OMRON G79

9
Relay Output Blocks
G70D
Compact, 16-Point Output Blocks
Save Space in Control Panels
1 Compact standard version or
quick-to-service vertical models
1
1
1
1
Power MOSFET or relays installed
Built-in diode absorbs coil surge
All have operation indicators
Terminal blocks accept M3.5 fork-type
crimp terminals
1 Expansion terminal block for vertical
èò
models allows power line connections
1 Mounts to DIN rail track or with screws
1 Dedicated cables for high-density PLC
modules available (sold separately)
Ordering Information
3 RELAY OUTPUT BLOCKS
Appearance
Output points
16 points
(SPST
NO x 16)
(SPST-NO
includes relay
g tool.
pulling
Rated
voltage
24 VDC
Output type
Internal I/O
circuit common
Part number
NPN (+ common)
G70D-SOC16 DC24
PNP (-- common)
G70D-SOC16-1 DC24
NPN (+ common)
G70D-FOM16
PNP (-- common)
G70D-FOM16-1 DC24
Relay outputs
NPN (+ common)
G70D-VSOC16
Power MOSFET
relay outputs
NPN (+ common)
G70D-VFOM16
Relay outputs
Power MOSFET
relay out
uts
outputs
16 points
(SPST-NO x 16)
24 VDC
G70D
G70D
3 GENERAL-PURPOSE CONNECTING CABLES
The following cables can be connected to I/O boards and PLC modules from any manufacturer.
Length
Item
Connecting cable with
crimp hook
terminals
Connecting cable with
loose wires
Part number
1 m (3.28 ft)
G79-Y100C
1.5 m (4.92 ft)
G79-Y150C
2 m (6.56 ft)
G79-Y200C
3 m (9.84 ft)
G79-Y300C
5 m (16.40 ft)
G79-Y500C
2 m (6.56 ft)
G79-A200C
5 m (16.40 ft)
G79-A500C
3 DEDICATED CONNECTING CABLES FOR OMRON PLC MODULES
The following cables are designed to connect directly to Omron PLC modules and have dedicated connectors for specific models.
Item
Connecting cable with
one connector
for high-density
I/O modules
Connecting cable with
two connectors
g
y
for high-density
I/O modules
d l
Connecting cable with
three connectors
for CS1 highdensity I/O
modules
Length
Part number
1 m (3.28 ft)
G79-100C
1.5 m (4.92 ft)
G79-150C
2 m (6.56 ft)
G79-200C
3 m (9.84 ft)
G79-300C
5 m (16.40 ft)
G79-500C
1 m (3.28 ft) + 0.75 m (2.46 ft)
G79-O100C-75
2 m (6.56 ft) + 1.75 m (5.74 ft)
G79-O200C-175
3 m (9.84 ft) + 2.75 m (9.02 ft)
G79-O300C-275
5 m (16.40 ft) + 4.75 m (15.58 ft)
G79-O500C-475
1.5 m (4.92 ft) + 1.25 m (4.10 ft) + 1 m (3.28 ft)
G79-150C-125-100
2 m (6.56 ft) + 1.75 m (5.74 ft) + 1.5 m (4.92 ft)
G79-200C-175-150
3 m (9.84 ft) + 2.75 m (9.02 ft) + 2.5 m (8.20 ft)
G79-300C-275-250
3 ACCESSORIES
Item
Applicable output blocks
Rated voltage
Part number
Shorting bar
G70D-VSOC16, G70D-VFOM16

G6D-4-SB
Expansion terminal block
G70D-VSOC16, G70D-VFOM16

G70D-ET
Replacement relays
y
G70D-VSOC16, G70D-SOC16
24 VDC; minimum load 10 mA at 5 VDC
G6D-1A DC24
G70D-VFOM16, G70D-FOM16
24 VDC
G3DZ-2R6PL DC24
2
G70D
G70D
Specifications
Power MOSFET Relay (G3DZ) Specifications
3 RATINGS
The following values apply to the G6D Relay mounted to the
G70D and do not apply to the G6D Relay itself before it is
mounted.
