MAGNETROL P61-2G3B-PEA

Pneumatic Modulevel®
& APM Controllers
Installation and Operating Manual
Liquid
Level
Control
Read this Manual Before Installing
This manual provides information on F10 and F50 Flow
Switches. It is important that all instructions are read carefully and followed in sequence. Detailed instructions are
included in the Installation section of this manual.
Conventions Used in this Manual
Certain conventions are used in this manual to convey
specific types of information. General technical material,
support data, and safety information are presented in
narrative form. The following styles are used for notes,
cautions, and warnings.
NOTES
Notes contain information that augments or clarifies
an operating step. Notes do not normally contain
actions. They follow the procedural steps to which
they refer.
Cautions
Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce
a component’s mechanical integrity. Cautions are also
used to alert the technician to unsafe practices or the
need for special protective equipment or specific
materials. In this manual, a caution box indicates a
potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
WARNINGS
Warnings identify potentially dangerous situations or
serious hazards. In this manual, a warning indicates an
imminently hazardous situation which, if not avoided,
could result in serious injury or death.
Safety Messages
Follow all standard industry procedures for servicing electrical equipment when working with or around high
voltage. Always shut off the power supply before touching any components.
WARNING! Explosion hazard. Do not connect or disconnect equipment unless power has been switched off or
the area is known to be non-hazardous.
Low Voltage Directive
For use in Installation Category II. If equipment is used
in a manner not specified by the manufacturer, protection provided by the equipment may be impaired.
Notice of Trademark, Copyright, and Limitations
Magnetrol and Magnetrol logotype, and Modulevel are
registered trademarks of Magnetrol International.
Copyright © 2009 Magnetrol International,
Incorporated. All rights reserved.
Performance specifications are effective with date of
issue and are subject to change without notice.
Magnetrol reserves the right to make changes to the
product described in this manual at any time without
notice. Magnetrol makes no warranty with respect to
the accuracy of the information in this manual.
Warranty
All Magnetrol mechanical level and flow controls are warranted free of defects in materials or workmanship for five
full years from the date of original factory shipment.
If returned within the warranty period; and, upon factory
inspection of the control, the cause of the claim is
determined to be covered under the warranty; then,
Magnetrol will repair or replace the control at no cost to
the purchaser (or owner) other than transportation.
Magnetrol shall not be liable for misapplication, labor
claims, direct or consequential damage or expense arising
from the installation or use of equipment.
There are no other warranties expressed or implied,
except special written warranties covering some
Magnetrol products.
Quality Assurance
The quality assurance system in place at Magnetrol guarantees the highest level of quality throughout
the company. Magnetrol is committed to providing full
customer satisfaction both in quality products and quality
service.
Magnetrol’s quality assurance system is
registered to ISO 9001 affirming its
commitment to known international
quality standards providing the
strongest assurance of product/service
quality available.
48-620 Modulevel Pneumatic Liquid Level Control
Modulevel Pneumatic
Liquid Level Control
Table of Contents
1.0 Introduction
1.1 Principle of Operation ..............................................5
1.2 Operating Cycle ........................................................5
1.3 Description ...............................................................6
1.3.1 Controller Action ...........................................6
1.3.1.1 Proportional Control...............................6
1.3.1.2 Transmitter..............................................6
1.3.1.3 Transmitter/Receiver Controller ..............6
1.3.1.4 Proportional Plus Integral Control ..........6
1.3.1.5 Differential Gap ......................................7
1.3.2 Controller Options.........................................7
1.3.2.1 Direct or Reverse Action .........................7
1.3.2.2 Electric Limit Switches............................7
1.3.3 Mounting Arrangements ................................7
1.3.3.1 Flanged Top P51, P61 and P62
Displacer Models ....................................7
1.3.3.2 Top Mounted APM-131 .........................7
1.3.3.3 External Cage P53, P55, P63, P64, P65,
P66, P71, P72, P73 and P74 Displacer
Models ....................................................7
1.3.3.4 External Cage APM-W251,
APM-W254 and APM 291.....................8
1.3.3.5 Side Mounted P68 Float Model ..............8
2.0 Installation
2.1 Unpacking ................................................................8
2.1.1 P51, P61, P62 and APM-131 Models............8
2.1.2 P53, P55, P63, P64, P66,
P71, P72, APM-W251, APM-W254
and APM-W291 Models ................................8
2.1.3 P68 Models ....................................................8
2.1.4 Transmitter – Receiver Controller Units.........9
2.1.5 Specifications..................................................9
2.2 Mounting................................................................10
2.2.1 Top Mounted Models – P51, P61 & P62 ....11
2.2.2 External Cage Models – P53, P55, P63,
P64, P65, P66, P71 & P72 ..........................11
2.2.3 Side Mount Models – P68 ...........................12
2.2.4 Transmitter – Receiver Models .....................12
48-620 Modulevel Pneumatic Liquid Level Control
2.3 Calibration..............................................................13
2.3.1 Proportional Controllers...............................13
2.3.1.1 Calibration Chart instructions ..............15
2.3.2 Reset Controllers ..........................................16
2.3.3 Transmitters .................................................17
2.3.4 Receiver Controllers .....................................18
2.3.5 Differential Gap ...........................................18
2.3.6 Interface Models...........................................19
2.3.7 Electric High/Low Limit Switches................20
2.3.7.1 Electrical Ratings...................................20
2.3.7.2 Wiring Information ..............................20
2.3.7.3 Adjustment Procedure...........................21
2.4 Field Modifications and Adjustments......................21
2.4.1 Changing Controller Action.........................21
2.4.2 Proportional Band Models to
Differential Gap ...........................................21
2.4.3 Pneumatic-to-Current (P/I) Converter .........21
2.4.4 Reset Installation ..........................................22
2.4.5 Reset Cleaning .............................................23
2.4.6 Disabling Reset ............................................23
3.0 Reference Information
3.1 Troubleshooting ......................................................24
3.1.1 Installation ...................................................24
3.1.2 Calibration ...................................................24
3.1.3 Operation.....................................................25
3.2 Specifications ..........................................................27
3.2.1 Standard Flanged Top and Flanged Cage
Displacer Models P62, P63, P64, P65
and P66 Dimensional Specifications ............27
3.2.2 High Pressure Flanged Top and
Flanged Cage Displacer Models P51, P53
and P55 Dimensional Specifications ............28
3.2.3 Standard Sealed Cage Displacer Models
P71 and P72
Dimensional Specifications...........................29
3.2.4 Models APM-131, APM-W251,
APM-W254 and APM-W291 Dimensional
Specifications ............................................30
3.2.5 Standard Side Mount Float Models P68
Dimensional Specifications .......................31
Modulevel Pneumatic
Liquid Level Control
Table of Contents (continued)
3.3 Replacement Parts...................................................32
3.3.1 Model P68 Threaded and Flanged
Parts Identification .......................................32
3.3.1.1 Model P68-2F2A Threaded 3" NPT.....33
3.3.1.2 Model P68-2H3A, P68-2H4A and
P68-2H5A 4" Flanged ..........................33
3.3.2 Model Series P6x Parts Identification ...........34
3.3.2.1 Series P61, P62, P63, P64,
P65, P66, P71 and P72.........................36
3.3.3 Series P51, P53 and P55 Parts
Identification................................................37
3.3.3.1 Series P51, P53 and P55 .......................38
3.3.4 Model APM-131 Parts Identification ...........39
3.3.4.1 Model APM-131 Part Number ...............39
3.3.5 Models APM-W251, APM-W254
and APM-W291 Parts Identification............40
3.3.5.1 Models APM-W251, APM-W254
and APM-W291 Parts Numbers .............41
3.3.6 Controller Parts............................................42
3.3.6.1 Controller Replacement
Assemblies Parts Identification ..............43
3.3.6.2 Tubing Kit 89-8501-015
@ 3–15 and 6–30 psig ..........................44
3.3.6.3 Nozzle Lever Kit 89-8501-002
@ 3–15 and 6–30 psig ..........................44
3.3.6.4 Carriage Assembly Kit
89-8501-003 @ 3–15 and 6–30 psig.....44
3.3.6.5 Feedback Assembly Kit
89-8501-005 @ 3–15 and 6–30 psig.....45
3.3.6.6 Gasket Kit for Relay Assembly
89-8501-014 @ 3–15 and 6–30 psig ...45
3.3.6.7 Additional Replacement Parts ...............45
3.3.7 Reset Replacement Parts...............................46
3.3.7.1 Reset Replacement Assemblies ..............47
3.3.7.2 Replacement Kits (Reset Valve,
O-Ring and Offshore)...........................47
3.3.8 Receiver Controller Parts..............................48
3.3.8.1 Receiver Controller Replacement
Assemblies.............................................48
3.3.9 Transmitter Mounted Receiver
Controller Parts............................................49
3.3.9.1 Transmitter Mounted Receiver
Controller Replacement Assemblies ......49
3.3.10 Pneumatic Modulevel Replacement
Head Kits..............................................50
3.4 Model Numbers......................................................52
3.4.1 Standard Flanged Top and
Flanged Cage Displacer Models....................52
3.4.2 High Pressure Flanged Top and
Flanged Cage Displacer Models....................54
3.4.3 Standard Sealed Cage Displacer Models .......56
3.4.4 Standard Side Mount Displacer Models .......58
3.4.5 APM Pneumatic Control Models .................59
48-620 Modulevel Pneumatic Liquid Level Control
1.0
Introduction
Modulevel pneumatic controls are displacement actuated
level sensors that provide output signals in direct proportion to changes in liquid level.
Simple modular design and proven magnetic coupling
make Modulevel controls versatile, highly stable, vibration
resistant and adaptable to extremes of temperature and
pressure.
1.1
Pilot Nozzle
Flapper
Cam
Attraction Ball
Magnet
Enclosing
Tube
Zero Adjustment
Indicator
The key elements of the Modulevel
pneumatic control are the magnetic
coupling, which allows the controller
to be mechanically isolated from the
sealed sensing unit; the range spring,
which converts the change in buoyancy
force on the displacer into motion; and
the controller head, which provides a
modulated pneumatic signal in direct
proportion to the motion of the spring.
Proportional Band
Adjustment
Proportional
Band Spring
0
100
Range
Spring
Actuating
Lever
Set Point
Adjustment
Feedback
Bellows
Reset
Valve
Relay
Chamber
Displacer
OUTPUT
Supply Pressure
Reset
Bellows
Check
Valve
Orifice
SUPPLY
Filter
Regulator
Control
Valve
Output pressure
Pilot Pressure
Figure 1
48-620 Modulevel Pneumatic Liquid Level Control
Principle of Operation
Reset Pressure
1.2
Operating Cycle
The result of liquid level changes in
the vessel is a change in the buoyancy
force acting on the displacer and in the
load on the spring from which the displacer is suspended. As the spring
extends or compresses with the change
in load, an attraction ball attached to
the spring via a stem assembly moves
within the enclosing tube.
A magnet encircling the enclosing
tube follows the attraction ball, transferring the motion to a rotating cam,
which in turn operates a flapper
against a nozzle which increases or
decreases the pressure within the pneumatic relay. The output pressure signal
can be used in a variety of ways to
operate a control valve or signal
alarms, indicators, process controls or
other devices.
5
1.3
Description
Modulevel pneumatic instruments are available for a
variety of functions to handle different application
requirements.
1.3.1 Controller Action
1.3.1.1 Proportional Control
Proportional control instruments are used to maintain
the level in a tank within a predetermined band. The
output from the Modulevel head controls the opening
and closing of a valve to control the increase or
decrease of the liquid flow through the vessel.
1.3.1.2 Transmitter
Transmitters provide a pneumatic signal proportional
to the level of a liquid. The signal can be fed to a
variety of devices as the application requires.
1.3.1.3 Transmitter/Receiver Controller
There are two devices in this version. The transmitter
senses level directly at the vessel, and provides a pneumatic signal to the receiver/controller. The receiver/
controller operates in the same manner as a direct
connected level device, such as a proportional controller, which allows varying the proportional band
and level set point. This unit may be mounted either
integrally with the transmitter, or at a more
convenient remote location.
1.3.1.4 Proportional Plus Integral Control
Proportional plus integral control instruments (i.e.,
with reset) operate in the same manner as the proportional unit with one major difference. The offset
between the desired level and the actual level is eliminated, thus maintaining the level at a point rather
than within a band.
6
48-620 Modulevel Pneumatic Liquid Level Control
1.3.1.5 Differential Gap
A differential gap instrument provides two distinct outputs,
either opened or closed. One distinct output value is
obtained when the level exceeds the upper switching point.
This value remains constant until the level decreases below
the lower switching point. At this time the controller
changes to another distinct output value. The new value
remains constant until the level again rises above the upper
switching point causing the output value to return to the
first output value. The distance between the two switching
points is called the differential gap.
