LEM NNC-920A

Current Transducers NNC-920 .. 960A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronic circuit).
IPN = 2000 .. 6000 A
Electrical data
Primary nominal
r.m.s. current
IPN (A)
±
±
±
±
±
2000
3000
4000
5000
6000
VC
IC
Vd
Vb
V
R IS
VOUT
ROUT
RL
Primary current
measuring range
IP (A)
2200
3300
4400
5500
6600
Type
NNC
NNC
NNC
NNC
NNC
-
Features
• Hall effect measuring principle
• Galvanic isolation between primary
920A
930A
940A
950A
960A
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
R.m.s. rated voltage, safe separation
± 15
< ± 25
2.5
Isolation resistance @ 500 VDC
Output voltage @ ± IPN , RL = 10 kΩ, T A = 25°C
Output internal resistance
Load resistance
> 1000
100
10
and secondary circuit
• Isolation voltage 3000 V~
• Low power consumption
V
mA
kV
500
MΩ
± 10 V
Ω
kΩ
Advantages
• Easy mounting
• Space saving
• High immunity to external
interference.
Applications
• AC variable speed drives
• Battery supplied applications
• Uninterruptible Power Supplies
Accuracy - Dynamic performance data
XG
ε
L
VO E
VOH
VOT
TCε G
tr
Accuracy @ T A = 25°C
Linearity (0 .. ± IPN )
Electrical offset voltage, T A = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
< ± 1 % of IPN
< ± 1 % of IPN
< ± 50
mV
< ± 50
<±1
< ± 0.1
< 25
(UPS)
mV
mV/°C
%/°C
µs
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
- 10 .. + 60
- 15 .. + 65
1.4
°C
°C
kg
Notes : Linearity data exclude the electrical offset.
010301/1
www.nanalem.co.jp
NNC-920 .. 960A
UNIT: mm
NANALEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.