SYSTEMSENSOR PDRP-2001

3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: (630) 377-6495
PDRP-2001
Series
Deluge • Preaction Control
Panel
Instruction Manual
Document
5/08/07
PN 53043:A
#53043
Revision:
A
ECN 07-157
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
age of flammable materials, etc.).
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/
applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD
02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F and at a relative humidity of
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD
02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
Table of Contents
Table of Contents
SECTION 1: Product Description .........................................................................................................................11
1.1: Product Features ..........................................................................................................................................11
1.2: Specifications ..............................................................................................................................................13
1.3: Controls and Indicators................................................................................................................................14
1.4: Components.................................................................................................................................................15
1.5: Optional Modules and Accessories .............................................................................................................16
SECTION 2: Installation ........................................................................................................................................17
2.1: Backbox Mounting ......................................................................................................................................17
2.2: Operating Power..........................................................................................................................................20
2.3: Input Circuits ...............................................................................................................................................21
2.4: Output Circuits ............................................................................................................................................23
2.4.1: Outputs/Notification Appliance/Releasing Circuits..........................................................................23
2.4.2: Special Application DC Power Output Connections ........................................................................24
2.4.3: Relays - Programmable .....................................................................................................................24
2.5: Power-limited Wiring Requirements...........................................................................................................25
2.6: Installation of Optional Modules.................................................................................................................26
2.6.1: CAC-5X Class A Converter Module ................................................................................................26
2.6.1.1 Installation ...............................................................................................................................26
2.6.1.2 Wiring NACs and IDCs for Class A .......................................................................................27
2.6.2: 4XTM Municipal Box Transmitter Option Module..........................................................................28
2.6.2.1 4XTM Transmitter Module Installation ..................................................................................29
2.7: ANN-BUS Devices .....................................................................................................................................30
2.7.1: ANN-BUS Wiring .............................................................................................................................30
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................30
2.7.1.2 Wiring Configuration ..............................................................................................................32
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................33
2.7.2: ANN-BUS Device Addressing..........................................................................................................33
2.7.3: ANN-80 Remote LCD Annunciator .................................................................................................34
2.7.4: Specifications ....................................................................................................................................34
2.7.5: Installation .........................................................................................................................................34
2.7.5.1 Mounting .................................................................................................................................34
2.7.5.2 Opening/Closing Annunciator ................................................................................................34
2.7.5.3 Wiring ANN-80 to FACP .......................................................................................................35
2.7.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................37
2.7.6.1 Specifications ..........................................................................................................................37
2.7.6.2 PRN-6 Printer Installation .......................................................................................................37
2.7.6.2.1 Connecting PRN-6 Printer ...................................................................................................38
2.7.6.2.2 Setting Printer Options .........................................................................................................38
2.7.7: ANN-I/O LED Driver Module ..........................................................................................................39
2.7.7.1 ANN-I/O Board Layout ..........................................................................................................39
2.7.7.2 Specifications ..........................................................................................................................39
2.7.7.3 ANN-I/O Connection to FACP ...............................................................................................40
2.7.7.4 ANN-I/O Module LED Wiring ...............................................................................................41
2.7.8: ANN-LED Annunciator Module.......................................................................................................41
2.7.8.1 ANN-LED Board Layout ........................................................................................................42
2.7.8.2 Specifications ..........................................................................................................................42
2.7.8.3 Mounting/Installation ..............................................................................................................42
2.7.8.4 ANN-LED Connection to FACP ............................................................................................43
2.7.9: ANN-RLY Relay Module..................................................................................................................44
2.7.9.1 ANN-RLY Board Layout ........................................................................................................44
2.7.9.2 Specifications ..........................................................................................................................44
2.7.9.3 Mounting/Installation ..............................................................................................................44
2.7.9.4 ANN-RLY Connection to FACP ............................................................................................45
SECTION 3: Programming ..................................................................................................................................46
3.1: User Programming.......................................................................................................................................46
4
PDRP-2001 Series P/N: 53043:A 5/08/07
Table of Contents
3.2: Initial Power-up ...........................................................................................................................................47
3.3: Programming Screens Description..............................................................................................................47
3.4: Programming and Passwords ......................................................................................................................48
3.5: Master Programming Level.........................................................................................................................49
3.5.1: FACP CONFIG (Application Templates) .........................................................................................50
3.5.2: Input Zones........................................................................................................................................50
3.5.3: Output Circuits ..................................................................................................................................57
3.5.3.1 Enabled ....................................................................................................................................58
3.5.3.2 Type ........................................................................................................................................58
3.5.3.2.1 Release Circuit 1 or Release Circuit 2 .................................................................................58
3.5.3.2.2 Release Stage NAC ..............................................................................................................59
3.5.3.3 Silence .....................................................................................................................................59
3.5.3.4 Auto Silence ............................................................................................................................60
3.5.3.5 Silence Inhibited .....................................................................................................................60
3.5.3.6 Coding .....................................................................................................................................61
3.5.3.6.1 Synchronized NAC Operation .............................................................................................62
3.5.4: Cross Input Zones .............................................................................................................................63
3.5.5: On-Board Relays...............................................................................................................................64
3.5.6: System Setup.....................................................................................................................................64
3.5.6.1 Timers ....................................................................................................................................65
3.5.6.1.1 Soak 1 or Soak 2 ..................................................................................................................66
3.5.6.1.2 Waterflow Delay ..................................................................................................................66
3.5.6.1.3 AC Loss Delay .....................................................................................................................67
3.5.6.2 Banner .....................................................................................................................................67
3.5.6.3 Time-Date ...............................................................................................................................68
3.5.6.3.1 Time .....................................................................................................................................69
3.5.6.3.2 Date ......................................................................................................................................69
3.5.6.3.3 Clock Format ........................................................................................................................69
3.5.6.3.4 Daylight Savings Time .........................................................................................................70
3.5.6.4 Trouble Reminder ...................................................................................................................70
3.5.6.5 Charger Disable .......................................................................................................................70
3.5.7: ANN-BUS .........................................................................................................................................71
3.5.7.1 ANN-BUS Enabled .................................................................................................................71
3.5.7.2 ANN-BUS Modules ................................................................................................................72
3.5.7.3 Auto-Configure .......................................................................................................................73
3.5.7.4 ANN-S/PG Options .................................................................................................................73
3.5.7.5 ANN-I/O LED Zone Assignments ..........................................................................................75
3.5.7.6 ANN-80 Options .....................................................................................................................76
3.5.7.7 ANN-RLY Options .................................................................................................................77
3.5.8: History...............................................................................................................................................78
3.5.8.1 View Events ............................................................................................................................78
3.5.8.2 Erase History ...........................................................................................................................78
3.5.9: Walktest.............................................................................................................................................79
3.5.10: Clear Program .................................................................................................................................80
3.5.11: Password Change ............................................................................................................................80
3.6: Maintenance Programming Level ...............................................................................................................81
3.6.1: Input Zones - Enable/Disable............................................................................................................82
3.6.2: History...............................................................................................................................................82
3.6.3: Walktest.............................................................................................................................................83
3.6.4: Time-Date..........................................................................................................................................84
SECTION 4: Operating Instructions ....................................................................................................................85
4.1: Panel Control Buttons .................................................................................................................................85
4.1.1: Acknowledge/Step ............................................................................................................................85
4.1.2: Alarm Silenced..................................................................................................................................85
4.1.3: Drill/Hold 2 Sec ................................................................................................................................85
PDRP-2001 Series P/N: 53043:A 5/08/07
5
Table of Contents
4.1.4: Reset ..................................................................................................................................................85
4.2: Indicators .....................................................................................................................................................86
4.3: Normal Operation........................................................................................................................................86
4.4: Trouble Operation........................................................................................................................................87
4.5: Alarm Operation..........................................................................................................................................88
4.6: Supervisory Operation.................................................................................................................................89
4.7: Disable/Enable Operation............................................................................................................................89
4.8: Waterflow Circuits Operation......................................................................................................................89
4.9: 2nd-Shot Water Switch................................................................................................................................90
4.10: Detector Functions.....................................................................................................................................90
4.11: Time Functions: Real-Time Clock.............................................................................................................90
4.12: Coded NAC Operation ..............................................................................................................................90
4.13: Release Stages ...........................................................................................................................................91
4.14: Special System Timers ..............................................................................................................................91
4.14.1: Silence Inhibit Timer.......................................................................................................................91
4.14.2: Autosilence Timer ...........................................................................................................................91
4.14.3: Trouble Reminder............................................................................................................................91
4.14.4: Soak Timers.....................................................................................................................................91
4.14.5: Waterflow Delay Timer ...................................................................................................................91
4.15: Walktest .....................................................................................................................................................91
4.16: Read Status ................................................................................................................................................92
4.16.1: FACP Configuration........................................................................................................................93
4.16.2: Input Zones......................................................................................................................................93
4.16.3: Output Circuits ................................................................................................................................94
4.16.4: Cross Input Zones............................................................................................................................94
4.16.5: On-Board Relays .............................................................................................................................95
4.16.6: System Settings ...............................................................................................................................95
4.16.7: Timers..............................................................................................................................................96
4.16.8: Daylight Savings .............................................................................................................................96
4.16.9: History .............................................................................................................................................97
4.16.10: ANN-S/PG ....................................................................................................................................97
4.16.11: ANN-BUS .....................................................................................................................................98
SECTION 5: Power Supply Calculations .............................................................................................................99
5.1: Overview .....................................................................................................................................................99
5.2: Calculating the AC Branch Circuit..............................................................................................................99
5.3: Calculating the System Current Draw.........................................................................................................100
5.3.1: Overview ...........................................................................................................................................100
5.3.2: How to Use Table 5-3 on page 101 to Calculate System Current Draw ...........................................100
5.4: Calculating the Battery Size ........................................................................................................................102
5.4.1: NFPA Battery Requirements .............................................................................................................102
5.4.2: Selecting and Locating Batteries.......................................................................................................102
APPENDIX A: Circuit Mapping and Cross-Zoning ..........................................................................................103
A.1: Input-to-Output Circuit Mapping and Cross-Zone Operation ...................................................................103
A.1.1: Mapping Input Zones to Output Circuits for Direct Activation ......................................................104
A.1.2: Mapping Input Zones to Release Circuits for Cross Zone
Activation ........................................................................................................................................105
A.1.3: Complex Examples of Cross Zoning and I/O Mapping for
Release Circuits ..............................................................................................................................107
APPENDIX B: FACP Configuration Templates ................................................................................................108
B.1: Template 7: Single Hazard - 3 Zone .........................................................................................................109
B.2: Template 8: Single Hazard - Cross-Zone With Manual Release ..............................................................110
B.3: Template 9: Dual Hazard - Combined Release ........................................................................................111
B.4: Template 10: Dual Hazard - Split Release ................................................................................................112
B.5: Template 11: Single Hazard - 3 Zones and Low Pressure ........................................................................113
6
PDRP-2001 Series P/N: 53043:A 5/08/07
Table of Contents
B.6: Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active ....................................................114
B.7: Template 13: Single Hazard - Dual Zone .................................................................................................115
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................116
C.1: NFPA 72 Auxiliary Fire Alarm System ....................................................................................................119
C.2: Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts ...........................................................................................................122
APPENDIX D: FACP with Keltron .....................................................................................................................123
APPENDIX E: Testing & Maintenance ..............................................................................................................124
E.1: Testing .......................................................................................................................................................124
E.1.1: Inspection .........................................................................................................................................124
E.1.2: Alarm Test .......................................................................................................................................124
5.4.3: Detector Testing ................................................................................................................................124
E.2: Maintenance ...............................................................................................................................................125
APPENDIX F: Compatible Devices .....................................................................................................................126
APPENDIX F: Compatible Two-Wire Smoke Detectors (UL Listed)...............................................................126
APPENDIX F: ...........................................................................................................................................126
APPENDIX F: Maximum Number of Detectors per Zone ................................................................................127
APPENDIX F: Four-Wire Smoke Detectors/Devices (UL Listed) ...................................................................128
APPENDIX F: Notification Appliances (UL Listed).........................................................................................129
•: System Sensor - 24VDC .........................................................................................................................129
•: Releasing Applications ...................................................................................................................................130
•: Door Holders (UL Listed) ..............................................................................................................................130
•: Relays (UL Listed) .........................................................................................................................................130
PDRP-2001 Series P/N: 53043:A 5/08/07
7
Notes
8
PDRP-2001 Series PN 53043:A 5/08/2007
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•
Underwriters Laboratories Standards
•
NFPA 72 National Fire Alarm Code
•
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 13 Installation of Sprinkler Systems
NFPA 15 Water Spray Fixed Systems
NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray Systems
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Documents
411UD Manual
411UDAC Manual
Document #50759
Document #51073
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
PDRP-2001 Series PN 53043:A 5/08/2007
9
10
+
polarized
strobe
4
3
Power Supply Connector J15
2
Nonresettable or Resettable Power
1
Jumper selectable by JP31, 24 VDC filtered,
power-limited, Class 2 (0.500 amps maximum)
Supervise with a power supervision relay
EOLR-1. Nonresettable Power suitable for
powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31 pins 2 & 3.
• Nonresettable Power - jumper JP31
pins 1 & 2 (as shown).
Resettable Power - 24 VDC filtered,
power-limited, Class 2 (0.500 amps
maximum) to smoke detectors (IDC).
Supervise with a power supervision
relay EOLR-1
+
-
+
-
Battery
BATTERY
- +
J12
RST/NONRST
AUXPWR
3
2
1
JP31
OUT2
RST AUX
PWR
OUT1
-
BB
+ 5 5
J2
QZ_
*
7 PRS
manual
release
0
#
9
_/.
MODE
ESC
CLEAR
2 ABC 3 DEF 1ST
AC POWER
8 TUV
TB7
+
+
+
-
OUT3
+
-
OUT4
+
ENTER
RESET
ALARM
TROUBLE
FIRE ALARM
DRILL
TB6
TB3
ANN-BUS
GND PWR A B
- +
JP24
TB8
JP30
J5
J4
J6
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
NO NC C NO NC C NO NC C
Alarm* Trouble* Supervisory*
(*Factory default relay programming)
A Fail Safe Trouble NO NC C
relay switches to the
NC position during
trouble conditions and
under loss of all power.
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
J7
- +
Normally
Open
Waterflow
Devices
or
Pressure
Switches
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
+ -
Output
B B Circuit #4 B B
+ + 3 3
6 6
Input IDC
Waterflow
Circuit #6
CAC5 Class A Converter Module
4 GHI 5 JKL 6
1
J3
+ - + - + - + - + -
+
B B
+ 1 1
-
+
B B
+ 3 3
heat
detector
Normally
Open
Tamper
or
Pressure
Switches
Input IDC
Supervisory
Circuit #5
B B B B
+ - + 1 1 2 2
TB4
Output
Circuit #2
Releasing
pull
station
smoke
detector
Input IDC
Circuit #1
24 VDC, supervised,
nonpower-limited
26 Amp Hour maximum
J15
TB9
TB5
polarized +
horn
+
polarized
bell
Nonsupervised, power-limited circuits (Class 2)
Supervise with a power supervision relay EOLR-1
Special Application
DC Power Outputs (24 VDC)
Important! Removing Ground Fault
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
Output Circuits - TB5 & TB7
OUT
A A
+ 1 1
TB4/
TB6
A A
+ 1 1
J2
TB1
TB5
-
OUT1
+
-
OUT2
+
B B
+ 2 2
Releasing Circuit
(Supervised, Power-Limited, Class 2)
REL-4.7K
CAC5
Class A Converter Module
OUT
OUT2/4
2
Unused
Output Circuit
4.7K dummy load
P/N 71245
TB2
OUT1/3
A A
+ 1 1
A A
+ 1 1
TB5/
TB7
+
+
+
Style D (Class A) IDC
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
Style Z (Class A) NAC
Special Application Power
In this example NAC Output Circuits #1, #3 & #4, Style Y (Class B) (Supervised, Power Limited - Class 2)
NAC Output Circuit #2 (Releasing) is Style Y (Class B) (Supervised, NonPower-Limited, Class 1)
3.0 amps max. per circuit. (See Style Z illustrated near right edge of board).