1.3.2 Controller Options
Locking
Screw
1.3.2.1 Direct or Reverse Action
Direct acting controllers provide an output signal that
increases with level increase. Reverse acting controllers
provide an output signal that decreases with level increase.
1.3.2.2 Electric Limit Switches
Electric limit switches allow high and low level alarms to be
added to any of the pneumatic instruments described above.
1.3.3 Mounting Arrangements
Figure 2
Top Mount
1.3.3.1 Flanged Top P51, P61 and P62 Displacer Models
When mounting inside the tank is possible, flanged top
models are the answer (Figure 2). They are used extensively
in interface control applications where nonstandard displacers become necessary. An adjustable stainless steel displacer
hanger cable is also available. Top mounting models are
directly interchangeable with the external cage models.
1.3.3.2 Top Mounted APM-131
Figure 3
P6X External
Cage
When mounting inside the tank is possible, threaded
top models are the answer. An adjustable stainless steel
displacer suspension cable is provided as standard.
1.3.3.3 External Cage P53, P55, P63, P64, P65, P66, P71and
P72 Displacer Models
Figure 4
APM External Cage
48-620 Modulevel Pneumatic Liquid Level Control
External cage models (Figure 3) can be easily isolated from
the process to simplify maintenance and inspection
operations. The in-line design eliminates the need for
specifying "right hand" or "left hand". Any mounting
position is possible by rotating the instrument head. A
variety of models are available including sealed or flanged
cage with either side/side or side/bottom connections.
Carbon steel and stainless steel models are available.
7
1.3.3.4 External Cage APM-W251, APM-W254, APM-W291
Water Column external cage models (Figure 4) can be
easily isolated from the process to simplify maintenance
and inspection operations. Sight glass and Try-cock
tappings are provided.
1.3.3.5 Side Mounted P68 Float Model
Side mounted models (Figure 5) are ideally suited for
narrow level range applications. Carbon steel models are
available with either a 3" NPT threaded body or a 4"
flanged connection.
Figure 5
2.0
Installation
2.1
Unpacking
After unpacking, inspect all the components to see that no
damage has occurred during shipment. Care should be taken
not to bend the displacer stem or enclosing tube during
unpacking or installation.
Next, open controller case and remove magnet hold down and
nozzle lever retainers. Examine internal controller components
for any obvious damage or loosened parts. Check all air connections to make certain they are free of any foreign matter.
2.1.1 P51, P61, P62 and APM 131 Models
Top mounting Modulevel units are shipped from the factory
with the controller and displacer removed from the head
assembly and packed separately in the same carton or crate.
2.1.2 P53, P55, P63, P64, P66, P71, P72, APM-W251,
APM-W254 and APM-W291 Models
All cage type Modulevel units are shipped with the controller
removed from the chamber assembly and packed separately
in the same carton or crate.
A strap and wire assembly retains and protects the displacer
within the chamber during shipment. The assembly must be
removed through the bottom connection before start-up.
Caution: If reshipping to another location, displacer assembly must
again be secured using same strap and wire assembly.
2.1.3 P68 Models
The side mounting Modulevel units are shipped with the
controller and float and stem assembly removed from the
body and are packed separately in the same carton or crate.
After unpacking, inspect all components to see that no
damage has occurred during shipment.
8
48-620 Modulevel Pneumatic Liquid Level Control
2.1.4 Transmitter — Receiver Controller Units
Dual head receiver controller models may be supplied to
be integrally mounted to the top mounting or external
cage style Modulevel controls or to be remotely mounted
away from the Modulevel controls. Units supplied with
top mounting Modulevels may be shipped assembled and
connected to the transmitter head or separately for field
assembly. External chambered units will have the receiver
controller head connected to the transmitter head, but separate from the chamber. Any heads shipped unassembled
from the Modulevel will be packed in the same carton or
crate as the control. Handle controllers carefully to avoid
damage to the airline piping.
2.1.5 Specifications
Description
Process pressure
Process temperature
Specification
Up to 4265 psig at +100° F
(Up to 318 bar at +38° C)
-150° F to +700° F
(-101° C to +371° C)
Stainless steel chamber and bolting
required for temperatures below
-20° F. (Consult factory).
Specific gravity range
Minimum: 0.23
Maximum: 2.20
Interface detection
Minimum difference of 0.10 specific
gravity between liquids
Process connections
NPT, Socket Weld or Flanged
Supply pressure
Instrument quality air (clean and dry)
Regulated to 5 psig (.3 bar)
above maximum output.
Proportional &
Output
3–15 psig, 6–30 psig
transmitter
signal
pressure Differential gap 0–20 psig or 0–35 psig
Visual Indicator
% Span
Level range & proportional Limited only to displacer length. From
band adjustment
inches to 10 feet (3 meters).
48-620 Modulevel Pneumatic Liquid Level Control
Air consumption
3 SCFH at 9 psig output
6 SCFH at 15 psig output
Response speed
100 cu. in. output volume in 3.2 sec.
upon an output pressure increase
from 3–15 psig.
Wetted parts
Trim: 304 or 316 SS
Spring: 316 SS or inconel
Chamber: Carbon steel or 316 SS
Control action
Direct or reverse
Modes of operation
Proportional control,
Differential gap,
Transmitter
Housing (standard)
NEMA 1, 2, 3, and 3R
Limit switch ratings
Max. voltage: 120 VAC/VDC
Max. resistive load: 10 VAC/VDC
Max. current: 1⁄4" amp switching
1 amp holding
9
2.2
Mounting
Before assembling control to vessel, check with spirit level
to ensure that the mounting flange is horizontal. Proper
operation of the control depends on the Modulevel controller being within 3° of vertical in all directions. The
head assembly with sensing components is installed first,
then the controller is placed carefully over the enclosing
tube, rotated to desired position, and then locked in place
by securely tightening the locking screw. Check to be certain the controller magnet can move smoothly throughout
its actuating stroke without binding against the enclosing
tube. If binding occurs, loosen the slot-head screw, reposition magnet and tighten screw.
Caution: The spring and stem assembly that protrudes below
the mounting flange on a top mounted Modulevel is very
fragile. DO NOT handle this assembly or place control so
that any amount of force is exerted on the spring and stem
assembly. Proper operation of the control requires that
this assembly is not damaged or bent.
Caution: Displacer spring and stem are fragile. Do not drop displacers into tank. Hand feed cable into position to avoid bending stem.
Caution: All Modulevel units are shipped from the factory with the
enclosing tube tightened and the controller head set
screw locked to the enclosing tube (see figure 2, page 7).
Failure to loosen the set screw prior to repositioning the
supply and output connections may cause the enclosing
tube to loosen, resulting in the possible leakage of the
process liquid or vapor.
NOTE: Since controller is rotatable through 360°, it is important to
make certain controller locking screw is tight before installing
air or gas connections.
The supply and output air or gas connections provided on
the Modulevel are 1⁄4" NPT. These connections are clearly
indicated on the side of the controller. The filter-regulator
(if furnished) is to be set to deliver a 20 psig supply
pressure to a 3–15 psig output controller or a 35 psig supply pressure to a 6–30 psig output controller. The main
supply pressure to the regulator should be between 25 and
250 psig (or 40 and 250 psig) and connected to the inlet
side of the regulator. In order to protect the instrument
from contaminants, clean, dry air or gas must be used as
a supply medium.
Caution: Do not overtighten fittings in supply and output connections. Overtightening may crack the housing outlets.
10
48-620 Modulevel Pneumatic Liquid Level Control
Caution: Operation of all buoyancy type level devices should be
done in such a way as to minimize the action of dynamic
forces on the float or displacer sensing element. Good
practice for reducing the likelihood of damage to the control is to equalize pressure across the device very slowly.
Filter Regulator
Controller
Supply
Pressure
Output
Pressure
Control
Valve
Liquid
Level
Displacer
2.2.1 Top Mounted Models – APM-131, P51,
P61, and P62
Check to be certain there are no tubes, or other
obstacles in the vessel to interfere with the
operation of the displacer. Stillwells are recommended where a continuous agitation or
motion is prevalent.
NOTE: Stillwell installation should be checked to be certain tube (or pipe) is plumb. An out-of-plumb still
well may restrict displacer movement. Also,
ensure that the stillwell is vented at the top to
allow the liquid to rise in the tube with level
movement.
Figure 6 shows a typical piping installation for
a top mounted unit to a tank or vessel.
Figure 6
Top Mounted Units
2.2.2 External Cage Models – APM-W251, APMW254, APM-W291, P53, P55, P63, P64,
P65, P66, P71 and P72
Filter Regulator
Controller
Supply
Pressure
Output
Pressure
Liquid
Level
Control
Valve
Figure 7
External Cage Units
48-620 Modulevel Pneumatic Liquid Level Control
The external cage type Modulevel should be
mounted on the side of the tank or vessel with
either side/side connections or side/bottom
connections, as shown in Figure 7. Mid-range
mark on control cage should be aligned to
correspond with desired control level in tank
or vessel.
NOTE: It is essential that the external cage assembly be
mounted plumb to ensure frictionless operation
of its internal displacer.
It is recommended that isolation valves be
installed in each equalizing line to the cage as
well as a drain valve at the bottom of the
chamber (refer to Figure 7). Equalizing lines
should be sized at least as large as connections
provided on the cage.
11
2.2.3 Side Mount Models – P68
Side mount controls mount horizontally to any
tank or vessel through a flanged or threaded pipe
connection. Refer to the illustrations on page 31 for
threaded nozzle and flanged mounting dimensions. It is
essential that the control be mounted horizontal.
NOTE: To allow the 3" float to pass through the nozzle, the nozzle
bore diameter must not be less than 3.00" schedule
40 pipe size.
2.2.4 Transmitter – Receiver Models
Check installation considerations described for either top
mount or cage type mounting units and apply those
appropriate for joint installations with receiver controllers.
Figure 8 shows a typical piping installation of a receiver
controller to a top mounted transmitter type Modulevel
control. A chamber type Modulevel installation would be
the same, with obvious physical differences on a side of
tank installation. Piping for a separate receiver controller
would be done in a similar manner except unit would be
remotely wall or panel mounted in a control house or
installed at or near the control valve.
NOTE: Refer to page 49 for detailed assembly of receiver controller to
a transmitter type Modulevel controller.
Check alignment of mounting bracket for receiver controller to be certain top surface of collar is flush with top
head assembly so that tops of both controller heads are in
the same plane.
Filter Regulator
Receiver Controller
Transmitter
Displacer
Liquid
Level
Supply Pressure
Output
Pressure
Remote Mounted
Receiver Recorder
(or Indicator)
Control Valve
NOTE: Alignment of controllers is required only to
suit factory furnished piping and fittings
between controllers. If mounting is to be
accomplished using any other method,
including remote installations, all piping
must be provided by customer.
All pneumatic (piping) connections should
have threaded joints, sealed with Teflon thread
tape or pipe compound suitable for use on
pneumatic lines; 1⁄4" pipe size or
5⁄16" O.D. tubing is recommended.
Figure 8
Transmitter – Receiver Controller Units
12
48-620 Modulevel Pneumatic Liquid Level Control
2.3
Calibration
2.3.1 Proportional Controllers
Each Modulevel control is calibrated at the factory
before shipment. Specified actions have been preset
and all scales have been calibrated. However, upon
receipt of the instrument the following calibration
and adjustment procedure is recommended for all
controllers:
1
2
3
13
12
4
11
10
5
6
9
8
7
14
Figure 9
Proportional Controller with Reset
1
2
3
4
5
6
7
Proportional band adjustment knob
Zero adjustment screw
Supply pressure gauge
Level adjustment knob
Magnet carriage
Level indicator
Output pressure gauge
Proportional Control
8
9
10
11
12
13
14
Output connection
Supply connection
Action cam
Relay
Orifice cleanout plunger
Flapper nozzle assembly
Reset adjustment knob
Differential Gap Control
Actio
Rev
er
s
Dire
ct
e
Figure 10
Pilot Nozzle Assembly
48-620 Modulevel Pneumatic Liquid Level Control
n
n
Actio
1. Check supply pressure:
After appropriate piping has been made to the
filter regulator and output connections, and
checked for leaks, the supply gauge, shown in
Figure 9, should indicate 20 psig (35 psig for
6–30 psig controllers).
2. Check control action:
To check controller action, manually rotate the
magnet carriage to simulate an increase in level.
Note the direction of the output pressure
change. (Rising level will increase the output
pressure on direct acting controllers.
Conversely, rising level will decrease the output
pressure on the reverse acting controllers.) The
action cam and level adjustment knob must
both indicate the same action
Should it be required to change the controller
action, the action cam can be manually rotated
180° to the desired action. Make certain that
the notch in the cam is set into the tab of the
pilot nozzle assembly. Cam actions are clearly
marked on the cam face as indicated in Figure
10. A zero adjustment will normally be required
upon change.
