OMRON G7Z_13

Power Relays
G7Z
CSM_G7Z_DS_E_5_1
Multi-pole Power Relay for Contactor Current Range
Capable of Carrying and Switching 40 A at 440 VAC
• One pole, 40 A can be carried and switched.
• The maximum load capacity of 160 A when using 4-pole parallel connections.
• All materials used are compliant with the RoHS Directive
• EN 60947-4-1 certification for mirror contact mechanisms has been obtained by
using a combination of the relay and auxiliary contact blocks.
• A design with a small number of openings makes it difficult for dust or foreign
matter to enter.
• Ideal for supply power to industrial inverters, servo drivers, and other devices,
and switching power to motors and other equipment.
• Conforms to European PV standard (VDE0126).
Be sure to read the “Safety Precautions” on page 6 and the
“Precautions for All Relays with Forcibly Guided Contacts”.
Model Number Structure
Model Number Legend
Relay with Auxiliary Contact Block
Relay
G7Z-@-@@
G7Z-@
1
1
2 3
1. Relay Contact Configuration
4A:
4PST-NO
3A1B: 3PST-NO/SPST-NC
2A2B: DPST-NO/DPST-NC
2. Contact Configuration of Auxiliary Contacts
20:
DPST-NO
11:
SPST-NO/SPST-NC
02:
DPST-NC
3. Contact Mechanism of Auxiliary Contacts
Z:
Bifurcated crossbar contact
1. Contact Configuration
4A:
4PST-NO
3A1B: 3PST-NO/SPST-NC
2A2B: DPST-NO/DPST-NC
Auxiliary Contact Block
G73Z-@@
1 2
1. Contact Configuration of Auxiliary Contacts
20: DPST-NO
11: SPST-NO/SPST-NC
02: DPST-NC
2. Contact Mechanism of Auxiliary Contacts
Z: Bifurcated crossbar contact
Ordering Information
Relay with Auxiliary Contact Block
Relay with Auxiliary Contact Block (for Screw Terminals)
Structure
Classification
Relay with Auxiliary
Contact Block
4 poles +
2 poles
Contact configuration
Auxiliary Contact
Relay
Block
DPST-NO
4PST-NO
SPST-NO/SPST-NC
DPST-NC
DPST-NO
3PST-NO/SPST-NC
SPST-NO/SPST-NC
DPST-NC
DPST-NO
DPST-NO/DPST-NC SPST-NO/SPST-NC
DPST-NC
Rated Voltage
Model
12, 24 VDC
G7Z-4A-20Z
G7Z-4A-11Z
G7Z-4A-02Z
G7Z-3A1B-20Z
G7Z-3A1B-11Z
G7Z-3A1B-02Z
G7Z-2A2B-20Z
G7Z-2A2B-11Z
G7Z-2A2B-02Z
Note: 1. Relay contact terminals are M5, and the coil terminals are M3.5.
2. Auxiliary contact block terminals are M3.5.
3. When placing an order, specify the model number and rated supply voltage (12 VDC or 24 VDC).
1
G7Z
Relay
Structure
Contact configuration
Classification
Rated Voltage
Model
4PST-NO
Relay
4 poles
G7Z-4A
3PST-NO/SPST-NC
12, 24 VDC
G7Z-3A1B
DPST-NO/DPST-NC
G7Z-2A2B
Note: 1. Relay contact terminals are M5, and the coil terminals are M3.5.
2. When placing an order, specify the model number and rated supply voltage (12 VDC or 24 VDC).
Accessories (Order Separately)
Auxiliary Contact Block
Classification
Structure Contact Configuration
Auxiliary Contact Block
2 poles
Model
DPST-NO
G73Z-20Z
SPST-NO/SPST-NC
G73Z-11Z
DPST-NC
G73Z-02Z
Specifications
Ratings
Coil
Item
Rated
current
(mA)
Coil
resistance
(Ω)
12 VDC
308
39
24 VDC
154
156
Rated voltage
Must operate
voltage
Must release
voltage
Maximum
voltage
Power
consumption
(W)
Percentage of rated voltage
75% max.
10% min.
110%
Approx. 3.7
Note: 1. Rated current and coil resistance were measured at a coil temperature of 23°C with coil resistance of ±15%.
2. Operating characteristics were measured at a coil temperature of 23°C.
3. The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was
measured at an ambient temperature of 23°C.
There is, however, no continuous allowance.
