OMRON LY2-0-DC24

General Purpose Relay
LY
• Arc barrier equipped.
• High dielectric strength (2,000 VAC).
• Long dependable service life assured by Ag-Alloy contacts.
• Choose models with single or bifurcated contacts,
LED indicator, diode surge suppression,
push-to-test button, or RC circuit.
• UL, CSA, TUV, and CE approvals
on all standard LY Relay Part Numbers.
Ordering Information
To Order: Select the part number and add the desired coil voltage rating (e.g., LY1-DC6).
Type
Terminal
Contact
form
Model
Single contact
Standard
bracket
mounting
Standard
Plug-in/solder
Bifurcated contact
Upper
mounting
bracket
Standard
bracket
mounting
Upper
mounting
bracket
SPDT
LY1
LY1F
—
DPDT
LY2
LY2F
LY2Z
LY2ZF
3PDT
LY3
LY3F
—
—
4PDT
LY4
LY4F
—
—
SPDT
LY1-0
—
—
—
DPDT
LY2-0
—
LY2Z-0
—
3PDT
LY3-0
—
—
—
4PDT
LY4-0
—
—
—
SPDT
LY1N
—
—
—
DPDT
LY2N
—
LY2ZN
—
3PDT
LY3N
—
—
—
4PDT
LY4N
—
—
—
SPDT
LY1-D
—
—
—
DPDT
LY2-D
—
LY2Z-D
—
3PDT
LY3-D
—
—
—
4PDT
LY4-D
—
—
—
LED indicator
and diode surge
suppression
SPDT
LY1N-D2
—
—
—
DPDT
LY2N-D2
—
LY2ZN-D2
—
4PDT
LY4N-D2
—
—
—
RC circuit
SPDT
LY1-CR
—
—
—
DPDT
LY2-CR
—
LY2Z-CR
—
SPDT
LY1N-CR
—
—
—
DPDT
LY2N-CR
—
LY2ZN-CR
—
PCB
LED indicator
Diode surge
suppression
LED indicator
and RC circuit
Plug-in/solder
—
Note: 1. Types with specifications other than those listed are available. Contact your Omron Sales representative.
2. To order connecting sockets and mounting tracks, see “Accessories” section.
3. Relays with RC circuit are only available in AC coil voltages of 100 VAC or greater.
General Purpose Relay
LY
285
Type
Terminal
Contact
form
Model
Single contact
Standard
bracket
mounting
Push-to-test
button
Plug-in/solder
LED indicator and
push-to-test button
Plug-in/solder
Bifurcated contact
Upper
mounting
bracket
Standard
bracket
mounting
Upper
mounting
bracket
SPDT
LY1l4
—
—
—
DPDT
LY2l4
—
LY2Zl2
—
3PDT
LY3l4
—
—
—
4PDT
LY4l4
—
—
—
DPDT
LY2l4N
—
LY2Zl2N
—
4PDT
LY4l4N
—
—
—
Note: 1. Types with specifications other than those listed are available. Contact your Omron Sales representative.
2. To order connecting sockets and mounting tracks, see “Accessories” section.
■ Accessories
Connecting Sockets
To Order: Select the appropriate part numbers for sockets, clips, and mounting tracks (if required) from the following charts.
Track Mounted Sockets
Relay
Socket*
Relay hold-down clip
Standard
SPDT
PTF08A-E
Mounting track
RC circuit
PYC-A1
Y92H-3
PFP-100N/PFP-50N &
DPDT
PFP-M or PFP-100N2
3PDT
PTF11A
4PDT
PTF14A-E
PFP-S (Option spacer)
* Track mounted socket can be used as a front connecting socket.
Back Connecting Sockets
Relay
SPDT
Solder
terminal
socket
Wire wrap
terminal
socket
Relay hold-down clip
Standard
PYC-P
Push-to-test
PYC-P2
RC circuit
PYC-1
Socket Mounting Plate
Mtg. plate
PYC-S
1
PT08
PT08QN
PYP-1
3PDT
PT11
PT11QN
PTP-1-3
4PDT
PT14
PT14QN
PTP-1
10
–
12
18
–
PYP-18
–
PTP-12
–
PTP-10
–
–
DPDT
Note: Types PYP-18, PTP-12 and PTP-10 may be cut to any desired length.