NOTE: It is also important that the level adjustment knob
scale action be compatible with the cam action. The
level adjustment knob scale is printed DIRECT
ACTION on one side and REVERSE ACTION on the
other. To change scales, remove level adjustment
knob and turn over level scale. Replace knob with
same orientation on shaft as before removal.
3. Check level indicator zero setting.
A level indicator is furnished with each
Modulevel pneumatic controller and is conveniently located inside the instrument case. The
level indicator, shown in Figure 11, indicates
the level as a percentage of the displacer length.
13
Calibration Scale
Adjustment Screw
100°F
400
700
T
E
M
P
Magnet
Carriage
Slide Bar
0
NOTE: Consult factory for procedure to calibrate level indicator if precise
reading is required.
LEVEL
% DISPLACER
LENGTH
40
60
100
.90
1.0
1.1
S
.80
P.
.70
G
.60
R.
With the system at operating temperature, adjust level of
process liquid in the tank (or vessel) to allow the displacer to
"hang-free" above the liquid. The pointer on the level indicator should read zero percent on the indicator scale. Refer
to Figure 11. To adjust, loosen calibration adjustment screw
at the top of the indicator scale and move scale until the
pointer is aligned to zero. Retighten adjustment screw.
Pointer
20
80
Figure 11 shows a liquid specific gravity of .8 with a corresponding level reading of 45% and a process temperature of
approximately +250° F (+121° C). An adjustment is
provided on the level indicator to calibrate the pointer and
indicator scale when control is at operating temperature.
.50
4. Adjust the proportional band and the level:
(The proportional band is the span setting.) The
proportional band adjustment knob, located adjacent to
the pilot nozzle assembly, sizes the proportional band as a
percentage of the displacer length. When the proportional
band is set at 5, the output range will correspond to 50%
of the total displacer length. For example; on a control
with a 14" displacer, a proportional setting of 5 will
result in full output range over a 7" level change.
Figure 11
Level Indicator
(The level adjustment is the control set point.) The
level adjustment knob, located just below the supply
pressure gauge, positions the midpoint of the proportional band on the displacer. For example; on a control
with a 14" displacer, a level setting of 5 will locate the
midpoint of the proportional band 7" from the bottom
of the displacer.
Inches (mm)
The proper method for calibrating a proportional controller
follows:
9.10
(231)
PB = 4.2
(107)
0.7
(18)
Level = 2.8
(72)
PB = 3
Level = 2
Level = 7.0
(178)
PB = 5
Level = 5
Figure 12
Proportional Band & Level
3.50
(89)
Calibration example: 1.00 specific gravity liquid, 50%
proportional band desired, 50% level adjustment desired,
3–15 psig output, direct action.
PB = 7.0
(178)
4.1 Set the pointer on magnet carriage slide bar to 1.00
specific gravity.
3.50
(89)
4.2 Set both the level and proportional band knobs to
5 (or 50%) on each scale.
4.3 Move the magnet carriage by hand until the pointer reads
50% of displacer length, hold accurately at this position.
4.4 Adjust the zero screw until the output pressure gauge reads
9 psig.
4.5 Move the magnet carriage pointer to 75% displacer length.
Output pressure should read 15 psig.
NOTE: If required, small readjustments can be made at the level and
proportional band knobs.
14
48-620 Modulevel Pneumatic Liquid Level Control
.1
.2
.3
.4
.5
5.
.6
150
.7
.8
120
110
.9
1.0
100
90
1.2
80
70
1.4
60
1.6
1.8
50
40
SPECIFIC GRAVITY
% DISPLACER LENGTH
140
130
30
20
10
0
1
2
3
4
5
6
7
8
9
10
DIAL SETTING FOR LEVEL & PROPORTIONAL BAND
5.1 Set the magnet carriage slide bar to the correct liquid
specific gravity for your application.
5.2 To check the zero adjustment, bring the liquid level
up until the level indicator reads the desired level set
point. Set the zero adjustment screw until output
pressure gauge reads 9 psig.
6.
Figure 13
Dual Setting for Level & Proportional Band
Set the level and proportional band for your application. Use calibration chart and instructions given in
Figure 13 to select the level and proportional band
dial settings based on the specific gravity of liquid to
be measured.
To check the level and 3–15 settings:
Adjust the liquid level until the level indicator reads
the low value of the desired span range in terms of %
of displacer length. The output pressure should read
3 psig. Adjust the liquid level to the maximum value
of the desired span range in terms of % of
displacer length. The output pressure should read
15 psig.
2.3.1.1 Calibration Chart instructions
To set level:
1. Determine the desired level set point in terms of %
of displacer length.
2. Trace desired level from left to right to the specific
gravity line for the product.
3. Trace down from where the two lines intersect to the
appropriate dial setting.
4. Adjust the level setting on the controller to this value.
To set proportional band:
1. Determine the desired proportional band in terms of
% of displacer length.
2. Trace from left to right to the specific gravity line for
the product.
3. Trace down from where the two lines intersect to the
appropriate dial setting.
4. Adjust the proportional band setting on the controller to this value.
NOTE: If required, small readjustments can be made at the level and
proportional band knobs. To increase proportional band, the
band knob is turned to a higher number. For best control, it is
normally desirable to set the proportional band at the narrowest
setting which will not produce cycling. To raise the level, the
level adjustment knob is rotated in the desired direction indicated on the dial face.
48-620 Modulevel Pneumatic Liquid Level Control
15
2.3.2 Reset Controllers
Each Modulevel control is factory calibrated before shipment for 30% span and minimum reset. The following
calibration and adjustment procedures are recommended
for all reset controllers:
1. Check to make sure the reset knob is fully counterclockwise.
NOTE: This effectively reduces the reset time to a minimum, but does
not completely eliminate reset.
2. Follow the calibration steps 1 through 4 for proportional controllers beginning on page 13.
3. Use the calibration chart, Figure 13, to select the level
and proportional band initial settings, based on the
specific gravity of the liquid to be measured.
4. Adjust the reset clockwise until stable control is
maintained.
5. Set the magnet carriage slide bar to the correct liquid
specific gravity for your application.
The following adjustment procedure can be used to calibrate the reset controller to your specific application by
adjusting the liquid levels:
Alternate method to calibrate reset
1. Set the proportional band index to 10. (This setting is
comparable to 100% for S.G. equal to 1.0.)
2. Turn the reset dial fully counterclockwise.
3. Slowly open downstream and upstream manual control
valves and close by-pass valve.
4. Adjust control point to desired level by means of level
adjustment knob.
5. Narrow the proportional band until a cyclic control
condition occurs. Then, widen the proportional band
by approximately 20% to give stable control.
6. Decrease the reset time until a cyclic condition again
occurs. Then, increase the reset time until stable control is maintained.
7. Normally the narrowest proportional band and fastest
reset timing required to obtain stability will produce
the optimum control. It is recommended that a
momentary load upset is then produced to further
check system stability and response. (Load can be
imposed by moving magnet carriage manually.)
NOTE: Allow system enough time to stabilize after each adjustment.
16
48-620 Modulevel Pneumatic Liquid Level Control
2.3.3 Transmitters
For Modulevel transmitters, the output signal is directly
proportional to the level on the displacer. To calibrate a
Modulevel transmitter:
1. Follow steps 1 through 3 for Proportional Controllers
(page 13).
2. Set the zero adjustment knob to a vertical position
(arrow straight up at 12 o’clock).
NOTE: Don't confuse the zero adjustment knob with the zero screw
located on top of the pilot nozzle assembly.
3. Set the pointer on the magnet carriage slide bar to the
process specific gravity.
4. Set the specific gravity knob to the process specific
gravity.
NOTE: The specific gravity adjustment sets the span for the unit.
5. Rotate the magnet carriage on the visual level indicator by hand, until the pointer reads 50% of displacer
length.
6. While holding the magnet carriage at 50%, adjust the
zero screw to obtain 9 psig output pressure for 3–15
psig units (or 18 psig output for 6–30 units).
7. Rotate the magnet carriage by hand to 0% displacer
length. The output should be 3 psig. If it is not,
slightly adjust the specific gravity knob to obtain
3 psig output pressure.
8. Rotate the magnet marriage by hand to 100%
displacer length. The output pressure should be
15 psig. If it is not, slightly adjust the specific gravity
knob to obtain 15 psig output pressure.
9. Recheck the midpoint (50% displacer). Adjust the
zero screw to obtain 9 psig output pressure if it
has changed.
10. Recheck the zero output and full scale output.
The Modulevel transmitter has now been calibrated
using the level indicator to simulate process level. If a
more precise calibration to the actual process conditions
is required, the above procedure can be performed
using actual process level on the displacer to set the
calibration points.
48-620 Modulevel Pneumatic Liquid Level Control
17
2.3.4 Receiver Controllers
1. Connect the output from the transmitter to the receiver
controller input at the rear of the receiver controller
housing.
2. Connect a separate supply and output at the right side
of the receiver controller housing.
3. Set the proportional band knob at 100 (100%).
4. Set the direct acting knob at 5 (50%). The output
gauge should read the same as the transmitter output.
If it does not, adjust the zero knob on the receiver
controller until both readings are the same.
To increase or decrease span distance, turn the proportional band knob to the setting desired, for example,
50 = 50% of span. To move the span mid-point, turn
the direct action knob to the setting desired.
For a reverse acting output, from a direct acting
transmitter output, invert the spring/bellows assembly
so that the bellows are on top. Recalibrate as described
above.
Remove the direct acting indicator plate, and turn it to
reverse acting. Recalibrate as described above.
If reset is included with the receiver controller, turn the
reset knob fully counterclockwise and calibrate as
described above.
Adjust reset clockwise until stable control is maintained.
2.3.5 Differential Gap
1. Follow steps 1 through 4 of Proportional Controller
Calibration section. Refer to pages 13 through 17,
except the output is 0–20 psig or 0–35 psig with
no mid-range adjustment.
NOTE: When checking the control action for a direct action differential gap unit, set the cam to reverse action; for a reverse action
differential gap unit, set cam to direct action.
2. Check that the pilot nozzle assembly is set up for differential gap operation. Figure 10 on page 13 illustrates
the pilot nozzle flapper configurations used for the two
control modes, proportional and differential gap. If
your unit is already set up for differential gap mode,
proceed to step 3.
18
48-620 Modulevel Pneumatic Liquid Level Control
To change the control mode:
a. Loosen the tube clamp screw.
b. Remove the zero screw from the pilot nozzle assembly.
c. Remove both screws and top plate from the pilot
nozzle assembly.
d. Flip the pilot nozzle assembly 180° and install
screws with top plate in position.
e. Install the zero screw in the pilot nozzle assembly.
f. Rotate the tube clamp to horizontal and tighten the
tube clamp screw. The cam follower should now rest
on the action cam. If it does not, readjust bracket
without crimping the tube.
NOTE: Make sure the tube is not kinked and does not interfere with
the carriage and the nozzle lever.
g. Change the controller action. For direct action, set
the cam to reverse acting; for reverse action, set the
cam to direct acting.
3. Check zero output. Set level adjustment knob to 5 or
vertical position. Set proportional band knob to 3.
Place level indicator at 35% position (65% position for
reverse action units). Adjust zero screw to get supply
pressure value output; then, slowly readjust the zero
screw until output suddenly decreases to zero.
4. Check 20 psig or 35 psig output. Slowly move the
attraction sleeve to 65% (35% for reverse action units),
at which point the output should suddenly rise to
supply pressure. If not, adjust the proportional band
knob until it does.
5. Set the level and proportional band for your application.
2.3.6 Interface Models
For an interface application, the Modulevel has been
factory precalibrated to operate in liquids with specific
gravities supplied by the customer. The displacer is
weighted to obtain a zero (3 psig or 6 psig signal) with
the displacer fully submerged in the lighter liquid only
[15 psig or 30 psig with displacer covered with the heavier
fluid]. The indicator arrow should be set to the difference
between the two specific gravities of the liquids.
Follow the procedures given for installation and calibration of proportional controllers. Refer to pages 13 through
17. Keep in mind that the "hang–free" or zero setting
is obtained with the displacer fully submerged in the
lighter liquid, and completely uncovered by the interface
(heavier liquid).
48-620 Modulevel Pneumatic Liquid Level Control
19
As is indicated in the Calibration section for proportional
controllers, the signal should be at 9 psig or 18 psig output with the interface level at the control set point
(level knob setting) on the displacer. Because of the reduced
displacer motion for interface applications, the proportional
band should be set as wide as possible, with a minimum
of 50%.
2.3.7 Electric High/Low Limit Switches
The Pneumatic Modulevel is available with optional builtin, adjustable electric high/low level limit switching. This
economical, optional feature is well-suited to numerous
applications where a combination pneumatic control and
electric switch actuation is desired.
The Pneumatic Modulevel is used to pneumatically position a diaphragm-type feedwater control valve in response
to water level changes in the steam drum. The convenient
addition of electric limit switching provides economical
high and low level alarm indication. These switches are
not intended for primary control purposes.