Electromechanical Relay (G6D) Specifications
Coil Ratings
The following values apply to the G3DZ Relay mounted to the
G70D and do not apply to the G3DZ Relay itself before it is
mounted.
Input Ratings
Rated voltage
24 VDC
Operating voltage
19.2 to 28.8 VDC
Rated voltage
24 VDC
Rated current
10.5 mA
Coil resistance
2,880 Ω
Input impedance
Must operate voltage
70% max. of rated voltage
4 kΩ ±20%
Rated current
Release voltage
10% min. of rated voltage
8.2 mA ±20%
Max. allowable voltage
130% of rated voltage
Power consumption
Approx. 200 mW
Note: 1. The must operate voltage is 75% max. of the rated
voltage if the Relay is mounted upside down.
2. Rated current and coil resistance were measured at a
coil temperature of 23EC (73.4EF) with a tolerance of
±10%.
3. Operating characteristics were measured at a coil temperature of 23EC (73.4EF).
4. The maximum allowable voltage is the maximum value
of the allowable voltage range for the relay coil operating power supply. There is no continuous allowance.
5. The rated current includes the current consumption of
the operation indicator.
Voltage level
Must operate
19.2 VDC max.
Must release
1 VDC min.
Note: The rated current includes the current consumption of the
operation indicator.
Output Ratings
Load voltage
3 to 264 VAC, 3 to 125 VDC
Load current
100 µA to 0.3 A
Inrush current
6 A (10 ms)
Contact Ratings
Load
Resistive load (cosφ = 1)
Rated load
3 A at 250 VAC, 3 A at 30 VDC
Rated carry current
5 A (See Note 1)
Max. switching voltage
250 VAC, 30 VDC
Max. switching current
5A
Max. switching capacity
1,250 VA, 150 W
Error rate (level p)
(reference value)
(see note 2)
5 VDC, 1 mA
Life expectancy
Electrical: 100,000 operations
min. (under and at the rated
load at 1,800 operations/hr)
Mechanical: 20,000,000
operations min. (at 18,000
operations/hr)
Note: 1. This value is for when the maximum 8 points are ON.
2. This value is for a switching frequency of 120 times per
minute.
3
G70D
G70D
3 CHARACTERISTICS
Part number
G70D-VSOC16/
G70D-SOC16 (-1)
Output type
Relay outputs
Contact form
16 points (SPST-NO x 16)
Contact mechanism
Single

Contact resistance
100 mΩ max. measured at 1 A, 5 VDC

Insulation method

Photocoupler
Must operate time
10 ms max. at 23°C (73.4°F) ambient
temperature
6 ms max.
Release time
10 ms max. at 23°C (73.4°F) ambient
temperature
10 ms max.
Output ON-resistance

2.4 Ω max.
