CARLINGTECH FA2-B0-14-820-12A-BG

F-Series
Circuit Breaker
The F-Series hydraulic/magnetic high amperage circuit
breakers are designed to handle high current applications
in extremely hot and/or cold locations. Due to its timeproven hydraulic/magnetic design, the F-Series load
sensing mechanism is insensitive to changes in ambient
or enclosure temperature, providing a consistent trip
point over temperatures ranging from -40°C to +85°C.
Additionally, the F-Series circuit breakers come with a
choice of overload time delays, making them ideal for
critical applications having inductive loads.
Further, the F-Series breakers are available up to 700A
and an optional 25 millivolt metering shunt construction
provides a safe method for monitoring current flowing
through the breaker by simply connecting a meter with
light gauge wire to the appropriate terminals located on the
shunt housing at the rear of the breaker. Applications can
be customized by measuring and displaying percentage of
current, watts or safe/danger zones.
Features:
ŠŠ AC ratings to UL 489
ŠŠ DC voltage ratings up to 700A with metering
shunt section
ŠŠ Consistent trip point over temperatures ranging
from -40°C to +85°C
ŠŠ Optional 25 millivolt metering shunt construction
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
Applications:
ŠŠ Ideal for applications under extreme temperatures
ŠŠ Higher Amperage Applications
ŠŠ Battery Disconnect Systems
ŠŠ Solar Power Systems
ŠŠ Military
2 | F-Series Circuit Breaker - General Specifications
Electrical
Mechanical
Maximum Voltage
Current Rating
Endurance
125VDC, 277 VAC
Standard current coils: 100, 125,
150, 175, 225, 250 amps. 300, 350,
400, 500, 600, 700 amps available as
parallel pole construction.
Auxiliary Switch Rating SPDT; 10.1 Amps @ 250VAC, 1.0
Amps @ 65VDC, 0.5 Amps @ 80VDC
0.1 Amps @ 125VAC (with gold
contacts).
Insulation Resistance
Minimum: 100 Megohms at 500 VDC
Dielectric Strength
1960 VAC, 50/60 Hz for one minute
between all electrically isolated
terminals, except 2500 VAC for one
minute between alarm/aux. switch
and main terminals with contacts in
open and closed position. F-Series
circuit breakers comply with the
8mm spacing & 3750VAC 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main circuits
to auxilary circuits per Publications EN
60950 and VDE 0805.
Resistance, Impedance Values from Line to Load Terminal based on Series Trip Circuit Breaker.
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Trip Free
Trip Indication
4000 ON-OFF operations with rated
Current & Voltage & 4000 operations
with no load (8000 operations
total) @ 5 per minute. Parallel Pole
construction: 1000 operations with
rated Current and Voltage @ 5 per
minute.
All F-Series Circuit Breakers will trip on
overload, even when the actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the circuit breaker
to trip.
Physical
Number of Poles
1 - 3 Poles Note: Ratings over 250
Amps only available with parallel pole.
Internal Circuit Config. Series (with or without auxiliary
switch), Switch Only (with or without
auxiliary switch).
Available Accessories Factory installed: DC Current Metering
Shunt (25 mV @lr)
Weight
Varies depending on construction.
Consult factory.
Standard Colors
Housing - Black; Actuator- Black
or White with contrasting ON-OFF
legend.
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth while
carrying rated current per Method 213,
Test Condition “I”. Instantaneous and
ultra-short curves tested @ 90% of rated
current.
Vibration
Withstands 0.060” excursion from 1055 Hz, and 10 Gs 55-500 Hz, at rated
current per Method 204C, Test Condition
A. Instantaneous and ultrashort curves
tested at 90% of rated current.
Moisture Resistance
Method 106D; ten 24-hour cycles @ +
25°C to +65°C, 80-98% RH.56 days @
+85°C, 85% RH.
Salt Spray
Method 101, Condition A (90-95% RH @
5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (Five cycles
@ -55°C to +25°C to +85°C to +25°C).
Operating Temperature -40°C to +85°C.