NOTE: Not suitable for Class I, Div. 1 applications.
2.3.7.1 Electrical Ratings
Figure 14
Each reed switch carries the following electrical
ratings:
Maximum voltage............................120 VAC or 120 VDC
Maximum resistive load ...........................10 VAC or VDC
Maximum current ...........................1⁄4 ampere switching,
1 ampere holding
NOTE: For lamp or capacitive applications, the reed switches are
rated six (6) watts maximum.
2.3.7.2 Wiring Information
Each reed switch assembly is wired at the factory and
furnished with number-coded, 24.00 inch long silicone rubber insulated copper lead wires. Each reed
switch is SPDT in operation. Standard wiring follows:
High level reed switch
No. 5 lead is common
No. 6 lead energizes at high level
No. 4 lead de-energizes at high level
Low level reed switch
No. 2 lead is common
No. 3 lead energizes at low level
No. 1 lead de-energizes at low level
20
48-620 Modulevel Pneumatic Liquid Level Control
NOTE: Use extreme care in handling the reed switches during wiring
and adjustment procedures.
Reed Switch
2.3.7.3 Adjustment Procedure
Adjuster
Screw
Prior to adjusting the reed switches, the Pneumatic
Modulevel should be calibrated to obtain the desired
pneumatic proportional band and level position
adjustment.
Magnet
Attractor
Pivoted
Magnet
After wiring the reed switches to the device to be
operated, they may be adjusted manually to actuate at
the desired high and low liquid level positions. Move
the liquid indicator by hand to the desired low level
actuating point on the indicator scale.
Liquid Level
Indicator Scale
NOTE: Scale readings are expressed in percent of displacer length.
Non-Magnetic
Enclosing Tube
Hold the indicator at the desired low level actuating
point. Turn the left hand adjuster screw until the reed
switch actuates.
Level Sensing
Displacer
The high level reed switch is adjusted in the same
manner by moving the level indicator to the desired
high level actuating point, and by turing the right
hand adjuster screw until the high level reed switch
actuates.
Figure 15
2.4
Field Modifications and Adjustments
2.4.1 Changing Controller Action
The controller can be changed from direct acting to
reverse acting or vice versa. Should it be required to
change the controller action, refer to step 2 in the
Proportional Controllers section of Calibration.
Refer to page 13.
2.4.2 Proportional Band Models to Differential Gap
A proportional band controller can be changed to operate
in the differential gap mode. For the appropriate procedures, see the Differential Gap section on page 18.
2.4.3 Pneumatic-to-Current (P/I) Converter
Modulevel units are available with a P/I transducer to
provide an electronic output signal proportional to liquid
level change. Refer to the manufacturer's instructions
supplied with the transducer.
48-620 Modulevel Pneumatic Liquid Level Control
21
2.4.4 Reset Installation
Reset
Bellows
Spring
Reset, when added to a proportional controller, acts to
maintain the controlled liquid level at the desired control
point while eliminating any sustained offset from this
point.
The reset adjustment is accomplished by manually adjusting a precision needle valve. The reset dial is calibrated
from .03 to 1.0 minutes per repeat, with short intervals at
the low end of the scale to give precise settings. The reset
timing refers to the time in minutes required for the reset
to produce an additional output pressure change equal to
the previous change caused by proportional action.
Feedback
Assembly
Reset
Valve
The reset module assembly may be added to any
Modulevel Proportional Controller in the field.
The following procedure is recommended for adding reset
to a proportional controller in the field.
Cut Here
1. The knob on the reset assembly should point to the
12 o'clock position. Tear foam rubber from between
the two plates on the reset assembly. Make sure knob
remains at the 12 o'clock position.
Existing Tube
Figure 16
Reset Assembly
NOTE: Do not move the front plate or knob on the reset valve or the
reset assembly will not work.
2. Remove both screws from the reset valve assembly.
3. Drop the reset valve into position on the frame.
4. Install and tighten the two screws.
5. Add one clamp to each end of both tubes.
6. Slide the long piece of tube onto the barb at rear of
reset valve. Slide the clamp into position.
7. Slide the middle prong of the barbed tee onto short
piece of tube. Slide the clamp into position.
8. Slide the short piece of tube opposite the barbed tee
onto the vertical barb on bottom of reset valve. Slide
the clamp into position.
9. Cut the tube adjacent to the barbed tee below the
reset valve assembly. Refer to Figure 16.
10. Slide the clamps over the cut ends of the tube.
11. Slide the cut tubes onto the barbed tee.
12. Insert the reset bellows in the feedback assembly so
that the bellows end bushings are piloted in the
bracket locating holes.
13. Rotate the reset nipple to the 2 o’clock position as
you look down at the reset bellows.
22
48-620 Modulevel Pneumatic Liquid Level Control
14. Route the long piece of tube from the reset valve,
under the relay assembly, behind the enclosing tube
and to the reset bellows.
15. Slide the long piece of tube onto the reset bellows.
Slide the clamp into position.
16. Add the washer and screw through the lever assembly
and into the reset bellows. Tighten the screw.
17. Add the reset bias spring to the tail end of the lever
assembly.
18. Refer to the reset calibration procedure on page 16.
2.4.5 Reset Cleaning
Should it be required to clean the reset orifice, refer to the
reset replacement parts drawing on page 46 and proceed
as follows:
1. Disconnect the reset line adaptor fitting from the valve
body and remove the reset valve mounting screws.
2. Remove the reset valve and disassemble bushing along
with all related parts.
NOTE: Shaft and bracket assembly must not be disassembled.
3. Clean orifice and plunger set by dipping in carbon
tetrachloride or any suitable solvent being careful not to
mar any finished surfaces.
2.4.6 Disabling Reset
In the case that the proportional controller is supplied
with reset that is no longer required, the reset can be disabled to modify the controller head to proportional only.
To disable this action:
1. Turn the reset knob fully counter-clockwise
2. Disconnect hose (attached to rear of reset assembly) by
removing the compression fitting and pulling the hose
from the nozzle.
3. Trace the hose to the bellows assembly and remove the
bias spring completely from this assembly. Leave this
end of the hose attached to the bellows nozzle.
Unit will now be configured as a direct acting proportional
and is ready for calibration.
48-620 Modulevel Pneumatic Liquid Level Control
23
3.0
Reference Information
3.1
Troubleshooting
3.1.1 Installation
The magnet carriage assembly binds at either the
magnet or the indicator scale.
1. The magnet binds on the enclosing tube. Loosen the
retaining screw on magnet bracket and adjust the
magnet alignment.
2. The carriage binds on the indicator scale. Check for
damaged, bent, or loose parts.
3. Check for proper mounting of the controller head.
3.1.2 Calibration
Signal pressure does not change with simulated level
change or unit won't calibrate properly.
1. Make certain the output gauge is operational.
2. Make certain the supply gauge reads 20 psig for
3–15 models or 35 psig for 6–30 models.
3. Check for proper calibration settings, refer to appropriate calibration instructions on pages 13 through 18.
4. Check the proportional band and level settings for
proper process specific gravity. Refer to the calibration
chart, Figure 13 on page 15, in the Calibration section,
for settings corresponding to process specific gravities
other than 1.0.
5. The level indicator should be set for the proper process
temperature.
Cannot obtain proper midspan output (9 psig for
3–15 models or 18 psig for 6–30 models).
1. Adjust the zero adjustment screw.
2. Check if reset is included, the output signal will not
be steady.
Constant high output (pressure does not drop after
manually moving the carriage so that the flapper drops
away from the nozzle).
1. Clogged exhaust nozzle from contamination or poor
quality air supply. Clean nozzle by removing the small
screw on the top of the nozzle and blow out any foreign material, or run fine monofilament type line
through the opening.
24
48-620 Modulevel Pneumatic Liquid Level Control
Nozzle
1/16"
2. Damaged or bent flapper spring. The flapper should
stroke approximately 1⁄16" away from the nozzle in the
free hanging position. If it does not, carefully bend the
spring down with a screwdriver forcing the flapper
away from the nozzle. Refer to Figure 17.
3. Obstructed output. Check connection at signal output.
Constant low output, cannot obtain full scale signal.
Flapper spring
Differential gap units adjustment screw
is inverted as shown by dotted line
Figure 17
Reset Assembly
Flapper
1. Check for a clogged relay/wiper by depressing the
orifice clean out plunger. If this does not solve the
problem, the relay may be internally damaged.
Consult the factory.
2. Check for proper supply pressure, described above.
3. Check for leaks at all field connections and tubing.
4. Check calibration settings.
3.1.3 Operation
Control valve continually oscillates or hunts.
1. Proportional band setting is too narrow. To ensure that
the optimum proportional band setting has been made,
create a momentary load upset by manually moving the
magnet carriage and allowing the controller to again
come into balance. If a cyclic condition recurs, widen
the band slightly and repeat the above procedure until
stability is maintained.
2. Distance between the control valve and Modulevel controller is too great (time lag). Install volume booster in
the signal line.
3. If reset is included:
The reset response setting may be too fast. Increase the
reset time until stable control is maintained
Excessive offset. Check the reset line for leaks; these
connections must be airtight.
No output change as level changes.
1. Check that all gasketed joints on the relay are tight.
2. Check for leaks.
3. Depress relay/wiper plunger since the orifice may be
plugged.
4. Remove the enclosing tube and inspect it for internal
buildup.
5. Unbolt the head assembly and check for displacer
interference.
48-620 Modulevel Pneumatic Liquid Level Control
25
6. Remove parts from the head assembly and inspect
internal components.
7. Consult factory.
8. Check sizing and operation of control valve. An oversized valve or excessive friction are possibilities.
9. Check the output capacity. Controllers tend to be
unstable when dead-ended due to their high degree of
sensitivity. This condition is particularly aggravated
when coupled with 1 and 8 above.
26
48-620 Modulevel Pneumatic Liquid Level Control
3.2
Specifications
3.2.1 Standard Flanged Top and Flanged Cage Displacer Models P61, P62, P63, P64, P65 and P66
Dimensional Specifications
NOTE: Controller head may be rotated through 360°.
Inches (mm)
1/4"
1/4"
NPT x 2.00 (51)
Long min. nipple
required
7.68
(195)
3.84
(98)
NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
Optional nipple
mounted filter
regulator
(4) 1/4" NPT
(4) 1/4" NPT
6.50
(165)
1
13.71
(348)
6.50
(165)
1
1
18.71
(475)
1
9.77
(248)
14.25
(362)
5.00
(127)
2
5.00
(127)
ANSI standard
flange
Level
range
Level
range
1.00
(25)
C
Mid
Range
2.56
(65) Level
range
+ 2.00 (51)
A
Figure 18
P61 and P62 Series Top
Mounting
8.75
(222)
9.00 (229)
8.38
(213)
1/4"
1/4"
B
3.25
8.62 (82)
(219)
Optional 3/4" NPT gauge
glass tapping
(2) 11/2" or 2" NPT or
socket weld
(2) 11/2" or 2" ANSI
standard flange
Figure 19
P63 and P64 Series with Side/Bottom Connections
NPT output
7.68
(195)
Vent
5.94
(151)
1/4" NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
NPT supply
.63 (16)
3.84
(98)
2.00 (51)
Figure 20
Controller Head (side view)
(4) 1/4" NPT
6.50
(165)
1
Outlet Size
Dimension A
11⁄2" NPT or Socket Weld
2" NPT or Socket Weld
3.19 (81)
3.31 (84)
18.71
(475)
5.00
(127)
1
14.77
(375)
1.00
(25)
C
Outlet Size
11⁄2" Flanged
2" Flanged
Flange Size & Class
11⁄2" or 2", 150 lb.
11⁄2" or 2", 300 lb.
11⁄2" or 2", 600 lb.
Dimension B
6.25 (159)
6.25 (159)
Dimension C
7.50 (191)
8.25 (210)
8.25 (210)
Add 3.12 (79) for units with specific gravity and
temperature codes 4, 5 or 6.
Distance without stem extension is 5.00 (127) standard. Can be furnished to a minimum distance of
3.00 (76).
48-620 Modulevel Pneumatic Liquid Level Control
2.56
(65)
Level
range
Mid
Range
(2) 11/2" or 2"
ANSI standard
flange
3.00
(76)
(2) 11/2" or 2" NPT
or socket weld
A
B
Level
range
+ 2.00 (51)
(2) Optional 3/4" NPT
gauge glass tapping
1" NPT
Figure 21
P65 and P66 Series with Side/Side Connections
27
3.2.2 High Pressure Flanged Top and Flanged Cage Displacer Models P51, P53 and P55
Dimensional Specifications
NOTE: Controller head may be rotated through 360°.