Relay
PC terminal socket
Relay hold-down clip
Standard
SPDT
PT08-0
PYC-P
DPDT
3PDT
PT11-0
4PDT
PT14-0
286
General Purpose Relay
LY
Push-to-test
PYC-P2
RC circuit
PYC-1
Specifications
■ Contact Data
Load
Single contact
SPDT
Resistive load
(p.f. = 1)
Rated load
Bifurcated contact
DPDT, 3PDT, 4PDT
Inductive load
(p.f. = 0.4)
(L/R = 7 ms)
Resistive load
(p.f. = 1)
DPDT
Inductive load
(p.f. = 0.4)
(L/R = 7 ms)
Resistive load
(p.f. = 1)
Inductive load
(p.f. = 0.4)
(L/R = 7 ms)
15 A at 110 VAC
10 A at 110 VAC
10 A at 110 VAC
7.5 A at 110 VAC
5 A at 110 VAC
4 A at 110 VAC
15 A at 24 VDC
7 A at 24 VDC
10 A at 24 VDC
5 A at 24 VDC
5 A at 24 VDC
4 A at 24 VDC
Contact material
Ag-Alloy
Carry current
15 A
Max. operating
voltage
250 VAC
125 VDC
Max. operating
current
15 A
Max. switching
capacity
1,700 VA
1,100 VA
1,100 VA
825 VA
550 VA
440 VA
360 W
170 W
240 W
120 W
120 W
100 W
Min. permissible
load
100 mA, 5 VDC
10 A
7A
10 A
7A
10 mA, 5 VDC
■ Coil Data
1- and 2-pole Types – AC
Rated
voltage (V)
Rated current (mA)
50 Hz
60 Hz
Coil
resistance
(Ω)
Coil inductance
(ref. value) (H)
Armature
OFF
Armature
ON
6
214.10
183
12.20
0.04
0.08
12
106.50
91
46
0.17
0.33
24
53.80
46
180
0.69
1.30
50
25.70
22
788
3.22
5.66
100/110
11.70/12.90
10/11
3,750
14.54
24.60
110/120
9.90/10.80
8.40/9.20
4,430
19.20
32.10
200/220
6.20/6.80
5.30/5.80
12,950
54.75
94.07
220/240
4.80/5.30
4.20/4.60
18,790
83.50
136.40
Pick-up
voltage
Dropout
voltage
Maximum
voltage
(% of rated voltage)
80% max.
30% min.
110%
Power
consumption
(VA, W)
Approx.
1.00 to 1.20
(60 Hz)
Approx.
0.90 to 1.10
(60 Hz)
1- and 2-pole Types – DC
Rated
voltage (V)
Rated current (mA)
Coil
resistance
(Ω)
Coil inductance
(ref. value) (H)
Armature
Armature
OFF
ON
6
150
40
0.16
0.33
12
75
160
0.73
1.37
24
36.90
650
3.20
5.72
48
18.50
2,600
10.60
21
100/110
9.10/10
11,000
45.60
86.20
Pick-up
Dropout
Maximum
voltage
voltage
voltage
(% of rated voltage)
80% max.
10% min.
110%
Power
consumption
(VA, W)
Approx.
0.90
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C (73°F) with tolerances of +15%, -20% for AC rated
current, and ±15% for DC rated coil resistance.
2. The AC coil resistance and inductance are reference values at 60 Hz.
3. The performance characteristics are measured at a coil temperature of 23°C (73°F).
4. Class B coil insulation is available.
General Purpose Relay
LY
287
3-pole Type – AC
Rated
voltage (V)
Rated current (mA)
50 Hz
Coil
resistance
(Ω)
60 Hz
Coil inductance
(ref. value) (H)
Armature
OFF
Armature
ON
6
310
270
6.70
0.03
0.05
12
159
134
24
0.12
0.21
24
80
67
100
0.44
0.79
50
38
33
410
2.24
3.87
100/110
15.90/18.30 13.60/15.60 2,300
10.50
18.50
120
17.30
2,450
11.50
20.60
200/220
10.50/11.60 9.00/9.90
8,650
34.80
59.50
240
9.40
10,400
38.60
74.60
14.8
8
Pick-up
voltage
Dropout
voltage
Maximum
voltage
Power
consumption
(VA, W)
(% of rated voltage)
80% max.