Input Initiating Device Circuit - TB4 & TB6
4.7K , ½ watt End-of-Line Resistor PN 71252
IDCs 1 through 6, Style B (Class B) (Supervised, Power Limited, Class 2)
Output
Output
(See Style D illustrated near right edge of board).
Circuit #3
Circuit #1
4.7K , ½ watt End-of-Line Resistor PN 71252
NAC
NAC
4XTM OPT BD
Basic System Connections
Main Circuit Board
PDRP-2001 Series PN 53043:A 5/08/2007
Product Features
Product Description
Product Description
SECTION 1
The PDRP-2001 is a six zone FACP for single and dual hazard deluge and preaction applications.
The FACP provides reliable fire detection, signaling and protection for commercial, industrial and
institutional buildings requiring water-based releasing. The FACP is compatible with System
Sensor’s i3 detectors which are conventional smoke detectors that can transmit a maintenance
trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when
the ambient temperature falls below the detector rating of approximately 45o F (refer to System
Sensor for i3 Installation and Maintenance Instructions). In addition, the control panel is
compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke
detectors, pull stations, waterflow devices, tamper switches and other normally-open contact
devices. Refer to Device Compatibility Appendix for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids.
Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory)
and 24 VDC special application resettable and nonresettable power outputs are also included on the
main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicator, display alarm information on
the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate
an optional module used to notify a remote station or initiate an auxiliary control function.
The PDRP-2001E offers the same features as the PDRP-2001 but allows connection to 220/240
VAC. Unless otherwise specified, the information in this manual applies to both the 110/120 VAC
and 220/240 VAC versions of the panels.
1.1 Product Features
•
Six programmable Style B (Class B) IDCs (Initiating Device Circuit)
•
Four programmable Style Y (Class B) output circuits - (special application power)
•
Three programmable Form-C relays
•
7.0 amps total 24 VDC output current
•
Resettable and non-resettable output power
•
Built-in Programmer
•
ANN-BUS for connection to optional:
ANN-80 Remote LCD Annunciator
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Relay Module
ANN-LED Annunciator Module
•
80-character LCD display (backlit)
•
Real-time clock/calendar with daylight savings time control
•
History log with 256 event storage
PDRP-2001 Series PN 53043:A 5/08/2007
11
Product Description
Product Features
•
Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
•
Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Discharge
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Outputs Programmable for:
Releasing Solenoids
NACs programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
Release Stage Sounder
12
•
Designed for sprinkler standards NFPA 13, 15 and 16
•
Disable/Enable control per input zone and output zone
•
Extensive transient protection
•
Dual hazard operation
•
Adjustable waterflow discharge timer and two soak timers
•
Cross-zone (double-interlock) capability
•
Pre-programmed and custom application templates
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional Dress Panel DP-51050 (red)
•
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
•
Optional CAC-5X Class A Converter Module for Outputs and IDCs
•
Optional 4XTM Municipal Box Transmitter Module
•
Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
PDRP-2001 Series PN 53043:A 5/08/2007
Specifications
Product Description
1.2 Specifications
AC Power
PDRP-2001: 120 VAC, 60 Hz, 3.66 amps
PDRP-2001E: 240 VAC, 50 Hz, 2.085 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed
in the FACP cabinet.Larger batteries require separate battery box such as the BB-26 or BB-55)
Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 and TB6
Alarm Zones 1 - 5 on TB 4
Alarm Zone 6 on TB6
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to the Device Compatibility Appendix for listed compatible devices
Notification Appliance and Releasing Circuit(s) - TB5 and TB71
Four Output Circuits
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 1.5 VDC
Refer to the Device Compatibility Appendix for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Relay Contact Ratings: 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive)
Auxiliary Trouble Input
The Auxiliary Trouble Input is an open collector, unsupervised circuit which can be used to
monitor external devices for trouble conditions. It can be connected to the trouble bus of a
peripheral, such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to the Device Compatibility Appendix for compatible listed devices
1. Total current for resettable power, nonresettable power and Output Circuits must not exceed
7.0 amps.
PDRP-2001 Series PN 53043:A 5/08/2007
13
Product Description
Controls and Indicators
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Appendix for compatible listed devices
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED
backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED
backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
Acknowledge/Step
•
Alarm Silence
•
Drill
•
System Reset (lamp test)
14
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 (recall) key
•
1st Event key
•
Clear key
•
Escape key
•
Mode key
•
Four cursor keys (up, down, left and right)
•
Enter key
MRP2001kypd.cdr
Service/program keys:
Figure 1.1 Membrane/Display Panel
PDRP-2001 Series PN 53043:A 5/08/2007
Components
Product Description
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory
conditions.
Indicators
Indicators are provided to annunciate the following conditions:
•
Fire Alarm - red indicator
•
Supervisory - yellow indicator
•
AC Power - green indicator
•
System Trouble - yellow indicator
•
Alarm Silence - yellow indicator
•
Discharge - red indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse ½ second on and ½ second off
•
Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring
interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available is an optional dress panel (DP-51050
[red] and supplied standard with Canadian versions only, DP-51050LED for mounting ANN-LED
annunciator modules) which mounts inside the cabinet and also trim-ring (TR-CE [red]).
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the . Batteries must be ordered separately.
PDRP-2001 Series PN 53043:A 5/08/2007
15
Product Description
Optional Modules and Accessories
1.5 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required
to convert all six Output Circuits and four Initiating Device Circuits.
4XTM Transmitter Module
The 4XTM provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTM mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator that mimics the information displayed on the FACP
LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module mounts in the DP-51050LED Dress Panel and provides three
LEDs for each zone: Alarm, Trouble and Supervisory.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
Dress Panel
A dress panel DP-51050 (red) is available as an option. The dress panel restricts access to the
system wiring while allowing access to the membrane switch panel.
DP-51050LED Dress Panel
A DP-51050LED dress panel is provided standard only with Canadian versions of the FACP. The
dress panel restricts access to the system wiring while allowing access to the membrane switch
panel. It also allows the installation of an optional ANN-LED annunciator module.
TR-CE Trim-ring
A trim-ring TR-CE (red) is available as an option. The trim-ring allows semi-flush mounting of the
cabinet.
Battery Box
The battery box may be used to house two batteries greater than 18 Amp Hour. The battery box
mounts directly below the control panel cabinet, centered to the main circuit board.
16
PDRP-2001 Series PN 53043:A 5/08/2007
Backbox Mounting
Installation
Installation
SECTION 2
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the
installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots
at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures or levels of humidity are not encountered. The area
should be readily accessible with sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the
left. Determine the number of conductors required for the devices to be installed. Sufficient
knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the
conductors into the box. All wiring should be in accordance with the National and/or Local codes
for fire alarm systems.
2.1 Backbox Mounting
!
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist
strap before handling any boards so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis
assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 18
Install center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” on-center stud mounting
Install remaining fasteners and tighten
Board on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
Backbox
5UDBRDINBOX.CDR
grounding stud:
attach solid earth
ground wire (refer to
Figure 2.4 on page 20)
mounting tabs
Figure 2.1 Chassis Mounting in Backbox
PDRP-2001 Series PN 53043:A 5/08/2007
17
Installation
Backbox Mounting
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
avoid covering venting
holes on top of box.
Hinge Slot for
optional Dress Panel
Mounting
slots for
optional
Trim Ring
Semi-Flush
mounting hole
9050UDencl.cdr
Hinge Slot for optional
Dress Panel
Figure 2.2 Cabinet Dimensions
18
PDRP-2001 Series PN 53043:A 5/08/2007
Installation
9050udcab.cdr
Backbox Mounting
Figure 2.3 Backbox
PDRP-2001 Series PN 53043:A 5/08/2007
19
Installation
Operating Power
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the
panel is 120 VAC, 60 Hz, 3.66 amps for the PDRP-2001 or 240 VAC, 50 HZ, 2.085 amps for the
PDRP-2001E. Run a pair of wires (with ground conductor) from the protected premises main
breaker box to the AC terminal block TB1 on the main power supply. As per the National
Electrical Code, use 14 AWG (2.00 mm2, 1.6 mm O.D.) or heavier gauge wire with 600V
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be
provided with overcurrent protection and may not contain any power disconnect devices. A
separate Earth Ground connection must be made to ensure proper panel operation and lightning and
transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm2)] to the
grounding stud in the backbox. Do not use conduit for the Earth Ground connection since this does
not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
!
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
120 VAC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
-
+
rp2001powr.cdr
Batteries
Figure 2.4 Operating Power Connections
20
PDRP-2001 Series PN 53043:A 5/08/2007
Input Circuits
Installation
2.3 Input Circuits
The PDRP-2001 has six programmable IDCs (Initiating Device Circuits). Each circuit is
compatible with System Sensor’s i3 smoke detectors which generate a maintenance signal when the
detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls
below the detector rating of approximately 45oF. The maximum loop resistance limit for each IDC
is 100 ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is
supervised for opens, shorts and ground faults. All conditions are visually and audibly
annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Device Compatibility Appendix for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
UL listed Power Supervision Relay
(refer to Device Compatibility Appendix for list of compatible relays)
UL listed compatible 4-wire smoke detector
manual pull stations
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
manual
release
heat detectors
Input IDC
Waterflow Circuit
Normally Open
Waterflow
Devices or
Pressure Switches
mrp-2001idc.cdr
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Figure 2.5 IDC Connections
PDRP-2001 Series PN 53043:A 5/08/2007
21
Installation
Input Circuits
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
ms10udcomboIDC.cdr
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the InLine Resistor as shown in Figure 2.6
Program the FACP Initiating Device Circuit as a Combination circuit as described in
"Input Zones" on page 50. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to
"Waterflow Delay" on page 66.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition
is cleared) if the Combo Autoresettable Supervisory type code is selected
22
PDRP-2001 Series PN 53043:A 5/08/2007
Output Circuits
Installation
2.4 Output Circuits
2.4.1 Outputs/Notification Appliance/Releasing Circuits
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and
provides special application power. Refer to the Device Compatibility Appendix for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter
module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Polarized Bell
Polarized Bell
Polarized Strobe
Polarized Strobe
Polarized Horn
Polarized Horn
Releasing Solenoid
Dummy load any unused
circuits (P/N: 71245)
Notification Appliance Circuits
polarity shown in alarm condition
+
- +
Ferrite Bead
P/N 29150
-
+
- +
-
rp2001nac.cdr
Ferrite Beads
P/N 29150
Note: Short Circuit Supervision must be enabled when using the
REL-4.7K for Canadian Applications. Refer to the section titled
"Release Circuit 1 or Release Circuit 2" on page 58 for information
on enabling short circuit supervision.
Ferrite Bead (P/N 29150)
Large gauge wire
should be looped
through bead at least
once as illustrated.
Smaller gauge wire can
be looped more often.
Ferrite Bead in open position
Ferrite Bead in closed position
Figure 2.7 NAC/Output Connections
PDRP-2001 Series PN 53043:A 5/08/2007
23
Installation
Output Circuits
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the PDRP-2001
control panel.
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be
obtained from these terminals (power-limited)
•
Jumper JP31 pins 1 & 2 for nonresettable power (as
illustrated in figure to right)
•
Jumper JP31 pins 2 & 3 for resettable power
- 4
+ 3
- 2
+ 1
ms-10UDtb9.cdr
Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The PDRP-2001control panel provides a factory default programmed alarm relay, fail-safe trouble
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer
to "On-Board Relays" on page 64). Each Form-C relay is rated for 2 amps @ 30VDC (resistive)
and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
ms10udrelay.cdr
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
Figure 2.9 Relay Terminals
24
PDRP-2001 Series PN 53043:A 5/08/2007
Power-limited Wiring Requirements
Installation
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent
to a releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Nonpower-limited Circuits*
Power-limited Circuits
(Class 2)
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
CAC-5X
CAC-5X
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
4XTM
Nonpowerlimited
Circuit
earth
ground
Nonpowerlimited
Circuit
Power-limited
Circuit
(Class 2)
RP2001ULwire.cdr
Deluge - Preaction Control FACP
Figure 2.10 Typical UL Power-limited Wiring Requirements
PDRP-2001 Series PN 53043:A 5/08/2007
25
Installation
Installation of Optional Modules
2.6 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.6.1 CAC-5X Class A Converter Module
2.6.1.1 Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Two CAC-5X Modules are required to convert all Output Circuits and/or Initiating
Device Circuits to Class A. The modules plug into connector J2 which is located at the top left
of the main circuit board and J7 which is located at the top center of the main circuit board.
To install the CAC-5X, remove the two main circuit board mounting screws referenced in the
following illustration and replace with the two supplied male/female standoffs in the locations
indicated in the following figure. Carefully align the connector on the CAC-5X with J2 on the
FACP main circuit board and press the module securely into place. Make certain the pins are
properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to
the standoffs with the screws that were just removed.
To install the second CAC-5X on J7, remove the main circuit board mounting screw referenced
in the following illustration and replace with the supplied male/female standoff. Insert the
supplied plastic standoff in the location indicated in the following illustration. Carefully align
the connector on the CAC-5X with J7 and press the module securely into place. Make certain
the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the
CAC-5X to the metal standoff with the screw that was just removed.
Installation on J7 Connector
Installation on J2 Connector
CAC-5X Module
CAC-5X Module
Metal
Standoff
Metal
Standoff
Plastic
Standoff
rp2001cac5mnt.cdr
Metal
Standoff
Main Circuit Board
Figure 2.11 CAC-5X Module Installation
26
PDRP-2001 Series PN 53043:A 5/08/2007
Installation of Optional Modules
Installation
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit
board and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits
using TB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will
be identical when using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity
when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed
and return for the positive side of a device and the B- and A- terminals must comprise the feed
and return for the negative side of a device. To configure any of the zones for Class B when the
CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the
End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+
and A- terminals on the CAC-5X module.
Class B (Style B) IDC - 4.7 KΩ
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Class A (Style D) IDC
(supervised and power-limited)
Smoke
Smoke
Pull Station
Pull Station
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Bell
Polarized
Strobe
Heat
Heat
Polarized
Horn
Ferrite Bead
P/N 29150
Circuit polarities
shown in alarm
condition
B+
B-
B+
B+ B- B+ B- B+ B- B+ B- B+ B-
B-
Dummy load all unused
circuits - 4.7 KΩ
½ watt ELR resistor
(P/N: 71245)
FACP Main
Circuit Board
A-
A+
A-
A+
A- A+ A- A+ A- A+ A- A+ A-
ms10udclassa.cdr
A+
Large gauge wire should be looped through
bead at least once as illustrated. Smaller
gauge wire can be looped more often.
Ferrite Bead in open position
2550ferr.cdr
CAC-5X Class A Converter Module
Ferrite Bead in closed position
Figure 2.12 Wiring NACs and IDCs for Class A Operation
PDRP-2001 Series PN 53043:A 5/08/2007
27
Installation
Installation of Optional Modules
2.6.2 4XTM Municipal Box Transmitter Option Module
The 4XTM module can be plugged into connectors J4 and J5 on the main circuit board.
The following steps must be followed when installing the 4XTM module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the
placement of the 4XTM option module
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide
the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP
main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in
the following sections
7. Test system for proper operation
Standoffs
J4
rp2001bord.cdr
J5
Figure 2.13 4XTM Option Module Connection
28
PDRP-2001 Series PN 53043:A 5/08/2007
Installation of Optional Modules
Installation
2.6.2.1 4XTM Transmitter Module Installation
The 4XTM provides a supervised output for a local energy municipal box transmitter in
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. A disable switch
allows disabling of the transmitter output during testing to prevent accidental calling of the
monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble indicator will turn on
to indicate the Disconnect condition.