Inches (mm)
1/4" NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
1/4" NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
(4) 1/4" NPT
(4) 1/4" NPT
6.50
(165)
E
B
A
6.50
(165)
K
D
F
C
ANSI standard
flange
Level
range
1.00
(25)
Level
range
Figure 22
L
P51 Series with Top Mounting
M
H
3.75
Max. Level
(95) range
+ 2.00 (51)
Mid
Range
G
(2) Optional 3/4" NPT
gauge glass tapping
(2) 11/2" or 2" NPT or
socket weld
(2) 11/2" or 2" ANSI standard flange
(See chart for size and class)
1/4"
NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
Figure 23
P53 Series with Upper Side/Bottom Connections
(4) 1/4" NPT
6.50
(165)
E
K
F
8.75
(222)
9.00 (229)
8.38
(213)
D
1.00
(25)
1/4"
Level
range
(2) 11/2" or 2"
ANSI standard
flange (see chart
for size and
class)
Mid
Range
J
(2) 11/2" or 2" NPT
or socket weld
L
3.75
Max.
(95)
1/4"
Level
range
+ 2.00 (51)
(2) Optional 3/4"
NPT gauge
glass tapping
Figure 24
P55 Series with Side/Side Connections
NPT output
NPT supply
Vent
.63 (16)
5.94
(151)
Flange Size
& Class
2.00 (51)
Dimensions
A
B
C
D
E
F
G
7.25
8.48 12.41 9.31 17.96 21.89 9.31 (184)
(215) (315) (236) (456) (556) (236) 8.18
2"–900 lb.
(208)
11⁄2" –900 lb.
G
Figure 20
Controller Head
(side view)
H
J
K
8.43
(214) 3.44 11.50
9.38 (87) (292)
(238)
7.93 9.13
8.86 12.79 9.31 18.34 22.27 9.31 (201) (232) 3.44 12.25
(225) (325) (236) (466) (566) (236) 8.87 10.13 (87) (311)
2"–1500 lb.
(225) (257)
11⁄2" –1500 lb.
Outlet Size
11⁄2" NPT or Socket Weld
2" NPT or Socket Weld
28
Dimensions
L
M
4.00
(102)
4.38
(111)
3.44
(87)
3.50
(89)
9.06 10.25
9.73 13.66 9.31 19.21 23.14 9.31 (230) (267) 3.44 14.00
(247) (347) (236) (488) (588) (236) 9.87 11.13 (87) (356)
2"–2500 lb.
(251) (283)
11⁄2" – 2500 lb.
48-620 Modulevel Pneumatic Liquid Level Control
3.2.3 Standard Sealed Cage Displacer Models P71 and P72
Dimensional Specifications
NOTE: Controller head may be rotated through 360°.
Inches (mm)
1/4"
1/4"
NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
(4)
1/4"
7.68
(195)
3.84
(98)
(4) 1/4" NPT
NPT
6.50
(165)
6.50
(165)
1
20.69
(525)
1
20.69
(525)
NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
1
1
16.75
(425)
16.75
(425)
1.00
(25)
1.00
(25)
2.56
(65) Level
range
+ 2.00 (51)
Mid
Range
Level
range
(2) 11/2" or 2"
ANSI standard
flange
Level
range
Mid
Range
2.56
(65) Level
range
+ 2.00 (51)
A
B
3.00
(76)
3.25
8.62 (82)
(219)
(2) Optional 3/4" NPT gauge
glass tapping
(2) 11/2" or 2" NPT or
socket weld
(2) 11/2" or 2" ANSI
standard flange
(2) Optional 3/4" NPT
gauge glass tapping
1" NPT
A
(2) 11/2" or 2" NPT
or socket weld
B
Figure 26
P72 Series with Side/Side Connections
150, 300, 600 lb. Class
Figure 25
P71 Series with Upper Side/Bottom
Connections 150, 300, 600 lb. Class
Outlet Size
11⁄2" NPT or Socket Weld
2" NPT or Socket Weld
Outlet Size
Dimension B
6.25
(159)
6.25
(159)
1
1 ⁄2" Flange
2" Flange
8.75
(222)
9.00 (229)
8.38
(213)
1/4"
1/4"
NPT output
Add 3.12 (79) for units with Specific Gravity
Codes 4, 5 or 6.
600 lb. Pressure/temperature ratings
NPT supply
Temperature
Vent
5.94
(151)
Dimension A
3.19
(81)
3.31
(81)
Pressure
.63 (16)
°F
°C
psig
Bar
2.00 (51)
100
37.7
1440
99
200
93
1240
85
300
149
1120
77
400
204
1020
70
500
260
940
65
600
315
900
62
700
371
860
59
Figure 20
Controller Head (side view)
48-620 Modulevel Pneumatic Liquid Level Control
29
3.2.4 Models APM-131, APM-W251, APM-W254 and APM-W291 Dimensional Specifications
inches (mm)
7.69
(195)
3.85
(98)
11.25
(285)
21/2" NPT
Adjustable
6.00 (152) to
120.00 (3048)
Span
adjustable
2.80 (71)
to
14.00 (355)
14.75
(374)
2.00
(50)
Figure 28
Figure 27
APM-W251, APM-W254, and APM-W291
APM-131
Catalog
Number
A
APM-W251
25.62
APM-W254
29.50
APM-W291
30.50
B
C
D
Gauge
Drum
Mid
glass
connector
range
centers
centers
of
and
and
throttling
pipe size pipe size
band
13.50
NPT
15.00
3⁄4" NPT
15.00
3⁄4" NPT
1⁄2"
13.50
1" NPT
16.00
11⁄4" NPT
15.00
11⁄4" NPT
6.00
8.00
7.50
E
Try-Cock
tappings
and
pipe
size
Three
NPT
Six
3⁄4" NPT
Three
3⁄4" NPT
1⁄2"
Dimensions are in inches and subject to change without notice. Certified
and detailed submittal drawings are available from the factory.
Figure 29
Controller Head (side view)
30
48-620 Modulevel Pneumatic Liquid Level Control
3.2.5 Standard Side Mount Float Models P68 Dimensional Specifications
NOTE: Controller head may be rotated through 360°.
Inches (mm)
1/4" NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
1/4"
NPT
Supply
Maximum length to
inside of tank
2.38
(60)
(4) 1/4" NPT
6.50
(165)
10.00
(254)
6.12
(155)
Vent
38°
19°
1/4"
NPT
output
3.50 (89)
Diameter
Maximum
8.50 level
(216) change
3" NPT
.63 (16)
2.00 (51)
5.93
(150)
3.00" (76)
Diameter float
10.25
(260)
Figure 30
P68 Series with Threaded Side Mounting
1/4" NPT x 2.00 (51)
Long min. nipple
required
Optional nipple
mounted filter
regulator
7.68
(195)
3.84
(98)
1/4"
NPT
Supply
(4) 1/4" NPT
6.50
(165)
6.50
(165)
10.00
(254)
Maximum length to
inside of tank
Vent
7.38 Maximum
(187) level
change
20°
10°
1/4"
NPT
output
.63 (16)
3.00" (76)
Diameter float
2.00
(51)
A
B
Figure 31
P68 Series with Flanged Side Mounting
8.75
(222)
9.00 (229)
8.38
(213)
1/4"
1/4"
NPT output
Figure 20
Controller Head
(side view)
Flange Size
and Class
4", 150 lb.
NPT supply
4", 300 lb.
Vent
5.94
(151)
.63 (16)
2.00 (51)
48-620 Modulevel Pneumatic Liquid Level Control
4", 600 lb.
Dim.
A
Dim.
B
5.38
(137)
5.38
(137)
5.88
(149)
20.12
(511)
20.12
(511)
19.62
(498)
No. of Dia. of
Bolt
Bolt
Holes Holes
8
8
8
.75
(19)
.88
(22)
1.00
(25)
31
3.3
Replacement Parts
1
2
3
1
2
3
18
18
9
17
17
4
5
9
12
13
15
12 13
15
6
4
5
6
11
11
8
7
16
10
14
16
10
14
7
8
Figure 32
Figure 33
Typical Side Mounted Threaded Assembly
Typical Side Mounted Flanged Assembly
3.3.1 Model P68 Threaded and Flanged Parts Identification
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Description
Attraction sleeve
Hex nut #8-32
Stem
Stem retaining bracket
Screw #6-32
Bracket
Cotter pin
Washer
Pivot pin
Fulcrum
Lock washer
Hex nut #1/4-20
Stem
Hex nut #10-32
Float
Body
E-tube gasket
Enclosing tube
IMPORTANT:
When ordering replacement parts, please specify:
32
A. Model and serial number of control.
B. Name and number of replacement part.
48-620 Modulevel Pneumatic Liquid Level Control
3.3.1.1 Model P68-2F2A Threaded 3" NPT (See Figure 32)
15
16
17
18
Sleeve and stem kit
(includes items 1 through 14)
Float
Body
E-tube gasket
Enclosing tube
089-5562-001
Z07-1102-005
Z33-6120-003
012-1204-001
Z32-6201-006
3.3.1.2 Models P68-2H3A, P68-2H4A and P68-2H5A 4" Flanged (See Figure 33)
Item
15
16
17
18
Flanged cage
Sleeve and stem kit
(includes items 1 through 14)
Float
Body
E-tube gasket
Enclosing tube
IMPORTANT:
When ordering replacement parts, please specify:
48-620 Modulevel Pneumatic Liquid Level Control
150#
300#
600#
Z33-6118-001
089-5562-002
Z07-1102-005
Z33-6118-002
012-1204-001
Z32-6201-006
Z33-6118-002
A. Model and serial number of control.
B. Name and number of replacement part.
33
3.3.2 Model Series P6x Parts Identification
1
15 CONTROLLER (Ref.)
2
7
8
3
9
8
Serial No.
Tag (Ref.)
7
5
6
4
16
10
9
1
10
2
11
3
12
14
13
14
Figure 34
Figure 35
Typical Top Mounting Head Assembly
(Series P6x Shown)
Typical Fabricated External Cage Assembly
(Series P6x Shown)
Items not furnished on Series P50.
Series P50 head flanges are ANSI standard.
34
48-620 Modulevel Pneumatic Liquid Level Control
3.3.2
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Series P61, P62, P63, P64, P65, P66, P71 and P72 Parts Identification (See Figures 34 & 35)
Description
Enclosing tube
Enclosing tube gasket
Mounting head kit
Head flange gasket
Studs
Hex nuts
Stem and spring kit
Adjusting sleeve
Jam nut
Cotter pins
Spacer tube
Stop ring
Stop
Displacer
Controller case only
Filter regulator
Gauge (not shown)
IMPORTANT:
When ordering replacement parts, please specify:
48-620 Modulevel Pneumatic Liquid Level Control
A. Model and serial number of control.
B. Name and number of replacement part.
35
3.3.2.1 Series P61, P62, P63, P64, P65, P66, P71 and P72 (See Figures 34 & 35)
Item
1
2
3
Matl.
Enclosing tube
C.S.
304
316
Enclosing tube gasket
Mounting head kits
150# flange 0.23 – 0.54 SG
0.55 – 1.09 and 1.10 – 2.20 SG
300# flange 0.23 – 0.54 SG
0.55 – 1.09 and 1.10 – 2.20 SG
600# flange 0.23 – 0.54 SG
0.55 – 1.09 and 1.10 – 2.20 SG
4
5
Head flange gasket
Studs
6
Hex nuts
7
Stem and spring kits 4th digits 1, 2 & 3
(+400° F/+204° C maximum)
7
Stem and spring kits 4th digits 4, 5 & 6
(+700° F/+371° C maximum)
8
Adjusting sleeve
9
Jam nut
10
Cotter pins
Lgth.
14
Displacer
14"
32"
48"
60"
72"
84"
96"
108"
120"
15
Controller case only
Receiver
16
Filter regulator
Gauge (not shown)
Adjustable Hanger
Adjustable stainless suspension cable for
flanged top mounting models
36
150#
012-1301-017
010-1701-004
(4 required)
010-2104-011
(8 required)
0.23 – 0.54 SG
089-5533-001
089-5533-002
Part Number
400° F Max.
