OMRON K8AB

Temperature Monitoring Relay
K8AB-TH
CSM_K8AB-TH_DS_E_2_1
Compact and Slim Relay Ideal for
Temperature Alarms and Monitoring
• Excessive temperature increases can be prevented and
abnormal temperatures can be monitored.
• Temperature monitoring in slim design with a width of just
22.5 mm.
• Simple function settings using DIP switch.
• Universal-input support for thermocouple or Pt100 sensor input.
• Selectable output relay: Non-fail safe/fail safe.
• Alarm status identification with LED indicator.
Refer to Safety Precautions for All
Temperature Controllers.
Features
• This Temperature Monitoring Relay was designed specially for
monitoring abnormal temperatures to prevent excessive
temperature increase and to protect equipment.
• A relay capacity of 3 A at 250 VAC (resistive load) is provided in a
slim body only 22.5 mm wide.
An output latch function is also supported.
• Settings can be made and functions can be selected using the DIP
switch.
• Reduce the number of models by using universal-input support for
thermocouple or Pt100 sensor input.
Selecting Functions and Modes
• The following settings are provided: alarm mode (upper limit/lower
limit), enable/disable latch, °C/°F, relay output non-fail safe/fail safe,
setting protection.
Terminal Wiring with Ferrules
• Wire with 2 × 2.5 mm2 solid wire or 2 × 1.5 mm2 wiring ferrules.
Third-party Certification of CE Mark Compliance, Certified UL
Standard Compliance, and Certified TÜV and SUD Standard
Compliance
Model Number Structure
■ Model Number Legend
K8AB-TH1@@
1
2
3 4
1. Basic Model
K8AB: Measuring and Monitoring Relay
2. Function
TH1: Temperature Monitoring Relay
3. Setting Range
1: Low-temperature range (0 to 399°C: setting in increments of
1°C)
2: High-temperature range (0 to 1700°C max.: setting in
increments of 10°C)
4. Output Form
S: One SPDT relay output
Ordering Information
■ List of Models
Size
Supply voltage
Type
K8AB-TH
100 to 240 VAC Temperature
22.5 × 90 × 100 mm
input
24 VAC/VDC
Number of
outputs
1 (relay)
Input type
Setting unit (setting range)
Thermocouple/Pt100 Unit: 1°C/°F (0 to 399°C/°F)
Thermocouple
Unit: 10°C/°F (See note 1.)
Model
K8AB-TH11S
K8AB-TH12S
Thermocouple/Pt100 Unit: 1°C/°F (0 to 399°C/°F)
K8AB-TH11S
Thermocouple
K8AB-TH12S
Unit: 10°C/°F (See note 1.)
Note: 1. Refer to page 3 for setting ranges.
2. Specify the power supply voltage when ordering. Different models must be ordered for 100 to 240 VAC and 24 VAC/DC.
1
K8AB-TH
Specifications
■ Ratings
Item
Power supply voltage
100 to 240 VAC 50/60 Hz
Allowable voltage range
85% to 110% of power supply voltage
Power consumption
5 VA max.
Sensor inputs
24 VAC 50/60 Hz or 24 VDC
2 W max. (24 VDC), 4 VA max. (24 VAC)
K8AB-TH11S
Thermocouple: K, J, T, E; Platinum-resistance thermometer: Pt100
K8AB-TH12S
Thermocouple: K, J, T, E, B, R, S, PLII
Contact input
ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input
ON residual voltage: 1.5 V max., OFF leakage current: 0.1 mA max.