Leakage current at OFF-state

10 µA max. at 125 VDC
Max. switching frequency
Mechanical: 18,000 operations/hr
Rated load: 1,800 operations/hr

Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC for 1 min between coil and contact
Noise immunity
Power input (normal mode):
Power input (common mode):
Input cable (coiling):
Unit body (coiling):
Vibration resistance
Shock resistance
G70D-SOC16(-1)
G70D-VFOM16/
G70D-FOM16 (-1)
G70D-FOM16 (-1)
Power MOSFET Relay outputs
2,000 VAC for 1 min between input and output
terminals
600 V for 10 min with a pulse width of 100 ns/1 µs
1.5 kV for 10 min with a pulse width of 100 ns/1 µs
1.5 kV for 10 min with a pulse width of 100 ns/1 µs
600 V for 10 min with a pulse width of 100 ns/1 µs
Destruction
10 to 55 Hz, 1.0--mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction
10 to 55 Hz, 0.75--mm double amplitude for 2 hrs each in X, Y, and Z directions
Destruction
300 m/s2
Malfunction
100 m/s2
Operating voltage range
24 VDC +10%/ --15%
Current consumption
Approx. 170 mA at 24
VDC (See Note 2)
Cable length
Between block and controller:
5 m max. (reference value for AWG28)
Between block and external device: Dependent on load
LED color
Operation indicator:
orange
Operation indicator:
orange
Power supply: green
Operation indicator:
orange
Operation indicator:
orange
Power supply: green
Coil surge absorber
Ambient
temperature
Ambient humidity
Approx 300 mA at 24
VDC (See Note 2)
Approx. 125 mA at 24
VDC (See Note 3)
Approx. 300 mA at 24
VDC (See Note 3)
Diode (600 V, 1 A)
Diode (400 V, 0.3 A)
Diode (600 V, 1 A)
Diode (400 V, 0.3 A)
Operating
--25°C to 55°C (--13°F
to 131°F) with no
icing or condensation
0°C to 55°C (32°F to
131°F) with no icing
or condensation
--25°C to 55°C (--13°F
to 131°F) with no
icing or condensation
0°C to 55°C (32°F to
131°F) with no icing
or condensation
Storage
--25°C to 65°C (--13°F
to 149°F) with no
icing or condensation
--20°C to 65°C (--4°F
to 149°F) with no
icing or condensation
--25°C to 65°C (--13°F
to 149°F) with no
icing or condensation
--20°C to 65°C (--4°F
to 149°F) with no
icing or condensation
Operating
45% to 85% RH
35% to 85% RH
45% to 85% RH
35% to 85% RH
Mounting strength
No damage when 49 N pull load was applied for 1 s in all directions (except for 9.8 N min. in
direction of rail)
Terminal strength
Tightening torque: 0.78 to 1.18 N : m
Pull strength:
49 N for 1 min
Weight (See Note 4)
Approx. 280 g
Approx. 200 g
Approx. 280 g
Approx. 200 g
Note: 1. The above values are initial values.
2. Current consumption is when all points are ON and includes G6D Relay coil current but does not include any external load
current.
3. Current consumption is when all points are ON and includes G3DZ input current but does not include any external load current.
4. The Relay Output Block weighs approximately 315 g with the Expansion Terminal Block mounted.
4
G70D
G70D
Engineering Data
3 RELAY OUTPUT MODELS
G70D-SOC16(-1)/G70D-VSOC16
DC resistive load
Life Expectancy
AC resistive load
Life expectancy (x 104 operations)
Switching current (A)
Max. Switching Capacity
Switching voltage (V)
250 VAC/30 VDC resistive load
Switching current (A)
3 POWER MOSFET OUTPUT MODELS
G70D-FOM16(-1)/G70D-VFOM16
Inrush Current Resistivity
Non-repetitive (Keep the inrush current to half the rated
value or less if it occurs repeatedly.)
Load current (A)
Inruch current (A.Peak)
Load Current vs. Ambient Temperature Characteristics
Ambient temperature (°C)
Energizing time (ms)
5
G70D
G70D
Operation
3 INTERNAL CIRCUIT
G70D-SOC16/G70D-FOM16
NPN-compatible output terminal (+ common output): A controller with an NPN transistor (-- common output) can be connected.
Connector Terminal
Arrangement
(Top View)
A0...(1)20
19(11)...A8
A1...(2)18
17(12)...A9
A2...(3)16
15(13)...A10
A3...(4)14
13(14)...A11
A4...(5)12
11(15)...A12
A5...(6)10
9(16)...A13
A6...(7) 8
7(17)...A14
A7...(8) 6
5(18)...A15
0 V..(9) 4
3(19)...0 V
24 V...(10)2
1(20)...24 V
Connector pin No.
I/O indications on
Screw Terminals
(Black
triangle
mark)
Note:
Connector pin numbers in
parentheses are for G79 Cable.
