OMRON D4BS-6AFS

Safety-door Switch
D4BS
Safety-door Switch’s Special Operation
Key Directly Pulls Apart the Contacts
from Each Other and Contributes to the
Safety of the Production Site
• Conforms to EN (TÜV) standards corresponding to
the CE marking.
• Approved by UL, CSA, BIA, and SUVA standards.
• The switch contact is opened by a direct opening
mechanism (NC contacts only) when the protective
cover is opened. The EN-approved direct opening
mechanism is indicated by
on the Switch.
• Degree of protection of the switch box: IP67
(EN60947-5-1).
• Series includes models with gold-plated contacts for
handling the micro-load range.
• Metric conduit types available.
Model Number Structure
Model Number Legend
Switch
D4BS -
Operation Key
D4BS - K
S
1
2
3
1
1. Conduit
1: PG13.5 (1 conduit)
2: G1/2 (1 conduit)
3: 1/2-14NPT (1 conduit)
4: M20
5: PG13.5 (3-conduit)
6: G1/2 (3-conduit)
7: 1/2-14NPT (3-conduit)
8: M20 (3-conduit)
2. Built-in Switch
1. Operation Key Type
5: 1NC/1NO (slow-action)
1: Horizontal mounting
6: 1NC/NO (slow-action), gold-plated contacts
2: Vertical mounting
A: 2NC (slow-action)
3: Adjustable mounting (Horizontal)
B: 2NC (slow-action), gold-plated contacts
3. Head Mounting Direction
F: Four mounting directions possible (front-side mounting at
shipping)
Ordering Information
List of Models
Switches
Type
Mounting direction
1-conduit
Front-side
mounting
3-conduit
D-104
Conduit size
Pg13.5
G1/2
M20
Pg13.5
G1/2
M20
1NC/1NO
(Slow-action)
D4BS-15FS
D4BS-25FS
D4BS-45FS
D4BS-55FS
D4BS-65FS
D4BS-85FS
2NC (Slow-action)
D4BS-1AFS
D4BS-2AFS
D4BS-4AFS
D4BS-5AFS
D4BS-6AFS
D4BS-8AFS
Safety Sensors / Components
Operation Keys (Order Separately)
Type
Model
Horizontal mounting
D4BS-K1
Vertical mounting
D4BS-K2
Adjustable mounting
(Horizontal)
D4BS-K3
Specifications
Approved Standards
Agency
Standards and EC Directives
Standard
File No.
EN60947-5-1
R9351022
(Direct opening: approved)
UL
CSA
BIA
SUVA
UL508
CSA C22.2 No. 14
GS-ET-15
SUVA
E76675
LR45746
9303323
E6187.d
D4BS
TÜV Rheinland
Conforms to the following EC Directives:
Machinery Directive
Low Voltage Directive
EN50041
EN1088
Approved Standard Ratings
TÜV (EN60947-5-1)
Utilization category
Rated operating current (Ie)
Rated operating voltage (Ue)
AC-15
2A
400 V
Note: Use a 10-A fuse type a gI or gG that conforms to IEC269 as a short-circuit protection device.
UL/CSA (UL508, CSA C22.2 No. 14)
A600
Rated voltage
120 VAC
240 VAC
480 VAC
600 VAC
D4BS
Current
Carry current
10 A
Make
60 A
30 A
15 A
12 A
Volt-amperes
Break
6A
3A
1.5 A
1.2 A
Make
7,200 VA
Break
720 VA
D-105
Characteristics
Degree of protection (see note 2)
IP67 (EN60947-5-1)
Mechanical:1,000,000 operations min.
Electrical:500,000 operations min. (10 A at 250 VAC, resistive load)
0.1 m/s to 0.5 m/s
30 operations/min max.
50/60 Hz
2 x 2 mm min.
19.61 N min. (EN60947-5-1)
20 mm min. (EN60947-5-1)
23 mm min.
100 MW min. (at 500 VDC) between terminals of same or different
polarity, between each terminal and ground, and between each terminal and non-current-carrying metal part
25 mW max. (initial value)
600 V (EN60947-5-1)
20 A (EN60947-5-1)
Impulse dielectric strength (Uimp) 4 kV (EN60947-5-1) between terminals of same or different polarity, between current-carrying metal
parts and ground, and between each terminal and non-current-carrying metal part
1,500 V max. (EN60947-5-1)
100 A (EN60947-5-1)
3 (EN60947-5-1)
Class I (with ground terminal)
Malfunction: 10 to 500 Hz, 0.65-mm single amplitude
Destruction:1,000 m/s2 min. (IEC68-2-27)
Malfunction:300 m/s2 min. (IEC68-2-27)
Operating:-40°C to 80°C (with no icing)
Operating:95% max.