700° F Max
Z32-6201-006
Z32-6201-002
Z32-6201-007
Z32-6201-008
Z32-6201-001
Z32-6201-003
012-1204-001
Carbon Steel
Stainless Steel
089-4217-001
089-4238-001
089-4218-001
089-4238-002
089-4219-001
089-4238-003
089-4220-001
089-4238-004
089-4221-001
089-4238-005
089-4222-001
089-4238-006
300#
600#
012-1301-018
012-1204-021
010-1701-007
010-1701-020
(8 required)
(8 required)
010-2104-012
010-2104-012
(16 required)
(16 required)
0.55 – 1.09 SG
1.10 – 2.20 SG
089-5532-001
089-5531-001
089-5532-002
004-5359-123
010-2107-004
010-5203-001 (2 required)
0.23 – 0.54 SG and 0.55 – 1.09SG
089-6125-001
089-6125-002
089-6125-003
089-6125-004
089-6125-005
089-6125-006
089-6125-007
089-6125-008
089-6125-009
Pneumatic 046-1505-001
046-1505-002
006-9501-002
006-9501-003
Lgth. (in)
Lgth. (m)
96
2.4
089-5531-002
1.10 – 2.20 SG
089-6126-001
089-6126-002
089-6126-003
089-6126-004
089-6126-005
089-6126-006
089-6126-007
089-6126-008
089-6126-009
032-3110-001
48-620 Modulevel Pneumatic Liquid Level Control
3.3.3 Series P51, P53 and P55 Parts Identification (See Figures 34 & 35)
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Description
Enclosing tube
Enclosing tube gasket
Head flange
Head flange gasket
Studs
Hex nuts
Stem and spring kit
Adjusting sleeve
Jam nut
Cotter pins
Displacer
Controller case only
Filter regulator
Gauge (not shown)
IMPORTANT:
When ordering replacement parts, please specify:
48-620 Modulevel Pneumatic Liquid Level Control
A. Model and serial number of control.
B. Name and number of replacement part.
37
3.3.3.1 Series P51, P53 and P55 (See Figures 34 & 35)
Item
1
2
Matl.
Enclosing tube C.S.
Enclosing tube gasket
3
4
5
Head flange
Head flange gasket
Studs
6
Hex nuts
7
8
9
10
12
Stem and spring kit 0.55 – 1.09 SG
Adjusting sleeve
Jam nut
Cotter pins
Lgth.
Displacer
14"
32"
48"
60"
Controller case only
13
14
Filter regulator
Gauge (not shown)
11
IMPORTANT:
When ordering replacement parts, please specify:
38
900# flange
Z04-8606-001
012-1204-009
010-1701-022
(4 required)
010-2104-016
(8 required)
Part Number
+700° F Max
Z32-6206-001
012-1204-001
1500# flange
2500# flange
Z04-8606-002
Z04-8606-003
012-1204-010
012-1204-011
010-1701-017
010-1701-023
(6 required)
(8 required)
010-2104-017
010-2104-019
(12 required)
(16 required)
032-8120-002
004-5359-123
010-2107-004
010-5203-001 (2 required)
0.55 – 1.09 SG
089-6125-010
089-6125-011
089-6125-012
089-6125-013
Pneumatic 046-1505-001
Receiver 046-1505-002
006-9501-002
006-9501-003
A. Model and serial number of receiver controller.
B. Name and number of replacement assembly (kit).
48-620 Modulevel Pneumatic Liquid Level Control
Controller mechanism
20
15
14
4
1
10
2
7
12
13
3
11
6
5
8
9
19
18
3.3.4
Model APM-131 Parts Identification
Item
1
2
3
4
5
6
7
8
9
Description
Enclosing tube
Gasket (E-tube)
Spacer tube
Mounting bushing
Snap ring
Stop washer
Range spring
Connecting link
Lock nut
10
11
12
13
14
15
16
17
18
19
20
Spring cup (upper)
Screw
Spring cup (lower)
Retaining bracket
Jam nut
Attraction ball & stem assembly
Displacer
Clamp screw
Displacer cable
Connector nut
Controller case only
17
16
3.3.4.1 Model APM-131 Part Number
1
2
20
Enclosing tube
Gasket (E-tube)
Mounting bushing kit
(includes items 2 through 5)
Stem and spring kit
(includes items 5 through 15)
Displacer kit
(includes items 16 through 19)
Controller case only
Z32-6201-006
012-1204-001
089-5703-001
089-5505-001
089-6106-001
046-1505-001
Figure 36
Typical Top Mounting
Head Assembly
48-620 Modulevel Pneumatic Liquid Level Control
39
3.3.5
Models APM-W251, APM-W254 and APM-W291 Parts Identification
1
2
6
3
5
4
7
12
8
11
10
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Description
Enclosing tube C.S.
Enclosing tube gasket
Head flange kit
Head flange gasket
Studs
Hex nuts
Head flange gasket
Spring mounting plate
Jam nut (not shown)
Cotter pin
Spring cup
Spring & stem assembly
Attraction sleeve (not shown)
Screws (not shown)
Chamber assembly
Displacer
Chamber liner (not shown)
Filter regulator (not shown)
Gauge (not shown)
Controller case only (shown on page 39)
15
16
Figure 37
Typical Carbon Steel Fabricated
External Cage Assembly
IMPORTANT:
When ordering replacement parts, please specify:
40
A. Model and serial number of receiver controller.
B. Name and number of replacement assembly (kit).
48-620 Modulevel Pneumatic Liquid Level Control
3.3.5.1
Models APM-W251, APM-W254 and APM-W291 Parts Numbers
Model APM-W251 Part Number
1
Enclosing tube C.S.
2
Enclosing tube gasket
Head flange kit
(includes items 3 through 6)
Stem and spring kit
(includes items 7 through 14)
10
Cotter pin
15
Chamber assembly
16
Displacer
17
Chamber liner (not shown)
18
Filter regulator (not shown)
19
Gauge (not shown)
20
Controller case only
(shown on page 39)
Z32-6201-006
012-1204-001
089-4202-001
089-5320-001
010-5202-005
089-4607-001
Z07-5422-121
089-4403-001
006-9501-002
006-9501-003
046-1505-001
Model APM-W254 Part Number
1
Enclosing tube C.S.
2
Enclosing tube gasket
Head flange kit
(includes items 3 through 6)
Stem and spring kit
(includes items 7 through 14)
10
Cotter pin
15
Chamber assembly
16
Displacer
17
Chamber liner (not shown)
18
Filter regulator (not shown)
19
Gauge (not shown)
20
Controller case only
(shown on page 39)
Z32-6201-006
012-1204-001
089-4202-001
089-5320-001
010-5202-005
089-4608-001
Z07-5421-121
089-4404-001
006-9501-002
006-9501-003
046-1505-001
Model APM-W291 Part Number
1
Enclosing tube C.S.
2
Enclosing tube gasket
Head flange kit
(includes items 3 through 6)
Stem and spring kit
(includes items 7 through 14)
10
Cotter pin
15
Chamber assembly
16
Displacer
17
Chamber liner (not shown)
18
Filter regulator (not shown)
19
Gauge (not shown)
20
Controller case only
(shown on page 39)
Z32-6201-006
012-1204-001
089-4203-001
089-5320-001
010-5202-005
Z33-1004-001
Z07-5421-121
N/A
006-9501-002
006-9501-003
046-1505-001
48-620 Modulevel Pneumatic Liquid Level Control
41
3.3.6 Controller Parts
16
2
31
10
15
14
32
23
30
22
1
12
11
33
33
17
18
19
20
21
3
5
7
2
6
6
8
4
3
9
Figure 38
Controller Replacement Parts
Controller Replacement Parts
42
48-620 Modulevel Pneumatic Liquid Level Control
3.3.6.1 Controller Replacement Assemblies Parts Identification (See Figures 38 & 39)
Item
Description
1
2
3
4
5
6
7
8
9
10
11
12
13
Tube,
Tube,
Tube,
Tube,
Barbed tee Barbed elbow Tube elbow Silicone tape, 1.25" length
Silicone tape, 2.00" length
Silicone tape, .75" length
Cable clamp
#10-32 x .25 round head screw
Tube, 30" length 14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Nozzle level assembly
Plate
#4-40 x .25 round head screw
Bridge adjustment screw assembly
Selector cam
Spring washer
Magnetic carriage assembly
Palnut
Nameplate
Feedback assembly
Gasket
O-ring, Viton®
O-ring, Viton®
O-ring, Viton®
O-ring, Viton®
Gasket
Gasket, relay mounting
Wiper assembly
Relay assembly
Pressure gauge
2.25"
4.75"
7.75"
3.13"
length
length
length
length
48-620 Modulevel Pneumatic Liquid Level Control
43
NOTE:
Replacement assemblies listed are furnished in preassembled kit form
only for standard temperature model proportional (P), proportional/reset
(PR), differential gap (D), and transmitter (T) pneumatic controllers.
3.3.6.2 Tubing Kit 089-8501-015
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
@ 3-15 and 6-30 psig (See Figure 38)
Tube, 2.25" length Tube, 4.75" length Tube, 7.75" length Tube, 3.13" length Barbed tee Barbed elbow Tube elbow Silicone tape, 1.25" length
Silicone tape, 2.00" length
Silicone tape, .75" length
Cable clamp
#10-32 x .25 round head screw
Tube, 30" length Qty.
1
2
2
1
1
4
2
1
1
1
1
1
31
25
24
26
27
28
1
29
3.3.6.3 Nozzle Lever Kit 089-8501-002@ 3-15
and 6-30 psig (See Figure 38)
Item
10
11
12
13
14
15
16
Silicone tape, .75" length
Cable clamp
#10-32 x .25 round head screw
Tube, 4.75" length Nozzle level assembly
Plate
#4-40 x .25 round head screw
Qty.
1
1
1
1
1
1
2
3.3.6.4 Carriage Assembly Kit 089-8501-003
Item
17
18
19
20
21
44
Bridge adjustment screw assembly
Selector cam
Spring washer
Magnetic carriage assembly
Palnut
28
30
Figure 39
Relay Assembly (Item 32)
@ 3-15 and 6-30 psig (See Figure 38)
Qty.
1
1
1
1
1
48-620 Modulevel Pneumatic Liquid Level Control
3.3.6.5 Feedback Assembly Kit 089-8501-005 @ 3–15 psig
and 89-8501-006 @ 6–30 psig (See Figure 38)
Item
1
22
23
Qty.
1
1
1
Tube, 7.50" length Nameplate Feedback assembly
3.3.6.6 Gasket Kit for Relay Assembly 089-8501-014 @ 3–15 psig and 6–30 psig (See Figure 39)
Item
24
25
26
27
28
29
30
Qty.
1
1
1
Gasket
O-Ring, Viton®
O-Ring, Viton®
O-Ring, Viton®
1
2
1
1
O-Ring, Viton® Gasket
Gasket, relay mounting
3.3.6.7 Additional Replacement Parts (See Figures 38 & 39)
Item
33
31
32
Pressure gauge
Wiper assembly
Relay assembly Qty.
1
1
1
NOTE:
3-15 psig
6-30 psig
006-8112-030
006-8112-060
089-7833-001
089-7803-001
Use tubing kit 089-8501-015 for units with brass fittings.
Controller heads with reset require 4 compression rings. All
others require 2. Use tubing kit 089-8501-001 for units with the
plastic fittings (items 6, 7, and 8) and process temperature
below +450° F (+232° C). Consult factory for units with plastic
fittings and process temperatures above +450° F.
Customer is to cut tube lengths to correspond to those previously supplied on the unit.
Carriage assembly kit part number 089-8501-004 for Model
P68 only.
Appropriate nameplate to be applied by customer, depending
on application.
IMPORTANT:
When ordering replacement parts, please specify:
48-620 Modulevel Pneumatic Liquid Level Control
Used only when mating surface has counter bore, otherwise
discard.
Relay assembly includes wiper assembly.
Clear tubing does not require compression ring (as did older
white tubing).
Plastic settings are obsolete. Call factory for replacement parts.
Brass fittings are now supplied.
A. Model and serial number of receiver controller.
B. Name and number of replacement assembly (kit).
45
3.3.7 Reset Replacement Parts
7
2
10
4
9
8
14
15
1
3
11
16
6
5
12
13
Figure 40
Reset Replacement Parts
18
17
20
19
22
21
Figure 41
Offshore Kit
46
48-620 Modulevel Pneumatic Liquid Level Control
3.3.7.1 Reset Replacement Assemblies (See Figures 40 & 41)
Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Qty.
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
2
2
1
1
Description
Valve assembly
Spacer
Dial
Set screw
Knob assembly
#2-56 x .33 round head screw
#4-40 x 16 bridge head screw
Washer
Spring, bias
Bellows assembly
Tube 8.50" length Tube .81" length Barbed tube tee O-Ring, Viton®
O-Ring, Viton®
O-Ring, Viton®
O-Ring, Viton®
Seal washer
O-Ring, Viton®
Adapter
Air relief valve
O-Ring, Viton®
3.3.7.2 Replacement Kits (See Figures 40 & 41)
Reset valve kit includes items 1 through 13
O-ring kit includes items 14 through 16
Offshore kit includes items 17 through 22
3-15 psig
6-30 psig
089-8501-008
089-8501-009
089-8501-010
089-8501-007
NOTE:
Replacement assemblies listed are furnished in preassembled kit form only, complete with gaskets for field installation.
The offshore kit allows air to exit the controller case while preventing air intake to the unit.
Clear tubing does not require compression ring (as did older white tubing).
Plastic settings are obsolete. Call factory for replacement parts. Brass fittings are now supplied.