The pin numbers are indicated
for user’s convenience. The
black triangle mark can be used
to determine orientation.
Note: Wiring shown above is for G6D Power Relays.
G70D-SOC16-1/G70D-FOM16-1
PNP-compatible output terminal (-- common output): A controller with an PNP transistor (+ common output) can be connected.
Connector Terminal
Arrangement
(Top View)
A0...(1)20
19(11)...A8
A1...(2)18
17(12)...A9
A2...(3)16
15(13)...A10
A3...(4)14
13(14)...A11
A4...(5)12
11(15)...A12
A5...(6)10
9(16)...A13
A6...(7) 8
7(17)...A14
A7...(8) 6
5(18)...A15
0 V..(9) 4
3(19)...0 V
24 V...(10)2
1(20)...24 V
Connector pin No.
I/O indications on
Screw Terminals
(Black
triangle mark)
Connector pin numbers in
parentheses are for G79 Cable.
Note:
The pin numbers are indicated
for user’s convenience. The
black triangle mark can be
used to determine orientation.
Note: Wiring shown above is for G6D Power Relays.
6
G70D
G70D
G70D-VSOC16/G70D-VFOM16
NPN-compatible output terminal (+ common output): A controller with an NPN transistor (-- common output) can be connected.
Connector Terminal
Arrangement
(Top View)
Connector pin No.
I/O indications on
Screw Terminals
(Triangle mark)
With Expansion Terminal Block
Note: 1. The terminal block shows the G70D-VSOC16, which operates with G6D relays mounted.
The G70D-VFOM16 terminal block uses G3DZ power MOSFET relays in place of G6D relays.
2. Terminals C0 to C15 are electrically independent from each other.
3. When the terminal block and relay block are connected to each other, each electrical check terminal of
the relay block is connected to the corresponding terminal of the terminal block.
3 TERMINAL ARRANGEMENT AND LOAD CONNECTION EXAMPLES
Load
Load
Load
Power
supply
Load
Power
supply
Power
supply
Load
Power
supply
Load
Load
Load
Load
Load
Load
Power
supply
Load
Power
supply
Load
Power
supply
Load
Load
Load
Power supply
24 VDC
Power
supply
Connector
G70D-SOC16(-1)/G70D-FOM16(-1)
Note: 1. Dotted lines show internal connections.
2. B2, B3, B4, and B5 are each found in two locations. Connect power to either of them.
7
G70D
G70D
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
24 VDC
Load
G70D-VSOC16/VFOM16 Without Expansion Terminal Block
G70D-VSOC16/VFOM16 With Expansion Terminal Block
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
24 VDC
Electrical check terminals (See Note)
Connector
Operation indicators
Note: When the terminal block and relay block are connected to each other,
each electrical check terminal of the relay block is connected to the
corresponding terminal of the terminal block.
8
G70D
G70D
Dimensions
Unit: mm (inch)
G70D-SOC16(-1)
G70D-FOM16(-1)
53 (2.09)
25
(0.98)
156 (6.14) max.
135±0.2 (5.31±0.008)
54
(2.12)
40±0.2
(1.57
±0.008)
51 (2.01)
max.
7
6
30--M
3
6
39 (1.53)
max.
Mounting Holes
Two, 4.2 dia. or M4
40±0.2
(1.57
±0.008)
135±0.2 (5.31±0.008)
G70D-VSOC16
G70D-VFOM16
81 (3.19) max.
46.5 (1.83)
135 (5.31)
5
100±0.2 (3.94±0.008)
46
(1.81)
max.
54.5
(2.15)
max.
50±0.2
(1.97
±0.008)
Relay block
Terminal block
Terminal Block (with Expansion Terminal Block)
Terminal Block (without Expansion Terminal Block)
135 (5.31) max.
6.8
10
10
40
(1.57)
max.
11.6
13.6
2
3
7.62
12.8
34, M3 Phillips-head screws
Mounting Holes
7.62
6.2 min.
6.2 min.