30% min.
110%
Approx.
1.60 to 2.00
(60 Hz)
3-pole Type – DC
Rated
voltage
(V)
Rated current (mA)
Coil
resistance
(Ω)
Coil inductance
(ref. value) (H)
Armature
OFF
Pick-up
voltage
Armature
ON
6
234
25.70
0.11
0.21
12
112
107
0.45
0.98
24
58.60
410
1.89
3.87
48
28.20
1,700
8.53
13.90
100/110
12.70/13
8,500
29.60
54.30
Dropout
voltage
Maximum
voltage
(% of rated voltage)
80% max.
10% min.
110%
Power
consumption
(VA, W)
Approx.
1.40
4-pole Type – AC
Rated
voltage (V)
Rated current (mA)
50 Hz
60 Hz
Coil
resistance
(Ω)
Coil inductance
(ref. value) (H)
Armature
OFF
Armature
ON
6
386
330
5
0.02
0.04
12
199
170
20
0.10
0.17
24
93.60
80
78
0.38
0.67
50
46.80
40
350
1.74
2.88
100/110
22.50/25.50 19/21.80
1,800
10.50
17.30
120
19.00
2,200
9.30
19
200/220
11.50/13.10 9.80/11.20
6,700
33.10
57.90
240
11.00
9,000
33.20
63.40
16.40
9.50
Pick-up
voltage
Dropout
voltage
Maximum
voltage
(% of rated voltage)
80% max.
30% min.
110%
Power
consumption
(VA, W)
Approx.
1.95 to 2.50
(60 Hz)
4-pole Type – DC
Rated current (mA)
Rated
voltage (V)
Coil
resistance
(Ω)
Coil inductance
(ref. value) (H)
Armature
OFF
Pick-up
voltage
Armature
ON
6
240
25
0.09
0.21
12
120
100
0.39
0.84
24
69
350
1.41
2.91
48
30
1,600
6.39
13.60
100/110
15/15.90
6,900
32
63.70
Dropout
voltage
Maximum
voltage
(% of rated voltage)
80% max.
10% min.
110%
Power
consumption
(VA, W)
Approx.
1.50
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C (73°F) with tolerances of +15%, -20% for AC rated
current, and ±15% for DC rated coil resistance.
2. The AC coil resistance and inductance are reference values at 60 Hz.
3. The performance characteristics are measured at a coil temperature of 23°C (73°F).
4. Class B coil insulation is available.
288
General Purpose Relay
LY
■ Characteristics
Contact resistance
50 mΩ max.
Operate time
25 ms max.
Release time
Operating frequency
25 ms max.
Mechanically
18,000 operations/hour
Under rated load
1,800 operations/hour
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 minute
1,000 VAC, 50/60 Hz for 1 minute between contacts of same polarity
Vibration
Shock
Ambient temperature
Mechanical durability
10 to 55 Hz, 1.00 mm (0.04 in) double amplitude
Malfunction durability
10 to 55 Hz, 1.00 mm (0.04 in) double amplitude
Mechanical durability
1,000 m/s2 (approx. 100 G)
Malfunction durability
200 m/s2 (approx. 20 G)
Operating
LY1, LY2, LY3: -25° to 55°C; LY4 =-25° to 40°C
Humidity
Service Life
35 to 85% RH
Mechanically
AC: 50 million operations min. (at operating frequency of 18,000 operations/hour)
DC: 100 million operations min. (at operating frequency of 18,000 operations/hour)
Electrically
See “Characteristic Data”
Weight
SPDT, DPDT: Approx. 40 g (1.41 oz), 3PDT: Approx. 50 g (1.76 oz)
4PDT: Approx. 70 g (2.47 oz)
Note: Data shown are of initial value.