Approx. 285 g (in the case of D4BS-15FS)
Durability (see note 3)
Operating speed
Operating frequency
Rated frequency
Contact gap
Direct opening force (see note 4)
Direct opening travel (see note 4)
Full stroke
Insulation resistance
Contact resistance
Rated insulation voltage (Ui)
Conventional enclosed thermal current (Ithe)
Dielectric strength (Uimp)
Switching overvoltage
Conditional short-circuit current
Pollution degree (operating environment)
Insulation class
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Weight
Note: 1. The above values are initial values.
2. Although the switch box is protected from dust, oil, or water penetration, do not use the D4BS in places where dust, oil, water, or chemicals
may penetrate through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
3. The durability is for an ambient temperature of 5° C to 35° C and an ambient humidity of 40% to 70%. Contact your OMRON sales representative for more detailed information on other operating environments.
4. These figures are minimum requirements for safe operation.
Contact Form (Diagrams Show State with Key Inserted)
Model
Contact form
Diagram
Zb
D4BS-#5#S
1NC/1NO
11
12
23
24
Zb
D4BS-#A#S
2NC
11
12
21
22
11 - 12
23 - 24
Stroke
Operation Key
insertion completion position
ON
Extraction
completion
position
11 - 12
21 - 22
Stroke
Operation Key
insertion completion position
Remarks
Terminals 11-12 and
23-24 can be used as
unlike poles.
ON
Extraction
completion
position
Only NC contact 11-12
has an approved direct
opening mechanism.
NC contacts 11-12 and
21-22 have an
approved direct
opening mechanism.
Terminals 11-12 and
21-22 can be used as
unlike poles.
Note: The terminal numbers are in accordance with EN50013, and the contact symbols are in accordance with IEC947-5-1.
D-106
Safety Sensors / Components
Nomenclature
Head
The switch head is coated with easy-to-see red
paint. The mounting direction of the switch head can
be varied to any of the four directions.
Operation Key
D4BS's exclusive-use Operation Key is provided
to assure accurate switching operation.
Set Zone Mark
A triangular Set Zone Mark makes it
easy to adjust the operating position
when inserting the Operation Key.
Seal Ring (NBR)
Oil Seal (NBR)
The operation plunger employs an oil seal, with
which the switch box meets the requirements of
IP67 (the sealing capability of the Operation Key's
insertion mouth is IP00).
Built-in Switch
A shearing force contact separating mechanism (NC
contact) is employed, which positively pulls apart the
contacts from each other by using shearing force if
any abnormality such as contact welding should occur
in the contact area.
Seal Packing (NBR)
Conduit Opening
Available in four different types of conduit
threads: Pg 13.5, G1/2, or 1/2-14NPT, M20.
There is a difference in level between the NC and NO
terminal, which assures easy wiring.
D4BS
Ground Terminal Screw
A ground terminal is provided to
improve safety. (Built into the
Unit.)
D4BS
D-107
Dimensions
Note: 1. All units are in millimeters unless otherwise indicated.
2. Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.
3. The conduit thread varies with the model as follows:.
Conduit thread
Pg 13.5
G1/2
M20
Model
D4BS-1##S, D4BS-5##S
D4BS-2##S, D4BS-6##S
D4BS-4##S, D4BS-8##S
Switches
1-conduit
D4BS-1##S
D4BS-2##S
D4BS-4##S
31.4
17
41
Red
16
Four, M3.5 head
clamping screws
7
34.5
35
(111.5)
Two, 5.3 dia.
mounting holes
Two, M4 cover
clamping screws
60±0.2
31.4
17
41
10±5 mm
Direct opening force
Direct opening stroke
19.61 N min.
20 mm min.
