PROTEC 587B051

05016
587B051
thru
587B301
Only One Name Means ProTek’Tion™
120V AC POWER LINE SURGE SUPPRESSOR
APPLICATIONS
✔ Hard Wired Equipment AC Power Protection
✔ Load Side Distribution Systems
✔ Secondary Protection for Light Industrial AC Power
IEC COMPATIBILITY (EN61000-4)
✔ 61000-4-5 (Surge): 1kA, 8/20µs - Level 4(Line-Line) & 333A Level 4(Line-Ground)
FEATURES
U.S PATENT 4,563,720
✔
✔
✔
✔
✔
✔
Meets ANSI/IEEE C62.41 Requirements
Listed to CSA, File LR65240
Differential and Common Mode Protection
Low Clamping Voltage
Nanosecond Response Time
Long Life and Maintenance Free
FIGURE 1
TRANSIENT VOLTAGE THREAT
CONDITION
8
✔ Plastic Package
✔ Weight: 485 Grams (Approximate)
✔ Flammability Rating UL 94V-0
✔ Device Marking: Part Number, Date Code, Logo, Voltage and Current Rating
Kilovolts
6
MECHANICAL CHARACTERISTICS
4
2
0
0
05016.R4 12/03
1
40
50
60
6
4
2
0
0
The 587B Series offers a high degree of protection against 120 VAC EMI line noise. It
is ideal for protecting 400 Volt components because the solid state TVS technology
assures that the line-to-neutral voltage will not exceed 400 Volts. While the modules
are designed for transient voltage protection, the advanced circuitry will also attenuate
the amplitude and slow the rate of rise of high frequency noise acting as an EMI filter.
The 587B Series includes differential mode and common mode protection, which is
effective in reducing interference from line to equipment and are effective in reducing
equipment generated noise to meet FCC, VDE and CSA interference requirements.
30
FIGURE 2
TYPICAL CLAMPING ACTION
OF A 16 AMP MODULE
Kilovolts
This series is designed to protect AC powered equipment from the 6,000 Volt peak
open circuit voltage and 3,000 Amp short circuit current as defined in ANSI/IEEE
C62.41, Category C1.
20
Time - µs
DESCRIPTION
The 587B Series of 120 Volt AC Surge Suppressors is designed for use by the OEM,
equipment installer and or maintenance contractor. These modules employ a three
stage technology proven to be the most cost effective and reliable method in protecting sensitive electronic equipment from over voltage transients.
10
10
20
30
Time - µs
40
50
60
Figures 1 and 2 are photographs of digitized waveforms
showing the typical clamping action of a 16 ampere module.
A 12 Ohm resistor is used to represent a 10 Amp equipment
load. The load is then subjected to the ANSI/IEEE C62.41
Category CI test conditions (6,000V/3,000A). These photographs contrast the effect on equipment with and without the
protector.
www.protekdevices.com
587B051
thru
587B301
DEVICE CHARACTERISTICS
SPECIFICATIONS @ 25°C
RESPONSE TO TRANSIENT VOLTAGES
MAXIMUM RATINGS
Operating Line Voltage: 130 VAC Max
Maximum Line Current: 587B051: 5A
587B151: 15A
587B201: 20A
(Line-to-Neutral Only) 587B301: 30A
Transient Voltage: 6000Vpeak
Transient Current: 3000Apeak
Current Leakage:
Line-to-Neutral:
Neutral-to-Ground:
Storage & Operating
Temperature:
(Measured at center of
mounting surface)
@ 130 VAC
1.0mA
0.5mA
CLAMPING
TEST CONDITION
PROTECTION
MODE
MAXIMUM
CLAMPING
VOLTAGE
OPEN CIRCUIT
VOLTAGE
@ 1.2/50 µs
SHORT CIRCUIT
CURRENT
@ 8/20 µs
DIFFERENTIAL
(Line-to-Neutral)
295V
350V
1000V
6000V
500A
3000A
COMMON
(Neutral-to-Ground)
500V
650V
1000V
6000V
500A
3000A
FILTER CHARACTERISTICS (Noise Attenuation dB)
-40°C to 85°C
Frequency (MHz)
Common Mode Attenuation
Differential Mode Attenuation
0.15
10
30
0.5
25
55
1.0
35
55
5.0
55
55
10
50
50
30
40
45
ARRESTER DEFINITIONS
Clamping Voltage: The clamping voltage of an arrester is the voltage that appears across its terminals during conduction of a transient current.
Standard Wave Form: The waveform of a surge current or voltage is designated by a combination of two numbers. The first number is for the time
of the wave front expressed in microseconds from zero to the peak of the wave. The second number is for the time of the wavetail also expressed in
microseconds from zero to the instant that the wavetail reaches one half of the crest or peak value, i.e., 8/20 µs waveform.
Transient Current: The transient current of an arrestor is the peak surge current which flows through the arrester when voltage clamping occurs.
OPERATION
For maximum effectiveness, the protector should be installed directly after the AC line on/off switch and fuse. This will protect the electronics from
the AC line switch arcing and the severe transients caused by a fuse clearing.
Some heat is produced when operating at full current load, and heat sinking may be required to maintain case temperature below 85°C. The case
temperature is measured at the center of the mounting surface. The unit should not be mounted to a low combusting temperature material such as
wood.
High energy transients will cause a large circulating current in the AC input line (2,500A is possible). To prevent electromagnetic coupling, the AC line
on the input side of the protector must be dressed away from other wiring, magnetic shielding may be required. In addition, the electrical service
must be connected to a low impedance earth ground.
05016.R4 12/03
2
www.protekdevices.com
587B051
thru
587B301
PACKAGE OUTLINE & DIMENSIONS
D
F
C
LINE OUT
Model 587B051
120V
50/60 Hz
NEUTRAL
B
37464-00001
LINE IN
E
INCLUDES HARDWARE
2 NUTS, 2 WASHERS
PER TERMINAL
5 AMP
GROUND
0.169” Nom. Dia.
2 Places
A
PROTEK
PART
NUMBER
587B051
587B151
587B201
587B302
CASE (INCHES)
A
2
3
3
3
B
2
2
3
3
C
2.5
3.5
3.5
3.5
D
2.85
3.85
3.85
3.85
CASE (CENTIMETERS)
E
1.5
1.5
1.5
1.5
F
0.6
0.6
0.6
0.6
B
5.08
5.08
7.62
7.62
A
5.08
7.62
7.62
7.62
COPYRIGHT © ProTek Devices 2003
SPECIFICATIONS: ProTek reserves the right to change the electrical and or mechanical characteristics described herein
without notice (except JEDEC).
DESIGN CHANGES: ProTek reserves the right to discontinue product lines without notice, and that the final judgement
concerning selection and specifications is the buyer’s and that in furnishing engineering and technical assistance,
ProTek assumes no responsibility with respect to the selection or specifications of such products.
05016.R4 12/03
3
C
6.35
8.89
8.89
8.89
D
7.62
10.16
10.16
10.16
E
3.81
3.81
3.81
3.81
F
1.52
1.52
1.52
1.52
APPROX.
WEIGHT
IN GRAMS
TERMINAL
THREADS
250
500
750
850
#8-32
#8-32
M5
M5
ProTek Devices
2929 South Fair Lane, Tempe, AZ 85282
Tel: 602-431-8101 Fax: 602-431-2288
E-Mail: [email protected]
Web Site: www.protekdevices.com
www.protekdevices.com