Contacts
Relay
Auxiliary Contact Block
Model
Load
Item
G7Z-4A-@Z, G7Z-3A1B-@Z,
G7Z-2A2B-@Z
Model
Inductive
load cosφ =
0.3
Load
Resistive
load
Contact structure
Double break
Contact material
Ag alloy
40 A at
440 VAC
22 A at
440 VAC
5 A at
110 VDC
NC
25 A at
440 VAC
10 A at
440 VAC
5 A at
110 VDC
NO
40 A
NC
25 A
Maximum contact voltage
480 VAC
Rated load
Maximum contact
current
NC
25 A
10 A
5A
Maximum switching
capacity
NO
17,600 VA
9,680 VA
550 W
NC
11,000 VA
4,400 VA
550 W
Inductive
load cosφ =
0.3
Au clad + Ag
1 A at
440 VAC
0.5 A at
440 VAC
0.5 A at
110 VDC
1A
Maximum contact voltage
Failure rate P value
(reference value)
Resistive
load L/R = 1
ms
Double break
Rated carry current
Maximum switching capacity
125 VDC
22 A
Contact structure
Maximum contact current
NO
Failure rate P value
(reference value)
40 A
Item
Resistive
load
Contact material
NO
Rated load
Rated carry current
Resistive
load L/R = 1
ms
G73Z-20Z, G73Z-11Z, G73Z-02Z
480 VAC
1A
440 VA
125 VDC
0.5 A
220 VA
55 W
1 mA at 5 VDC
5A
2 A at 24 VDC
Note: The ratings for the auxiliary contact block mounted on the G7Z
are the same as those for the G73Z auxiliary contact block.
2
G7Z
Characteristics
Relay *5
Auxiliary contact block
G7Z-4A-@Z, G7Z-3A1B-@Z, G7Z-2A2B-@Z
G73Z-20Z, G73Z-11Z, G73Z-02Z
Classification
Item
Model
Contact resistance *1
400 mΩ max.
Operating time *2
50 ms max.
Release time *2
100 mΩ max.
50 ms max.
Maximum operating
frequency
Mechanical
1,800 operations/h
Rated load
1,200 operations/h
Insulation resistance *3
Dielectric strength
Impulse withstand
voltage
Vibration resistance
Shock resistance
Durability
1,000 MΩ min.
Between coil and contacts
4,000 VAC, 50/60 Hz for 1 min
Between contacts of different polarity
4,000 VAC, 50/60 Hz for 1 min
---
Between contacts of the same polarity
2,000 VAC, 50/60 Hz for 1 min
Between coil and contacts
10 kV, 1.2 × 50 µs
Between contacts of different polarity
10 kV, 1.2 × 50 µs
Between contacts of the same polarity
4.5 kV, 1.2 × 50 µs
Destruction
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Malfunction
NO: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
NC: 10 to 32 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Destruction
Screw mounting: 700 m/s2, DIN Track mounting: 500 m/s2
Malfunction
NO: 100 m/s2
NC: 25 m/s2
Mechanical
1,000,000 operations min. (at 1,800 operations/h, contact no load)
Electrical *4
AC resistive load: 80,000 operations
AC inductive load: 80,000 operations
DC resistive load: 100,000 operations
(at 1,200 operations/h, rated load)
---
Failure rate (P level) (reference value) *6
2 A at 24 VDC
Ambient operating temperature
−25 to 60°C (with no icing or condensation)
Ambient operating humidity
5% to 85%
Weight
Approx. 330 g
1 mA at 5 VDC
Approx. 18 g
Note: The above values are initial values.
*1. The contact resistance for the Relay (G7Z) was measured with 1 A at 5 VDC using the voltage drop method.
The contact resistance for the auxiliary contact block (G73Z) was measured with 0.1 A at 5 VDC using the voltage drop method.
*2. The operate time was measured with the rated voltage imposed with any contact bounce ignored at the ambient temperature of 23°C.
*3. The insulation resistance was measured with a 1,000-VDC megohmmeter applied to the same places as those used for checking the dielectric
strength.
*4. The electrical endurance was measured at an ambient temperature of 23°C.
*5. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.
*6. The failure rate is based on an operating frequency of 1,800 operations/h.
