Nfinity - Emerson Network Power

AC Power Systems
Nfinity
High Availability Power Protection
The Problem Is That You Depend On Your Network
More Than Ever
The digital lifeblood of many organizations - computers, servers, phones, datacom
links-now resides on networks…outside of the traditional “glass house” protection. This may make companies more flexible and responsive, but it also makes
them far more vulnerable to power problems, and the threat of catastrophic losses
in sales, customers, pro ductivity…your business lifeblood.
The Solution Is A UPS Designed Like Never Before
Now for the first time, your can achieve the highest levels of UPS reliability in a system
that is sized to protect network applications. The Liebert Nfinity UPS is designed for
use with workstations, servers, networks, telecommunications equipment or other
sensitive electronics. It provides continuous, high-quality AC power to your missioncritical systems, protecting them from any power aberrations due to blackouts,
brownouts, surges or noise interference. The Nfinity power system is a scalable 4 to
16 kVA UPS, designed with N+x parallel redundancy to provide a fault-tolerant network of power protection formaximum systems availability. Its modular design
makes Nfinity the most adapt able UPS on the market, offering easy upgrades and
servicing.
Scalability Is Just The Start Of The Value
} Configure
the system that’s right for you today and tomorrow
you need shipped complete, ready for final connection
} Everything
Intelligence Means Maximum Performance
} Power
responsiveness
ability to communicate
} Self diagnosis
} The
Highest Levels Of Redundancy Mean Maximum Systems
Availability
} Redundancy
at all the critical points of UPS operation
without shutdown
} Maintainability
Liebert Puts It All Together In The Nfinity UPS System
It looks and works like no UPS we’ve offered before. Nfinity’s unique frame design
houses all of the modular system components. It contains bays to hold the power
modules, battery modules and system control modules. The modules offer hotswap
capability, making it easy to add capacity or replace modules. The Nfinity class of
power protection offers a variety of advantages.
The Right Size For Your Network Protection Plans
Nfinity’s modular design was devised to provide easy scalability to users as their power demands grow. By simply installing additional power or battery modules, you can expand your current system, extend yourbackup runtime or add redundancy.
Scalability Provides The Flexibility To expand
Nfinity’s patent-pending frame design provides the user with the maximum adaptability that is demanded in today’s everchanging network environment. Because Nfinity is scalable for redundancy, power capacity or battery run time, you have
greater flexibility in how you can use the system. Configurations can be cost-effectively upgraded without re-investing in
a new system or installation.
Longer Battery Run Time
The system’s flexible frame design allows battery backup times to be customized to customer needs while maintaining a smaller footprint. To extend run times, just add battery modules. Nfinity also has a faster recharge time than similar units.
Hot-Swappable
Hot-swappable modules allow you to add or replace power, battery and control modules without shutting the load down or
affecting power to it. In redundant mode, this means no downtime for repair. Nfinity’s hot-swappable modules also
make it easy for the user to handle basic service.
Cabinet Stands Small, Stays Small
Nfinity’s compact, efficient design allows you to pack more power and battery capability into a much smaller sized unit, so it
takes up less of your valuable floor space.
Initial System
4 kVA Redundant
Upgrade
System Capacity
8 kVA Redundant
Extend System
Run Time
8 kVA Redundant
Power Modules
Power Modules
Power Modules
Blank
Blank
Batteries
Batteries
Batteries
The system control module provides communications and control for the unit.
The system utilizes independent 4 kVA power modules. Up to four power modules
can be operating at one time.
Each battery module is composed of ten individual 12-volt batteries encased in a
plastic housing.
Power and battery modules are housed in identical bays within the frame. Power
modules must be contained in the top half of the frame, while battery modules can
be utilized in any of the bays. This allows battery backup times to be configured to
customer needs.
Fault-Tolerant Dual Control Modules
Fasieners
Fault LED
Status LED
User interfce Module
Lever
System Control Module
IntelliControl™ Module - The system control module works with the user interface to provide vital information about
the condition of the power and battery modules. The use of a paired system control provides full systems functionality in the event of any single failure and ensures that operations and communications are always available.
