-wire, sharing neutral with the rectifier input and providing neutral reference to the output Rated Current 380V 400V 415V Overload Capacity Upstream Protection, Bypass Line (by others) Current Rating of Neutral Cable Frequency 2 Transfer Time (between bypass and inverter) Bypass Voltage Tolerance Bypass Frequency Tolerance Synchronisation - Window A A A % N/A A Hz ms % VAC % Hz 15 15 14 23 30 45 22 29 43 21 28 42 135% long term 170% 10 min 1000% 100 ms Thermomagnetic circuit breaker, rated up to 125% of nominal output current. IEC 60947-2 curve C. 1.7 x In 50 / 60 Synchronous transfer: ≤1ms Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz) or 40, 60, 80, 100 ms, selectable Upper limit: +10, +15 or +20, default +15 Lower limit –10, -20, -30 or -40, default: -20 (delay time to accept steady bypass voltage: 10 sec) ± 2.5 ± 5 ± 10 or ± 20 default ±10 Rated frequency ±2Hz (selectable ± 0.5 to ±3Hz) 1. Factory set to 400V – 380 or 415V selectable by commissioning engineer. 2. Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter. 76 Technical Specifications NOTES 77 Technical Specifications 78 Ensuring The High Availability 0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs. Technical Support / Service Web Site www.liebert.com Monitoring 800-222-5877 [email protected] Outside the US: 614-841-6755 Single-Phase UPS 800-222-5877 [email protected] Outside the US: 614-841-6755 Three-Phase UPS 800-543-2378 [email protected] Environmental Systems 800-543-2778 Outside the United States 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-25410_REV2_08-06 Emerson Network Power. The global leader in enabling Business-Critical Continuity™. Embedded Computing AC Power Systems Embedded Power Connectivity DC Power Systems Integrated Cabinet Solutions EmersonNetworkPower.com Outside Plant Services Site Monitoring Power Switching & Control Precision Cooling Surge Protection Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2006 Emerson Electric Co.