Approved Standards
UL Standard: UL508, UL840 (File No. E41643)
Model
Coil
ratings
Contact ratings
NO
contact
G7Z
40 A, 480 VAC, 60 Hz
(Resistive)
80,000
5 A, 120 VDC (Resistive)
100,000
22 A, 480 VAC, 60 Hz
(General Use)
100,000
D300* (1-A current applied)
12, 24 VDC
NC
contact
Number of
test
operations
25 A, 480 VAC, 60 Hz
(Resistive)
5 A, 120 VDC (Resistive)
10 A, 480 VAC, 60 Hz
(General Use)
D300* (1-A current applied)
CSA Standard: CSA Certification by
: CSA C22.2 No. 14
CCC Certification (File No.2009010304361493)
GB14048.4
EN Standard/TÜV Certification: EN 60947-4-1
(Certification No. R50079155)
Model
Coil ratings
100,000
G7Z
---
G73Z
Contact ratings
NO contact
NC contact
D300 (1-A current applied)
G73Z
NO
contact
AC-1: 40 A, 440 V, 50/60 Hz
AC-3: 16 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC-15: 0.5 A, 440 V, 50/60 Hz
*DC-13: 0.5 A, 110 V
NC
contact
AC-1: 25 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC-15: 0.5 A, 440 V, 50/60 Hz
*DC-13: 0.5 A, 110 V
12, 24 VDC
* Auxiliary contact ratings
Model
Contact ratings
---
---
NO
contact
NC
contact
AC-15: 0.5 A, 440 V , 50/60 Hz
DC-13: 0.5 A, 110 V
* Auxiliary contact ratings
< Reference > Information
UL 508:
Industrial control devices
UL 840:
Insulation coordination including clearance and
creepage distance for electrical devices
CSA C22.2 No. 14: Industrial control devices
EN 60947-4-1:
Contactors
3
G7Z
Dimensions
(Unit: mm)
Dimensions
Relay (12 VDC, 24 VDC) with Auxiliary Contact Block
4 Poles
Mounting Hole Dimensions
Two, M4
45
39±0.2
15
Four, M3.5
47
Eight, M5
92
84
75.7
Two, M3.5
70.7
60
51.5
62
Note: The dimensions are typical values.
Relay (12 VDC, 24 VDC)
4 Poles
Mounting Hole Dimensions
Two, M4
62
45
23
39±0.2
6
11
9.25
14.5 14.5 14.5
12.5
8-M5
2-M3.5
70.7
60
51.5
20.5
Note: The dimensions are typical values.
Contact Block
Auxiliary DIN Track Mounting Height
(when using the PFP-100N or PFP-50N mounting rail)
15
13
47
32.2
24.2
30
Four, M3.5
15.7
96.3
88.3
75.0
11
15
Note: The dimensions are typical values.
64.3
Note: The dimensions are typical values.
4
G7Z
Terminal Arrangement/Internal Connections
Relay with Auxiliary Contact Block
G7Z-4A-20Z
G7Z-4A-11Z
G7Z-4A-02Z
62
5
7
A1 1
3
5
7
A1 1
3
5
7
A2 2
4
6
8
A2 2
4
6
8
A2 2
4
6
8
54 63
62
52 61
53
3
53
54 61
51
64
A1 1
Note: The coil has no polarity.
Note: The coil has no polarity.
Note: The coil has no polarity.
G7Z-3A1B-20Z
G7Z-3A1B-11Z
G7Z-3A1B-02Z
53
54 63
64
53
54 61
62
51
52 61
62
A1 1
3
5
21
A1 1
3
5
21
A1 1
3
5
21
A2 2
4
6
22
A2 2
4
6
22
A2 2
4
6
22
Note: The coil has no polarity.
Note: The coil has no polarity.
Note: The coil has no polarity.
G7Z-2A2B-20Z
G7Z-2A2B-11Z
G7Z-2A2B-02Z
53
54 63
64
53
54 61
62
51
52 61
62
A1 1
3
11
21
A1 1
3
11
21
A1 1
3
11
21
A2 2
4
12
22
A2 2
4
12
22
A2 2
4
12
22
Note: The coil has no polarity.
Note: The coil has no polarity.
Note: The coil has no polarity.
G73Z-11Z
G73Z-02Z
Auxiliary Contact Block
G73Z-20Z
53
54 63
64
53
54 61
62
51
52 61
62
5
G7Z
Safety Precautions
Refer to the “Precautions for All Relays” and “Precautions for All Relays with Forcibly Guided Contacts”.
!WARNING
Take measures to prevent contact with charged parts
when using the Relay for high voltages.
!CAUTION
• The Relay can be mounted directly on a mounting rail (PFP) or a
DIN Track (EN 50022-35 × 7.5, 15). The Relay cannot be mounted,
however, to some reinforced rails (e.g., those produced by
Kameda Denki or Toyogiken).
• Mount the Relay sideways when it is mounted on a rail.
• Use End Plates (PFP-M) on both sides of the Relay to make sure
that it is properly secured.
Up
Do not touch the terminal section (charged parts) when
power is being supplied.
Always use the Relay with terminal covers mounted.
Contact with charged parts may result in electric shock.
Do not touch the Relay when power is being supplied or
right after the power has been turned OFF.
The hot surface may cause burn injury.
Precautions for Correct Use
Installation
DIN Track
(35 mm)
• Provide at least 5 mm of space between the sides and top of the
Relay and nearby grounded metal surfaces.
• Mount the G7Z with the coil terminal at the top.
5 mm min.
Grounded metal surface
Up
Coil terminal
5 mm min.