Output relay
One SPDT relay (3 A at 250 VAC, resistive load)
External inputs
(for latch setting)
Leakage current: Approx. 10 mA
Setting method
Rotary switch setting (set of three switches)
Indicators
Power (PWR): Green LED, Relay output (ALM): Red LED
Other functions
Alarm Mode (upper limit/lower limit), non-fail safe/fail safe selection, output latch, setting protection, temperature
unit °C/°F
Ambient operating temperature
−10 to 55°C (with no condensation or icing)
Ambient operating humidity
Relative humidity: 25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)
■ Characteristics
Setting accuracy
±2.0% of full scale
hysteresis width
2°C
Output relay
Resistive load
3 A at 250 VAC (cosφ = 1), 3 A at 30 VDC (L/R = 0 ms)
Inductive load
1 A at 250 VAC (cosφ = 0.4), 1 A at 30 VDC (L/R = 7 ms)
Minimum load
10 mA at 5 VDC
Maximum contact voltage
250 VAC
Maximum contact current
3 A AC
Maximum switching capacity
1,500 VA
Mechanical life
10,000,000 operations
Electrical life
Make: 50,000 times, Break: 30,000 times
Sampling cycle
500 ms
Insulation resistance
20 MΩ (at 500 V) between charged terminals and exposed uncharged parts
20 MΩ (at 500 V) between any charged terminals (i.e., between input, output, and power supply terminals)
20 MΩ (at 500 V) between contacts (open)
Dielectric strength
2,000 VAC 50/60 Hz for 1 min between charged terminals of different polarity
Vibration resistance
Vibration of 10 to 55 Hz and acceleration of 50 m/s2 for 5 min with 10 sweeps each in X, Y, and Z directions
Shock resistance
150 m/s2 (100 m/s2 for relay contacts) 3 times each in 6 directions in X, Y, and Z directions
Weight
130 g
Degree of protection
IP20
Memory protection
Non-volatile memory (number or writes: 200,000)
Safety
Standards
Approved standards
EN 61010-1
EMC
EN 61326
Application standards
EN 61010-1 (pollution level 2, overvoltage category II)
EMC
EMI:
Radiation Interference Field Intensity:
Noise Terminal Voltage:
EMS:
Immunity ESD:
Immunity RF:
Immunity Burst:
Immunity Conducted Disturbance:
Immunity Surge:
Commercial Frequency
Immunity Magnetic Field:
Immunity Voltage Dip/Interrupting:
Terminal screw tightening torque
EN 61326
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61326
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
EN 61000-4-3: 10 V/m, amplitude-modulated
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3)
EN 61000-4-4: 2 kV power line (level 3)
2 kV output line (relay output) (level 4)
1 kV measurement line and I/O signal lines (level 4)
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 3)
EN 61000-4-5: 1 kV line-to-line: power line, output line
(relay output) (level 2)
2 kV line-to-ground: power line, output line
(relay output) (level 3)
EN 61000-4-8: 30 A/m (50Hz) continuous time
EN 61000-4-11: 0.5 cycle, 100% (rated voltage)
0.54 to 0.55 N·m
Crimp terminals
Two solid wires of 2.5 mm2 or two ferrules of 1.5 mm2 with insulation sleeves can be tightened together.
Case color
Munsell 5Y8/1 (ivory)
Case material
ABS resin (self-extinguishing resin)
Mounting
Mounted to DIN Track or with M4 screws
Dimensions
22.5 × 100 × 90 mm (W × D × H)
2
K8AB-TH
■ Setting Ranges
K8AB-TH11S
Centigrade
Input
Setting
temperature
range
500
400
300
200
100
0
K
J
T
E
Pt100
399
399
399
399
399
0
0
0
0
0
Minimum setting
increment
1°C
Fahrenheit
Input
500
400
300
200
100
0
Setting
temperature
range
K
J
T
E
Pt100
399
399
399
399
399
0
0
0
0
0
Minimum setting
increment
1°F
K8AB-TH12S
Centigrade
Input
Setting
temperature
range
1,800
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
K
J
T
E
B
R
S
1,700
1,700
PLII
1,800
1,300
1,300
850
600
400
100
0
0
0
0
Minimum setting
increment
0
0
0
R
S
PLII
3,000
3,000
10°C
Fahrenheit
Input
Setting
temperature
range
3,200
3,100
3,000
2,900
2,800
2,700
2,600
2,500
2,400
2,300
2,200
2,100
2,000
1,900
1,800
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
Minimum setting
increment
K
J
T
E
B
3,200
2,300
2,300
1,500
1,100
700
300
0
0
0
0
0
0
0
10°F
3
K8AB-TH
Connections
■ Wiring Diagrams
K8AB-TH11S
K8AB-TH12S
Power supply
voltage (See note 1.)
A1
A2
Power supply
14 11 12
Relay output
Power supply
Relay output
Power supply
voltage (See note 1.)
External input
(LATCH_RST)
(See note 2.)
4
5
6
1
2
3
Thermocouple B
B
A
Sensor input
Not used.
External input
(LATCH_RST)
(See note 2.)
Sensor input
A1
A2
14 11 12
4
5
6
Not used.
1
2
3
Not used.
Note: 1. The input power supply depends on
the model: 100 to 240 VAC or
24 VAC/VDC (no polarity)
2. Wiring of the external input terminals
is as shown below.