Note: 4XTM Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application using reverse polarity of a supervisory signal,
refer to the Appendix titled "FACP with Keltron" on page 123.
Polarities are shown for module activation
TB1
1+
23+
45
6+
7-
TBL Jumper
}Municipal Box (nonpower-limited)*
4xtmf.cdr
J1
J2
No connection
* Wiring from these terminals can
exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
TBL
Disconnect
Switch
shown in
disconnect
position
}Remote Alarm (power-limited)*
}Remote Trouble (power-limited)*
Disconnect LED
Connect to FACP Connectors J4 & J5
Figure 2.14 4XTM Transmitter Module
PDRP-2001 Series PN 53043:A 5/08/2007
29
Installation
ANN-BUS Devices
2.7 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.
Compatible devices include:
•
ANN-80 LCD Annunciator
•
ANN-S/PG Serial/Parallel Printer Interface Module
•
ANN-I/O LED Driver Module
•
ANN-LED Annunciator Module (annunciates alarms, troubles and supervisories)
•
ANN-RLY Relay Module
2.7.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor
bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table:
Model Number
Worst Case Current Draw
ANN-80 LCD Annunciator
0.040 amps
ANN-S/PG Serial/Parallel Printer Interface Module
0.040 amps
ANN-I/O LED Driver Module
0.200 amps
ANN-LED Annunciator Module
0.068 amps
ANN-RLY Relay Module
0.075 amps
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
30
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance
the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more
than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is
shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case Current
Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1,852 ft.
4,688 ft.
* 6,000 ft.
*6,000 ft.
0.200
926 ft.
2,344 ft.
3,731 ft.
5,906 ft.
0.300
617 ft.
1,563 ft.
2,488 ft.
3,937 ft.
0.400
463 ft.
1,172 ft.
1,866 ft.
2,953 ft.
0.500
370 ft.
938 ft.
1,493 ft.
2,362 ft.
Table 2.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms)
=
6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)
(6,000 feet maximum)
=
Maximum Resistance (Ohms)
Rpu
*500
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge
22
18
16
14
Ohms per 1,000 feet (Rpu)
16.2
6.4
4.02
2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring
limitations:
Wire Gauge
18
16
14
12
PDRP-2001 Series PN 53043:A 5/08/2007
Maximum Wire Length
312 feet
497 feet
787 feet
1,250 feet
31
Installation
ANN-BUS Devices
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
•
2 ANN-80 Remote LCD Annunciators
•
1 ANN-S/PG Serial/Parallel Printer Interface Module
•
1 ANN-I/O LED Driver Module
The total worst case current is calculated as follows:
ANN-80 Current Draw
= 2 X 0.040 amps
= 0.080 amps
ANN-S/PG Current Draw
= 1 X.0.040 amps
= 0.040 amps
ANN-I/O Current Draw
= 1 X.0.200 amps
= 0.200 amps
Total Worst Case Current Draw
= 0.320 amps
Using this value and referring to the Wiring Distance Table 2.1 on page 31, it can be found that
the available options are:
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
2.7.1.2 Wiring Configuration
Figure 2.15 illustrates the wiring between the FACP and ANN-BUS devices.
FACP
TB3
aan80toRP2001.cdr
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.15 FACP wiring to ANN-BUS Device
32
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.16 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24S6/8, when the maximum number of ANN-BUS devices exceeds the ANN-BUS
power requirements.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
FACP
ANN-BUS
-24 VDC
ANN-80
+24 VDC
ann80toFCPSrp2001.cdr
ANN-BUS and power wiring are
supervised and power-limited
FCPS-24S6/8
Figure 2.16 Powering ANN-BUS Devices from FCPS-24S6/8
2.7.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 71).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and
above must be set to OFF.
Address
not valid
01
02
03
04
05
06
07
08
PDRP-2001 Series PN 53043:A 5/08/2007
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Switch 3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Switch 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
33
Installation
ANN-BUS Devices
2.7.3 ANN-80 Remote LCD Annunciator
The ANN-80 LCD Annunciator is a compact, 80 character, backlit LCD remote fire annunciator
which mimics the FACP display. It also provides system status indicators for AC Power, Alarm,
Trouble, Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication
format. The devices are powered, via two additional wires, from either the host FACP or remote
UL-listed, filtered, power supply.
2.7.4 Specifications
•
Operating Voltage Range: 18 VDC to 28 VDC
•
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail (not backlit): 15.0 mA
•
For use indoors in a dry location
2.7.5 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.
2.7.5.1 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical
box. Select and remove the appropriate knockout(s), pull the necessary wires through the
knockouts and mount the annunciator in or on the wall depending on the type of installation
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the
annunciator has been mounted.
2.7.5.2 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover with LCD display
Annunciator backplate
Press in latch and pull
annunciator cover open
Key switch shown in ON position
34
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.5.3 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1
terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2
(+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box
PDRP-2001 Series PN 53043:A 5/08/2007
35
Installation
ANN-BUS Devices
FACP
TB3
4 3 2 1
ann80 torp2001.cdr
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.17 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the FACP.
FACP (TB3)
Terminal 4 GND (-)
Terminal 3 PWR (+)
Terminal 2 A (ANN-BUS)
Terminal 1 B (ANN-BUS)
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD
option for programming.
36
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.6 ANN-S/PG Serial/Parallel Printer Interface Installation
The ANN-S/PG Serial/Parallel Interface module allows the ancillary connection of a serial or
parallel printer to the FACP for a real-time log of system events, detector status reports and event
history. Note that either a serial or parallel printer may be installed, not both. Proceed with the
installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.18
TB3
FACP
ANN-S/PG Module
Cable
Connectors for
connection to
printer
Serial
Figure 2.18 ANN-S/PG Connection to FACP
annSPGrp2001.cdr
Parallel
ANN-BUS and power wiring are
supervised and power-limited
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number
(address) to the module
4. Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to "ANN-BUS" on page 71)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 73)
5. Connect a printer to the ANN-S/PG Parallel or Serial connector (refer to Figure 2.18 on page
37)
2.7.6.1 Specifications
•
Operating Voltage: 24 VDC
•
Current (Alarm and Standby): 45 mA
•
Ambient Temperature: 32oF to 120oF (0oC to 49oC)
•
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•
Mounting: Surface
•
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•
For indoor use in a dry location only
2.7.6.2 PRN-6 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6 prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer
options.
PDRP-2001 Series PN 53043:A 5/08/2007
37
Installation
ANN-BUS Devices
2.7.6.2.1 Connecting PRN-6 Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.
2.7.6.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Table 2.2 PRN-6 Setup Options
Option
Font
LPI
ESC Character
Bidirectional Copy
CG-TAB
Country
Auto CR
Color Option
Formien
Lines
Standard
38
Setting
HS Draft
6 LPI
ESC
ON
Graphic
E-US ASCII
OFF
Not Installed
6LPI=60
Exec 10.5
Option
CPI
Skip
Emulate
I/O
Buffer
Serial
Baud
Format
Protocol
Character Set
SI.Zero
Auto LF
PAPER
BIN 1
BIN 2
SINGLE
PUSH TRA
PULL TRA
PAP ROLL
Setting
10CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard
On
On
12/72”
12/72”
12/72”
12/72”
12/72”
12/72”
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.7 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section titled "ANNBUS" on page 71 for programming information.
2.7.7.1 ANN-I/O Board Layout
Figure 2.19 illustrates the ANN-I/O board showing locations of screw terminals for connection
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANNBUS ID number.
Terminals not used (future)
ANN-BUS (ID#)
Address DIP
switch
ANN-BUS Connector
Figure 2.19 ANN-I/O Board Layout
2.7.7.2 Specifications
•
Max. ANN-BUS Voltage: 28 VDC
•
Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
•
Operating Temperature: 32oF to 120oF (0oC to 49oC)
•
For indoor use in a dry location only
PDRP-2001 Series PN 53043:A 5/08/2007
39
Installation
ANN-BUS Devices
TB3
FACP
ANN-I/O Module
ann-IOtorp2001.cdr
2.7.7.3 ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.20. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.
ANN-BUS and power wiring are
supervised and power-limited
Figure 2.20 ANN-I/O Connection to FACP
40
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.7.4 ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized
so that there is approximately 10 mA of current for each LED. No series resistors are required.
LED outputs are mapped to output circuits. Refer to the section titled "ANN-I/O LED Zone
Assignments" on page 75 of this manual.
The LEDs are wired as illustrated in Figure 2.21. Note that the illustration depicts only
connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
Figure 2.21 ANN-I/O Board Layout
2.7.8 ANN-LED Annunciator Module
The ANN-LED annunciator modules provide LED annunciation of general system faults and input
zones when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble
(yellow) and supervisory (yellow) indication for up to ten input zones.
PDRP-2001 Series PN 53043:A 5/08/2007
41
Installation
ANN-BUS Devices
2.7.8.1 ANN-LED Board Layout
Figure 2.22 illustrates the ANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.22 ANN-LED Board Layout
2.7.8.2 Specifications
•
Max. ANN-BUS Voltage: 24 VDC
•
Max. Current:
Alarm: 68 mA
Standby: 28 mA
•
Operating Temperature: 32o F to 120o F (0o C to 49o C)
•
For indoor use in a dry location only
2.7.8.3 Mounting/Installation
Install the ANN-LED Module as described in the documentation supplied with the annunciator.
42
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.8.4 ANN-LED Connection to FACP
Figure 2.23 illustrates the ANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
FACP
ANN-LED
-24 VDC
+24 VDC
ANN-BUS
Figure 2.23 ANN-LED Connection to FACP
PDRP-2001 Series PN 53043:A 5/08/2007
43
Installation
ANN-BUS Devices
2.7.9 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
2.7.9.1 ANN-RLY Board Layout
Figure 2.22 illustrates the ANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.24 ANN-RLY Board Layout
2.7.9.2 Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Relay Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•
Operating Temperature: 32o F to 120o F (0o C to 49o C)
•
For indoor use in a dry location only
2.7.9.3 Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
44
PDRP-2001 Series PN 53043:A 5/08/2007
ANN-BUS Devices
Installation
2.7.9.4 ANN-RLY Connection to FACP
Figure 2.23 illustrates the ANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
FACP
ANN-RLY
-24 VDC
+24 VDC
ANN-BUS
Figure 2.25 ANN-RLY Connection to FACP
PDRP-2001 Series PN 53043:A 5/08/2007
45
Programming
User Programming
Programming
SECTION 3
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited
to specific values or not used at all as indicated below.
Program feature or option
Permitted in UL 864? (Y/N)
Possible settings
Settings permitted in UL 864
ANN-80 Lock Enable
Y
Lock Enable Yes
Lock Enable No
Refer to Lock Enable in
"ANN-80 Options" on page 76
Lock Enable Yes
3.1 User Programming
!!
The FACP is completely field programmable using the panel keypad and requires no special
software skills. While programming the FACP, the fire protection capabilities of the control panel
are enabled.
Program Templates have been provided to allow the panel to be quickly programmed with typical
job-site configurations. Refer to "Circuit Mapping and Cross-Zoning" on page 103 for an
explanation of mapping and cross-zoning and "FACP Configuration Templates" on page 108 for a
detailed description of each template.
Site-specific programming may be accomplished:
•
by Manual programming or editing, using the FACP keypad
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
SYSTEM ALL NORMAL
10:00A 092105
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
The exception to this is the programmer/operator can access Programming mode if the supervisory
is due to the Disable Release event. Refer to Table 3.1 on page 52.
To access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
WATER RELEASE PANEL
1=READ STATUS MODE
2=PROGRAMMING MODE
See Page
46
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 92 for a
detailed description of this feature.
PDRP-2001 Series PN 53043:A 5/08/2007
Initial Power-up
Programming
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Note that the data which is entered during Programming mode
is automatically saved by the panel as soon as the data is entered. If the Reset key is pressed or
power is lost before exiting Programming mode, all data just entered will not be lost.
User Programming Levels
There are two user programming levels:
•
•
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.2 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.
OPEN
PULL STATION
ZONE 1 OPEN FAULT
09:03A 012106
3.3 Programming Screens Description
See Page
Two options are available when the Enter key is pressed: Read Status and Programming Mode.
The Read Status and Programming options have multiple functions or features which may be
chosen. To view all of the choices, it is necessary that the programmer scroll through a number of
additional subscreens. These selections are displayed on multiple screens to make them more
readable for the programmer. Refer to "Master Programming Level" on page 49, for additional
information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
PDRP-2001 Series PN 53043:A 5/08/2007
47
Programming
Programming and Passwords
3.4 Programming and Passwords
See Page
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 80. If an invalid password is entered, the blinking cursor will return to
the first password character position. To exit Programming or Read Status mode at any time, press
the ESC (Escape) key repeatedly. Note that as soon as program data is entered, the data is
automatically saved by the panel. If the Reset key is pressed or power is lost before exiting
Programming mode, the data just entered will not be lost.
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
1=READ STATUS MODE
2=PROGRAMMING MODE
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
*****
Entering the Master level password (default 00000) will cause the following screen to appear:
PROGRAMMING
1=FACP CONFIG
T5
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
If the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
48
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble indicator flashes until Programming mode is exited. The following display will
appear:
PROGRAMMING
1=FACP CONFIG
T7
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
Programming Screen #2
PROGRAMMING
1=ANN-BUS
2=HISTORY 256 EVENTS
3=WALKTEST
Programming Screen #3
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4
PDRP-2001 Series PN 53043:A 5/08/2007
49
Programming
Master Programming Level
3.5.1 FACP CONFIG (Application Templates)
For a detailed description of each Template, refer to "FACP Configuration Templates" on page
108. The FACP Configuration option allows the user to program the FACP with one of seven
factory preprogrammed templates or one custom template which can be programmed by the user.
The templates have been provided to allow the user to quickly program the panel with typical jobsite configurations. The user may choose to select one of the templates or bypass this option,
proceeding to the next sections which detail customized programming of the FACP.
PROGRAMMING
1=FACP CONFIG USER
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
A factory template may be chosen and later changed to better fit a site requirement. The changed
template can be saved as the one custom template.
Pressing 1, while viewing Programming Screen #1, will select the FACP Config option and display
the following screen:
FACP CONFIG
1=N/A
2=N/A
3=N/A
FACP Config Screen #1
Pressing the down arrow key will display screens for additional Templates and the Custom
Template. During initialization of the panel following power-up or reset, the selected Template will
be displayed by the LCD.
Note: Only Templates 7 through 13 are available for the PDRP-2001 Pre-Action/Deluge Control
Panel.
To select a pre-programmed templates, press the number key corresponding to the desired template.
Note that the factory templates may pre-set most programmable features of the FACP.
3.5.2 Input Zones
The Input Zones option allows the user to initially program or change the programming for the six
input zones (circuits). Pressing 2, while viewing Programming Screen #1, will select the Input
Zones option and display a screen similar to the following:
INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
Input Zone Screen #1
Pressing the down arrow key will display additional screens for Input Zones 4 through 6. To
program a specific zone, press the number key corresponding to the desired zone while viewing one
of the Input Zone screens.
To program Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following
screens will be displayed:
INPUT ZONE 1
Normal PULL STATION
PRESS
TO EDIT
Edit Input Zone Screen #1
50
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to
view the Edit Zone screens.
The following examples show the editing of Input Zone 1:
INPUT ZONE 1
1=ENABLED
YES
2=TYPE PULL STATION
3=OUTPUT CIRCUIT MAP
Edit Input Zone Screen #2
INPUT ZONE 1
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Input Zone Screen #3
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled
No is selected, the zone will be disabled by the control panel, preventing the circuit from
reporting alarms and troubles to the panel. The control panel LCD will display the zone which
has been disabled and FACP will turn on the Trouble indicator.