Communications Capability
The Liebert Nfinity UPS incorporates extensive firmware designed to provide a comprehensive range of control and
operating information, as well as communications capability.
User Interface Control Panel
The user interface module is the main source of communication between the Nfinity UPS and the user. It features an easy-toread LCD display and LED mimic diagram. The control panel informs the user of the status of the UPS, including the power and
battery modules, and allows you to configure the system to fit specific needs or preferences. You can
also review the event log and even receive instructions on replacing modules.
Redundant Monitoring Options
Dry contacts and a serial communications port are standard. The unit also includes four Intellislot™ ports for multiple user
options including:
} SNMP cards that allow the Nfinity to communicate with an Ethernet network.
} MultiPort4 cards that enable up to four client computers to monitor UPS status.
} Relay contact cards to provide contact closures or remote monitoring of alarm conditions.
}The system also communicates to and monitors internal and extended battery cabinets.
Flexible Power Modules Keep Your Business Online
Intelligent Power Modules - provide protection against power outages, spikes, surges, noise, and sags. Designed in
4kVA “building blocks,” they utilize patent pending current sharing technology that ensures premium quality power.
Nfinity power modules feature a power factor corrected (PFC) rectifier to create a sinusoidal input current waveform.
This allows the system to use utility power more efficiently and reduces reflected distortion.
A true on-line system, Nfinity provides continuous, regenerated sinewave output power.
Nfinity is a 4 to 16 kVA UPS designed with N+x parallel redundancy to provide a fault tolerant network of power protection for
maximum systems availability. Redundant Power Modules - parallel redundancy is achieved by adding extra
powermodules that equally share the electrical load.
Wider Input Voltage Window
A wider, variable input voltage range minimizes transfer to battery to increase battery life. For lighter loads, low line transfer
can range down to 110V.
Generator Compatible
Full time output voltage and frequency regulation is provided - a necessity for sensitive electronic equipment and a must for
sites with back up generators.
Highest Overload Capability
Nfinity offers the highest overload capability of any system in its class - capable of sustaining 110% of the system’s rated
load for an extended period of time.
Power
odule
Battery Module
Shipping serews
Fastner
Status LED
Fault LED
Cooling Fan
Lever
FRONT
FRONT
Under normal operation, the Status LED (green) will blink and the Fault LED (amber) will be off.
Longer Runtimes For Maximum Availability
IntelliBattery™ Module - Nfinity’s innovative battery module continuously monitors the battery’s voltage, current, and
temperature to determine the state of its batteries and predict performance. Each module contains an intelligent battery sensing circuit that will take it off-line if a problem is detected, so as not to affect the pefor mance of other good
battery modules in the system.
Extended Battery Cabinets
The Nfinity extended battery cabinet is available when extra run time is critical to your protected loads. This unit has 12 bays that
accept up to 12 standard Nfinity intelligent battery modules, allowing you to add battery capacity as needs change. A built-in
microprocessor in each battery module provides the intelligence and communication capability to allow the module to automatically remove itself from the critical DC bus if necessary. The extended battery cabinet reports and tracks individual module capacity, temperature and charge level, as well as other data and reports this information to the Nfinity system control.
