ETC JTD32/10ID

JTD_ID Series Indicator POWR-PRO® Class J Fuses
600 VAC
■
Time Delay
■
8/10 – 600 Amperes
POWR-PRO
FUSES
SPECIFICATIONS
Voltage ratings: AC: 600 Volts
DC: Contact Factory
Interrupting ratings:
AC: 200,000 amperes rms symmetrical.
300,000 amperes rms symmetrical
(Littelfuse self-certified)
Ampere range:
8/10 – 600 amperes
Approvals:
UL Listed Class J fuses
per UL 248 (formerly 198C)
(File No. E81895).
CSA certified HRCI-J per C22.2 #106
(File No. LR29862)
AMPERE RATINGS
NEW
8
/10
1
11/4
11/2
16/10
18/10
2
21/4
21/2
28/10
3
32/10
31/2
4
41/2
5
56/10
6
7
8
9
10
12
15
171/2
20
25
30
35
40
45
50
60
70
80
90
100
110
125
150
175
200
225
250
300
400
450
500
600
Example part number (series & amperage): JTD 60 ID
RECOMMENDED FUSE BLOCKS
LJ600 series
Refer to Fuse Block section of this catalog for additional
information.
The Littelfuse® POWR-PRO® JTD_ID Indicator Class J fuse
provides visual blown fuse indication and maximum protection in a compact package. The compact Class J package
was designed specifically for circuits where space is at a
premium. The current limiting time delay JTD_ID offers a
patented true dual-element design that is ideal for use in
circuits with high inrush currents. Superior performance
characteristics of JTD_ID Indicator fuses reduce nuisance
fuse opening and the blown fuse indication reduces downtime and increases safety.
APPLICATIONS
No fuse testing required. Machine operators can immediately determine that there is an open fuse and request
maintenance personnel to bring the proper replacement.
■
Reduce nuisance opening — Indicator fuses have
superior time-delay and cycling characteristics which can
lengthen fuse life and decrease needless opening.
■
Reduce fuse inventory — Because JTD_ID Indicator
fuses have superior performance characteristics they can
be used on a variety of applications, thus decreasing fuse
inventory.
■
Reduce equipment damage — Indicator fuses provide
superior overload and short circuit protection that can
reduce equipment damage. Indicator fuses also provide
IEC Type II “No Damage” protection to IEC and NEMA type
motor starters.
■
Reduce accidents — The JTD_ID Indicator fuse improves
safety by minimizing exposure to live circuits. Unlike other
forms of blown fuse indication, once the indicator window
darkens, it stays dark. It does not matter if the power is on
or off or if the fuse is in a tool box. Other forms of indication
require the power to remain on, which causes a safety
hazard for personnel.
Fused combination motor controllers to provide IEC Type II
(no damage) motor branch-circuit short-circuit and ground
fault protection
Motor control centers
Transformer protection
Protection for UL Listed series-rated molded case circuit
breaker panels
General purpose circuits — mains, feeders and branch
circuits — especially when space is at a premium
FEATURES/BENEFITS
■
Reduce down-time — A glance at the indicating window of
a JTD_ID Indicator fuse pinpoints open fuses immediately.
If the window is dark, the fuse has opened. It’s that simple.
13
JTD_ID Series Indicator POWR-PRO® Class J Fuses
600 VAC
■
Time Delay
■
8/10 – 600 Amperes
POWR-PRO
FUSES
An Inside Look . . .
Plated End Caps – help reduce
corrosion and provide superior
contact that aids in lower heat
generation.
Superior Short-Circuit Elements –
reduce damage to equipment and
enables the Littelfuse JTD_ID to
provide IEC Type II “NO DAMAGE”
protection to IEC and NEMA
motor starters.
Blown Fuse Indicator – incorporates precision-wound elements to
provide consistant and reliable
blown fuse indication.