INPUT ZONE
1=ENABLED
2=TYPE
3=OUTPUT CIRCUIT MAP
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
Edit Input Zone Screen #2
ZONE 1 TYPE
1=PULL STATION
2=N/A
3=MANUAL RELEASE
Zone Type Screen #1
PDRP-2001 Series PN 53043:A 5/08/2007
51
Programming
Master Programming Level
Pressing the down arrow key displays additional zone types as indicated in the following table.
Table 3.1 Zone Types
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Manual Release
Fire Alarm
Normally Open Contact
Fire
1
N/A
N/A
Waterflow
Fire
Waterflow NS (nonsilenceable)
Fire, nonsilenceable
Combo
Fire/Supervisory
Combo w/AutoResettable Superv
Fire/Supervisory, nonlatching
2-Wire Smoke
Fire Alarm
2
2-Wire Heat
Fire Alarm
Linear Heat
Fire Alarm
N/A
N/A
Fire
Fire Alarm
Low Pressure
Supervisory, latching
Low Pressure AutoResettable2
Supervisory, nonlatching
High Pressure
High Pressure AutoResettable
Supervisory
2
Supervisory, nonlatching
Disable Release3
Supervisory, nonlatching (disables Release Circuits)
Supervisory
Supervisory, latching
Supervisory
AutoResettable2
Supervisory, nonlatching
N/A
2nd-Shot Water Switch4
Fire Alarm, nonlatching
Table Footnote
1. Activation of a Manual Release Switch will override Predischarge Delay,
resulting in an immediate water release.
2. AutoResettable means that a device with this type code, when activated, will
automatically reset when the corresponding condition is cleared.
3. Disable Release allows the installer to disable the releasing solenoids during
system testing. Disable Release will only work when the system is not in alarm.
4. The 2nd-Shot Water Switch provides the option of performing another immediate
water release manually. Refer to "2nd-Shot Water Switch" on page 90.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
52
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
Output Circuit MAP
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits
that will be activated when a particular Input Zone or cross-zoned releasing group goes active.
Pressing 3 for Output Circuit Map while viewing Edit Input Zone Screen #2 will display
screens which show the Output Circuits programmed to activate when the selected Input Zone
(or cross-zoned releasing group) is activated. Output Map Screen #1 displays the Output Type
Codes and programming for Output Circuits 1 through 3 and Output Map Screen #2 displays
the Output Type Code and programming for Output Circuit 4.
INPUT ZONE #
1=ENABLED
2=TYPE
3=OUTPUT CIRCUIT MAP
As an example, if Template 7 has been selected as the FACP Configuration [refer to "FACP
CONFIG (Application Templates)" on page 50], selecting the Output Circuit Map for Input
Zone 1 will display the following screens:
Edit Input Zone Screen #2
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=WATERFLOW NAC
NO
3=RELEASE 1
YES
Output Map Screen#1
OUTPUT MAP ZONE 1
4=SUPV BELL NAC
N/A
Output Zone Screen#2
The screens indicate that when Input Zone 1 is activated:
Output Circuit #1 default programmed as Alarm NAC will activate (Yes)
Output Circuit #2 default programmed as Waterflow NAC will not activate (No)
Output Circuit #3 default programmed as Release 1 will activate (Yes)
Output Circuit #4 default programmed as Supv Bell NAC is not mapped (N/A)
Note that the MAP may indicate that an Input Zone is programmed to a particular Output
Circuit but, if it is cross-zoned with one or more other Input Zones, all must be active in order to
activate the Output Circuit. Refer to the examples in "Circuit Mapping and Cross-Zoning" on
page 103.
The Output Circuit Map can be customized by selecting or deselecting any of the four output
circuits for activation. Pressing the number key corresponding to the selected output will toggle
the display between Yes for activation by the Input Zone to No for no activation. The new
customized programming is automatically saved by the panel as soon as it is entered.
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Input Zone Screen #3
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #3 will
cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
Noun/Adjective Screen
PDRP-2001 Series PN 53043:A 5/08/2007
53
Programming
Master Programming Level
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the detector currently being programmed. When an adjective has been selected,
it will appear at the top of the display as indicated by the asterisks.
**********************
1=NORTH
2=SOUTH
3=EAST
**********************
1=3RD
2=4TH
3=5TH
Adjective Screen #1
Adjective Screen #5
**********************
1=WEST
2=FRONT
3=CENTER
**********************
1=FLOOR1
2=FLOOR2
3=FLOOR3
Adjective Screen #2
Adjective Screen #6
**********************
1=REAR
2=UPPER
3=LOWER
Adjective Screen #3
**********************
1=FLOOR4
2=FLOOR5
3=ROOM
Adjective Screen #7
*********************
1=MAIN
2=FIRST
3=2ND
Adjective Screen #4
54
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the detector currently being programmed. When a noun has been selected, it will appear at the
top of the display as indicated by the asterisks.
**********************
1=BASEMENT
2=BOILER RM
3=CLASSROOM
**********************
1=HVAC RM
2=ISLAND
3=KITCHEN
Noun Screen #4
Noun Screen #1
**********************
1=COMPUTER RM
2=CONTROL RM
3=DATA ROOM
**********************
1=ROOM
2=STOREROOM
3=TELCO ROOM
Noun Screen #2
Noun Screen #5
**********************
1=DOCUMENT RM
2=ELECTRIC RM
3=GARAGE
**********************
1=UPS ROOM
2=VAULT
Noun Screen #6
Noun Screen #3
Description
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Input Zone Screen #3
The Description selection allows the programmer to enter additional information about the
detector currently being programmed. This information will be displayed as part of the device
label on the display. Pressing 2 while viewing Edit Input Zone Screen #3 will cause the
following screen to be displayed:
ZONE # DESCRIPTION
PRESS ENTER IF DONE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the display along with the standard device label information.
PDRP-2001 Series PN 53043:A 5/08/2007
55
Programming
Master Programming Level
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Detector Screen #5, displaying the new information at the bottom of the
screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Description, Adjective or Noun field as follows:
•
If the zero key is pressed, a 0 is placed in the first letter position
•
If the zero key is then pressed a second time with no intervening key actions, the entire field
is replaced with the field entered for the previous device programmed, and the cursor moves
to the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter
•
If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last
character are also numbers, they are also incremented (overflow)
•
The above increment function may be repeated with each press of the zero key
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the Enter key to store the information
56
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.3 Output Circuits
The options for the Output Circuits on the control panel main circuit board can be configured by
pressing 2 while viewing Programming Screen #2. The following screens will be displayed:
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
PROGRAMMING
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
NAC Selection Screen
OUTPUT CIRCUITS
1=OUTPUT 4
Programming Screen #1
NAC Selection Screen
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or 4 for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
OUTPUT #
1=ENABLED
YES
2=TYPE
ALARM NAC
Output Screen #1
OUTPUT #
1=SILENCE
NON-SIL
2=AUTO SILENCE
NO
3=SIL INHIBIT
NO
Output Screen #2
OUTPUT #
1=CODING
STEADY
Output Screen #3
PDRP-2001 Series PN 53043:A 5/08/2007
57
Programming
Master Programming Level
3.5.3.1 Enabled
Pressing 1 while viewing Output Screen #1 will cause the display to change to Enabled No.
This will prevent the selected main circuit board NAC from activating its devices. Each press
of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is
enabled. The exception is when a Release Circuit is disabled, a supervisory will be logged on
the FACP until the circuit is enabled.
3.5.3.2 Type
Pressing 2 while viewing Output Screen #1 will cause the following screen to be displayed:
NAC #
1=ENABLED
2=TYPE
ALARM NAC
EDIT OUTPUT # TYPE
1=RELEASE CIRCUIT 1
2=RELEASE CIRCUIT 2
3=ALARM NAC
NAC Screen #1
Edit Output # Type Screen
Pressing the down arrow key while viewing the Edit Output Type Screen will display additional
screens with the types shown in the following table:
Release Circuit 1
Release Circuit 2
Alarm NAC
Waterflow NAC
Release Stage NAC
Horn NAC
Strobe NAC
Supv Bell NAC
Trouble Bell NAC
Press the number key corresponding to the desired Output Type to program the selected Output.
3.5.3.2.1 Release Circuit 1 or Release Circuit 2
If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreen
will be displayed:
EDIT RELEASE CIR #
1=UNSUPV SHORTS
2=SUPV SHORTS
This screen allows the programmer to select whether or not to supervise the Releasing Circuit
Output for shorts.
•
When a normally-closed releasing solenoid is connected to the output circuit, pressing 1 will
prevent the FACP from supervising the output circuit for shorts.
•
When a normally-open releasing solenoid is connected to the output circuit, pressing 2 will
allow the FACP to supervise the output circuit for shorts.
Note: Release circuits may be directly activated by a single input zone or may be activated using
cross-zoned inputs. Refer to "Circuit Mapping and Cross-Zoning" on page 103 for a description of
cross-zoning and input to output circuit mapping.
58
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.3.2.2 Release Stage NAC
If Release Stage NAC is selected as the Output Type, the following subscreen will be displayed:
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY
An NAC can be used to signal the two stages of a release operation. This screen allows the
programmer to select the NAC output that will indicate the release stages for Release Circuit 1
or Release Circuit 2. For a description of this feature, refer to "Release Stages" on page 91.
OUTPUT #
1=SILENCE NON-SIL
2=AUTO SILENCE NO
3=SIL INHIBITED NO
3.5.3.3 Silence
Pressing 1 while viewing Output Screen #2 will cause the following screen to be displayed:
Output Screen #2
SILENCEABLE
1=SILENCEABLE
2=NON SILENCEABLE
3=SYNC MUTE
Silenceable Screen
Pressing 1 while viewing the Silenceable Screen will program the selected Output as a
silenceable circuit. This will allow the Output to be silenced by pressing the Alarm Silence key
or by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen will program the selected Output as a
nonsilenceable circuit. This will prevent the selected main circuit board Output from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen will program the selected Output as a
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 62 for a
description of synchronization.
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Silenceable
Option will not be available and the display will indicate N/A next to it.
Important: When an Output Circuit with a mix of audible and visual devices is programmed for
Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
PDRP-2001 Series PN 53043:A 5/08/2007
59
Programming
Master Programming Level
3.5.3.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press 2 while viewing Output
Screen #2. The following screens will be displayed:
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
OUTPUT #
1=SILENCEABLE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
Output Screen #2
60
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #1.
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence
Option will not be available and the display will indicate N/A next to it.
3.5.3.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board Output for a period of one minute. Resetting the FACP will also be prevented for one
minute while the Output programmed for silence inhibit is activated. Pressing 3 while viewing
Output Screen #2 will cause a screen to be displayed with the options 1=No Silence Inhibit and
2=1 Min. Silence Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2
will enable a 1 minute Silence Inhibit for the selected Output.
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.3.6 Coding
The Coding feature allows the programmer to select the type of output that the main circuit
board outputs will generate when activated. Pressing 1 while viewing Output Screen #3 will
cause the following displays to appear:
OUTPUT #
1=CODING
Output Screen #3
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=FUTURE USE
3=FUTURE USE
Coding Screen #2
CODING
1=CROSS ZONE
2=SYNC SYSTEM SENSOR
3=SYNC WHEELOCK
Coding Screen #3
CODING
1=SYNC GENTEX
2=SYNC FARADAY
3=SYNC AMSECO
Coding Screen #4
PDRP-2001 Series PN 53043:A 5/08/2007
61
Programming
Master Programming Level
The programmer can select the notification appliance output coding by pressing the number
corresponding to the desired output. The coding selections are:
•
•
•
•
•
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off
Cross-Zone:
1st zone of a cross-zoned group in alarm causes programmed NAC output to pulse 1
second on and 1 second off
2nd zone of a cross-zoned group in alarm causes programmed NAC output to pulse ½
second on and ½ second off - Note: if more than three zones are cross-zoned, the
programmed NAC output will continue to pulse ½ second on and ½ second off for each
subsequent zone in alarm, until the final zone in the cross-zoned group goes into alarm
All zones of a cross-zoned group in alarm causes the output programmed as a Releasing
Circuit to perform a release and the programmed NAC output to turn on steady
•
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to
"Synchronized NAC Operation" on page 62 for additional information
Selection of one of the above options will cause the control panel to store the information in
memory and return the display to Output Screen #1, which will display the new coding choice.
Note: If the Output Circuit has been programmed as a Releasing Circuit, the Coding Option
will not be available and the display will indicate N/A next to it.
3.5.3.6.1 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such
a way that all devices will turn on and off at exactly the same time. This is particularly critical
when activating strobes which must be synchronized to avoid random activation and a potential
hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s
devices.
Notes:
1. The NAC1 output can be used to synchronize notification appliances connected to external
panels such as remote power supplies.
2. For Dual Hazard applications, NAC circuits are not synchronized.
3.5.3.6.1.1 Maximum Number of Strobes for Synchronization
The maximum current draw for a Notification Appliance Circuit cannot exceed 3.0 amps.
Refer to the manufacturer’s documentation supplied with the Strobes to determine the
maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that
can be attached to each circuit. Following is a list of the strobes that have been tested with this
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC
maximum current is not exceeded:
62
System Sensor: 46 Strobes
Wheelock: 50 Strobes
Gentex: 39 Strobes
Faraday: 33 Strobes
Amseco: 34 Strobes
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.4 Cross Input Zones
An application may require that two or more input zones become active at the same time before a
particular releasing output activates. This is referred to as cross-zoning. For example, an installer
may want four particular zones to become active at the same time before a releasing circuit is
activated. By using the Cross Input Zone feature, the programmer can designate the input zones
that must become active and the output circuits that will be affected.
PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
The Cross Input Zone option allows the user to view and program the groups of input zones that
will be used to activate one of the releasing output circuits. Pressing 1 while viewing Programming
Screen #2 will display a screen similar to the following:
CROSS INPUT ZONES
1=RELEASE 1 GROUPS
2=RELEASE 2 GROUPS
Programming Screen #2
This screen allows the programmer to view the cross-zoned grouping for Release Circuit 1 or
Release Circuit 2. In the following example, Template 7 has been chosen as the FACP
Configuration [refer to "FACP CONFIG (Application Templates)" on page 50]. Pressing 1 for
Release 1 Groups will display the following screen:
REL 1 CROSS GROUPS
1=
X 1 2
2=
NONE
3=
NONE
The display indicates that Input Zone 1 is cross-zoned with Input Zone 2. Input Zone 3 is not crosszoned.
The user can alter the cross-zoning by pressing the number key corresponding to the Zone to be
reprogrammed. Screens similar to the following will be displayed:
REL 1
1=ZONE
2=ZONE
3=ZONE
CROSS GROUP 1
1
YES
2
YES
3
NO
Select Cross Zone Screen #1
REL 1
1=ZONE
2=ZONE
3=ZONE
CROSS GROUP 1
4
NO
5
NO
6
N/A
Select Cross Zone Screen #2
PDRP-2001 Series PN 53043:A 5/08/2007
63
Programming
Master Programming Level
In this example, since the cross-zoning for Release Circuit 1 (Zone 1) is being displayed, Yes is
shown for Zone 1 which is cross-zoned with Zone 2. Zone 2 displays Yes since it is cross-zoned
with Zone 1. The remaining zones display NO or N/A for no cross-zoning to Zone 1. By pressing
the number key corresponding to the desired zone, the display for that zone will toggle between Yes
and No indicating cross-zoning to Zone 1 or no cross-zoning to Zone 1.
3.5.5 On-Board Relays
Pressing 2 while viewing Programming Screen #2 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:
ON-BOARD RELAYS
1=RELAY 1
ALARM
2=RELAY 2
TROUBLE
3=RELAY 3
SUPERVSRY
Relays Selection Screen
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screens will appear for each relay to be programmed:
RELAY TYPE
1=ALARM
2=TROUBLE
3=SUPERVISORY
Relay Screen #1
RELAY TYPE
1=FUTURE USE
2=DISCHARGE
3=AC LOSS
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
3.5.6 System Setup
System Setup allows the programmer to configure the following control panel features:
•
•
•
•
•
•
64
Abort Type: Future Use
Timers: This option allows the programmer to set the Soak 1, Soak 2, Waterflow and AC
Loss time delays.
