SeriesOne DR Dual Series • Dual Output with Ratings of 6 Amps each channel • Load voltage ratings of 24-280VAC and 48-600VAC • Fits standard 35mm DIN-RAIL • LED input status indicator • DC control (4-32V) • Zero-crossing (resistive loads) or random turn-on (inductive loads) output • UL and cUL Recognized (General Purpose and Motor Control) • CE & RoHS Compliant • 100K-cycle UL 508 Endurance Rating for Enhanced Reliability PRODUCT SELECTION Description 280V, 6A 600V, 6A 4-32 VDC Control DRD24D06 DRD48D06 DRD24D06 DRD48D06 24-280 600 6 0.15 0.1 500 1.3 715/750 2560/2330 1/6 0.5 22/14 AWG 22/14 AWG 48-600 1200 6 0.15 0.25 500 1.3 715/750 2560/2330 1/6 0.5 22/14 AWG 22/14 AWG AVAILABLE OPTIONS OUTPUT SPECIFICATIONS (1) Description Operating Voltage (47-63Hz) [Vrms] Transient Overvoltage [Vpk] Maximum Load Current per channel, resistive [Arms] (2) Minimum Load Current [Arms] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3) Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum Surge Current (50/60 Hz, 1 cycle) [Apk] Maximum I²t for Fusing (50/60 HZ, 1/2 cycle) [A² sec] HP Rating @ 240V Minimum Power Factor (with Maximum Load) Min/Max stranded wire Min/Max solid wire INPUT SPECIFICATIONS (1) Description DRDxxD06 Control Voltage Range [Vdc] (4) Minimum Turn-Off Voltage [Vdc] Minimum Input Current [mA] (5) Maximum Input Current [mA] (5) Minimum Turn-On Voltage [Vdc] Maximum Turn-On Time (6) Maximum Turn-Off Time Min/Max stranded/solid wire 4.0-32 1.0 9 11 4.0 1/2 Cycle 1/2 Cycle 22/16 AWG GENERAL SPECIFICATIONS (1) Description Dielectric Strength, Input to Output (50/60Hz) Minimum Insulation Resistance (@ 500 V DC) Maximum Capacitance, Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range Recommended Terminal Screw Torque Range: Weight (typical) Parameters 2500Vrms 109 Ohms 10 pF -30ºC to 80ºC -30ºC to 100ºC 4.4-7.0 in lb (0.5-0.8 Nm) 3.17 oz. (90g) GENERAL NOTES 1) All parameters at 25°C unless otherwise specified. 2) See Derating Curves 3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 4) DC control includes reverse polarity protection. 5) Input circuitry incorporates active current limiter. 6) Turn-on time for DC control random turn-on versions is 0.1 msec MECHANICAL SPECIFICATIONS WIRING DIAGRAM THERMAL DERATE INFORMATION AGENCY APPROVALS E116949 Rev 120910