■ Characteristic Data
Maximum switching capacity
Rated operating voltage (V)
Rated operating voltage (V)
Rated operating current (A)
LY2Z
Rated operating current (A)
LY3, LY4
Rated operating current (A)
LY2
Rated operating current (A)
LY1
Rated operating voltage (V)
Rated operating voltage (V)
Electrical service life
Switching current (A)
Switching current (A)
Service Life (X106 operations)
LY2Z
Service Life (X106 operations)
LY3, LY4
Service Life (X106 operations)
LY2
Service Life (X106 operations)
LY1
Switching current (A)
Switching current (A)
General Purpose Relay
LY
289
Dimensions
Unit: mm (inch)
■ Relays
LY1
Terminal
arrangement
(Bottom view)
LY2
LY3
Terminal
arrangement
(Bottom view)
LY4
LY1-0, LY2-0, LY3-0, LY4-0
LY1F, LY2F
SPTD
Mounting
holes
Note: The above drawing shows LY1F. With LY2F, dimension “*”
should read as eight 3.05 mm (0.12 in) dia. holes.
General Purpose Relay
Terminal
arrangement
(Bottom view)
Mounting holes for LY1-0, LY2-0, LY3-0, LY4-0
(Bottom view)
Note: The above drawing shows LY2-0. With LY1-0,
dimension “*” should read as eight 6.35 (.25).
290
Terminal
arrangement
(Bottom view)
LY
LY3F
DPDT
3PDT
4PDT
Mounting
holes
LY4F
Mounting holes
LY1S, LY2S
Round hole
Rectangular hole
LY3S
Round hole
Rectangular hole
LY4S
Round hole
Rectangular hole
Note: The above drawing shows LY2S-US. With LY1S-US, dimension “*”
should read as eight 2.03 mm (0.08 in) dia. holes.
General Purpose Relay
LY
291
■ Accessories
Unit: mm (inch)
Track mounted sockets (UL File No. E87929) (CSA Report No. LR31928)
PTF08A
(see note 3)
Terminal arrangement/
mounting holes
(Top view)
PTF11A
Terminal arrangement/
mounting holes
(Top view)
Track mounting sockets (UL File No. E87929) (CSA Report No. LR31928)
PTF14A
(see note 3)
Terminal arrangement/
mounting holes
(Top view)
Mounting height of
relay with socket
(Applies to all PTF❏A sockets)
Note: 1. UL/CSA does not apply to wire wrap (Q) type sockets.
2. Values in brackets for LY❏CR.
3. PTF08A-E and PTF14A-E = touch safe screws. Height = 33 mm max.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08
292
Terminal arrangement/
(Bottom view)
General Purpose Relay
LY
PT11
Terminal arrangement/
(Bottom view)
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT14
Terminal arrangement
(Bottom view)
Mounting height of relay with socket
(Applies to all PT sockets)
PT
Note: Values in brackets for LY❏CR.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08QN
Panel cut-out and terminal
arrangement are the same
as Type PT08.
PT11QN
Panel cut-out and terminal
arrangement are the same
as Type PT11.
PT14QN
Panel cut-out and terminal
arrangement are the same
as Type PT14.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08-0
Terminal arrangement is
the same as Type PT08.
Mounting holes
(Bottom view)
PT11-0
Terminal arrangement is
the same as Type PT11.
Mounting holes
(Bottom view)
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT14-0
Terminal arrangement is
the same as Type PT14.
Mounting holes
(Bottom view)
General Purpose Relay
LY
293
Unit: mm (inch)
Relay hold-down clips
PYC-A1
For PTF❏A socket
PYC-S
For relay mounting plates
(Applicable to Type PYP-1 and PYP-18
socket mounting plates only.)