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readoutto a user defined readout when the control panel is in Normal
condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If
the Trouble Reminder feature is not enabled and a trouble condition is not cleared within 24
hours, the panel will reactivate the trouble sounder an send an Abnormal 24 hour Test
message via the optional communicator.
Charger Disable: This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used.
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
SYSTEM SETUP
1=FUTURE USE
2=TIMERS
3=BANNER
PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
System Setup Screen #1
Programming Screen #2
SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE
NO
NO
System Setup Screen #2
SYSTEM SETUP
1=ABORT TYPE
2=TIMERS
3=BANNER
3.5.6.1 Timers
Timers for Soak, Waterflow Delay and AC Loss Delay can be programmed by pressing 2 while
viewing System Setup Screen #1. The following screen will be displayed:
System Setup Screen #1
TIMERS
1=SOAK 1
10 MIN
2=SOAK 2
10 MIN
3=WATERFLOW DELAY 60S
Timer Screen #1
TIMERS
1=AC LOSS DELAY
2 HR
Timer Screen #2
PDRP-2001 Series PN 53043:A 5/08/2007
65
Programming
Master Programming Level
3.5.6.1.1 Soak 1 or Soak 2
The factory default setting for Soak Time is 10 minutes. To select a Soak Time delay of 10 to
30 minutes, press 1 for Soak 1 (Release Circuit 1) or 2 for Soak 2 (Release Circuit 2) while
viewing Timer Screen #1. The following display will appear:
SOAK # TIME
1=ALWAYS ON
2=ENTER MINUTES
Soak Time Setup Screen
Pressing 1 while viewing the Soak Time Setup Screen will program the corresponding releasing
circuit to remain on during alarm activation until the alarm is cleared and the panel is reset.
Pressing 2 while viewing the Soak Time Setup Screen will display the following screen:
SOAK # TIME
RANGE 10-30 MINUTES
Soak Time Screen
This screen allows the user to program a specific length of time for the releasing circuit to
remain active after an input initiating a release has cleared. A flashing cursor is positioned in
the lower left corner of the display. Enter a soak time consisting of two digits, such as 10 for ten
minutes. Upon entering the second digit, the time delay will be stored in the control panel
memory and the display will return to the Delay Screen which will indicate the new soak time.
In this example, when the input circuit which initiated a release has cleared, the soak timer will
start, allowing the releasing circuit to continue releasing water for a total of ten minutes and
then deactivate.
TIMER
1=SOAK 1
1 MIN
2=SOAK 2
2 MIN
3=WATERFLOW DELAY 0 S
Timer Screen #1
3.5.6.1.2 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 00
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for
Waterflow delay, press 3 while viewing Timer Screen #1 to display the following screen:
WATERFLOW DELAY
RANGE 00-90 SECONDS
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the
time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
66
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.6.1.3 AC Loss Delay
The reporting of a loss of AC power can be delayed by programming the length of the desired
delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
RANGE 00-24 HOURS
TIMER
1=AC LOSS DLAY 2 HR
Timer Screen #2
SYSTEM SETUP
1=ABORT TYPE
2=TIMERS
3=BANNER
System Setup Screen #1
AC Loss Delay Screen #1
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC
Loss Delay setting.
3.5.6.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will
cause the following to be displayed:
SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
Select Banner Screen
Pressing 1 while viewing the Select Banner Screen will display the following screen:
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
This screen allows the user to select the factory default Banner which will be displayed when
the system is in Normal Mode of operation. Press the Enter key to accept this as the default
display. Press the Escape key to cancel and return to the Select Banner Screen.
PDRP-2001 Series PN 53043:A 5/08/2007
67
Programming
Master Programming Level
Pressing 2 while viewing the Select Banner Screen will display the following screen:
USER BANNER-LINE 1
PRESS ENTER IF OK
User Defined Banner Screen
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in
the bottom left corner of the display. A maximum of 20 characters (including spaces) can be
entered into the screen. After entering up to 20 characters in the screen, press Enter to store the
entry. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until
the desired character is displayed in the first position. For example, to enter the letter B, press
the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow
key to move the cursor one position to the right and repeat the process to enter the next
character. To enter a space, press the * (QZ) key four times to place a blank in the desired
position. When all characters have been entered, press the Enter key to store the information.
The display will return to the Select Banner Screen.
3.5.6.3 Time-Date
The control panel time and date can be changed by pressing 1 while viewing the System Setup
Screen #2. The following screen will be displayed:
SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE
System Setup Screen #2
TIME AND DATE
1=TIME
10:00A
2=DATE
04072006
3=CLOCK FORMAT
12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
68
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.6.3.1 Time
To change the time, press 1 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER TIME AS 12HRS
:
10:00
1=AM
2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
time. To change the time, enter the two-digit hours followed by the two-digit minutes. The
cursor will move one position to the right each time a digit is entered. After the last minutes
digit is entered, the cursor will again move one position to the right. At this point enter 1 for
AM or 2 for PM. The display will then return to the Time-Date Screen which will show the
new time entry. If an error is made while entering a digit, press the CLR key to delete the entire
entry and beginning again.
3.5.6.3.2 Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER DATE
**-**-****
MONTH DAY YEAR
04-07-2006
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
date. To change the date, enter the two-digit month followed by the two-digit day and then the
two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right
each time a digit is entered. After the last year digit is entered, the display will return to the
Time-Date Screen which will show the new date entry. If an error is made while entering a
digit, press the CLR key to delete the entire entry and beginning again.
3.5.6.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time.
Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR
and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
Note: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
PDRP-2001 Series PN 53043:A 5/08/2007
69
Programming
Master Programming Level
3.5.6.3.4 Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
TIME AND DATE
1=DAYLIGHT SAVINGS
DAYLIGHT SAVINGS
1=ENABLED
YES
2=START MONTH
MAR
3=START WEEK
WK 2
Daylight Savings Screen #1
Time & Date Screen #2
DAYLIGHT SAVINGS
1=END MONTH
NOV
2=END WEEK
WK 1
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows
the programmer to select the month that daylight savings time will begin. In this sub-screen,
pressing 1 will select March, 2 will select April and 3 will select May.
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will begin. In the
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and
2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows
the programmer to select the month that daylight savings time will end. In this sub-screen,
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will end. In the first
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will
select the last week of the selected month.
SYSTEM SETUP
1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE
System Setup Screen #2
3.5.6.4 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 64, for
a detailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will
cause the display to toggle to Trouble Remind Yes, which enables this feature. Each press of the
2 key will cause the display to toggle between Trouble Remind Yes and Trouble Remind No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for
more than 24 hours will cause the FACP to resound the trouble sounder.
3.5.6.5 Charger Disable
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or
disable the onboard battery charger. If an external battery charger is being used, the onboard
battery charger must be disabled. Each press of the 3 key will toggle between Chargr Disable
No and Chargr Disable Yes.
70
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.7 ANN-BUS
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
Programming Screen #3 will cause the control panel to display the following screens.
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
ANN-BUS
1=BUS ENABLED
2=BUS MODULES
3=AUTO CONFIGURE
Programming Screen #3
NO
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
ANN-BUS Screen #2
ANN-BUS
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
An ANN-S/PG Printer module, ANN-I/O module, ANN-80 LCD annunciator module, ANNRLY relay module and ANN-LED module can be installed in the FACP. These devices
communicate with the FACP over the ANN-BUS terminals on the control panel.
3.5.7.1 ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANNBUS Enabled Yes and ANN-BUS Enabled No.
PDRP-2001 Series PN 53043:A 5/08/2007
71
Programming
Master Programming Level
3.5.7.2 ANN-BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select
ANN-BUS addresses for the module(s). The following screen will be displayed.
ANN-BUS MODULES
1=ADDR. 1
NONE
2=ADDR. 2
NONE
3=ADDR. 3
NONE
On Board DACT Screen #1
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.
72
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.7.3 Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and
automatically program the device type and address into the system. Pressing 3 while viewing
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to
be displayed:
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
3.5.7.4 ANN-S/PG Options
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing
the ANN-BUS Screen #2 will display the following screens:
ANN-BUS Screen #2
ANN-S/PG OPTIONS
1=PORT
PARALLEL
2=PRINTER SUPV
NO
3=OFFLINE TIMER
60
Printer Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE
N/A
2=DATA BITS
N/A
3=PARITY
N/A
Printer Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS
N/A
Printer Options Screen #3
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the
display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that
the interface selected determines which options are available to the user.
PDRP-2001 Series PN 53043:A 5/08/2007
73
Programming
Master Programming Level
If the Parallel Port option is selected, the user has the option to supervise the printer and select
an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print
Options screen #1. Each press of the 2 key will cause the display to toggle between Printer
Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option
is not selectable if the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by
pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer
to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer
supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be
available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the
Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600 or 2400.
Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select 5, 6, 7 or 8 Data Bits.
Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity or Odd Parity.
Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear
which allows the user to select between 0.5, 1.0 or 2.0 Stop Bits.
74
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.7.5 ANN-I/O LED Zone Assignments
The information displayed by LEDs on every ANN-I/O module is not programmable and will
therefore be as indicated in the following table.
LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
PDRP-2001 Series PN 53043:A 5/08/2007
Zone (any address)
AC Fault
General Alarm
General Supervisory
General Trouble
Alarm Silenced
Earth Fault
Battery Fault
Charger Fault
Disable
Maintenance
Zone 1 Alarm
Zone 2 Alarm
Zone 3 Alarm
Zone 4 Alarm
Zone 5 Alarm
Zone 6 Alarm
Not Used
Not Used
Not Used
Not Used
Zone 1 Trouble
Zone 2 Trouble
Zone 3 Trouble
Zone 4 Trouble
Zone 5 Trouble
Zone 6 Trouble
Not Used
Not Used
Not Used
Not Used
Zone 1 Supervisory
Zone 2 Supervisory
Zone 3 Supervisory
Zone 4 Supervisory
Zone 5 Supervisory
Zone 6 Supervisory
Not Used
Not Used
Not Used
Not Used
75
Programming
Master Programming Level
3.5.7.6 ANN-80 Options
Pressing 2 while ANN-BUS screen #2 will display the following screen:
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80
1=SIL BTN
2=RST BTN
3=DRL BTN
OPTIONS
ENABLE
ENABLE
ENABLE
ANN-80 Options Screen #2
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 annunciator will ever sound. Pressing 1 while viewing the ANN-80 Options
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80 LCD
annunciator must be unlocked by its key before any annunciator key presses will function.
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock
position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 LCD annunciator will function normally
or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the
display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack
Btn Enable No (Ack/Step button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether
the Silence button on any installed ANN-80 LCD annunciator will function normally or always
be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to
toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No
(Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether
the Reset button on any installed ANN-80 LCD annunciator will function normally or always
be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to
toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No
(Reset button never functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether
the Drill button on any installed ANN-80 LCD annunciator will function normally or always be
ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill
button never functions).
76
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.7.7 ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
ANN-RLY OPTIONS
1=RELAY 1
IN ZONE 1
2=RELAY 2
IN ZONE 2
3=RELAY 3
IN ZONE 3
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-RLY Options Screen
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
General Alarm
General Trouble
General Supervisory
Future Use
Future Use
Future Use
General Discharge
Discharge Release 1
Discharge Release 2
AC Loss
Waterflow Delay
Future Use
Future Use
Future Use
General 2nd Shot Release
2nd Shot Release 1
2nd Shot Release 2
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
PDRP-2001 Series PN 53043:A 5/08/2007
77
Programming
Master Programming Level
3.5.8 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 2 while viewing Programming Screen #3 will display the History options
as shown in the following display:
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
Programming Screen #3
History Screen
3.5.8.1 View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be
viewed as illustrated in the following:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3
to view other events. Use the up and down arrow keys to scroll through all of the displayed
events.
3.5.8.2 Erase History
The Erase History option allows a user to erase all events from the history file. This will
provide a clean slate in order to use the history file to track future events. Pressing 2 while
viewing the History Screen will display the following screen:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file.
During this process, the display will read as follows:
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
After the History file has been erased, the display will return to the History Screen.
78
PDRP-2001 Series PN 53043:A 5/08/2007
Master Programming Level
Programming
3.5.9 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Pressing 3 while viewing the Programming Screen #3 will cause
the following Walktest options to be displayed:
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
Walktest Screen
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
UNIT IN WALKTEST
Walktest Active Screen
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the
walktest screen from an actual alarm screen.
ALARM ZONE 1
<ADJ> <NOUN>
Z01
10*00A 010805
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
WALKTEST EVENTS
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
PDRP-2001 Series PN 53043:A 5/08/2007
79
Programming
Master Programming Level
3.5.10 Clear Program
Pressing 1 while viewing Programming Screen #4, will select the Clear Program option. The
control panel will provide a warning to the user by prompting with the following display:
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES
2=NO
Pressing 1 for Yes will cause the control panel to carry out the selected clear option. Pressing 2 for
No will prevent programming from being cleared.
3.5.11 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 2 while viewing Programming Screen #4 will
cause the following screen to be displayed:
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
Password Change Screen
Press 1 to change the Master Programming Level password or 2 to change the Maintenance Level
password. Note that the passwords will not be displayed on annunciators.
The following screen will appear when either change option is selected:
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
VERIFY NEW
PASSWORD
Password Change Screen
The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.
80
PDRP-2001 Series PN 53043:A 5/08/2007
Maintenance Programming Level
Programming
3.6 Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key. The LCD will display the
following:
1=READ STATUS
2=PROGRAMMING
To enter the Maintenance Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
When the Maintenance level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.
PROGRAMMING
1=TIME-DATE
PDRP-2001 Series PN 53043:A 5/08/2007
81
Programming
Maintenance Programming Level
3.6.1 Input Zones - Enable/Disable
The Input Zones option allows the user to enable or disable desired zones. Pressing 1 for Input
Zones, while viewing Maintenance Screen #1 will cause the following screens to be displayed:
POINT PROGRAM
1=ZONE 1
2=ZONE 2
3=ZONE 3
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Zone Select Screen
Maintenance Screen #1
Pressing the down arrow key will display additional Zones 4 - 6. Select the number corresponding
to the desired zone. A screen will appear which will allow enabling or disabling of the selected
zone, as illustrated in the following example:
INPUT ZONE 1
1=ENABLED
YES
TYPE
PULL STATION
Enable/Disable Select Screen
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
3.6.2 History
Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file
82
PDRP-2001 Series PN 53043:A 5/08/2007
Maintenance Programming Level
Programming
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
To view all the events which have occurred in the control panel since the history file was last
erased, press 1 while viewing the Events screen. To view only alarms which have occurred, press 2
while viewing the Events screen. To view events other than alarms, press 3. The most recent event
will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS
IN HISTORY.
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY,
PLEASE WAIT to be displayed. The display will then return to the History Screen. Pressing 2 will
cause the display to return to the History Screen without erasing the History file.
3.6.3 Walktest
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
To perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be
displayed:
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW EVENTS
Maintenance Screen #1
Walktest Screen
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The
display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the
walktest.
PDRP-2001 Series PN 53043:A 5/08/2007
83
Programming
Maintenance Programming Level
3.6.4 Time-Date
To program the time and date into the control panel, press 1 while viewing Maintenance Screen #2.
The following display will appear:
PROGRAMMING
1=TIME-DATE
Maintenance Screen #2
TIME AND DATE
1=TIME
01:00A
2=DATE
01012006
3=CLOCK FORMAT
12HRS
Time and Date Screen
To change the time, press 1 to display the following screen:
ENTER TIME AS 12HRS
:
01:00
1=AM
2=PM
Time Screen
A flashing cursor will appear on the left side of the display. Enter the four digit number
corresponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one
position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will
return to the Time and Date Screen displaying the new time.