50, M3 Phillips-head screws
Two, 4.2 dia. or M4 holes
50±0.2
(1.97
±0.008)
100±0.2 (3.94±0.008)
9
G70D
G70D
3 GENERAL-PURPOSE CONNECTING CABLES
Unit: mm (inch)
G79-YPC Cable with Crimp Terminals
Convenient for connecting screw terminals to Output Blocks
Side A
Side B
Connecting to
devices
Connecting to
G70D Relay
Output Block
ç
300
G79-APC Cable with Loose Wires
Device connection end provides loose wires.
Side A
Side B
Connecting to
peripheral devices
Connecting to
G70D Relay
Output Block
ç
300
With loose wires and crimp terminals
1,000 mm (3.28 ft)
1,500 mm (4.92 ft)
2,000 mm (6.56 ft)
3,000 mm (9.84 ft)
5,000 mm (16.40 ft)
With loose wires
Part number
Length (ç)
Part number
Length (ç)
G79-Y100C
G79-Y150C
G79-Y200C
G79-Y300C
G79-Y500C
2,000 mm (6.56 ft)
5,000 mm (16.40 ft)
G79-A200C
G79-A500C
3 DEDICATED CONNECTING CABLES FOR OMRON PLC MODULES
Guidelines
The number of I/O points used must correspond to the number of Output Blocks.
The number of I/O connectors used must correspond to the number of cables.
G79-PC Cable with Connector (1:1)
Side A
Side B
Connection to
PLC high--density
output modules
Connection to
G70D Relay
Output Block
ç
Applicable Omron PLC
High-density I/O Modules
Part number
C200H-OD215
C200H MD215
C200H-MD215
C500-OD415CN
C500-MD211CN
C500
MD211CN
10
Connector Cable for Output Blocks
No. of output points
32 output points (2
( cables))
16 inputs/16
i
t /16 outputs
t t (1 cable)
bl )
32 output points (2 cables)
16 inputs/16
in uts/16 outputs
out uts (1 cable)
Length (ç)
Part number
1,000 mm
G79-100C
1,500 mm
G79-150C
2,000 mm
G79-200C
3,000 mm
G79-300C
5,000 mm
G79-500C
G70D
G70D
G79-OPC-P Cable with Connector (1:2)
A
Side A
Side B
Connection to
PLC high-density
output modules
Connection to
G70D Relay
Output Blocks
CN2
CN1
B
Straight length
Connector Cable for Output Blocks
Applicable
pp
Omron PLC
High-density
Hi
hd
it I/O Modules
M d l
Part number
C200H-OD218
C200H OD219
C200H-OD219
C500-OD213
CQM1-OD213
CQM1
OD213
Part number
Length (ç)
No. of output points
32 points (1
( cable))
64 points
i t (2 cables)
bl )
64 points (2 cables)
32 points
oints (1 cable)
A
B
1,000 mm (3.28 ft)
750 mm (2.46 ft)
G79-O100C-75
1,500 mm (4.92 ft)
1,250 mm (4.10 ft)
G79-O150C-125
2,000 mm (6.56 ft)
1,750 mm (5.74 ft)
G79-O200C-175
3,000 mm (9.84 ft)
2,750 mm (9.02 ft)
G79-O300C-275
5,000 mm (16.40 ft)
4,750 mm (15.58 ft)
G79-O500C-475
G79-PC-P-P Cable with Connector (1:3)
A
Side A
B
Side B
Connection to
PLC high-density
output modules
CN3
Connection to
G70D Relay
Output Blocks
CN2
CN1
C
Straight length
Connector Cable for Output Blocks
Applicable
pp
Omron PLC
High-density
Hi
hd
it I/O Modules
M d l
Part number
CS
CS1W-OD29P
O 9
CS1W MD29
CS1W-MD29P
No. of output points
96 points (2
( cables))
48 inputs/48
i
t /48 outputs
t t
(1 cable)
Part number
Length (ç)
A
B
C
1,500 mm (4.92 ft)
1,250 mm (4.10 ft)
1,000 mm (3.28 ft)
G79-150C-125-100
2,000 mm (6.56 ft)
1,750 mm (5.74 ft)
1,500 mm (4.92 ft)
G79-200C-175-150
3,000 mm (9.84 ft)
2,750 mm (9.02 ft)
2,500 mm (8.20 ft)
G79-300C-275-250
11
G70D
G70D
3 ACCESSORIES
Unit: mm (inch)
These accessories are for G70D-VSOC16 and G70D-VFOM16 Terminal Blocks.