5 mm min.
• Provide at least 30 mm of space between Relays when two or more
Relays are mounted in a row.
• Do not use the Relay with the terminal screw surfaces facing down.
30 mm min.
• The auxiliary contact block (G73Z) can be mounted on the Relay.
Mounting and Removal
Mounting
Terminal screw surface
• To mount the Relay, secure M4 screws in two locations.
Use a screw-tightening torque of 1.2 to 1.3 N·m.
Insert the tab on the auxiliary contact
block into the groove on the Relay and
press down until the hook on the
auxiliary contact block catches in the
mounting hole on the Relay.
(1)
Hook
Tab
(2)
39 mm
Removing
Slide the auxiliary contact block, remove
the auxiliary contact block tab from the
groove on the Relay, and remove the
auxiliary contact block hook from the
Relay.
Be careful not to apply excessive force
on the hook.
(1)
Tab
(2)
Hook
6
G7Z
Connecting
Coil
• Use round or open-end (Y-type) crimp terminals and connect the
terminals with the appropriate tightening torque. Refer to the
terminal section space in the following figure for the crimp terminal
dimensions.
Relay Contacts (Unit: mm)
(Internal Connections of Coils)
DC Coil
A2
• If a transistor drives the G7Z, check the leakage current and
connect a bleeder resistor if necessary.
14.5
12.5
11
6
6
• The must operate voltage is the minimum value for the Relay
armature to operate and the contacts to turn ON. Therefore,
fundamentally apply the rated voltage to the coils, taking into
consideration the increases in coil resistance caused by voltage
fluctuation and coil temperature rise.
• Counter-electromotive voltage generated by the coil when the coil
is OFF may destroy semiconductor elements or cause
malfunctions. Attach surge-absorbing diodes to both ends of the
coil as a countermeasure. Particularly, when driving G7Z with
semiconductor elements, always attach the surge-absorbing
diodes.
Note that the relay reset time will be extended, so always use after
verifying implementation under actual usage conditions.
Use surge-absorbing diodes with a minimum of 600 V reverse
voltage resistance, and a forward current of approximately 1A.
G7Z does not have coil polarity so attach surge-absorbing diodes
so that the polarity is reverse to the applied voltage of the coil.
M5
Relay Coil
6.8
4.3
M3.5
Auxiliary Contact Block
9.5
6.8
Mirror Contact Mechanism
5.5
5.5
M3.5
• One crimp terminal can be used for the Relay contact section (M5
screw). Two crimp terminals can be connected for the coil terminal
and auxiliary contact block.
By combining a Relay with an auxiliary contact block, all NC contacts
of the auxiliary contact block will satisfy an impulse withstand voltage
of 2.5 kV or higher or maintain a gap of 0.5 mm or greater when the
coil is de-energized even if at least one NO contact (main contact) of
the Relay is welded.
Description of Mirror Contact Mechanism
Recommended Crimp Terminals and Wire
Location
Contact
section
Coil
section
Crimp
terminals
A1
Impulse withstand voltage: 2.5 kV min. or
contact separation (a + b): 0.5 mm min.
Appropriate wire size
a
b
Auxiliary contact block
2
5.5-5
2.63 to 6.64 mm (AWG12, 10)
8-5
6.64 to 10.52 mm2 (AWG8)
1.25-3.5
0.5 to 1.65 mm2 (AWG20 to 16)
• Use the following tightening torque when tightening screws. Loose
screws may result in fire caused by abnormal heat generated when
the power is being supplied.
M5 screws:
2.0 to 2.2 N·m
M3.5 screws: 0.8 to 0.9 N·m
• Allow suitable slack on leads when wiring, and do not subject the
terminals to excessive force.
Relay
NC
NO
NC
NO
NO
NO
Contact welding
Microloads
The G7Z is used for switching power loads, such as current carry for
device power supplies and heater loads. Use an auxiliary contact
block (G73Z) if microloads are required for signal applications and
operation status feedback.
7
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2010.8
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
G73Z-11Z G7Z-2A2B-02Z DC12 G7Z-2A2B-02Z DC24 G7Z-2A2B-11Z DC12 G7Z-2A2B-20Z DC12 G7Z-2A2B-20Z
DC24 G7Z-3A1B-02Z DC12 G7Z-3A1B-02Z DC24 G7Z-3A1B-11Z DC12 G7Z-3A1B-11Z DC24 G7Z-3A1B-20Z DC12
G7Z-3A1B-20Z DC24 G7Z-4A-02Z DC12 G7Z-4A-02Z DC24 G7Z-4A-11Z DC12 G7Z-4A-11Z DC24 G7Z-4A-20Z
DC12 G7Z-4A-20Z DC24 G7Z-2A2B-11Z DC24