PYC-P
For PT❏ socket
Y92H-3
For RC circuit type
PYC-1
For RC circuit type
Relay hold-down clips
PYC-P2
For push-to-test button type with
PT❏ socket
Mounting track/end plate/spacer
PFP-100N, PFP-50N
(Conforming to EN 50022)
PFP-100N2
(Conforming to EN 50022)
16
7.3±0.15
4.5
4.5
35±0.3
15
25
25
10
25
1000 (500)*
10
25 *
15 (5)
35±0.3 27
27±0.15
1
15
25
25
10
25
1000±4
25 15
10
24
29.2
1
1.5
* The figure in parenthesis is for PFP-50N.
*This dimension is 14.99 mm (0.59 in) on both ends in the case of PFP-100N, but on one end in the case of PFP-50N.
** L = Length
PFP-50N
L = 497.84 mm (19.60 in)
PFP-100N
L = 990.60 mm (39.00 in)
PFP-100N2
L = 990.60 mm (39.00 in)
***A total of twelve 24.89 x 4.57 mm (0.98 x 0.18 in) elliptic holes are provided, with six holes cut from each end of the track at a pitch
of 9.91 (0.39) between holes.
294
General Purpose Relay
LY
PFP-M end plate
PFP-S spacer
Socket mounting plates [t=1.52 (.06)]
PYP-1
PTP-10
PTP-1-3
Number of socket specs.
Socket needed
1
10
12
18
PT08, PT08QN
PYP-1
–
–
PYP-18
PT11, PT11QN
PTP-1-3
–
PTP-1-2
_
PT14, PT14QN
PTP-1
PTP-10
–
–
PTP-10
PTP-12
PTP-1
PYP-18
PTP-12
General Purpose Relay
LY
295
■ Relay Options
LED Indicator
Specifications and dimensions same as the Standard Type with the following exception. With the LED indicator type, the rated current is approximately 0 to 5.0 mA higher than the Standard Type.
Terminal arrangement/Internal connections (Bottom view)
LY2N
DC coil rating type
AC coil rating type
1
2
1
2
3
4
3
4
5
6
5
6
7
8
7
8
Note: 1. The coil terminals 10 and 11 of Type LY3N become (-) and (+) and terminals 13 and 14 of Type LY4N become (-) and (+), respectively.
2. Pay special attention to the polarities when using the DC type.
Diode Surge Suppression
Specifications and dimensions same as the Standard Type with the following exception. Ambient operating temperature: -25° to 40°C
(-13° to 104°F)
Without Diode
With Diode
Terminal arrangement/Internal connections (Bottom view)
LY2(N)-D(2)
LY2-D
6, 12, 24, 48
100/110 VDC
Note: 1.
2.
3.
4.
296
LY2N-D2
6, 12, 24, 48 VDC
Pay special attention to the polarities when using the DC type.
The release time is somewhat longer, but satisfies the standard specifications of 25 ms.
The reverse-breakdown voltage of the diode is 1,000 VDC.
Available on DC versions only.
General Purpose Relay
LY
LY2N-D2
100/110 VDC
■ Relay Options
RC Circuit
Specifications and dimensions same as the Standard Type with the following exceptions.
Characteristic Data
Without RC circuit
With RC circuit
LY1-CR, LY2(Z)-CR
Terminal arrangement/Internal connections (Bottom view)
LY1-CR
LY2(Z)-CR
Note: 1. The above drawing shows LY2(Z)-CR. With LY1-CR, “*” should read eight 2.03 mm (0.08 in) dia. holes.
2. Available on AC versions only.
Push-to-test Button
Specifications and dimensions same as the Standard Type with the following exceptions.
LY❏I2
LY1I2, LY2I2
Note: Type LY1I2 has the same dimensions and appearances as Type LY2I2 shown except that dimensions “*” is 2.03 mm (0.08 in) dia. holes.