G70D-ET Expansion Terminal Block
24.75
(0.97)
131.8
(5.19)
11
10.65
(0.42)
6.3
7.62
G6D-4-SB Short Bar
9.6
(0.38)
28.56 (1.12)
Precautions
3 GENERAL PRECAUTIONS
The G70D is used only for outputs.
If the Output Block is connected to a DC inductive load, connect
a diode to the Output Block to protect against counterelectromotive voltage. This may result in damage to the output
element and a short or open--circuit malfunction.
Electric Shock
It is extremely dangerous to connect or disconnect relays with the
power turned on. Always turn off the power before wiring the
Output Block or replacing the relays.
3 CORRECT USE
Do not connect or disconnect connectors with the power turned
on; faulty operation may occur.
The G70D-SOC16(-1) and G70D-VSOC16 are equipped with
G6D-1A, 24 VDC relays. The G70D-FOM16(-1) and
G70D-VFOM16 are equipped with G3DZ-2R6PL, 24 VDC power
MOSFET solid state relays.
Wiring
Be sure to turn OFF the power when wiring the Output Block and do
not touch the charged terminals of the Output Block, or an electric
shock may result. Turn ON the power after the Output Block is wired
and the relay block is mounted.
Apply specified voltages to the input terminals. Otherwise, the
Output Block may malfunction, be damaged, or burn.
Relay Models
Do not connect the Output Block to any load exceeding the rated
switching voltage or current of the Output Block. Otherwise, faulty
insulation, contact weld, or faulty contact of the Relays, damage
to the Relays may result or the Relays may malfunction or burn.
The life of a Relay varies with the switching condition. Test the
Relays under the actual operating conditions before using the
Relays within the permissible switching frequency. The use of
deteriorated Relays may result in the faulty insulation of the
Relays or cause the Relays to burn.
Do not use the Output Block in places with flammable gas. A fire
or explosion may result from the heat of the Relays or a spark
from the Relays when they are switched.
Power MOSFET Models
Do not connect the Output Block to loads consuming a total
current exceeding the rated output current of the Output Block.
You may damage the output element and a short or open--circuit
malfunction may result.
12
Replacing Relays
Turn OFF the Output Block to replace Relays. Otherwise, an
electric shock may result or the Output Block may malfunction.
Mount the Relay by pressing the upper part straight down until
the Relay is locked with the hooks. Make sure none of the Relay
terminals are bent or the Output Block may malfunction or radiate
heat.
Wiring
Make sure that the polarity of each terminal is correct, the power
lines are wired properly, and the terminal voltage is appropriate.
Do not disconnect or connect the connector while the Output
Block is turned ON. Otherwise, the Output Block may
malfunction.
Cable Connector Locks
Before the Output Block is turned ON, make sure that the
connectors of all the cables connected to the Output Block are
locked.
G70D
G70D
Installation Environment
Do not install the Output Block in the following locations or
damage or malfunction may result.
-
Locations with direct sunlight.
-
Locations with ambient temperature ranges not within --25°C
to 55°C (--13°F to 131°F).
Terminal block
-
Locations with rapid temperature changes resulting in
condensation or relative humidity exceeding 45% to 85%.
Expansion
terminal block
-
Locations with corrosive or inflammable gas.
-
Locations with excessive dust, salinity, or metal powder.
