LEM HNC-200P

Current Transducer HNC- 200 .. 300P
IPN = 200 .. 300 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary nominal
DC current
Primary current
measuring range
IPN (A)
Type
IP (A)
200
300
0 .. ± 400
0 .. ± 650
HNC - 200P
HNC - 300P
HNC - 200P HNC - 300P
RM
ISN
KN
Measuing resistance
Second nominal current
Turns ratio
20 .. 60
100
1 : 2000
20 .. 35
100
1 : 3000
VC
IC
Vd
Supply voltage (± 5 %)
± 15
Current consumpution
15 + ISN
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 2.5
Ω
mA
V
mA
kV
Accuracy-Dynamic performance data
X
ε
L
IO
IHC
IOT
tr
TCε G
Accuracy @ T A = 25°C
Linearity (0 .. ± IPN )
Electrical offset current @IP = 0, @T A = 25°C
Hysteresis offset current @ IP = 0,
after an excursion of IPN
0°C .. +70°C
Thermal drift of IO
Response time @ 90% of IP
Thermal drift of the gain (% of reading)
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500 V
• Low power consumption
Advantages
< ± 1 % of IPN
< 0.25 % of IPN
± 0.5
mA
± 0.3
mA
± 0.005mA/K°C
<1
µs
± 0.04
%/°C
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external interference
Applications
• DC motor drives
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
General data
TA
TS
Ambient operating temperature
Ambient storage temperature
RS
Secondary coil Resistance
@T A = 25°C
m
Mass
- 10 .. + 80 °C
- 15 .. + 85 °C
HNC - 200P
HNC - 300P
10
20
(UPS)
• Battery supplied applications
• Inverters
Ω
160
g
010301/1
www.nanalem.co.jp
HNC- 200 .. 300P