ETC JLS10

JLS CLASS J FUSES
600 VAC
■
Fast-Acting
■
1 – 600 Amperes
SPECIFICATIONS
Voltage ratings: 600 Volts AC
Interrupting ratings: 200,000 amperes rms symmetrical
Ampere range: 1— 600 amperes
Approvals: UL Listed Class J fuses per UL 248
(formerly UL 198C)
(File No. E81895)
CSA Certified HRCI-J (File No. LR29862)
Federal Specification No. WF1814 (QPL)
GENERAL
PURPOSE
FUSES
AMPERE RATINGS
1
3
6
10
15
20
25
30
35
40
45
50
60
70
80
90
100
110
125
150
175
200
225
250
300
350
400
450
500
600
Example part number (series & amperage): JLS 110
RECOMMENDED FUSE BLOCKS
LJ600 series
Refer to Fuse Block section of this catalog for additional information.
JLS series fuses provide space-saving, fast-acting overload
and short-circuit protection for non-inductive loads. When
used for motors or other inductive loads, the ampere rating of
JLS series fuses must be increased to prevent nuisance
opening on inrush currents. In such applications, JLS fuses
may provide only short circuit protection. Consider using
Littelfuse POWR-PRO® JTD series time-delay fuses in such
circuits.
APPLICATIONS
LONGER EQUIPMENT LIFE
■
ECONOMICAL
■
Extremely current-limiting design often permits use of
readily available, less costly equipment.
■
Manufacturers of equipment containing dual voltage
devices can simplify manufacturing and reduce inventory
by standardizing on 600 volt JLS fuses and Class J fuse
blocks for all AC voltage ratings.
General purpose circuits with little or no motor load.
Resistive loads, such as resistance electric heat.
Loads requiring fast-acting overload protection, such as
equipment containing solid-state devices.
SPACE SAVING
■
JLS fuse characteristics are similar to KLNR/KLSR fastacting Class RK1 fuses, but they are much smaller.
SAFETY
■
200,000 A.I.R. — Reliable interruption of all overcurrents up
to 200,000 amperes.
■
Extremely current limiting — Stops damaging short-circuit
current faster than any mechanical protective device.
■
Fast-acting — Provides fast-acting protection to equipment
such as variable speed drives, rectifiers and other equipment containing surge-sensitive components.
Current-limiting design reduces damage to equipment
caused by heating and magnetic effects of short-circuit
currents.
EASY TO USE
■
200,000 A.I.R. rating minimizes need for short-circuit
calculations.
NOTE: Littelfuse JLS fuses are not time-delay fuses. For
applications where short-duration surges and spikes may
cause nuisance fuse opening, consider the use of Littelfuse
POWR-PRO® JTD series time-delay fuses.
37
JLS CLASS J FUSES
600 VAC
■
Fast-Acting
1 — 600 Amperes
■
C
G
F
D
GENERAL
PURPOSE
FUSES
E
Fig. 2
Fig. 1
DIMENSIONS IN INCHES (mm in parentheses)
REFER TO
FIG. NO.
AMPERES
H
A
B
C
D
A
A
B
C
D
E
F
G
H
—
1/2
(12.7)
13/16
(20.6)
—
—
—
—
—
5/8
(15.9)
1-1/16
(27.0)
—
—
—
—
70 – 100
2
2-5/8
(66.7)
3-17/32
(89.7)
3-23/32
(94.5)
4-5/8
(117.5)
1
(25.4)
3/4
(19.1)
9/32
(7.1)
1/8
(3.2)
110 – 200
2
3
(76.2)
4-9/32
(108.7)
4-15/32
(113.5)
5-3/4
(146.1)
1-1/2
(38.1)
1-1/8
(28.6)
9/32
(7.1)
3/16
(4.8)
225 – 400
2
3-3/8
(85.7)
5-1/8
(130.2)
5-3/8
(136.5)
7-1/8
(181.0)
2
(50.8)
1-5/8
(41.3)
13/32
(10.3)
1/4
(6.4)
450 – 600
2
3-3/4
(95.3)
5-27/32
(148.4)
6-5/32
(156.4)
8
(203.2)
2-1/2
(63.5)
2
(50.8)
17/32
(13.5)
3/8
(9.5)
60A
600A
2-3/8
(60.3)
400A
1
200A
35 – 60
100A
1
30A
1 – 30
2-1/4
(57.2)
1000
800
600
1000000
800000
600000
400
300
400000
300000
200
200000
100
80
60
100000
80000
60000
PEAK LET-THRU IN AMPERES
40
30
10
8
6
4
3
2
1
.8
.6
.4
.3
200A
100A
60A
10000
8000
6000
30A
4000
3000
2000
200
.04
.03
60000
80000
100000
30000
40000
20000
6000
8000
10000
3000
4000
2000
600
800
1000
300
400
200
60
80
100
30
40
20
8
10
CURRENT IN AMPERES
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
200000
60000
80000
100000
30000
40000
20000
6000
8000
10000
3000
4000
2000
600
800
1000
300
400
100
100
.02
5
20000
400
300
.1
.08
.06
38
400A
1000
800
600
.2
.01
600A
40000
30000
200
TIME IN SECONDS
20