Operating
characteristics
D4BS-5##S
D4BS-6##S
D4BS-8##S
Key insertion force
Key extraction force
19.61 N max.
19.61 N max.
Four, M3.5 head
clamping screws
16
7
Red
19.61 N max.
19.61 N max.
D4BS-1##S: Pg13.5
D4BS-2##S: G1/2
D4BS-4##S: 1/2-14NPT
15
31.5
43
40+1
0
3-conduit
D4BS-5##S
D4BS-6##S
D4BS-8##S
Key insertion force
Key extraction force
Pretravel (PT)
5.3
30±0.1
8
D4BS-1##S
D4BS-2##S
D4BS-4##S
77
Cover
7.3
Operating
characteristics
34.5
5.3
(110)
Six, 5.3 dia.
mounting holes
Four, M3.5 x 10 cover
clamping screws
Two caps
Cover
30±0.2
50.9
66.4
Pretravel (PT)
71.4 75.4
17.2
51
28.5
57
63
D4BS-5##S: 3-Pg13.5
D4BS-6##S: 3-G1/2
D4BS-8##S: 3-1/2-14NPT
10±5 mm
Direct opening force
Direct opening stroke
19.61 N min.
20 mm min.
Two, 5+0.15
dia. holes (6 mm deep)
-0
35.7
38.3
Operation Keys
53.7
D4BS-K1
D4BS-K2
78.7
20±0.15
40.7
12
Black
26
5.3 5.3
26
40±0.15 52.4
15
Two, 2.65R
7.5
2.5
36
20
11.4
5.3 12
7.5
20
11.4
5
5
4 dia.
4 dia.
40
12 20
2.5
15
D4BS-K3
Black
26
40
30±0.15
(80.7)
36
2.5
11.4
Red
30
5.3 dia.
mounting hole
D-108
5.3 ¥ 7.3 mounting long hole
Black
7.3 15
15
36
13
19.5±0.15
5
(37.8)
4 dia.
17.5
34.6
M4 Allen-head bolt
Safety Sensors / Components
With Operation Key Inserted
Horizontal Mounting
D4BS-1##S +D4BS-K1
D4BS-2##S +D4BS-K1
D4BS-4##S +D4BS-K1
Red
53.5 min.
58 max.
Vertical Mounting
D4BS-1##S +D4BS-K2
D4BS-2##S +D4BS-K2
D4BS-4##S +D4BS-K2
54.5 min.
59 max.
Operation Key insertion
radius in horizontal
direction: R ≥ 1000
Operation Key insertion
radius in horizontal
direction: R ≥ 1200
53.5 min.
58 max.
Operation Key insertion
radius in horizontal
direction: R ≥ 1000
Operation Key insertion
radius in horizontal
direction: R ≥ 1200
54.5 min.
59 max.
D4BS
Red
Adjustable Mounting (Horizontal)
D4BS-1##S +D4BS-K3
D4BS-2##S +D4BS-K3
81.5 min.
D4BS-4##S +D4BS-K3
86 max.
Operation Key insertion
radius in horizontal
direction: R ≥ 150
81.5 min.
86 max.
Operation Key insertion
radius in horizontal
direction: R ≥ 1000
Red
Note: "R" is the Operation Key insertion radius.
Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.
D4BS
D-109
Precautions
Securing the Door
Caution
Do not dismount the Operation Key from the door intentionally and
insert it to the Switch with the door open. Machine may start operating and injury or death may be caused.
Mount the Operation Key at a location where it will not come in contact with users when the door is opened or closed.
If the Operation Key on the closed door is pulled outside the set zone
by a force caused by vibration, the door’s weight, or the door cushion
rubber, the switch contact may be opened (causing the machinery to
stop) or the D4BS may be damaged. Secure the door with hooks so
that it will remain within the set zone.
When operating the D4BS as a part of a safety category circuit to
prevent injury, operate the NC contacts that have a direct opening
mechanism in direct opening mode. For safety purposes, tighten the
switch body and Operation Key with one-way screws or equivalents
or install a switch protection cover and warning label for safety purposes to prevent easy removal of the D4BS.
Extra space
Connect the fuse to the D4BS in series to prevent it from short-circuit
damage. The value of the breaking current of the fuse must be calculated by multiplying rated current by 150% to 200%. When using the
D4BS with EN ratings, use 10-A fuse Type gI or gG that complies
with IEC60269.
Set zone
Correct Use
Operating Environment
Mounting
Make sure in advance that the environment is suitable, with no oil,
water, or chemicals, as these may cause the seal to deteriorate,
resulting in faulty contact, faulty isolation, current leakage, or burning.
Do not use the Switch as a stopper. Be sure to install a stopper as
shown in the following illustration when mounting the Switch. The
range of space “a” must be determined according to the available set
zone of the Operation Key.
Do not use the D4BS in the following locations:
•
•
•
•
Locations subject to severe temperature changes
Locations subject to high temperatures or condensation
Locations subject to severe vibration
Locations where the product may come into direct contact with processing waste or dust
Stopper
a
Switch
Operation Key
Be sure to use a special Operation Key only. Do not operate the
D4BS with anything other than the special Operation Key, otherwise
the D4BS may break or the safety of the system may not be maintained.
