LEM NNC-940A-4000A-10V

Current Transducer NNC-920..960A
IPN = 2000..6000 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary D.C.
current
IPN (A)
Primary current
measuring range
IP (A)
2000
3000
4000
5000
6000
VC
IC
Vd
RIS
VOUT
RL
±
±
±
±
±
2300
3400
4500
5600
6600
Type
NNC-920A
NNC-930A
NNC-940A
NNC-950A
NNC-960A
Supply voltage (±5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Load resistance
2000A-10V
3000A-10V
4000A-10V
5000A-10V
6000A-10V
±15
<±30
2.5
>500
±10
10
V
mA
kV
MΩ
V
kΩ
<±1
<±1
<±50
% of IPN
% of IPN
mV
<±70
<±2
<±0.1
<25
mV
mV/K
%/K
µs
Accuracy - Dynamic performance data
X
ε
L
VOE
VOH
VOT
TCε G
tr
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Thermal drift of VOE
Thermal drift (% of reading)
Response time @ 90% of IP
Ambient operating temperature
Ambient storage temperature
Mass
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500V
• Low power consumption
Advantages
• Easy to mount
• Small size and space saving
• Large-current application
• High immunity to external
interference.
General data
TA
TS
m
Features
-10 .. +50
-15 .. +60
1.7
Applications
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Battery supplied applications
• Power supplies for welding
applications, cable TV,
communication devices
• Commutator power supplies
• Electric transmission
°C
°C
Kg
Notes :
040824/3
LEM Components
www.lem.com
NNC-920..960A
Dimensions (in mm)
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.