IMPORTANT:
When ordering replacement parts, please specify:
48-620 Modulevel Pneumatic Liquid Level Control
A. Model and serial number of receiver controller.
B. Name and number of replacement assembly (kit).
47
NOTE:
Replacement assemblies listed are furnished in preassembled kit form
only for standard temperature model proportional (P), proportional/reset
(PR), differential gap (D), and transmitter (T) pneumatic controllers.
3.3.8 Receiver Controller Parts (See Figure 42)
Item
1
2
3
4
5
Qty.
1
1
1
1
2
6
7
8
1
1
1
9
10
11
12
13
14
1
1
2
1
1
1
Description
Nozzle lever
Bushing
Adjustment screw
Spring
#4-40 round head screw
Plate
#2-56 flat head screw
O-Ring, Viton®
Tube 7.75" length Tape, silicone
#8-32 round head screw
Tube 4.75" length Inlet connector
Input module
3.3.8.1 Receiver Controller Replacement Assemblies (See Figure 42)
3-15 psig
Receiver controller nozzle lever kit includes
items 1 through 10
Input module kit includes items 11 through 14
6-30 psig
089-8501-011
089-8501-012
089-8501-013
NOTE:
Clear tubing does not require compression ring (as did older white tubing).
3
1
9 10
7
8
11
14
13
2
12
5
6
4
Figure 42
Receiver Controller Parts
48
48-620 Modulevel Pneumatic Liquid Level Control
3.3.9 Transmitter Mounted Receiver Controller Parts
Transmitter
Receiver/Controller
OU
TP
UT
3
4
1
SU
PP
LY
2
UT
INP
OU
TP
UT
SU
PP
LY
5
6
10
11
7
13 12
9
8
Figure 43
Transmitter Mounted Receiver Controllers
(Configuration A Shown)
3.3.9.1 Transmitter Mounted Receiver Controller Replacement Assemblies (See Figure 43)
Item
1
2
3
4
5
6
7
8
12
13
Output tube (item 1)
Supply tube (item 2)
Male elbow (item 3)
Tee (item 4)
Male connector (item 5)
7
⁄8" Close Nipple (item 6)
13⁄4" nipple (item 7)
Bracket assembly (item 8)
Saddle, U-bolt, hex nuts
(items 9 through 11)
Filter regulator (item 12)
Gauge (item 13 – not shown)
Replacement Assemblies
Configuration A
Configuration B (not shown)
Qty.
Part No.
Qty.
Part. No.
1
Consult Factory
1
Consult Factory
1
Consult Factory
1
Consult Factory
2
011-4102-042
3
011-4102-042
2
011-2212-001
2
011-2212-001
2
011-4707-002
1
011-4707-002
2
011-1102-007
1
011-1102-007
1
011-1102-016
2
011-1102-016
1
036-3802-001
1
036-3802-001
1
1
1
010-1706-001
006-9501-002
006-9501-003
1
2
2
010-1706-001
006-9501-002
006-9501-003
CONFIGURATION:
A. For receiver-controller installation on transmitter with same input/output range.
B. For receiver-controller installation on transmitter with different input/output range,
requiring use of two filter regulators.
48-620 Modulevel Pneumatic Liquid Level Control
49
3.3.10 Pneumatic Modulevel Replacement Head Kits
8th, 9th &
10th digits
Function
Supply
Pressure
Output
Action
Limit
Switches
PAA
proportional
20 psig
3–15 psig
direct
no
089-8502-001 089-8502-033 089-8502-065
PAB
proportional
35 psig
6–30 psig
direct
no
089-8502-002 089-8502-034 089-8502-066
PBA
prop. w/reset
20 psig
3–15 psig
direct
no
089-8502-003 089-8502-035 089-8502-067
PBB
prop. w/reset
35 psig
6–30 psig
direct
no
089-8502-004 089-8502-036 089-8502-068
PCA
transmitter
20 psig
3–15 psig
direct
no
089-8502-005 089-8502-037 089-8502-069
PCB
transmitter
35 psig
6–30 psig
direct
no
089-8502-006 089-8502-038 089-8502-070
PDA
differential gap
20 psig
0 or 20 psig
direct
no
089-8502-007 089-8502-039 089-8502-071
PDB
differential gap
35 psig
0 or 35 psig
direct
no
089-8502-008 089-8502-040 089-8502-072
PIA
proportional
20 psig
3–15 psig
direct
yes
089-8502-017 089-8502-049 089-8502-081
PIB
proportional
20 psig
6–30 psig
direct
yes
089-8502-018 089-8502-050 089-8502-082
PJA
prop. w/reset
20 psig
3–15 psig
direct
yes
089-8502-019 089-8502-051 089-8502-083
PJB
prop. w/reset
35 psig
6–30 psig
direct
yes
089-8502-020 089-8502-052 089-8502-084
PKA
transmitter
20 psig
3–15 psig
direct
yes
089-8502-021 089-8502-053 089-8502-085
PKB
transmitter
35 psig
6–30 psig
direct
yes
089-8502-022 089-8502-054 089-8502-086
PLA
differential gap
20 psig
0 or 20 psig
direct
no
089-8502-023 089-8502-055 089-8502-087
PLB
differential gap
35 psig
0 or 35 psig
direct
no
089-8502-024 089-8502-056 089-8502-088
PEA
proportional
20 psig
3–15 psig
reverse
no
089-8502-009 089-8502-041 089-8502-073
PEB
proportional
35 psig
6–30 psig
reverse
no
089-8502-010 089-8502-042 089-8502-074
PFA
prop. w/reset
20 psig
3–15 psig
reverse
no
089-8502-011 089-8502-043 089-8502-075
PFB
prop. w/reset
35 psig
6–30 psig
reverse
no
089-8502-012 089-8502-044 089-8502-076
PGA
transmitter
20 psig
3–15 psig
reverse
no
089-8502-013 089-8502-045 089-8502-077
PGB
transmitter
35 psig
6–30 psig
reverse
no
089-8502-014 089-8502-046 089-8502-078
PHA
differential gap
20 psig
0 or 20 psig
reverse
no
089-8502-015 089-8502-047 089-8502-079
PHB
differential gap
35 psig
0 or 35 psig
reverse
no
089-8502-016 089-8502-048 089-8502-080
PMA
proportional
20 psig
3–15 psig
reverse
yes
089-8502-025 089-8502-057 089-8502-089
PMB
proportional
35 psig
6–30 psig
reverse
yes
089-8502-026 089-8502-058 089-8502-090
PNA
prop. w/reset
20 psig
3–15 psig
reverse
yes
089-8502-027 089-8502-059 089-8502-091
PNB
prop. w/reset
35 psig
6–30 psig
reverse
yes
089-8502-028 089-8502-060 089-8502-092
POA
transmitter
20 psig
3–15 psig
reverse
yes
089-8502-029 089-8502-061 089-8502-093
POB
transmitter
35 psig
6–30 psig
reverse
yes
089-8502-030 089-8502-062 089-8502-094
PPA
differential gap
20 psig
0 or 20 psig
reverse
yes
089-8502-031 089-8502-063 089-8502-095
PPB
differential gap
35 psig
0 or 35 psig
reverse
yes
089-8502-032 089-8502-064 089-8502-096
50
1 or 4
Model Fourth Digit
2 or 5
3 or 6
48-620 Modulevel Pneumatic Liquid Level Control
3.3.10 Pneumatic Modulevel Replacement Head Kits (cont.)
Model Fourth Digit
2 or 5
3 or 6
8th, 9th &
10th digits
Function
Supply
Pressure
Output
Action
Limit
Switches
RAA*
proportional
20 psig
3–15 psig
direct
no
089-8502-129 089-8502-145 089-8502-161
RAB*
proportional
35 psig
6–30 psig
direct
no
089-8502-130 089-8502-146 089-8502-162
RBA*
prop. w/reset
20 psig
3–15 psig
direct
no
089-8502-131 089-8502-147 089-8502-163
RBB*
prop. w/reset
35 psig
6–30 psig
direct
no
089-8502-132 089-8502-148 089-8502-164
REA*
transmitter
20 psig
3–15 psig
reverset
no
089-8502-133 089-8502-149 089-8502-165
REB*
transmitter
35 psig
6–30 psig
reverse
no
089-8502-134 089-8502-150 089-8502-166
RFA*
differential gap
20 psig
3–15 psig
direct
no
089-8502-135 089-8502-151 089-8502-167
RFB*
differential gap
35 psig
6–30 psig
direct
no
089-8502-136 089-8502-152 089-8502-168
TAA
proportional
20 psig
3–15 psig
direct
no
089-8502-137 089-8502-153 089-8502-169
TAB*
proportional
20 psig
6–30 psig
direct
no
089-8502-138 089-8502-154 089-8502-170
TBA*
prop. w/reset
20 psig
3–15 psig
direct
no
089-8502-139 089-8502-155 089-8502-171
TBB*
prop. w/reset
35 psig
6–30 psig
direct
no
089-8502-140 089-8502-156 089-8502-172
TEA*
transmitter
20 psig
3–15 psig
direct
no
089-8502-141 089-8502-157 089-8502-173
TEB*
transmitter
35 psig
6–30 psig
direct
no
089-8502-142 089-8502-158 089-8502-174
TFA*
differential gap
20 psig
3–15 psig
direct
no
089-8502-143 089-8502-159 089-8502-175
TFB*
differential gap
35 psig
6–30 psig
direct
no
089-8502-144 089-8502-160 089-8502-176
PAJ
proportional
20 psig
3–15 psig
direct
no
n/a
089-8502-097
n/a
PAK
proportional
35 psig
6–30 psig
reverse
no
n/a
089-8502-098
n/a
PBJ
prop. w/reset
20 psig
3–15 psig
reverse
no
n/a
089-8502-099
n/a
PBK
prop. w/reset
35 psig
6–30 psig
reverse
no
n/a
089-8502-100
n/a
PCJ
transmitter
20 psig
3–15 psig
reverse
no
n/a
089-8502-101
n/a
PCK
transmitter
35 psig
6–30 psig
reverse
no
n/a
089-8502-102
n/a
PDJ
differential gap
20 psig
0 or 20 psig
reverse
no
n/a
089-8502-103
n/a
PDK
differential gap
35 psig
0 or 35 psig
reverse
no
n/a
089-8502-104
n/a
PEJ
proportional
20 psig
3–15 psig
reverse
no
n/a
089-8502-105
n/a
PEK
proportional
35 psig
6–30 psig
reverse
no
n/a
089-8502-106
n/a
PFJ
prop. w/reset
20 psig
3–15 psig
reverse
no
n/a
089-8502-107
n/a
PFK
prop. w/reset
35 psig
6–30 psig
reverse
no
n/a
089-8502-108
n/a
PGJ
transmitter
20 psig
3–15 psig
reverse
no
n/a
089-8502-109
n/a
PGK
transmitter
35 psig
6–30 psig
reverse
no
n/a
089-8502-110
n/a
PHJ
differential gap
20 psig
0 or 20 psig
reverse
no
n/a
089-8502-111
n/a
PHK
differential gap
35 psig
0 or 35 psig
reverse
no
n/a
089-8502-112
n/a
1 or 4
* Kits for receiver controllers include both heads
48-620 Modulevel Pneumatic Liquid Level Control
51
3.4
Model Numbers
3.4.1 Standard Flanged Top and Flanged Cage Displacer Models
DESIGN TYPE
P 6
Standard design Pneumatic Modulevel
MOUNTING AND CHAMBER MATERIALS
flanged top cage side/bottom
cage side/side
tank connection
steel
316 SS
steel
316 SS
steel
316 SS
1
2
3
4
5
6
chamber material
code
Adjustable 8' hanger cable (p/n 32-3110-001), required when distance from flange face to top of displacer
must be greater than 5.00"
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
+400° F (+204° C)
+700° F (+371° C) maximum temperature
1
4
0.23 – 0.54 specific gravity
2
5
0.55 – 1.09 specific gravity
3
6
1.10 – 2.20 specific gravity
Inconel spring furnished on models P62, P64 and P66 with codes 4, 5, or 6
TANK CONNECTION
Top mounted connection type
External cage models
ANSI Head Flange rating
RF 150 lbs RF 300 lbs RF 600 lbs
ANSI Cage rating
Size
RF 150 lbs RF 300 lbs RF 600 lbs Size / Type
G3
G4
G5
3"
C5
C7
C9
11⁄2" NPT
H3
H4
C8
C0
11⁄2" S.W.
K4
4"
6"
C6
K3
H5
K5
P3
P4
P5
11⁄2" flanged
D5
D7
D9
2" NPT
D6
D8
D0
2" S.W.
Q3
Q4
Q5
2" flanged
Maximun pressure rating for units with 600 lb.
ANSI flange construction is 1330 psi @ 100° F
(967 bar @ 38° C).