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
F-Series Circuit Breaker - General Specifications | 3
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance
capabilities as aTables
Molded Case Circuit Brekaer
Electrical
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance capabilities as a Molded Case Circuit Breaker
F SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
CIRCUIT
CONFIGURATION
MAX
RATING
FREQUENCY PHASE
125
SERIES
CURRENT
RATING
INTERRUPTING
CAPACITY (AMPS)
FULL LOAD
AMPS
UL / CSA
1 - 3 POLES
TUV 2
1 or 2 POLES
DC
---
50 - 250
50,000
25,000
1
50 / 60
50 / 60
1
1
100 - 250
100 - 250
10,000
10,000
-----
208Y / 120
50 / 60
3
100 - 250
10,000
---
120 / 240
277
Notes:
NOTES:
1 120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
1.
rating
in 2ACorratings.
3 poles. In a 3 pole construction the center pole is Neutral.
2 120/240V
TUV constructions
are available
not available with
2. TUV constructions are not available with AC ratings.
Table B: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A
Agency Certifications
UL Listed
UL 489
UL 489A
Circuit Breakers , Molded Case
(Guide DIVQ, File E129899)
Complies with the requirements
of the CSA Standard for Molded
Case Circuit Breakers,
CANCSA- C22.2 No. 5.1 –M
Circuit Breakers for Use in
Communications Equipment
(Guide DITT, File E189195)
TUV Certified
IEC 60947-2
Low Voltage Switchgear and Control
Gear under TUV License No.
R72031058
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
4 | F-Series Handle – Ordering Scheme
F A 2 — B 0 — 14 — 820 — 1 2 A — B G
1
Series
2
Actuator
4
Circuit
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
1 SERIES
F
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
3 POLES
1
2
One
Switch Only (no coil)
Series Trip (current)
Series Trip (voltage)
w/o Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
8
9
A6 B6
14 16 22 24 26 S.P.S.T., 0.187 Q.C.
Terminals
S.P.D.T., 0.187 Q.C.
Terminals.
S.P.S.T., 0.093 Round QC
Terminals.
S.P.D.T., 0.093 Round Q.C.
Terminals.
DC Medium
DC Long
AC Short
AC Medium
AC Long
7 CURRENT RATING (AMPERES)
CODE
AMPERES
CODE
AMPERES
810 100.00
820 200.00
8358350.00
912 125.00
922225.00
8408400.00
815 150.00
825 250.00
8458450.00
917 175.00
8308300.00
8508500.00
OR VOLTAGE COIL (VOLTS, MIN. TRIP RATING)7
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
8 TERMINAL
10
Mounting
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
Back Connected (Front Mounted Only)
19
3/8-16 Stud 214
3/8-16 Screw, Line & Load 514
3/8-16 Short Stud Front Connected (Back Mounted Only)11 3
Box Wire Connector, Line & Load 414
3/8-16 Screw, Line & Load 11
Max. App.
Rating
12
Agency
Approval
Dual
Marking Color
1Black
2White
Back Mounting Inserts
10-32 screw clearance holes
10-32 screw clearance holes
Three
Parallel Pole Construction:
M3,4 Series Trip (Current) with
Metering Shunt
N3,4 Switch Only with
Metering Shunt
P3
Series Trip (Current)
3
Q
Switch Only
6 FREQUENCY & DELAY
03 107 11 12 Front Mounting Inserts
A
10-32
B
ISO M5
3
5 AUXILIARY/ALARM SWITCH5
0
2
3
4
5
6
7
9
Actuator
Color
10 MOUNTING
Two
4 CIRCUIT
A1
B
C2
8
Terminal
9 ACTUATOR COLOR & LEGEND12,13
Acuator Color
I-O
ON-OFF
White
AB
Black
CD
2 ACTUATOR
A
S
T
7
Current Rating
8608600.00
8708700.00
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
11 MAXIMUM APPLICATION RATING
VOLTAGECURRENT
B
125 VDC
700A
C15
120/240250A
F
277 VAC
250A
716
120/208 VAC
250A
12 AGENCY APPROVAL
A
No approvals
G
UL 489 Listed & CUL Certified
J
UL 489 Listed, CUL Certified & TUV Certified
T
UL489A (Telecom) Listed
Notes:
1 For 100 to 250 amps, select Current Code 825. For 300-400 amps, select Current Code 840. For 450-700 amps, select Current Code 870.
