MEANWELL SD-100D-12

SD-100
100W Single Output DC-DC Converter
series
Features :
2:1 wide input range
Protections: Short circuit / Overload / Over voltage
1500VAC I/O isolation
Built-in EMI filter, low ripple noise
100% full load burn-in test
Fixed switching frequency at 83KHz
24V and 48V input voltage design refer to LVD
Low cost
High reliability
2 years warranty
(for D type only)
SPECIFICATION
MODEL
SD-100B-5
SD-100C-5
SD-100D-5
5V
12V
24V
RATED CURRENT
20A
8.5A
4.2A
CURRENT RANGE
0 ~ 20A
0 ~ 8.5A
0 ~ 4.2A
RATED POWER
100W
102W
100.8W
RIPPLE & NOISE (max.) Note.2 100mVp-p
OUTPUT
INPUT
VOLTAGE ADJ. RANGE
1.0%
1.0%
0.5%
0.3%
0.2%
LOAD REGULATION
0.5%
0.3%
0.2%
SETUP, RISE TIME
2s, 50ms(only D mode) at full load
HOLD UP TIME (Typ.)
20ms(only D mode) at full load
VOLTAGE RANGE
B:19 ~ 36VDC
EFFICIENCY (Typ.)
74%
75%
76%
75%
77%
80%
78%
81%
83%
DC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
4.8A/24V
2.4A/48V
1.8A/96V
4.8A/24V
2.4A/48V
1.8A/96V
4.8A/24V
2.4A/48V
1.8A/96V
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
C:36 ~ 72VDC
D:72 ~ 144VDC or 85 ~ 132VAC
D:18A/96VDC
<0.75mA/120VAC(SD-100D)
105 ~ 135% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
5.75 ~ 6.75V/10% load
16.8 ~ 20V/10% load
Protection type : Hiccup mode, recovers automatically after fault condition is removed
-10 ~ +60
(Refer to output load derating curve)
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
IEC60950-1 CB approved by TUV (for D type only)
I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
/ 70% RH
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,6,8; ENV50204, light industry level, criteria A
MTBF
356.7K hrs min.(SD-100B)
355.5K hrs min.(SD-100C)
199*98*38mm (L*W*H)
0.65Kg; 20pcs/13.8Kg/0.8CUFT
DIMENSION
31.5 ~ 37.5V/10% load
20 ~ 90% RH non-condensing
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
PACKING
NOTE
23 ~ 30VDC
2.0%
OVERLOAD
OTHERS
150mVp-p
11 ~ 16VDC
LINE REGULATION
PROTECTION
(Note 4)
4.5 ~ 5.5VDC
120mVp-p
VOLTAGE TOLERANCE Note.3
LEAKAGE CURRENT
EMC
SD-100B-12 SD-100C-12 SD-100D-12 SD-100B-24 SD-100C-24 SD-100D-24
DC VOLTAGE
341.9K Hrs min.(SD-100D)
MIL-HDBK-217F (25
)
1. All parameters NOT specially mentioned are measured at 24,48,96VDC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:SD-100-SPEC 2010-10-18
SD-100
100W Single Output DC-DC Converter
Mechanical Specification
Case No. 902
series
Unit:mm
7
3.5
9
12
197
1
9.5
2
98
80
4
85.5
3
8.2
5
6
7
4-
3.5
M
3
Terminal Pin No. Assignment
57.5
4.5
Pin No.
1,2
3
120
199
28.5
38
3.5
9.5
3
18
18
9
3.5
3-M
Pin No.
4,5
6,7
Assignment
DC OUTPUT -V
DC OUTPUT +V
SD-100B,C
Pin No. Assignment
1
DC INPUT V+
2
DC INPUT V-
190
6.5
Assignment
INPUT
FG
SD-100D
Pin No. Assignment
1,2
AC/DC INPUT
157
22
Block Diagram
fosc : 83KHz
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
FG
O.L.P.
+V
-V
DETECTION
CIRCUIT
PWM
CONTROL
O.V.P.
Derating Curve
Static Characteristics(SD-100D-24V)
OUTPUT VOLTAGE (V)
100
80
SD-100B-5,12,24
SD-100C,D-5,12
LOAD (%)
60
40
20
-10
-10
0
0
10
20
30
40
50
45
AMBIENT TEMPERATURE ( )
60
55
(VERTICAL)
(HORIZONTAL)
32
350
28
300
24
250
20
200
16
150
12
100
8
50
55
60
65
70
75
80
90
100
110
120
OUTPUT RIPPLE (mVp-p)
Ta=25
SD-100C,D-24
130
INPUT VOLTAGE (V)
File Name:SD-100-SPEC 2010-10-18