Thermocouple
Platinum resistance thermometer
■ Operation (Using the Upper-limit Alarm Mode)
Output Latch Enabled (Default Setting:
Latch Enabled)
Power supply
Output Latch Disabled
Power supply
Hysteresis width: 2°C
Alarm setting
Input (current temperature)
Alarm (red) indicator
Latch reset (See note.)
Non-fail safe,
Alarm (relay) output
Fail safe,
Alarm (relay) output
Hysteresis width: 2°C
Alarm setting
Input (current temperature)
Alarm (red) indicator
Non-fail safe,
Alarm (relay) output
Fail safe,
Alarm (relay) output
Note: The output latch is reset using the output latch reset button
on the Temperature Monitoring Relay or the external input terminal.
4
K8AB-TH
Nomenclature
■ Front Operations
Indicators
Item
Usage
Power indicator
(PWR)
Lit: Power supply is ON.
Flashing: SV protected.
Alarm indicator
(ALM)
Lit: Relay is operating.
Flashing: Sensor is disconnected or there is a
Temperature Monitoring Relay error. (See note 1.).
Operation Switches
Power indicator (PWR): Green
Alarm indicator (ALM): Red
Output latch
reset button
Item
Alarm setting
rotary switch
Usage
Output latch reset
button
The output latch can be reset by pressing this button.
(Enabled when latch is enabled.) (See note 2.)
Alarm setting
rotary switch
Set each digit of the alarm set temperature.
K8AB-TH11S: x1, x10, x100 digits
K8AB-TH12S: x10, x100, x1000 digits
Note: 1. The ALM indicator will flash and the relay outputs will turn ON if any
of the following conditions occur.
(1) The temperature input value exceeds the specified range.
(2) The temperature set value exceeds the specified range.
(3) There is an error in the internal circuits.
2. The SV protection will function when the latch reset button is pressed
for at least 5 s.
The power indicator will flash when the SV is protected. To release
the protection, press the latch reset button again for at least 5 s.
TH11
Alarm Setting Rotary Switch
901
456
78
Turn the arrow in the direction of the number to set.
23
■ Function Setting DIP Switch
Function
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
SW1
Alarm mode
SW2
Output latch selector
SW3
SW4
SW5
This DIP switch is provided on the side
of the Temperature Monitoring Relay.
(All switches are OFF for the default
settings.)
OFF
ON
Default
OFF
Upper-limit alarm
ON
Lower-limit alarm
OFF
Enabled
ON
Disabled
OFF
Operation selector: Non-fail safe/ OFF
fail safe
ON
Non-fail safe
Temperature unit
OFF
°C
ON
°F
Input type selector
OFF
OFF
Fail safe
OFF
Refer to the following table.
OFF
SW6
OFF
SW7
SW8
OFF
Not used.
---
OFF
K8AB-TH11S
Sensor type
K
J
T
E
SW5
OFF
OFF
OFF
OFF
SW6
OFF
OFF
ON
ON
SW7
OFF
ON
OFF
ON
Pt100*
ON
Pt100*
Pt100*
Pt100*
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
* The type will be Pt100 for any of these settings.
K8AB-TH12S
Sensor type
K
J
T
E
SW5
OFF
OFF
OFF
OFF
SW6
OFF
OFF
ON
ON
SW7
OFF
ON
OFF
ON
B
ON
R
S
PLII
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
5
K8AB-TH
■ Functions
SV Protection
This function protects (i.e., prohibits changing) the alarm setting,
operating method, and modes for the Temperature Monitoring Relay
that have been set on the rotary switches and DIP switch.
The protection function is activated by pressing the output latch reset
button on the Temperature Monitoring Relay for at least 5 s or by
turning ON the input to the external input terminal for at least 5 s.
The power indicator will flash when the protection is activated.
The protection function can be released by pressing the output latch
reset button on the Temperature Monitoring Relay for at least 5 s or
by turning ON the input to the external input terminal for at least 5 s.
The power indicator will light while the protection is being reset.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Temperature Monitoring Relay
K8AB-TH
Mounting Hole Dimensions
Two, M4 screws or two, 4-dia screws
22.5
5
100
102
90
5
Note: Pull out and use the
hooks when mounting
using screws.
■ Track Mounting Products (Sold Separately)
Mounting Track
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
1000 (500) (See note.)
10
25
15 (5)
(See note.)
27±0.15
1
Note: Dimensions in parentheses are for the PFP-50N.
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
6
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2008.12
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2008 All Right Reserved.