To change the date, press 2 while viewing the Time and Date Screen. The following screen will be
displayed:
ENTER DATE
**-**-****
MONTH DAY YEAR
01-01-2006
Date Screen
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit
day and four digit year. The cursor will move one position to the right after each entry. When the
fourth digit of the year has been entered, the display will return to the Time and Date Screen which
will show the new date.
To change between 12 hour and 24 hour format, press 3 for Clock Format while viewing the Time
and Date screen. Each press of the 3 key will toggle the display between 12 HR and 24 HR format.
84
PDRP-2001 Series PN 53043:A 5/08/2007
Panel Control Buttons
Operating Instructions
Operating Instructions
SECTION 4
Factory programmed Templates have been provided to facilitate the installation and configuration
of the Fire Alarm Control Panel. The factory default programming for this panel is Template #7.
Refer to "FACP Configuration Templates" on page 108 for a detailed description of the FACP
operation for Template #7.
4.1 Panel Control Buttons
4.1.1 Acknowledge/Step
The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to
steady and also changes the status field on the LCD display from capital letters to small letters
(TROUBL to troubl). When the piezo is silenced, an acknowledge message is sent to the printer and
the history file. Acknowledge also sends a silence piezo command to the optional annunciators
connected to the FACP. The Acknowledge key will have no effect on the Notification Appliance
Circuits.
When more than one event exists, the first press of the Acknowledge/Step key functions as
described in the preceding paragraph. Subsequent pressing of the key steps through each active
event.
4.1.2 Alarm Silenced
The Alarm Silenced key performs the same functions as Acknowledge/Step, except it will not step
through each event when multiple events are present at the panel. In addition, if an alarm exists, it
turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm Silenced
indicator to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and
optional annunciators. A subsequent new alarm will resound the system NACs. The Alarm
Silenced indicator is turned off by pressing the Reset key, the Drill key or subsequent activation of
the NACs.
Note:
1. If Silence Inhibit has been enabled, NACs cannot be silenced for one minute following
initiation of an alarm.
2. When the system is configured for dual hazard operation, an alarm in one hazard area may
reactivate notification appliance circuits programmed for that area only.
4.1.3 Drill/Hold 2 Sec
When the Drill key is held for a minimum of two seconds (time required to prevent accidental
activations), the FACP turns on all NAC outputs and turns off the Alarm Silenced indicator if it was
previously on. The EVAC IN SYSTEM message is shown on the LCD display. The same message
is sent to the printer and history file. The Alarm Silence key can be used to turn off all silenceable
NAC outputs following activation by the Drill key.
4.1.4 Reset
Pressing and releasing the Reset key turns off all NACs, temporarily turns off resettable power to 4wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the
same message to the printer and history file. It also performs a lamp test by turning on all LEDs,
piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that
exists after a reset will resound the system.
Note that if Silence Inhibit has been enabled, the FACP cannot be reset for one minute following
initiation of an alarm.
PDRP-2001 Series PN 53043:A 5/08/2007
85
Operating Instructions
Indicators
4.2 Indicators
The eight indicators, which are located on the front panel, operate as follows:
AC Power
This is a green indicator which illuminates if AC power is applied to the FACP. A loss of AC
power will turn off this indicator.
Fire Alarm
This red indicator flashes when one or more alarms occur. It illuminates steady when the
Acknowledge/Step or Alarm Silence key is pressed. The Fire Alarm indicator turns off when the
Reset key is pressed. The indicator will remain off if all alarms have been cleared.
Supervisory
This is a yellow indicator that flashes when one or more supervisory conditions occur, such as a
sprinkler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm
Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory
alarms have been cleared.
Trouble
This is a yellow indicator that flashes when one or more trouble conditions occur. It stays on steady
when the Acknowledge/Step or Alarm Silence key is pressed. The indicator turns off when all
trouble conditions are cleared. This indicator will also illuminate if the microprocessor watchdog
circuit is activated.
Alarm Silenced
This is a yellow indicator that illuminates after the Alarm Silence key is pressed while an alarm
condition exists. It turns off when the Drill or Reset key is pressed.
Discharge
This is a red indicator that illuminates steadily when the water releasing circuit is activated.
4.3 Normal Operation
With no alarms or troubles in the system, the display message is System All Normal along with the
current time and date as shown below. To set the time and date, refer to the appropriate section in
this manual.
SYSTEM ALL NORMAL
10:00A 031106
The FACP performs the following functions at regular intervals in Normal mode:
Monitors AC input voltage and battery voltage
Monitors and reports status option cards and control panel
Refreshes LCD display and updates time
Scans control panel keypad for key presses
Tests memory
Updates and reads all communications busses (EIA-485, etc.)
i3 smoke detectors will be polled for maintenance and freeze conditions (temperature of
45oF or less) on initial entry into Normal mode. Thereafter, each device will be polled
every hour for freeze and every four hours for maintenance conditions
86
PDRP-2001 Series PN 53043:A 5/08/2007
Trouble Operation
Operating Instructions
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or
maintenance condition, the panel will continue to monitor for freeze conditions every hour and
maintenance conditions every four hours.
4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
•
The piezo to pulse 1 second On and 1 second Off
•
The system Trouble indicator to flash one second On and one second Off
•
The output circuits programmed as Trouble Bell NAC to activate
•
The trouble relay to activate
•
TROUBL with device type, noun/adjective, address and trouble description will appear on
the LCD display
•
The same message, along with the time and date, is sent to the optional printer and the history
buffer.
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn
off the AC Power indicator, etc.
Input Zone
For Input Zones, the following is a typical message that could appear on the LCD display for a
device trouble:
TROUBL PULL STATION
<ADJ> <NOUN>
ZONE 1 OPEN FAULT
10:00A 030806
The information displayed in the above example provides the following information:
•
First line in display:
The type of event; in this example OPEN indicating a circuit trouble
Device type identifier; in this example, PULL STATION indicates a manual device. Other
device type identifiers which can be displayed include 2-WIRE SMOKE for Smoke
Detector, 2-WIRE HEAT for Heat Detector, etc.
•
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
•
Third line in display indicates Zone and the fault condition. Other possible troubles include:
U OPEN - indicating an open circuit
•
U DIRTY - maintenance alert indicating that a detector is near but below the allowed
alarm limit and is in need of maintenance before the performance is compromised
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day
of the month and 06 for the year 2006
PDRP-2001 Series PN 53043:A 5/08/2007
87
Operating Instructions
Alarm Operation
Pressing the Acknowledge/Step or Alarm Silence key will cause the pulsing piezo to silence and the
system Trouble indicator to change from flashing to on steady. This block acknowledgment occurs
regardless of the number of troubles, alarms and supervisory events active in the system. When the
Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the
‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or
after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and
history file.
If all troubles clear and there are no supervisory or fire conditions active in the system, the system
returns to normal mode operation and the System All Normal message is shown on the LCD display
and sent to the history and printer files. The auto-restore feature will restore cleared troubles even
if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only
troubles exist in the system will have the same effect as pressing the Acknowledge/Step key except
the Alarm Silenced indicator will light.
4.5 Alarm Operation
For a detailed description of the alarm operation for each preprogrammed Template, refer to
"FACP Configuration Templates" on page 108 and "Circuit Mapping and Cross-Zoning" on page
103. Alarm operation is similar to trouble operation with the following differences:
•
•
•
•
•
•
•
•
•
•
•
The piezo sounder produces a steady output as opposed to a pulsed output
The Fire Alarm indicator flashes 1 second On and 1 second Off
The LCD displays Alarm along with the device name, type, adjective/noun, associated zones
and time/date
Alarms latch and are not allowed to clear automatically
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started
Soak and Waterflow Delay Timers are started (if enabled) for appropriate circuits
Alarms activate the general alarm relay
Silenced alarms are resounded
Release Solenoid circuits are activated to produce a water release
The trouble relay is not activated
Store event in history buffer
A typical alarm display would be as illustrated below:
ALARM PULL STATION
<ADJ> <NOUN>
ZONE 1
10:00A 030806
Note that the device type, which in this example is PULL STATION, can be any other
programmable alarm type.
The information displayed in the above example provides the following information:
•
First line in display:
•
The type of event; in this example ALARM indicating an alarm condition
Device type identifier; in this example, PULL STATION indicates a manual pull box.
Other device type identifiers which can be displayed include 2-WIRE SMOKE for Smoke
Detector, 2-WIRE HEAT for Heat Detector, etc.
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
•
88
Third line in display: Zone 1 indicates the zone programmed to this device which, in this
example, is Input Zone 1.
PDRP-2001 Series PN 53043:A 5/08/2007
Supervisory Operation
•
Operating Instructions
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 03 for March, 08 for the 8th day
of the month and 06 for the year 2006
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
The piezo sounder pulses ½ second On and ½ second Off
•
The Supervisory indicator flashes ½ second On and ½ second Off
•
The LCD displays the status label Active Supervisory along with the device name, type,
adjective/noun, associated zones and time/date
•
The output circuits programmed as Supervisory NAC are activated
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
A typical Supervisory event would be displayed as illustrated in the following:
FREEZE SUPERVISORY
<ADJ> <NOUN>
ZONE 05 FROZEN SUPRV
10:00A 030806
In the preceding example:
U FROZEN SUPRV - indicates zone detector is below approximately 45oF
Note that, like alarms, supervisory signals latch (except when programmed for supervisory
autoresettable). Supervisory alarms do not cause resound as do other alarm conditions. Open
circuits in supervisory wiring are processed by the control panel the same way as other trouble
conditions. Refer to "Alarm Operation" on page 88, for a description of the information displayed
on the control panel LCD.
4.7 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. Disabled zones/NACs are treated as if they were in trouble, with the exception
being the LCD status label that will be displayed is DISABL.
Note that disabled Releasing Circuits are treated as supervisory events.
4.8 Waterflow Circuits Operation
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.
PDRP-2001 Series PN 53043:A 5/08/2007
89
Operating Instructions
2nd-Shot Water Switch
4.9 2nd-Shot Water Switch
Following an initial waterflow release, an input circuit with the nonlatching Type Code of 2nd-Shot
Water Switch, when activated, will cause another waterflow release to occur immediately. If a
manual switch is connected to the circuit, an operator has the option to perform any number of
additional waterflow releases following an initial release.
4.10 Detector Functions
Maintenance Alert
i3 smoke detectors will be polled for maintenance and freeze conditions (temperature less than
45oF) on initial entry into Normal mode. Thereafter, each device will be polled every hour for
freeze and every four hours for maintenance conditions All alarm and system trouble conditions
are annunciated on the control panel’s LCD.
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or
maintenance condition, the panel will continue to monitor for freeze conditions every hour and
maintenance conditions every four hours.
4.11 Time Functions: Real-Time Clock
The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is
displayed as 12 or 24 hour time with month/day/year and is stored in RAM. Daylight savings time
change-over is programmable and automatic. If both AC and battery are lost, the time must be
reprogrammed.
4.12 Coded NAC Operation
The NAC circuits resident on the control panel main circuit board can be programmed for coded
operation. The available options which can be programmed for coded operation are as follows:
•
•
•
•
•
Steady - Steady output with no pulsing
March Time - Pulses at 120 ppm (pulses per minute)
California Code - 10 seconds On, 5 seconds Off
Temporal Code - Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off, ½
second On, 1½ second Off
Cross-Zone:
1st zone of a cross-zoned group in alarm causes programmed NAC output to pulse 1
second on and 1 second off
2nd zone of a cross-zoned group in alarm causes programmed NAC output to pulse ½
second on and ½ second off - Note: if more than three zones are cross-zoned, the
programmed NAC output will continue to pulse ½ second on and ½ second off for each
subsequent zone in alarm, until the final zone in the cross-zoned group goes into alarm
all zones of a cross-zoned group in alarm causes the output programmed as a Releasing
Circuit to perform a water release and the programmed NAC output to turn on steady
•
90
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to
"Synchronized NAC Operation" on page 62 for additional information.
PDRP-2001 Series PN 53043:A 5/08/2007
Release Stages
Operating Instructions
4.13 Release Stages
Outputs programmed as Release Stage NACs indicate the two stages of a release operation:
The activation of an output programmed as a Releasing Circuit will cause the programmed
indicating NAC output to turn on steady
Upon completion of the release, the programmed indicating NAC output will pulse at a 20
pulse-per-minute rate
4.14 Special System Timers
4.14.1 Silence Inhibit Timer
This option, if selected, prevents the Alarm Silence key from functioning for 60 seconds following
an alarm. A new alarm during the initial 60 second period will not cause the timer to restart with a
new 60 seconds. Silence Inhibit operation requires the approval of the local AHJ.
4.14.2 Autosilence Timer
If Autosilence is selected, the notification appliances, programmed as silenceable, will
automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the
Drill key will restart the timer. Autosilence operation requires the approval of the local AHJ.
4.14.3 Trouble Reminder
If selected, this feature causes a reminding ‘beep’ every 15 seconds during an alarm (after the
Alarm Silence key is pressed) and every two minutes during a trouble condition (after the
Acknowledge/Step or Alarm Silence key is pressed). The ‘beeps’ from the onboard piezo sounder
will occur until the alarm or fault is cleared.
Note that if Trouble Reminder feature is not selected and the trouble is not cleared within 24 hours,
the piezo will resound, indicating that the trouble condition still exists.
4.14.4 Soak Timers
Two Soak Timers allow the user to program a time between 10 and 30 minutes for each water
releasing circuit to remain active. Soak Timer 1 is used for Releasing Solenoid Circuit 1 and Soak
Timer 2 is used for Releasing Solenoid Circuit 2. Following an alarm condition in which the
releasing circuit is activated, the water release will stop when the corresponding Soak Timer
reaches zero.
4.14.5 Waterflow Delay Timer
If selected, this option will delay the activation of a waterflow type alarm for a programmable time
duration from 1 to 90 seconds. This delay is in addition to any time delay inherent in the waterflow
device. This feature requires the approval of the local AHJ.
4.15 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest
will momentarily sound the Notification Appliance Circuits in the building and store the walktest
information in a file at the panel. A silent walktest will not sound the NACs but will store the
walktest information in a file which can be viewed at the panel. Disabled NAC devices will not
activate during walktest. In addition, i3 smoke detectors will enter their own test mode causing
their LEDs to flash twice every five seconds (refer to i3 specification document).
PDRP-2001 Series PN 53043:A 5/08/2007
91
Operating Instructions
Read Status
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed
control outputs for four seconds, if those outputs have been programmed for silenceable activation.
It also stores each alarm in the walktest history file which can be sent to an optional printer. The
stored display will be the same as if the device actually activated except the colon (:) in the time
stamp is replaced with an asterisk (*).
Open Condition
Addressable devices as well as all main circuit board NACs are monitored for fault conditions
during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs
programmed for Walktest, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble indicator flashes (as in all
of the Program and status change operations). The alarm relay is not activated.
4.16 Read Status
Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm occurs during these functions, the Read Status is exited to prevent
confusion.
Read Status Entry
When the operator presses the control panel Enter key, the LCD will display the following:
1=READ STATUS MODE
2=PROGRAMMING MODE
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status mode which allows the user to view and print the programmed features and status of the
control panel.
The following screens will be displayed:
READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Read Status Screen #1
READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #2
92
READ STATUS
1=TIMERS
2=DAYLIGHT SAVINGS
3=HISTORY
Read Status Screen #3
READ STATUS
1=PRINT
2=ANN-BUS
Read Status Screen #4
PDRP-2001 Series PN 53043:A 5/08/2007
Read Status
Operating Instructions
4.16.1 FACP Configuration
Pressing 1 while viewing Read Status Screen #1 will display the type of configuration programmed
into the FACP (refer to "FACP CONFIG (Application Templates)" on page 50). As an example, if
Template 7 was programmed as the FACP configuration, the following screen will be displayed:
READ FACP CONFIG
TEMPLATE 7
SINGLE HAZARD
3 ZONE
4.16.2 Input Zones
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
READ INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
Pressing the down arrow key will allow the selection of Zones 4-6.