-
Locations with vibration or shock affecting the Output Block.
-
Locations with water, oil, or chemical sprayed on the Output
Block.
Relay block
Screw Tightening Torque
Removing and Mounting the Terminal Block and
Relay Block
Tighten all screws of the Output Block properly, or the Output
Block may malfunction.
Refer to the diagram below.
1. Removing
-
Terminal screws: Tighten each terminal screw to a torque of
0.78 to 1.18 N : m.
Check that the load and the Output Block are both turned OFF.
-
Mounting screws: Tighten each mounting screw to a torque
of 0.59 to 0.98 N : m
Turn the mounting screws of the relay block counterclockwise
alternately and equally until the relay block is slightly raised.
-
Relay block mounting screws: Tighten each mounting screw
to a torque of 0.59 to 0.98 N : m.
When the relay block is slightly raised, disconnect the protruding
part A of the relay block from the interior wall of the Output Block.
Cleaning
Do not use paint thinner to clean the surface because damage or
discoloration may result.
Further turn the mounting screws counterclockwise and remove
the mounting screws. Then remove the relay block.
2. Mounting
Handling
Check that the load and the Output Block are both turned OFF.
Do not drop the Output Block or shock or vibrate the Output
Block excessively. This may damage the Output Block and result
in malfunction.
Check that the part B of he terminal block is free of metal dust or
other foreign materials.
Disassembling, Repairing, and Modifying
Mount the relay block straight along the groove of the terminal
block.
Do not disassemble, repair, or modify the Output Block. An
electric shock may result or the Output Block may malfunction.
Press the both ends of the relay block and place the protruding
part A onto the interior wall of the Output Block.
Output Block Configuration
G70D-SOC/G70D-FOM
To open the protective cover, lift cover at both points marked “A”
in the following illustration.
Tighten the mounting screws of the relay block clockwise
alternately and equally to secure the relay block
Mounting screws
Relay block
Use the Relay Removal Tool provided to the left of the screw
terminals when replacing relays.
G70D-VSOC/G70D-VFOM
Terminal block
For ease-of-use and space-saving, the G70D-VSOC16
incorporates a terminal block and relay block that can be
separated from the Output Block. The relay block has operation
indicators and replaceable Relays along with electrical check
terminals for monitoring the operation of the Output Block.
The Expansion Terminal Block can be mounted to the Output
Block for power line connections.
13
G70D
G70D
Nameplate of Terminal Block
Electrical Check Terminals
As shown in Figure 1, the nameplate of the terminal block is
located on the bottom surface of the relay block.
The terminal block of the G70D-VSOC16 in operation is located
under the relay block. Therefore, unlike the terminal blocks of
other models, electrical checks on the terminals are not possible
with multimeter probes. The relay block of the G70D-VSOC16,
however, incorporates electrical check terminals, each of which is
connected to the corresponding terminal of the terminal block. All
the pairs of these terminals share single terminal numbers
respectively.
To fill in the nameplate, remove the nameplate from the relay
block. Then return it to the original location when finished.
To read the nameplate after the Output Block is mounted to a
panel, for example, pull out the nameplate from the bottom
surface of the relay block as shown in Figure 2.
To check these terminals, apply multimeter probes to these
terminals.
Do not touch these energized terminals with a thin metal object
or similar objects. Doing so may result in an electric shock.
Relay block
Nameplate
Figure 1
Multimeter probes
Nameplate
Electrical check terminals
Figure 2
Mounting the Expansion Terminal Block
Insert the hooks of the Expansion Terminal Block into the
mounting holes on the terminal block and slide the Expansion
Terminal Block so that it will not separate from the terminal block.
Tighten the mounting screw of the Expansion Terminal Block
securely.
Terminal block
Mounting screw
Expansion Terminal Block
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
9
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V
1-800-55-OMRON
416-286-6465
Cat. No. J099-E3-1
04/00
Specifications subject to change without notice.
Printed in U.S.A.