Nfinity Battery Run Times (min
8 Bay 1x1 Units
12 Bay 1x1 Units
12 Bay 3x1 Units
Quantity of Battery Modules
Load
VA
20,000
19,500
19,000
18,500
18,000
17,500
17,000
16,500
16,000
15,500
15,000
14,500
14,000
13,500
13,000
12,500
12,000
11,500
11,000
10,500
10,000
9,500
9,000
8,500
8,000
7,500
7,000
6,500
6,000
5,500
5,000
4,500
4,000
3,500
3,000
2,500
2,000
Load
Watt
14,000
13,650
13,300
12,950
12,600
12,250
11,900
11,550
11,200
10,850
10,500
10,150
9,800
9,450
9,100
8,750
8,400
8,050
7,700
7,350
7,000
6,650
6,300
5,950
5,600
5,250
4,900
4,550
4,200
3,850
3,500
3,150
2,800
2,450
2,100
1,750
1,400
1
7
9
11
14
18
2
7
8
8
9
11
12
14
15
19
23
28
33
42
3
7
7
7
8
9
10
11
12
13
14
16
17
19
21
23
25
31
37
44
52
65
4
7
7
7
8
8
8
9
10
12
12
12
14
15
15
16
17
19
21
23
24
24
23
28
37
43
51
60
71
88
5
7
7
7
8
8
8
9
9
9
10
11
12
13
13
13
14
16
17
17
18
19
21
22
23
25
28
30
32
36
39
42
47
55
65
76
89
112
6
9
9
9
11
12
12
13
13
13
13
14
15
16
16
17
18
20
21
21
23
24
26
28
29
31
34
36
40
43
47
52
57
66
79
93
109
136
7
12
12
13
13
14
14
15
15
17
17
18
19
20
20
21
22
24
25
26
28
29
30
33
35
37
40
43
47
51
56
61
67
79
93
109
128
160
8
19
20
21
22
23
24
25
26
28
29
30
32
34
36
38
40
43
47
50
55
60
66
72
78
91
107
126
147
183
Quantity of Extended
Battery Cabinets
9
32
34
35
37
38
41
44
46
49
53
57
62
68
74
80
88
104
123
143
167
207
10
55
59
64
69
76
82
90
98
115
136
159
185
230
11
128
151
176
205
254
1
25
25
26
27
28
28
29
30
32
33
34
36
37
38
39
42
44
46
48
51
54
57
60
64
68
73
78
84
92
101
110
119
140
165
192
224
276
2
51
56
57
58
61
63
64
66
68
70
72
74
82
85
86
90
93
97
101
111
113
119
131
139
142
149
161
174
190
203
223
245
285
333
387
448
554
3
75
80
81
82
97
99
100
102
104
106
108
110
130
133
134
138
141
145
149
171
173
179
203
211
214
221
245
258
286
299
331
365
429
489
567
652
818
4
99
104
105
106
133
135
136
138
140
142
144
146
178
181
182
186
189
193
197
231
233
239
275
283
286
293
329
342
382
395
439
485
573
645
747
856
1,082
NOTE: In Red backup times for 8-Bay units, in Blue backup times for 3x1 (up to 20kVA) units. Backup times are in minutes and are based on resistive loading at an ambient temperature of 25°C under controlled conditions, for non-redundant configurations. Extended battery cabinets are fully
loaded with 12 battery modules. Extended battery cabinets assume that the UPS frame is fitted with all available battery modules.
Maximum Protection For Mission Critical Applications
Nfinity is the first redundant UPS of its kind that ships as a complete, pre-configured system that is tested at the
factory. Everything you need is included in a single package that’s ready to roll-in an hook up.
User Interface
Control Enable
Switch (SW2)
REPO
Terminal
Intellislot
Commutations Port
Port 1
Port 2
COM1
Port 3
Port 4
COM2
DB-9
Commutations
Port
Power
Module
Bays
Battery
Module
Bays
Output Power
Terminal
220/240 Jumper
(option transformateur seulement)
Imput Power
Terminal
Imput Earth
Terminal
Manual
Bypass
Switch
Imput Circuit
Breaker(CB1)
Intate
Cooling
Fans
External Battery
Connection
Front
Back
8 Bay Model Displayed - Also Available: 12 Bay Model, Extended Battery Cabinet
Power Monitoring And Network Shutdown With Multilink Software
MultiLinkTM is the perfect complement to the Liebert Nfinity UPS because it prevents unexpected server shutdowns, protects data and minimizes downtime. The software provides unattended, orderly shutdown for one computer or many, and is especially effective with large server farms. MultiLink has full event management and displays UPS instrumentation on screen.