The operator selects the zone which is to be viewed by pressing the number corresponding to the
desired zone in each screen. For example, if 1 is pressed in the first screen, the display will change
to a screen similar to the following:
READ INPUT ZONE 1
Normal PULL STATION
PRESS
TO VIEW
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:
•
Enable/Disable Status
•
Device Type
•
Output Circuit MAP
•
Adjective/Noun descriptor
PDRP-2001 Series PN 53043:A 5/08/2007
93
Operating Instructions
Read Status
4.16.3 Output Circuits
Pressing 3 while viewing Read Status Screen #1 will display the following screens:
READ
1=OUTPUT
2=OUTPUT
3=OUTPUT
READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
OUTPUTS
1
2
3
Read Outputs Screen #1
Read Status Screen #1
READ OUTPUTS
1=OUTPUT 4
Read Outputs Screen #2
The operator can press 1 to view the programmed options for Output 1, 2 to view the programmed
options for Output 2, 3 to view the programmed options for Output 3 or 4 to view the programmed
options for Output 4.
The resulting screens will display the following information:
•
•
•
•
•
•
Enable/Disable Status
Circuit Type
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay (in minutes)
Silence Inhibit Enabled/Disabled
Coding Selection (Temporal, Steady, etc.)
4.16.4 Cross Input Zones
READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #2
Pressing 1 while viewing Read Status Screen #2 will display the following screens:
CROSS INPUT ZONES
1=RELEASE 1
2=RELEASE 2
Cross Input Zone Screen
Pressing 1 for Release 1 or 2 for Release 2 will display the cross-zoning, if any, for the selected
Releasing Circuit as illustrated in the following screen:
CROSS ZONE REL 1
X 1 4
NONE
NONE
Cross Input Zone Screen
The Cross Zone Release screen displays the zones that have been cross-zoned. In this example,
Zone 1 is cross-zoned with Zone 4.
94
PDRP-2001 Series PN 53043:A 5/08/2007
Read Status
Operating Instructions
4.16.5 On-Board Relays
Pressing 2 while viewing Read Status Screen #2 will display the following screen:
ON-BOARD RELAYS
RELAY 1
ALARM
RELAY 2
TROUBLE
RELAY 3
SUPERVSRY
This screen allows the operator to view the programmed option for each relay.
4.16.6 System Settings
Pressing 3 while viewing Read Status Screen #2 will display the following screens:
SYSTEM SETTINGS
FUTURE USE
TROUBLE REMIND
NO
CHARGER DISABLE
NO
SYSTEM SETTINGS
FACTORY BANNER
The operator can view the system settings options that have been programmed into the FACP.
PDRP-2001 Series PN 53043:A 5/08/2007
95
Operating Instructions
Read Status
4.16.7 Timers
Pressing 1 while Read Status Screen #3 will display the following screens:
READ STATUS
1=TIMERS
2=DAYLIGHT SAVINGS
3=HISTORY
TIMERS
SOAK 1
10 MIN
SOAK 2
10 MIN
WATERFLOW DELAY
0 S
Read Status Screen #3
TIMERS
AC LOSS DELAY
2 HR
These screens allow the operator to view the various timer settings.
4.16.8 Daylight Savings
Pressing 2 while Read Status Screen #3 will cause the following screens to be displayed:
DAYLIGHT SAVINGS
ENABLED
YES
START MONTH
MAR
START WEEK
WK 2
DAYLIGHT SAVINGS
END MONTH
NOV
END WEEK
WK 1
These screens allow the operator to view settings that have been programmed for Daylight Savings
Time.
96
PDRP-2001 Series PN 53043:A 5/08/2007
Read Status
Operating Instructions
4.16.9 History
Pressing 3 while viewing Read Status Screen #3 will display the following screens:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.
4.16.10 PRINT
READ STATUS
1=PRINT
2=ANN-BUS
To print control panel data, press 1 while viewing Read Status Screen #4. This allows printing to
the printer connected to the ANN-S/PG module. The following screens will be displayed:
Read Status Screen #4
PRINT
1=HISTORY
2=WALKTEST LOG
3=EXIT PRINTING
Pressing 1 allows the user to print the History file which will detail all of the system activities since
the file was last cleared from memory.
Pressing 2 allows the user to print the Walktest log which will detail all of the system activations
during walktest since the log was last cleared. Refer to "Walktest" on page 79 for additional
information on the display.
Pressing 3 will exit the Print operation.
PDRP-2001 Series PN 53043:A 5/08/2007
97
Operating Instructions
Read Status
4.16.11 ANN-BUS
Pressing 2 while viewing Read Status Screen #4 will display the settings for the ANN-BUS options
as shown in the following screens:
ANN-BUS
BUS ENABLED
NO
1=BUS MODULES
2=ANN-S/PG OPTIONS
ANN-BUS Screen #1
ANN-BUS
1=ANN-80 OPTION
2=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS Screen #1 indicates whether the ANN-BUS is enabled (Yes/No).
Pressing 1 while viewing ANN-BUS Screen #1 will display BUS Module addresses 1-8 and the
devices, if any, located at those addresses.
Pressing 2 while viewing ANN-BUS Screen #1 will display the programmed options for the ANNS/PG Module devices connected to the ANN-BUS.
Pressing 1 while viewing ANN-BUS Screen #2 will display the programmed options for the ANN80 LCD annunciators connected to the ANN-BUS.
Pressing 2 while viewing ANN-BUS Screen #2 will display the programmed options for the ANNRLY devices connected to the ANN-BUS.
98
PDRP-2001 Series PN 53043:A 5/08/2007
Overview
Power Supply Calculations
Power Supply Calculations
SECTION 5
5.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
5.2
Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the control panel. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm2)
wire with 600 volt insulation for this branch circuit.
Use Table 5-1 , to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
TABLE 5-1:120/240 VAC Branch Circuit Requirements
Device Type
Number of
Devices
Current Draw
(AC amps)
PDRP-2001
3.66
or
1
=
X
PDRP-2001E
2.085
[
]
X
[
]
X
=
[
]
Sum Column for AC Branch Current Required
PDRP-2001 Series PN 53043:A 5/08/2007
Total Current per
Device
=
=
99
Power Supply Calculations
5.3
Calculating the System Current Draw
Calculating the System Current Draw
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 5-3 on page 101. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 5-3 on page 101. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 5-3 on page
101.
When calculating current draw and the battery size, note the following:
• ‘Primary’ refers to the main power source for the control panel
• ‘Secondary’ refers to the control panel’s backup batteries
• All currents are given in amperes (A). Table 5-2 shows how to convert milliamperes and
microamperes to full amperes.
TABLE 5-2:Converting to Full Amperes
To convert...
Multiply
Example
Milliamperes (mA) to
amperes (A)
mA x 0.001
3 mA x 0.001 = 0.003A
Microamperes (µA) to
amperes (A)
µA x 0.000001
300 µA x 0.000001 = 0.0003 A
5.3.2 How to Use Table 5-3 on page 101 to Calculate System Current Draw
Use Table 5-3 on page 101 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Device Compatibility Appendix for
compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 5-4 on page 102
Following are the types of current that can be entered into Table 5-3 on page 101:
100
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire
alarm condition during a loss of AC power.
PDRP-2001 Series PN 53043:A 5/08/2007
Calculating the System Current Draw
Power Supply Calculations
Table 5-3 contains three columns for calculating current draws. For each column, calculate the
current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5-4 on page 102.
TABLE 5-3:System Current Draw Calculations
Device Type
Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)
Qty
Main Circuit Board
X[current draw]=
1
X[0.122]=
Calculation Column 2
Primary, Fire Alarm Current
(amps)
Total
Qty
0.122
X [current draw] =
1
1
X[0.185] =
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Total
Qty
0.185
1
[
]
X[current draw]=
Total
X[0.122]=
0.122
CAC-5X
[
]
X[0.001]=
[
]
X[0.001]=
X[0.001]=
4XTM
[
]
X[0.005]=
[
]
X[0.011]1=
[
]
X[0.005]=
ANN-80
[
]
X[0.037]=
[
]
X[0.040]=
[
]
X[0.037]=
2-wire Detector Heads
[
]
X[
]2=
[
]
X[
]=
[
]
X[
]=
4-wire Detector Heads
[
]
X[
]2=
[
]
X[
]=
[
]
X[
]=
Power Supervision
Relays3
[
]
X[0.025]=
[
]
X[0.025]=
[
]
X[0.025]=
NAC #14
[
]
X[
]=
NAC #2
[
]
X[
]=
NAC #3
NAC #4
Current Draw from
TB9 (nonalarm5)
Sum each column6
for totals
[
Primary Non-Alarm =
]=
[
Primary Alarm =
]=
[
]=
Secondary Non-Alarm =
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005
amps.
2. Refer to the Device Compatibility Appendix for standby current.
3. Must use compatible listed Power Supervision Relay.
4. Current limitation of Terminal TB5 circuits is 3.0 amps per NAC
5. The total standby current must include both the resettable (TB9 Terminals 3 & 4) and nonresettable/resettable (TB9 Terminals 1
& 2) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB9, Terminals 1 & 2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mVRMS,
nonresettable power and TB9, Terminals 3 & 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mVRMS, resettable
power.
6. Total current draw listed above cannot exceed 7.0 amps
PDRP-2001 Series PN 53043:A 5/08/2007
101
Power Supply Calculations
5.4
Calculating the Battery Size
Calculating the Battery Size
Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load
determines the battery size (in AH), required to support the control panel under the loss of AC
power. Complete Table 5-4 as follows:
1. Enter the totals from Table 5-3 on page 101, Calculation Columns 2 and 3 where shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm
ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)
5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door
TABLE 5-4:Total Secondary Power Requirements at 24 VDC
Secondary Standby Load
(total from Table 5-3 Calculation
Column 3)
[
]
Required Standby Time
(24 hours)
Primary Alarm Load
(total from Table 5-3 Calculation
Column 2)
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
[
]
X[
X[
]
]
Sum of Standby and Alarm Ampere Hours
=
AH
=
AH
=
Multiply by the Derating Factor
Battery Size, Total Ampere Hours Required
AH
X 1.2
=
AH
5.4.1 NFPA Battery Requirements
NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power
followed by 5 minutes in alarm
5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The control
panel can charge batteries in the 7 AH to 26 AH range. The control panel cabinet is capable of
housing batteries up to 18 AH. Batteries larger than 18 AH require the or other UL listed external
battery cabinet.
102
PDRP-2001 Series PN 53043:A 5/08/2007
Input-to-Output Circuit Mapping and Cross-Zone Operation
APPENDIX A
Circuit Mapping and Cross-Zoning
Circuit Mapping and Cross-Zoning
A.1 Input-to-Output Circuit Mapping and Cross-Zone Operation
The flexible cross-zoning and input-to-output (I/O) mapping capability of this fire panel provides a
powerful toolset to accommodate many site-specific configurations. To simplify initial setup,
preconfigured application templates that employ cross-zoning and I/O mapping are included from
the factory. Refer to "FACP Configuration Templates" on page 108 for a description of each
supplied template.
The following sections provide some examples of setting up your own cross-zoned or I/O mapped
system.
!
The Installer is responsible for completely testing the proper operation of the fire panel as set
up by programming.
Notes:
1. Any general system trouble, such as a battery fault, will activate any output circuit
programmed as TROUBLE NAC in the OUTPUT CIRCUITS menu. Circuit mapping does
not apply.
2. Any input zone programmed for supervisory operation or as a DISABLE RELEASE switch in
the INPUT CIRCUITS menus will activate any output circuit programmed as SUPV BELL
NAC in the OUTPUT CIRCUITS menus. Circuit mapping does not apply.
3. The programming menus will prevent you from mapping any incompatible input zone and
output circuit types together, such as mapping a supervisory input zone to a releasing output
circuit.
4. Timers and/or delays are not represented in these examples.
PDRP-2001 Series PN 53043:A 5/08/2007
103
Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
A.1.1 Mapping Input Zones to Output Circuits for Direct Activation
Using the INPUT ZONES menus, you can assign any input zone to directly activate (without crosszoning) any of the four output circuits provided they are assigned matching operational types (see
the OUTPUT CIRCUIT MAP menu within the INPUT ZONES menus).
Example 1: A waterflow input zone assigned to directly activate an alarm output circuit by setting
the OUTPUT CIRCUIT MAP assignment to YES.
•
•
•
•
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus.
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Input Zone 1 is programmed as a waterflow zone using the INPUT ZONES menus.
Waterflow Input Zone 1 will directly activate Output Circuit 1 (Alarm NAC) but not Output
Circuits 2, 3 or 4.
ZONE 1 TYPE
1=N/A
2=WATERFLOW
3=WATERFLOW NS
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=RELEASE 1
NO
3=RELEASE 2
NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC
N/A
Example 2: A single hazard application where a smoke detector input zone will directly activate
both an alarm NAC circuit and a releasing output circuit.
•
•
•
•
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as waterflow NAC using the OUTPUT CIRCUITS menus.
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Input Zone 1 is programmed as a smoke detector zone using the INPUT ZONES menus.
Smoke detector Input Zone 1 will directly activate Output Circuits 1 (Alarm NAC) and 2 (Release
1) but not output circuits 3 or 4.
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=RELEASE 1
YES
3=WATERFLOW NAC
NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC
N/A
104
PDRP-2001 Series PN 53043:A 5/08/2007
Input-to-Output Circuit Mapping and Cross-Zone Operation
Circuit Mapping and Cross-Zoning
A.1.2 Mapping Input Zones to Release Circuits for Cross Zone
Activation
Using the OUTPUT CIRCUITS menus, this fire panel will allow you to assign a release circuit type
of operation to any two of the four output circuits. Up to two releasing circuits (or hazards), called
RELEASE 1 and RELEASE 2, may be created. Input zones may be assigned in various ways to
activate either one or both of the release circuits. The fire panel treats RELEASE 1 and RELEASE
2 functions independently from each other, although they may share input circuits for activation.
Cross-zoning is set up in the CROSS INPUT ZONES menus, where you can create up to three
groups of input zones for each release circuit. When cross zone groups have been set up, the
OUTPUT CIRCUIT MAP associated with the input zones will automatically show YES for release
output circuits. This extremely flexible cross-zone with grouping capability is used in the
following examples.
Example 3: A single hazard, cross-zoned application using two smoke detector input zones and
one releasing output circuit. Input Zones 1 and 2 are cross-zoned to activate output circuit 2, which
is programmed as a RELEASE 1.
•
•
•
•
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as alarm NAC using the OUTPUT CIRCUITS menus
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Either of smoke detector Input Zones 1 or 2 will directly activate Output Circuit 1 (Alarm
NAC).
•
Smoke detector Input Zone 2 will also directly activate Output Circuit 3 (Alarm NAC) but
not Output Circuits 2 or 4.
•
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate
Output Circuit 2 (Release 1) but not Output Circuit 4.
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 2 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=RELEASE 1
YES
3=ALARM NAC
NO
OUTPUT MAP ZONE 2
1=ALARM NAC
YES
2=RELEASE 1
YES
3=ALARM NAC
YES
OUTPUT MAP ZONE 1
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 2
1=SUPV BELL NAC
N/A
REL 1 CROSS GROUP 1
1=ZONE 1
YES
2=ZONE 2
YES
3=ZONE 3
NO
PDRP-2001 Series PN 53043:A 5/08/2007
105
Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output
circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as
RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is
programmed as a RELEASE 2.
•
•
•
•
•
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm
NAC) but not Output Circuits 2, 3 or 4.
•
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate
Output Circuit 2 (Release 1) but not Output Circuits 3 or 4.
•
Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate
Output Circuit 3 (Release 2) but not Output Circuits 2 or 4.