Do not impose excessive force on the Operation Key inserted into
the D4BS or drop the D4BS with the Operation Key inserted, otherwise the Operation Key may deform or break.
Refer to Dimensions for the mounting dimension of the Operation
Key and mount the Operation Key correctly. The Operation Key will
soon become damaged or worn out if it is not mounted correctly.
Make sure that the Operation Key can be inserted properly with a tolerance of ±0.5 mm in the upward, downward, left, or right direction,
otherwise the D4BS may soon become damaged.
Excessive force
±0.5 min.
Drop
Secure the Operation Key with a one-way screw, or an equivalent, so
that the Operation Key cannot be easily removed.
D-110
±0.5 min.
Safety Sensors / Components
Other
Mounting Dimensions (M5)
Make sure that the D4BS is located outside the safety door and that
no metal dust, oil, or chemical will be sprayed onto the D4BS. Otherwise, the D4BS may soon fail to operate due to the penetration of
metal dust, oil, or chemical.
Standard Model
Three-conduit Model
30
40
42
Tightening Torque
Be sure to tighten each screw of the D4BS properly, otherwise the
D4BS may malfunction.
59.3±0.1
60
Protruding portions
27±0.1
30
5 -0.05
-0.15 dia. holes, max. height 5
Mounting hole
Mounting side
Insertion hole for protrusions
-0.05
dia. holes, max. height 5
5-0.15
1
2
3
4
5
6
7
Type
M3.5 terminal screw (including
ground terminal screw)
Cover mounting screw
(see note 1)
Head mounting screw
M5 body mounting screw
(see note 2)
Operation Key mounting screw
Connector
Cap screw
Torque
0.59 to 0.78 N·m
Operating Key Mounting Dimensions
Horizontal Mounting
1.18 to 1.37 N·m
Two, M5
D4BS
No.
The D4BS can be mounted more securely by adding two protruding
portions, each of which is 5 mm maximum in height and
5 –0.05/–0.15 mm in diameter as shown below.
0.78 to 0.98 N·m
20±0.1
4.90 to 5.88 N·m
2.35 to 2.75 N·m
1.77 to 2.16 N·m
1.27 to 1.67 N·m
Note: 1. Apply a torque of 0.78 o 0.88 N·m if the D4BS is a three-conduit model.
2. Apply a torque of 4.90 to 5.88 N·m in the case of an Allenhead bolt. If it is a pan head screw, apply a torque of 2.35 to
2.75 N·m.
Vertical Mounting
Two, M5
40±0.1
Adjustable Mounting (Horizontal)
Two, M5
30±0.1
Changes in Head Mounting Direction
By removing the screws on the four corners of the head, the head
can be reset in any of four directions. The head direction can be
changed with or without the Operation Key inserted in the head.
Make sure that no foreign materials penetrate through the head and
that the head is tightened securely within the proper torque range.
D4BS
D-111
Wiring
Connector
Do not connect the lead wires directly to the terminals. Connect the
lead wires through insulation tubes and M3.5 crimp terminals.
Tighten each terminal screw within the proper torque range.
Tighten the connector to a suitable torque. Excessive tightening
torque may damage the casing.
The proper lead wire is AWG20 to AWG14 (0.5 to 2.5 mm2) in size.
dz dia.:
D dia.:
B:
L:
F:
I:
3.7
4.5
7.0
20.2
7.7
9.0 (mm)
When using a 1/2-14NPT conduit, apply sealing tape between connector and conduit opening so that the enclosure will confirm to IP67.
If using a Pg13.5 conduit, use an ABS-08 Pg13.5 connector or an
ABS-12 Pg13.5 connector (manufactured by Nippon Flex).
Use a connector (SC Series, sold separately) suitable for the outer
diameter of the cable.
When wiring a 3-conduit model, securely tighten the cap screw provided for unused conduit openings.
D dia.
dz dia.
Make sure that all crimp terminals are correctly connected and
located within the casing or cover as shown below.
Incorrect
Correct
Maintenance and Repairs
The user must not maintain or repair equipment incorporating any
D4BS model. Contact the manufacturer of the equipment for any
maintenance or repairs required.
Terminal screw
Crimp terminal
Incorrect
Correct
Crimp
terminal
Terminal screw
Terminal screw
Cover
Cover
Casing
Crimp terminal
Casing
Crimp terminal
Crimp terminal
D-112