2 Available with Frequency and Delay code 10 or 20 only, and are not rated for continuous duty. Delay 10 and 20 are only available with voltage coils.
3 3 Codes M, N, P & Q (Parallel Poles) are supplied with factory installed Bus Bar on Line and Load.
4 4 Metering terminals are female pin type, ref. Molex part number 02-09-1101, model 1189-T.
5 Auxiliary Switch breakers are only available with Series Trip and Switch Only circuits. On multi-pole breakers, one Auxiliary Switch is supplied, mounted in the extreme right pole per figure A. Back-Mounted breakers require special mounting provisions when an Auxiliary Switch is specified.
6 Available with parallel pole construction (circuit codes P and Q, and breakers with circuit codes M and N).
7 Frequency and delay code 10 is only available with Voltage Coils. Voltage Coils are not rated for continuous duty.
8 Ratings over 250 amps are only available with Agency Approval code T (UL489A) and are Parallel Pole configuration (circuit codes M, N, P and Q.) 300-450 amp ratings are available on two pole breakers. 500-700 amp ratings are available on three pole breakers.
9 Per UL requirement, an “Anti-Flash Over Barrier” is supplied between poles on multipole
breakers with 3/8 - 16 stud terminals (Terminal Code 1)
10 Front connected breakers can also be front mounted by utilizing the supplied front panel mounting inserts.Terminal connections must be made before mounting.
11 Box Wire connector will accept #6 through 250 MCM copper wire.
12 Agency codes G & T must have ON-OFF or dual legends. Agency code J must have dual legend.
13 Other colors available. Consult factory.
14 Terminals 2,4 & 5 are shipped without terminal hardware.
15 2 or 3 Pole Circuit Breaker Required for 120/240 VAC Rating.
16 3 Pole Circuit Breaker Required for 120/208 VAC Rating.
Max Rating
250A
700A
250A
Max Rating
700A
700A
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
F-Series Handle – Circuit & Terminal Diagrams | 5
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
6 | F-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
F-Series Handle – Circuit & Terminal Diagrams | 7
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
8 | F-Series Handle – Form & Fit Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
F-Series Handle – Form & Fit Diagrams | 9
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
10 | F-Series Handle – Form & Fit Diagrams
F-Series breakers are available up to 700A, and are also available with a 25 millivolt metering shunt
construction. This optional construction provides a safe method for monitoring current flowing through
the breaker by simply connecting a meter with light gauge wire to the appropriate terminals located
on the shunt housing at the rear of the breaker. You can customize the application by measuring and
displaying percentage of current, watts or safe/danger zones.
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
F-Series Handle – Form & Fit Diagrams | 11
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
12 | F-Series Circuit Breaker - Time Delay Curves
11
12
14
16
22
24
26
Short - AC 22
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
.013 - .125
.475 - 10.0
10.0 - 110
110 - 1000
.700 - 12.0
10.0 - 160
50.0 - 700
AC
.010 - .070
.008 - .032
.275 - 2.80
.140 - .850
6.00 - 40.0
60.0 - 400
.350 - 4.00
6.00 - 60.0
32.0 - 350
2.50 - 15.0
22.0 - 150
.130 - 1.30
.220 - 20.0
10.0 - 90.0
.005 - .020
.004 - .020
.030 - .190
.015 - .125
.004 - .020
.010 - .050
.008 - .038
.500 - 3.00
4.00 - 25.0
.027 - .220
.300 - 3.00
1.50 - 15.0
.180 - 1.00
1.00 - 5.50
.008 - .130
.050 - 1.30
.500 - 7.00
.010 - .280
.008 - .080
.008 - .390
.004 - .045
.005 - .060
.006 - 2.00
.006 - .020
Ultrashort - DC
.010 - 1.80
.004 - .090
.007 - .500
.020 - 3.00
DC
F SERIES
50/60 HZ SHORT
CURVE NO. 22
Short - DC
Medium - AC 24
F SERIES
50/60 HZ MEDIUM
CURVE NO. 24
Medium - DC
Long - AC 26
F SERIES
50/60 HZ LONG
CURVE NO. 26
Long - DC
REV_CB_F_0612