MACOM 2-1393248-5

Catalog 1308242
Issued 3-03 (PDF Rev. 9-05)
P&B
W33 series
One- and Two-Pole, Switchable
Thermal Circuit Breaker / Power Switch
With Optional Indicator Lamp
Features
Electrical Data @ 25°C
• Combines on/off switch and circuit protection in a single unit.
• 2 to 20 amp ratings (<2A types available as special order).
• One or two pole sensing.
• Lighted or non-lighted rocker actuator in various colors.
• Convenient, snap-in mounting.
• Optional auxiliary switch available.
• Trip-free operation.
Calibration: Breaker will continuously carry 100% of rated load. It may trip
between 101% and 135%, but must trip at 135% within one
hour at +25°C.
Dielectric Strength: Over 2,000 volts RMS.
Maximum Operating Voltages: 50VDC; 250VAC to 400 Hz.
Interrupt Capacity: 1,000 amps at 50VDC; 250VAC, 60 Hz. and
125/250VAC, 400 Hz.
1,500 amps at 125/250VAC, 60 Hz.
Resettable Overload Capacity: Ten times rated current.
Agency Approvals
Mechanical/Environmental Data
W33 series is UL 1077 Recognized as Supplementary Protectors, File
E69543, and CSA Accepted as Supplementary Protectors (Appliance
Component Protectors), File LR15734.
Termination: Poles 1&2: .250” (6.35mm) quick connect/solder terminals.
Opt. Aux. Sw.: .110”(2.79mm) quick connect terminals.
Mounting: Snaps into panel from front.
Actuator: Rocker or lighted rocker.
Shock: 30g tested to IEC 68-2-27, test Ea.
Vibration: 8g tested to IEC 68-2-6, test Fc.
Switch Endurance Cycling: 50,000 operations at rated load.
1,000 operations at 200% rated load.
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Ambient Compensation Chart
Time vs. Current Trip Curve @ +25°C
1000
800
700
600
1.30
Correction Factor
900
Load Current As A Percent
Of Breaker Rating
1.40
All Models
Overload
Trip Times
No Trip
100%
Trip in 1 hour
135%
3.0 - 33 Sec.
200%
0.6 - 10 Sec.
400%
0.34 - 5 Sec.
600%
0.25 - 2.2 Sec.
800%
0.20 - 0.6 Sec.
1000%
500
0.90
0.80
–20 –10 0
10 20 30 40 50 60
Ambient Temperature In Degrees Centigrade (°C)
200
100
1
10
100
1000
Time In Seconds
Dimensions are shown for
1.00
0.60
300
114 reference purposes only.
1.10
0.70
400
0
.1
1.20
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
To use this chart: Read up from the ambient
temperature to the curve, and across to find a
correction factor. Multiply the breaker rating by the
correction factor to determine the compensated
rating. Calculate the overloads in terms of the
compensated rating to use the published trip curve.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 9-05)
P&B
Ordering Information
Typical Part No.
B
W
33
-S
1
N
1
Q
-20
1. Designator:
W = Circuit breaker
2. Series Number:
33 = Two pole, rocker actuated
3. Circuit Function:
S = Pole 1 – Switch only; Pole 2 – Series trip overload sensing.
T = Poles 1 & 2 – Series trip overload sensing.
SS = Same as S with auxiliary switch on pole 1.
TS = Same as T with auxiliary switch on pole 1.
D = 2 Pole switching.
4. Rocker Color:
1 = Black.
2 = White.
3 = Red.
4 = Amber.
5 = Smoke.
5. Light (available only with White, Red, Amber and Smoke rocker colors):
A = 24VDC (Incandescent).
B = 120VAC (Neon with resistor).
C = 240VAC (Neon with resistor).
6. Marking:
1 = International I/O.
N = No light.
2 = Contrasting I/O stamp (white toggle with black stamp).
7. Termination:
Q = .250” x .032” (6.35 x .813mm) quick connect / solder terminals.
8. Amp Rating:
2
5
7
10
12
15
16
20
Consult factory for availability of ratings <2A
Stock Items – Authorized distributors are more likely to stock the following items.
W33-T4B1Q-5
W33-T4B1Q-10
W33-T4B1Q-15
W33-S4B1Q-10
W33-S4B1Q-15
W33-T2N1Q-20
W33-S1N1Q-5
W33-S1N1Q-15
W33-S1N1Q-20
Schematic
Outline Dimensions
POLE
2
ROCKER
.980
(24.89)
1.724
(43.79)
.850
(21.59)
I
1.890
(48.01)
0
POLE
1
LINE SIDE
1.690
(42.93)
1.120
(28.45)
PANEL CLAMPING
ARRANGEMENT
.412
(10.46)
.250
(6.35)
LOAD SIDE
NEON - AC
INCANDESCENT - DC
FITS .875 x 1.750 (22.22 x 44.45) PANEL OPENING
FROM .032” - .250”(.813mm - 6.35mm) THICK
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.