LY3I2
LY4I2
General Purpose Relay
LY
297
■ Approvals
UL Recognized Type (File No. E41643)
Type
LY1❏
Contact form
SPDT
Coil ratings
Contact ratings
Number of test operations
6 to 240 VAC
15A, 30VDC (Resistive), 40°C
6 to 120 VDC
15A, 240VAC (General use), 40°C
6 x 103
TV-5, 120VAC, 40°C
25 x 103
1/2HP, 120VAC, 50°C
LY2❏
DPDT
15A, 28VDC (Resistive), 40°C
6 x 103
15A, 120VAC (Resistive), 40°C
12A, 240VAC (General use), 40°C
1/2HP, 120VAC, 50°C
25 x 103
TV-3, 120VAC, 40°C
LY3❏
LY4❏
3PDT
10A, 30VDC (Resistive), 40°C (Same polarity )
4PDT
10A, 240VAC (General use), 40°C (Same polarity )
LY2Z❏
(Bifurcated)
DPDT
7A, 240VAC (General use), 40°C
6 x 103
1/2HP, 240VAC, 40°C
6 x 103
7A, 28VDC (Resistive), 40°C
CSA Certified Type (File No. LR31928)
Type
LY1❏
Contact form
SPDT
Coil ratings
6 to 240 VAC
6 to 120 VDC
Contact ratings
15 A, 120 VAC (Inductive)
10 A, 240 VAC (Inductive)
15 A, 28 VDC (Resistive)
TV-5 (ACTV)
LY2❏
DPDT
13 A, 28 VDC (Resistive)
12 A, 120 VAC (Inductive)
10 A, 240 VAC (Inductive)
1/3 HP, 120 VAC (Motor)
TV-3 (ACTV)
LY3❏
LY3❏
3PDT
10 A, 240 VAC (Inductive)
4PDT
10 A, 28 VDC (Resistive)
VDE Approved Type (File No. 9903 [SPDT, DPDT & 3PDT], File No. 9947 [4PDT])
Type
LY❏-VD
Contact form
SPDT
LY❏-VD
Coil ratings
6, 12, 24, 50,
Contact ratings
10 A, 220 VAC (Resistive)
110, 220 VAC
10 A, 28 VDC (Resistive)
and 6, 12, 24,
7 A, 220 VAC (Inductive)
48, 110 VDC
7 A, 28 VDC (Inductive)
DPDT
7 A, 220 VAC (Resistive)
3PDT
7 A, 28 VDC (Resistive)
4PDT
4 A, 28 VDC and 4A, 220 VAC (Inductive)
LR (Lloyd's Register) Approved Type (File No. 562KOB-204523)
Type
LY❏
Contact form
Coil ratings
Contact ratings
DPDT
6 to 240 VAC
7.5 A, 230 VAC (Inductive)
4PDT
6 to 110 VDC
5 A, 24 VDC (Inductive)
SEV Listed Type (File No. D7 91/82 [2- & 4-pole], D 91/204a [1- & 3-pole])
Type
Contact form
Coil ratings
Contact ratings
LY❏-SV
SPDT
6 to 240 VAC
15 A, 220 VAC (Resistive)
LY❏-SV
DPDT
6 to 110 VDC
15 A, 24 VDC (Resistive)
10 A, 220 VAC (Resistive)
3PDT
10 A, 24 VDC (Resistive)
4PDT
Note: 1. The rated values approved by each of the safety standards (e.g., UL, CSA, VDE, and SEV) may be different from the performance characteristics individually defined in this catalog.
2. In the interest of product improvement, specifications are subject to change.
298
General Purpose Relay
LY
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
14
2010.1
In the interest
of product
improvement,
are subject
change without notice.
To convert millimeters into inches, multiply
by 0.03937.
To convert
gramsspecifications
into ounces, multiply
by to
0.03527.
OMRON Corporation
Industrial Automation Company
OMRON ELECTRONICS LLC • THE AMERICAS HEADQUARTERS • Schaumburg, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766
www.omron247.com
OMRON ARGENTINA • SALES OFFICE
Cono Sur • 54.11.4783.5300
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br
OMRON CHILE • SALES OFFICE
Santiago • 56.9.9917.3920
OMRON ELECTRONICS MEXICO SA DE CV • HEAD OFFICE
Apodaca, N.L. • 52.811.156.99.10 • 001.800.556.6766 • [email protected]
OTHER OMRON LATIN AMERICA SALES
54.11.4783.5300
Omron Europe B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.industrial.omron.eu
J002-E1-10
06/09
Note: Specifications are subject to change.
© 2010 Omron Electronics LLC