NTE NTE15050AC

NTE15040–ECG thru NTE15048–ECG
NTE15049AC & NTE15050AC
Surge Arresters (Gas Filled)
DC Breakdown Voltage
NTE Type No.
15040–ECG
15041–ECG
15042–EGC
15043–ECG
15044–ECG
15045–ECG
15046–ECG
15047–ECG
15048–ECG
15049AC
15050AC
Diag.
No.
628
628
628
628
628
628
628
628
628
628
628
Nominal Voltage
(VDC)
75
90
110
145
230
300
350
470
600
120VAC
240VAC
Minimum
Volts
60
72
88
116
195
255
297
400
510
225
425
Maximum
Volts
90
108
132
174
265
345
403
540
690
–
–
Impulse Breakdown
@ (100V/ms)
Maximum Voltage
400
400
450
500
600
700
750
850
1000
700
800
Maximum Capacitance
Between Electronics
@ 1MHz (pF)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
SPECIFICATIONS
Surge Life
10A 10/1000µs Pulse . . . . . . . . . . . . . . . . . . . . 2500 Operations
500A 10/1000µs Pulse . . . . . . . . . . . . . . . . . . . 1000 Operations
AC Suffix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 Operartions
Surge Current
8/20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20kA
AC Current
10 Operations 60Hz for 1sec., with 3 min. Intervals . . . . . . 20
AC Suffix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
AC Current
11 Cycles 60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20A
AC Suffix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10A
Insulation Resistance
100 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10,000 Megohms
Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . –65° to +125°C
Response Time (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 100ns
TYPICAL CIRCUIT APPLICATIONS
Application
CATV
Protected Equipment
NTE Type
Trunk Amplifier
15043–ECG
Cable Extender, Splitter
Grounding Block, Converter Box,
30 & 60 VAC Power Supply
15044–ECG
AC Line
Protection
117 VAC Line
15049AC
220 VAC Line, All AC Loads
15050AC
Communication
Modem
15046–ECG
Antenna Connected Equipment
15041–ECG,
15043–ECG,
15044–ECG
Power Supplies
Voltage Doubler, Capacitors,
Voltage Regulator, Rectifier
Diodes
15044–ECG,
15047–ECG
Computer
Data Lines
15041–ECG,
15044–ECG
Diagram 628
Application
Protected Equipment
NTE Type
Test Equipment Meter Inputs
15040–ECG,
15045–ECG
Capacitive
Discharge
Ignition Circuit Components,
Pulse Generator Components
15044–ECG,
15046–ECG
Signal Lines
(Single Ended)
Alarm Circuits
15040–ECG
Communications Telephone Line
(Lightning)
(Normal Mode)
15046–ECG
Power Line
(Lightning)
AC Wall Output (Long Branch
Circuit) 120 VAC
15049AC
Breaker Box (Short Branch
Circuit) 240 VAC
15050AC
Instrumentation Circuits
15040–ECG,
15041–ECG
Process Control
(24 MA Signal
Loop)
1.490 (37.7)
.245 (6.22)
.032 (0.813) Dia
.319 (8.1) Dia