Hiline Datasheet

Hiline
HIGH PERFORMANCE AIR CONDITIONING
Hiline PI is the package direct expansion type, air conditioner range, with built-in air cooled condenser, for
indoor installation, available in upflow and downflow version. Where there is minimum space, the compactness
of the Slim version solves this problem (3 and 4Kw
models available in a 295/600/2000 W/D/H frame).
Energy Saving And Cost Effective Cooling
The most modern design and components such as scroll
compressor, plug-type fans and the freecooling mode assure
high energy saving and greatly reduce running and lifetime
High Reliability
Faster Start-Up
Hiline can be powered by 48VDC emergency power source
in case of mains failure. Continued ventilation and the optional maximised freecooling assure constant operation of the
telecommunications equipment and continued revenue from
the site. 230/1/50 emergency supply is also available as an
option.
The cooling circuit is pre-charged, fine tuned and fully tested
before delivery. No pressure test is required on site. Installation
is speeded up by using the fast-plug electrical connections (on
request) and the automatic commissioning software: installation and commissioning are completed in less than 25 mins
without need of specialized personnel on site.
High Connectivity
High Versatility
The standard on board control allows teamwork with other
units and connectivity to innovative Liebert-HIROSS supervision system or to third-party monitoring. Connections can
make use of existing Ethernet LAN and new interactive solutions via Web are available.
Upflow or downflow air supply version, combined with the
back or side condenser connections make Hiline suitable for
the most different sites configuration. Use the available full
range of connection kit, to make your own installation true.
Model Hiline PI
Air supply
Main power supply
Emergency power supply (opt)
Performances
Total cooling capacity (1) U/O
Sensible cooling capacity (1) U/O
Compressor AC power input (1) U/O
Condenser fan AC power input (@50Pa) (1) U/O
Evaporator fan AC power input (1) U/O
Evaporator fan DC power input (1) U/O
Evaporator airflow
U (ESP 20 Pa)/O (ESP 50 Pa)
Condenser airflow 50Pa / 200 Pa
Freecooling max.airflow U/O
Outdoor sound pressure level (2)
Indoor sound pressure level (2)
Max.ambient temperature (3)
Refrigeration Circuit
Compressor type/quantity
Refrigerant
Expansion device
Evaporator Fan
Quantity/type/poles AC version
Quantity/type/poles DC version
Driven/motor protection
Condenser Fan
Quantity/type/poles
Driven/motor protection
Control system
Filter type/efficiency (EN 779)
Electric heating (opt)
Cabinet
Frame
Painting
Insulation type/thickness
Width
Depth
Height
Weight Under / Over
05
07
10
12
Under (U)/Over (O)
400V/3Ph+N+PE/50HZ
48V DC or 230V/1Ph/50HZ
230V/1Ph+N+PE/50HZ
15
kW
kW
kW
kW
kW
kW
m3/h
5,2/5,2
5,2/5,2
0,96/0,96
0,72/0,72
0,46/0,54
0,27
1.950/2.100
7,5/7,4
6,9/7,1
2,14/2,17
0,72/0,72
0,49/0,61
0,34
2.050/2.200
10,8/10,8
10,8/10,8
2,81/2,88
1,26/1,27
0,93/0,94
0,43
3.405/3.560
12,9/13,1
12,9/13,1
3,53/3,50
1,26/1,27
1,04/1,03
0,55
3.780/3.890
16,5/16,1
15,3/15,7
4,52/4,52
1,26/1,27
1,12/1,11
0,68
4.000/4.200
m3/h
m3/h
dB(A)
dB(A)
°C
1.500/1.890
60
55
45
2.740/2.380
1.570/1920
60
57
45
3.180/3.180
62
55
45
4.830/4.280
3.480/3.480
62
56
45
3.740/3.740
62
57
45
scroll/1
R407C
thermostatic valve
1/radial/4
1/plug/-
2/plug/direct/IP54
1/radial/4
direct/IP54
variable speed
pleated/G3
kW
-/mm
mm
mm
mm
kg
3,0
4,5
6,0
galvanized steel
epoxydic powder
synthetic foam class 1/10
650
650
1.990
228/232
231/236
287/292
900
750
2.050
287/292
297/302
(1) Reference conditions are 27°C, &47% R.H indoor, 35°C outdoor; nominal power supply.
(2) Measured with outdoor temperature 35°C, 2 meters from the unit, free field conditions.
(3) Maximum outdoor temperature referred to indoor air temperature =24°C.
UPFLOW
DOWNFLOW
Condenser fan
Condenser coil
Freecooling damper
Air filter
Evaporator coil
Compressor
Evaporator fan
Upflow version as example
Liebert HIROSS Headquarters
Via Leonardo da Vinci, 8
35028 - Piove di Sacco (PD)
tel. +39.0499719311 fax +39.0499719053
[email protected]
Downflow version
Freecooling mode
High Performance Air Conditioning
Via Leonardo da Vinci, 8
35028 - Piove di Sacco (PD)
tel. +39.0499719311 fax +39.0499719053
[email protected]
Uninterruptible Power Supply
Via Gioacchino Rossini, 6
20098 - San Giuliano Milanese (MI)
tel. +39.02982501 fax +39.0298250337
[email protected]
www.liebert-hiross.com
Upflow version
Freecooling mode
Services
Via Gioacchino Rossini, 6
20098 - San Giuliano Milanese (MI)
tel. +39.02982501 fax +39.0298250338
[email protected]
HILINE/E/103192/02-03/Conte+Oggioni+Partners/Printed in Italy
General Features