MultiLink is available for all popular operating systems and can be downloaded from the Liebert
web at www.liebert.com.
General & Environmental
Rating
Unit
kVA
4
8
12
16
20
kW
2.8
5.6
8.4
11.2
14
Conducted and Radiated EMC Levels
EN50091-2 Class A
Compliant Safety Standards
EN50091-1, EN 60950, CE, Low Voltage Directive
Compliant Immunity Standards
EN61000 - 4 - 2,3,4,5,6
Encombrements Unités
8 Bay
Dimensions: Width
mm
Dimensions: Depth
mm
711
Dimensions: Height
mm
1016
12 Bay
508
1372
Environmental
Operating Temperature (max)
°C
0°- 40°
Relative Humidity
%
de 0 à 95% sans condensation
Maximum Operating Altitude
m
Nominal Heat Dissipation
W
Acoustic Noise Level
Input Data
dBA
Nominal Input Voltage
VAC
3000
311 @
622 @
933 @
4kVA
8kVa
12kVA
1244 @16kVA
1265 @ 20kVA
<62@ 1m
220/230/240 for 1x1 units
380/400/415 for 3x1 units (12 bay only)
Power Factor
cosw
.98 for 1x1 units
.80 for 3x1 units
Input Frequency (nominal)
Hz
50
Input Frequency Range
Hz
40 - 70
Battery Module
Number Of Lead Acid Batteries
10
Number Of Battery Cells
60
Battery Capacity
Autonomy Time (full load)
AH
minutes
9
7 (with an equal number of Battery & Power modules
in non-redundant configuration)
Maximum Charge Current (full load)
A
3
Nominal Voltage
VDC
120
Recharge Time
Output Data
h
Units
3 à 5 (à 90% capacity)
Output Voltageie
VAC
220/230/240 VAC
Voltage Regulation
%
±3 %
Voltage Stability (100% step load)
%
±7 %
Recovery Time
ms
96 ms
Voltage distortion
%
< 3 % THD linear load
Output Frequency
Hz
Efficiency at 100% load
%
Output Overload Capability
%
< 7 % THD non-linear load
50 Hz
91 %
>100% - 110% for 10 min.
111% - 150% operates for 8 sec
151% - 200% operates for 0.25 sec
>201% operates for 2 cycles
for 1x1 units
>100% - 110% operates indefinitely
111% - 150% operates for 8 sec
151% - 200% operates for 0.25 sec
>201% operates for 2 cycles
for 3x1 units
NOTE: 3x1 units available in 12-Bay frames only. 16kVA 1x1 requires 12-Bay frame. 20kVA rating available for 3x1 models only.
While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert Corporation assumes no responsibility, and disclaims all liability
for damages resulting from use of this information or for any errors or omissions. © 2009 Liebert Corporation. All rights reserved throughout the world. Specifications subject
to change without notice. All names referred to are trademarks or registered trademarks of their respective owners.
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™. The company is the trusted source for custom, adaptive
and ultra-reliable solutions that enable and protect its customers’ business-critical technology infrastructures. Backed by the largest global services organization in the industry,
Emerson Network Power offers a full range of innovative power, precision cooling, connectivity and embedded products and services for computer, communications, healthcare
and industrial systems. Key product brands within the Emerson Network Power family include Liebert, Knuerr, ASCO, Astec, Lorain.
Emerson Network Power TM
The global leader in enabling
business-critical continuity.
Emerson Network Power EMEA
Via Leonardo da Vinci, 16/18
35028 - Piove di Sacco (PD) - Italy
tel. +39 0499719111 fax +39 0495841257
[email protected]
www.eu.emersonnetworkpower.com
Embedded Computing
AC Power
Connectivity
DC Power
Embedded Power
Monitoring
Out Side Plant
Power Switching & Controls
Precision Cooling
Rack & Integrated Cabinets
Services
Surge Protection
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co.
©2009 Emerson Electric Co.
BRO-NFIN-GB-XX
General Features