Stone-Sand Filler – helps provide
I2t and I Peak values well below UL
maximum limits and improves heat
disapation and reliability.
Solid State Overload Section –
patented thermally reversible design
utilizes high-tech aircraft grade
polymers to ensure reliable operation
every time.
Elastomeric Silicone EPR Plug –
a space-age material used in the
patented overload section of the
Littelfuse JTD_ID.
Granular Quartz Filler – assists in quenching
the arc that occurs during overload conditions.
C
D
G
A
14
REFER TO
FIG. NO.
H
A
B
C
D
FIG. 1
AMPERES
F
E
FIG.2
DIMENSIONS IN INCHES (mm in parentheses)
A
B
C
D
E
F
G
H
—
1/2
(12.7)
13/16
(20.6)
—
—
—
—
8/10– 30
1
2-1/4
(57.2)
35 – 60
1
2-3/8
(60.3)
—
5/8
(15.9)
1-1/16
(27.0)
—
—
—
—
70 – 100
2
2-5/8
(66.7)
3-17/32
(89.7)
3-23/32
(94.5)
4-5/8
(117.5)
1
(25.4)
3/4
(19.1)
9/32
(7.1)
1/8
(3.2)
110 – 200
2
3
(76.2)
4-9/32
(108.7)
4-15/32
(113.5)
5-3/4
(146.1)
1-1/2
(38.1)
1-1/8
(28.6)
9/32
(7.1)
3/16
(4.8)
225 – 400
2
3-3/8
(85.7)
5-1/8
(130.2)
5-3/8
(136.5)
7-1/8
(181.0)
2
(50.8)
1-5/8
(41.3)
13/32
(10.3)
1/4
(6.4)
450 – 600
2
3-3/4
(95.3)
5-27/32
(148.4)
6-5/32
(156.4)
8
(203.2)
2-1/2
(63.5)
2
(50.8)
17/32
(13.5)
3/8
(9.5)
JTD_ID Series Indicator POWR-PRO® Class J Fuses
600 VAC
■
Time Delay
8/10 – 600 Amperes
■
POWR-PRO
FUSES
Short Circuit
Current*
Let-Thru
30A
750
925
1,050
1,125
1,200
1,300
1,350
1,400
1,500
1,600
1,700
1,800
2,000
2,175
Current** For Various Fuse Ratings
60A
100A
200A
400A
1,500
1,800
2,800
4,800
1,900
2,450
3,600
5,700
2,100
2,800
4,100
6,500
2,300
3,000
4,400
7,250
2,500
3,300
5,000
8,000
2,600
3,500
5,100
8,400
2,700
3,700
5,400
9,000
2,800
3,900
5,600
9,200
3,000
4,200
6,000
10,000
3,200
4,500
6,400
10,500
3,400
4,900
7,200
11,200
3,600
5,200
7,800
12,200
3,950
6,000
9,000
14,500
4,000
6,500
10,000
16,000
600A
5,000
7,750
9,000
9,700
10,500
11,000
12,000
12,500
13,000
14,000
15,500
16,500
19,000
20,500
600A
400A
60A
1000
30A
15A
* Prospective RMS
Symmetrical Amperes
Short-Circuit Current
**Apparent RMS Symmetrical
Note: Data derived from Peak
Let-Thru Curves
200A
Current-Limiting
Effects of JTD_ID
(600V) fuses
100A
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
50,000
60,000
80,000
100,000
150,000
200,000
15A
565
675
775
825
900
950
1,000
1,050
1,100
1,200
1,300
1,375
1,500
1,600
1000000
PEAK LET-THRU IN AMPERES
TIME IN SECONDS
100
10
1
100000
600A
400A
200A
100A
60A
10000
30A
15A
12A
5.6A
1000
.1
.01
100
100
1
10
100
CURRENT IN AMPERES
1000
10000
1000
10000
100000 200000
AVAILABLE FAULT
SYMMETRICAL R.M.S. AMPERES
15