LEVEL RANGE
14
356
32
813
48
1219
60
1524
72
1829
84
2134
96
2438
108
2743
120
3048
inches
mm
A
B
C
D
E
F
G
H
I
CODE
PNEUMATIC INSTRUMENT (see opposite page)
P
52
6
complete order code for Standard
Pneumatic Modulevel
48-620 Modulevel Pneumatic Liquid Level Control
3.4.1 Standard Flanged Top and Flanged Cage Displacer Models (continued)
PNEUMATIC INSTRUMENT
Single Function Heads
Direct Acting
Std
Limit Sws
Reverse Acting
Std
Limit Sws
Function
Output
Mounting
PAA
PIA
PEA
PMA
Proportional
3–15 psig
Integral
PAB
PIB
PEB
PMB
Proportional
6–30 psig
Integral
PBA
PJA
PFA
PNA
Proportional w/reset
3–15 psig
Integral
PBB
PJB
PFB
PNB
Proportional w/reset
6–30 psig
Integral
PCA
PKA
PGA
POA
Transmitter
3–15 psig
Integral
PCB
PKB
PGB
POB
Transmitter
6–30 psig
Integral
PDA
PLA
PHA
PPA
Differential Gap
0–20 psig
Integral
PDB
PLB
PHB
PPB
Differential Gap
0–35 psig
Integral
Output
Mounting
TRANSMITTER/RECEIVER CONTROLLER
Dual Heads
Direct Acting
Reverse Acting
Std
Limit Sws
Std
Limit Sws
Function
RAA
n/a
REA
n/a
Proportional
3–15 psig
Integral
RAB
n/a
REB
n/a
Proportional
6–30 psig
Integral
RBA
n/a
RFA
n/a
Proportional w/reset
3–15 psig
Integral
RBB
n/a
RFB
n/a
Proportional w/reset
6–30 psig
Integral
TAA
n/a
TEA
n/a
Proportional
3–15 psig
Remote
TAB
n/a
TEB
n/a
Proportional
6–30 psig
Remote
TBA
n/a
TFA
n/a
Proportional w/reset
3–15 psig
Remote
TBB
n/a
TFB
n/a
Proportional w/reset
6–30 psig
Remote
48-620 Modulevel Pneumatic Liquid Level Control
53
3.4.2 High Pressure Flanged Top and Flanged Cage Displacer Models
DESIGN TYPE
P 5
High pressure design Pneumatic Modulevel
MOUNTING AND CHAMBER MATERIALS flanged top cage side/bottom
cage side/side
steel
steel
steel
1
3
5
tank connection
chamber material
code
P50 Series displacer material is 304 stainless steel.
Adjustable 8' hanger cable (p/n 32-3110-001), required when distance from flange face to top of displacer
must be greater than 9.31."
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
+700° F (+371° C)
maximum temperature
5
0.55 – 1.09 specific gravity
TANK CONNECTION
Top mounted connection type
External cage models
ANSI HEAD Flange rating
RF 900 lbs RF 1500 lbs RF 2500 lbs
H6
H7
H8
LEVEL RANGE
14
32
356
813
A
B
ANSI Cage rating
Size
4"
RF 900 lbs RF 1500 lbs RF 2500 lbs Size / Type
L5
L7
L9
11⁄2" NPT
M5
M7
M9
11⁄2" S.W.
P6
P7
P8
11⁄2" flanged
L6
L8
L0
2" NPT
M6
M8
M0
2" S.W.
Q6
Q7
Q8
2" flanged
48
1219
60
1524
inches
mm
C
D
code
PNEUMATIC INSTRUMENT
P
54
5
5
complete order code for High Pressure
Pneumatic Modulevel
48-620 Modulevel Pneumatic Liquid Level Control
3.4.2 High Pressure Flanged Top and Flanged Cage Displacer Models (continued)
PNEUMATIC INSTRUMENT
Single Function Heads
Direct Acting
Std
Limit Sws
Reverse Acting
Std
Limit Sws
Function
Output
Mounting
PAA
PIA
PEA
PMA
Proportional
3–15 psig
Integral
PAB
PIB
PEB
PMB
Proportional
6–30 psig
Integral
PBA
PJA
PFA
PNA
Proportional w/reset
3–15 psig
Integral
PBB
PJB
PFB
PNB
Proportional w/reset
6–30 psig
Integral
PCA
PKA
PGA
POA
Transmitter
3–15 psig
Integral
PCB
PKB
PGB
POB
Transmitter
6–30 psig
Integral
PDA
PLA
PHA
PPA
Differential Gap
0–20 psig
Integral
PDB
PLB
PHB
PPB
Differential Gap
0–35 psig
Integral
Output
Mounting
TRANSMITTER/RECEIVER CONTROLLER
Dual Heads
Direct Acting
Reverse Acting
Std
Limit Sws
Std
Limit Sws
Function
RAA
n/a
REA
n/a
Proportional
3–15 psig
Integral
RAB
n/a
REB
n/a
Proportional
6–30 psig
Integral
RBA
n/a
RFA
n/a
Proportional w/reset
3–15 psig
Integral
RBB
n/a
RFB
n/a
Proportional w/reset
6–30 psig
Integral
TAA
n/a
TEA
n/a
Proportional
3–15 psig
Remote
TAB
n/a
TEB
n/a
Proportional
6–30 psig
Remote
TBA
n/a
TFA
n/a
Proportional w/reset
3–15 psig
Remote
TBB
n/a
TFB
n/a
Proportional w/reset
6–30 psig
Remote
48-620 Modulevel Pneumatic Liquid Level Control
55
3.4.3 Standard Sealed Cage Displacer Models
DESIGN TYPE
P 7
Sealed cage design Pneumatic Modulevel
MOUNTING AND CHAMBER MATERIALS Carbon steel chamber material
side/bottom
side/side
tank connections
1
2
code
Inconel spring furnished on all models.
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
+400° F (+200° C)
+700° F (+371° C)
maximum temperature
1
4
0.23 – 0.54 specific gravity
2
5
0.55 – 1.09 specific gravity
3
6
1.10 – 2.20 specific gravity
TANK CONNECTION
EXTERNAL CAGE MODELS
ANSI Mounting flange rating
NPT
SW
RF 150 lbs
RF 300 lbs
RF 600 lbs
Size
C9
C0
P3
P4
P5
11⁄2"
D9
D0
Q3
Q4
Q5
2"
Maximun pressure rating for units with 600 lb. ANSI flange construction is 1330 psi @
100° F (967 bar @ 38° C).
LEVEL RANGE
14
356
32
813
48
1219
60
1524
72
1829
84
2134
96
2438
108
2743
120
3048
inches
mm
A
B
C
D
E
F
G
H
I
CODE
PNEUMATIC INSTRUMENT (see opposite page)
P
56
7
complete order code for Sealed Cage
Pneumatic Modulevel
48-620 Modulevel Pneumatic Liquid Level Control
3.4.3 Standard Sealed Cage Displacer Models (continued)
PNEUMATIC INSTRUMENT
Single Function Heads
Direct Acting
Reverse Acting
Std
Limit Sws
Std
Limit Sws
Function
Output
Mounting
PAA
PIA
PEA
PMA
Proportional
3–15 psig
Integral
PAB
PIB
PEB
PMB
Proportional
6–30 psig
Integral
PBA
PJA
PFA
PNA
Proportional w/reset
3–15 psig
Integral
PBB
PJB
PFB
PNB
Proportional w/reset
6–30 psig
Integral
PCA
PKA
PGA
POA
Transmitter
3–15 psig
Integral
PCB
PKB
PGB
POB
Transmitter
6–30 psig
Integral
PDA
PLA
PHA
PPA
Differential Gap
0–20 psig
Integral
PDB
PLB
PHB
PPB
Differential Gap
0–35 psig
Integral
TRANSMITTER/RECEIVER CONTROLLER
Dual Heads
Direct Acting
Reverse Acting
Std
Limit Sws
Std
Limit Sws
Function
Output
Mounting
RAA
n/a
REA
n/a
Proportional
3–15 psig
Integral
RAB
n/a
REB
n/a
Proportional
6–30 psig
Integral
RBA
n/a
RFA
n/a
Proportional w/reset
3–15 psig
Integral
RBB
n/a
RFB
n/a
Proportional w/reset
6–30 psig
Integral
TAA
n/a
TEA
n/a
Proportional
3–15 psig
Remote
TAB
n/a
TEB
n/a
Proportional
6–30 psig
Remote
TBA
n/a
TFA
n/a
Proportional w/reset
3–15 psig
Remote
TBB
n/a
TFB
n/a
Proportional w/reset
6–30 psig
Remote
48-620 Modulevel Pneumatic Liquid Level Control
57
3.4.4 Standard Side Mount Displacer Models
DESIGN TYPE
P68
Side mount in tank, carbon steel body, 316 SS float and trim
SPECIFIC GRAVITY AND PROCESS TEMPERATURE
+400° F (+200° C)
maximum temperature
2
0.60 minimum specific gravity
TANK CONNECTION
SIDE MOUNTING CONNECTION TYPE
ANSI Head Flange rating
NPT RF 150 lbs
RF 300 lbs
RF 600 lbs Size
F2A
N/A
N/A
N/A
3"
N/A
H3A
H4A
H5A
4"
Maximum pressure rating is limited to 800 psig @ 100° F
due to float.
PNEUMATIC INSTRUMENT
Single Function Heads for P68 model only
P
58
6
8
2
Direct
Acting
Reverse
Acting
Std
Std
Function
Output
Mounting
PAJ
PEJ
Proportional
3–15 psig
Integral
PAK
PEK
Proportional
6–30 psig
Integral
PBJ
PFJ
Proportional w/reset
3–15 psig
Integral
PBK
PFK
Proportional w/reset
6–30 psig
Integral
PCJ
PGJ
Transmitter
3–15 psig
Integral
PCK
PGK
Transmitter
6–30 psig
Integral
PDJ
PHJ
Differential Gap
0–20 psig
Integral
PDK
PHK
Differential Gap
0–35 psig
Integral
complete order code for Side Mount
Pneumatic Modulevel
48-620 Modulevel Pneumatic Liquid Level Control
3.4.5 APM Pneumatic Control Models
DESIGN TYPE
APM
Pneumatic Liquid Level Controls
MOUNTING AND MATERIALS OF CONSTRUCTION
Model
Code
Output
Signal
Mounting
Arrangement
Body
Material
Maximum
Pressure
Maximum
Temperature
Minimum
S.G.
Displacer
Size
131L
3–15
Top
Carbon steel
230 psig
(16 bar)
+250° F
(+120° C)
0.90
2" x 14"
131H
6–30
Top
Carbon steel
230 psig
(16 bar)
+250° F
(+120° C)
0.90
2" x 14"
W251
3–15
6–30
External
Flange Cage
Cast iron
250 lb. WSP
+406° F
(+208° C)
0.86
2.5" x 9"
W254
3–15
6–30
External
Flange Cage
Cast iron
250 lb. WSP
+406° F
(+208° C)
0.86
2" x 12"
W291
3–15
6–30
External
Flange Cage
Carbon steel
300 lb. WSP
+422° F
(+217° C)
0.85
2" x 12"
PNEUMATIC INSTRUMENT
Function
Proportional
A
P
Pressure
psig
3–15
6–30
Single Function Models
Direct Acting
Reverse Acting
Standard
w/Limit
Standard
w/Limit
Head
Switches
Head
Switches
PAA
PIA
PEA
PMA
PAB
PIB
PEB
PMB
M
48-620 Modulevel Pneumatic Liquid Level Control
59
ASSURED QUALITY & SERVICE COST LESS
Service Policy
Return Material Procedure
Owners of Magnetrol may request the return of a control
or any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Controls
returned under our service policy must be returned by
Prepaid transportation. Magnetrol will repair or replace
the control at no cost to the purchaser (or owner) other
than transportation if:
So that we may efficiently process any materials that are
returned, it is essential that a “Return Material
Authorization” (RMA) number be obtained from the
factory, prior to the material’s return. This is available
through Magnetrol’s local representative or
by contacting the factory. Please supply the following
information:
1. Returned within the warranty period; and
2. The factory inspection finds the cause of the claim
to be covered under the warranty.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be
charges for labor and the parts required to rebuild or
replace the equipment.
In some cases it may be expedient to ship replacement
parts; or, in extreme cases a complete new control, to
replace the original equipment before it is returned. If
this is desired, notify the factory of both the model and
serial numbers of the control to be replaced. In such
cases, credit for the materials returned will be determined
on the basis of the applicability of our warranty.
1.
2.
3.
4.
5.
Company Name
Description of Material
Serial Number
Reason for Return
Application
Any unit that was used in a process must be properly
cleaned in accordance with OSHA standards, before it is
returned to the factory.
A Material Safety Data Sheet (MSDS) must accompany
material that was used in any media.
All shipments returned to the factory must be by prepaid
transportation.
All replacements will be shipped F.O.B. factory.
No claims for misapplication, labor, direct or consequential damage will be allowed.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2009 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.