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 3 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 2 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 4 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=RELEASE 1
YES
3=RELEASE 2
NO
OUTPUT MAP ZONE 2
1=ALARM NAC
YES
2=RELEASE 1
YES
3=RELEASE 2
NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 2
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 3
1=ALARM NAC
YES
2=RELEASE 1
NO
3=RELEASE 2
YES
OUTPUT MAP ZONE 4
1=ALARM NAC
YES
2=RELEASE 1
NO
3=RELEASE 2
YES
OUTPUT MAP ZONE 3
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 4
1=SUPV BELL NAC
N/A
REL 1 CROSS GROUP 1
1=ZONE 1
YES
2=ZONE 2
YES
3=ZONE 3
NO
REL 2 CROSS GROUP 1
1=ZONE 1
NO
2=ZONE 2
NO
3=ZONE 3
YES
REL 2 CROSS GROUP 1
1=ZONE 4
YES
2=ZONE 5
NO
3=ZONE 6
NO
106
PDRP-2001 Series PN 53043:A 5/08/2007
Input-to-Output Circuit Mapping and Cross-Zone Operation
Circuit Mapping and Cross-Zoning
A.1.3 Complex Examples of Cross Zoning and I/O Mapping for
Release Circuits
Following are some complex examples of cross-zoning for more demanding applications that are
possible with this fire panel. Input zone entries in a single cross-zone group are effectively
AND’ed together while the cross-zone groups are effectively OR’ed together. For the purpose of
describing this, the following language is used:
R1
=
RELEASE 1
R2
=
RELEASE 2
Z1
=
INPUT ZONE 1
Z2
=
INPUT ZONE 2
Z3
=
INPUT ZONE 3
Z4
=
INPUT ZONE 4
Z5
=
INPUT ZONE 5
Z6
=
INPUT ZONE 6
OR
=
any input zone may cause a release
AND
=
all input zones must be active for a release
Example 5: Release Circuit 1 activates if either Input Zone 1 or 2 are active in addition to Input
Zone 3 being active.
•
R1 = (Z1 AND Z3) OR (Z2 AND Z3)
•
Set Zones 1 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT
ZONES menus.
•
Set Zones 2 and 3 to YES in Cross Zoning Group 2 for RELEASE 1 in the CROSS INPUT
ZONES menus.
•
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS
INPUT ZONES menus.
Example 6: Release Circuit 1 activates if Input Zones 1 and 2 and 3 are all active.
•
R1 = Z1 AND Z2 AND Z3
•
Set Zones 1, 2 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT
ZONES menus.
•
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS
INPUT ZONES menus.
Example 7: Release Circuit 1 activates if Input Zones 1 and 2 and 3 are all active. Release Circuit
2 activates if Input Zones 2 and 3 and 4 are all active.
•
R1 = Z1 AND Z2 AND Z3
•
R2 = Z2 AND Z3 AND Z4
•
Set Zones 1, 2 and 3 to YES in Cross Zoning Group 1 for RELEASE 1 in the CROSS INPUT
ZONES menus.
•
Set Zones 2, 3 and 4 to YES in Cross Zoning Group 1 for RELEASE 2 in the CROSS INPUT
ZONES menus.
•
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 1 in the CROSS
INPUT ZONES menus.
•
Set all other zones to NO in Cross Zoning Groups 1, 2 and 3 for RELEASE 2 in the CROSS
INPUT ZONES menus.
Example 8: Release Circuit 1 activates if Input Zone 1 activates followed in time by Input Zone 2
activating.
•
This kind of sequential reaction is not possible at this time.
PDRP-2001 Series PN 53043:A 5/08/2007
107
FACP Configuration Templates
APPENDIX B
Input-to-Output Circuit Mapping and Cross-Zone Operation
FACP Configuration Templates
The PDRP-2001 has been provided with preprogrammed templates which allow the user to quickly
configure the FACP [refer to "FACP CONFIG (Application Templates)" on page 50]. The user
also has the option to reprogram selected portions of the template for customized applications. The
following pages of this appendix describe the programming for each of the templates.
Note: PDRP-2001 Pre-Action/Deluge Control Panel can be configured using preprogrammed
Templates 7 through 13 only. Template 7 is the factory default template for the FACP.
(Templates 1 through 6 are not available for this panel.)
Important! Each Template has been programmed with specific Input Zone Types and Output
Circuit Types. If the FACP is configured with one of the preprogrammed Templates, the user must
ensure that the devices connected to each Input Zone and Output Circuit are compatible with the
programmed types. (The user can reprogram the circuit types if desired).
108
PDRP-2001 Series PN 53043:A 5/08/2007
Template 7: Single Hazard - 3 Zone
FACP Configuration Templates
B.1 Template 7: Single Hazard - 3 Zone
TEMPLATE 7: SINGLE HAZARD - 3 ZONE
INPUT ZONES
1
2
3
2-WIRE SMOKE
FIRE
WATERFLOW
OUTPUT CIRCUITS
#1 ALARM NAC
#2 WATERFLOW NAC
#3 RELEASE SOLENOID 1
#4 SUPV. BELL NAC
X
X
X
X
4
MANUAL
RELEASE
X
5
PULL
STATION
X
X
X
6
SUPV.
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - no waterflow delay since Waterflow Delay Timer is set to 0
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Supervisory
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - no waterflow delay since Waterflow Delay Timer is set to 0
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Supervisory Bell NAC
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 0 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#3. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
no FACP initiated delay in activation since the Waterflow Delay Timer is set to 0 seconds
•
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
•
Trouble Relay - any system trouble will activate the Trouble Relay
•
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
109
FACP Configuration Templates
Template 8: Single Hazard - Cross-Zone With Manual Release
B.2 Template 8: Single Hazard - Cross-Zone With Manual Release
OUTPUT CIRCUITS
#1 ALARM NAC
#2 WATERFLOW NAC
#3 RELEASE SOLENOID 1
#4 SUPV. BELL NAC
TEMPLATE 8: CROSS-ZONE WITH MANUAL RELEASE SWITCH
INPUT ZONES
1
2
3
4
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
X
X
X
X
C1
C1
X
5
PULL
STATION
X
6
SUPV.
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid
number must be active at the same time to turn on the corresponding solenoid output circuit
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 60 seconds (Waterflow Delay set to 60 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Supervisory
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 60 seconds (Waterflow Delay set to 60 sec)
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Supervisory Bell NAC
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 60 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
•
•
Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #3.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer
1. Activation of any one of these zones will operate Alarm NAC Output #1
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 60 second FACP initiated delay in activation since Waterflow Delay Timer is set to 60
seconds
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
•
•
110
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
Template 9: Dual Hazard - Combined Release
FACP Configuration Templates
B.3 Template 9: Dual Hazard - Combined Release
OUTPUT CIRCUITS
#1 ALARM NAC
#2 SUPV BELL NAC
#3 RELEASE SOLENOID 1
#4 RELEASE SOLENOID 2
TEMPLATE 9: DUAL HAZARD - COMBINED RELEASE
INPUT ZONES
1
2
3
4
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
X
X
X
X
5
PULL
STATION
X
6
SUPV.
X
X
X
X
X
X
X
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Supervisory
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Supervisory Bell NAC
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1, Release Solenoid 1 Output #3
and Release Solenoid 2 Output #4. Release Solenoid 1 will turn off water release following
time-out of the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release
following time-out of the 10 minute Soak Timer 2
•
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
•
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #2
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
•
Trouble Relay - any system trouble will activate the Trouble Relay
•
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
111
FACP Configuration Templates
Template 10: Dual Hazard - Split Release
B.4 Template 10: Dual Hazard - Split Release
TEMPLATE 10: DUAL HAZARD - SPLIT RELEASE
INPUT ZONES
1
2
3
4
2-WIRE SMOKE
FIRE
WATERFLOW
SUPV.
OUTPUT CIRCUITS
#1 ALARM NAC
#2 SUPV BELL NAC
#3 RELEASE SOLENOID 1
#4 RELEASE SOLENOID 2
X
X
X
5
MANUAL
RELEASE
X
6
PULL
STATION
X
X
X
X
X
X
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to secs.)
Zone 4 = Supervisory
Zone 5 = Manual Release
Zone 6 = Pull Station
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Supervisory Bell NAC
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and
Alarm NAC Output #1. Activation of Input Zone 2 (Fire) will operate Release Solenoid 2
Output #4 and Alarm NAC Output #1. Activation of Input 5 (Manual Release) or Input 6
(Manual Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and
Alarm NAC Output #1. Release Solenoid 1 will turn off water release following time-out of
the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release following
time-out of the 10 minute Soak Timer 2
•
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
•
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
•
•
112
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 5 (Manual Release) or Zone 6 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 4 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
Template 11: Single Hazard - 3 Zones and Low Pressure
FACP Configuration Templates
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure
OUTPUT CIRCUITS
#1 ALARM NAC
#2 WATERFLOW NAC
#3 SUPV. BELL NAC
#4 RELEASE SOLENOID 1
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
1
2
3
4
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
X
X
X
X
5
PULL
STATION
X
6
LOW
PRESS.
X
X
X
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Low Pressure
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
Output 3 = Supervisory Bell NAC
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
•
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
•
Trouble Relay - any system trouble will activate the Trouble Relay
•
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
113
FACP Configuration Templates
Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
B.6 Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
TEMPLATE 12: SINGLE HAZARD - 2 ZONES CROSS-ZONES WITH ALL ACTIVE
INPUT ZONES
1
2
3
4
5
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
PULL
RELEASE
STATION
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
#4 RELEASE SOLENOID 1
C1
C1
X
X
6
LOW
PRESS.
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid
number must be active at the same time to turn on the corresponding solenoid output circuit
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Low Pressure
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Output 3 = Supervisory Bell NAC
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #4.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer
1. Activation of any one of these zones will operate Alarm NAC Output #1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
•
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
•
•
114
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
Template 13: Single Hazard - Dual Zone
FACP Configuration Templates
B.7 Template 13: Single Hazard - Dual Zone
OUTPUT CIRCUITS
#1 ALARM NAC
#2 WATERFLOW NAC
#3 RELEASE SOLENOID 1
#4 WATERFLOW NAC
TEMPLATE 13: SINGLE HAZARD - DUAL ZONE
INPUT ZONES
1
2
3
4
2-WIRE SMOKE
FIRE
LOW
WATERFLOW
PRESS.
X
X
X
X
X
X
X
5
PULL
STATION
X
6
MANUAL
RELEASE
X
X
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
•
•
•
•
•
•
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Low Pressure
Zone 4 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 5 = Pull Station
Zone 6 = Manual Release
Output Circuit Types:
•
•
•
•
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Timers
•
•
•
•
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 5 (Pull Station) or
Zone 6 (Manual Release) will operate the Alarm NAC Output #1 and Release Solenoid 1
Output #3. Release Solenoid will turn off water release following time-out of the 10 minute
Soak Timer 1
•
Activation of Input Zone 4 (Waterflow) will operate the Alarm NAC Output #1, Waterflow
NAC Output #2 and Waterflow NAC Output #4. There is a 10 second FACP initiated delay
in activation of these outputs since the Waterflow Delay Timer is set to 10 seconds
•
Activation of Input Zone 3 (Low Pressure) will not operate any Output Circuits (see Relays)
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
•
•
•
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 3 (Low Pressure) will operate the Supervisory Relay
PDRP-2001 Series PN 53043:A 5/08/2007
115
NFPA Standard-Specific Requirements
Template 13: Single Hazard - Dual Zone
NFPA Standard-Specific Requirements
APPENDIX C
This panel has been designed for use in commercial, industrial and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:
PDRP-2001/E Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.
Batteries
Refer to "Power Supply Calculations" on page 99, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to one of the control panel's Output Circuits.
Releasing Devices
Connected to one of the control panel's Output Circuits.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
411UD may be installed as illustrated in Figure C.1, “FACP Connection to 411UD,”
on page 117
OR
4XTM Transmitter Module for connection to the RS82 Remote Station Receiver.
See Figure C.3 on page 120, for installation instructions for this unit
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled "4XTM Municipal Box Transmitter
Option Module" on page 28 and as outlined in Figure C.2, “Municipal Box Connected to 4XTM
Transmitter Module,” on page 119.
NFPA 72 Proprietary Fire Alarm System
FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.4,
“Proprietary Protective Signaling System,” on page 121, for installation instructions for this unit.
The relay contacts of this control panel may be used to trip any dialer that is UL-listed for Central
Station/Remote Station services. The illustrations in this appendix provide examples of possible
system configurations.
116
PDRP-2001 Series PN 53043:A 5/08/2007
Template 13: Single Hazard - Dual Zone
NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the PDRP-2001/E may be used to trip any dialer UL-listed for
Central Station/Remote Station Reporting Services.
411UD
Channel1
Channel 2
Channel 3
Channel 4 (2.2K ELR)
Jumper -VDC to Trouble Relay contact
+ 24 VDC nonresettable power
- 24 VDC nonresettable power
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
J4 Not Installed
Relay Output (DACT Trouble) from 411UD
FACP Supervisory Relay
FACP Trouble Relay
FACP Alarm Relay
2.2K ELRs P/N 27070
123456789
FACP
Trouble Input
(nonsupervised,
power-limited)
Figure C.1 FACP Connection to 411UD
PDRP-2001 Series PN 53043:A 5/08/2007
117
NFPA Standard-Specific Requirements
Template 13: Single Hazard - Dual Zone
Alarm
Trouble
Supervisory
411UD
FACP
TB2-1
TB8-1
TB2-2
TB8-3
TB2-3
TB8-4
TB2-4
TB8-6
TB2-5
TB8-7
TB2-6
TB8-9
Table C.1 411-UD Connections to FACP
Notes:
1. Reference the 411UD Manual for additional information.
2. All connections between the control panel and the 411UD must be in conduit, less than 20 ft.
(610 cm) in length in the same room.
3. Any zone of the 411UD can be wired to function as alarm, trouble or supervisory; the 411UD
must be programmed accordingly. In this example, Channel/Zone 1 is wired to the control
panel’s alarm relay, Channel 2/Zone 2 is wired to the control panel’s trouble relay and
Channel 3/Zone 3 is wired to the control panel’s supervisory relay.
4. Nonresettable 24 VDC power is supplied to the 411UD via TB9 terminals configured for
nonresettable power on the FACP. Jumper J4 on the 411UD must be removed for 24 VDC
power.
5. End-of-Line resistors must terminate all 411UD circuits, including unused circuits.
6. Program the 411UD for slave operation.
7. The PDRP-2001/E must be programmed for AC Loss Reporting Delay This prevents the
immediate transmission of a trouble on the loss of AC power.
8. A (-)VDC from the 411UD Trouble Contacts will activate the Trouble Input J6 on the FACP.
118
PDRP-2001 Series PN 53043:A 5/08/2007
NFPA 72 Auxiliary Fire Alarm System
NFPA Standard-Specific Requirements
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the PDRP-2001/E main circuit board to supervise placement of 4XTM module
and circuit.
3. Cut JP24 on the PDRP-2001/E main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTM Municipal Box Transmitter Option Module" on page 28 for detailed
information.
Figure C.2 Municipal Box Connected to 4XTM Transmitter Module
FIRE
+
Municipal Box
Circuit
Gamewell Model M34-56
Local Energy Municipal Box
Polarities shown in alarm condition
Nonpower-limited
+
-
4XTM
Figure A.2 Municipal Box Connected to 4XTM Transmitter Module
PDRP-2001 Series PN 53043:A 5/08/2007
119
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the PDRP-2001/E main circuit board to supervise placement of the
4XTM module.
2. Refer to "4XTM Transmitter Module Installation" on page 29 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
+
-
Polarity Shown is
Normal Standby
+
Power-limited
(Dummy load with a 4.7KΩ, ¼ watt
resistor when no connection is made)
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
4XTM Transmitter Module
Figure C.3 Remote Station Connection Using 4XTM Module
120
PDRP-2001 Series PN 53043:A 5/08/2007
NFPA 72 Auxiliary Fire Alarm System
NFPA Standard-Specific Requirements
NFPA 72 Proprietary Protective Signaling Systems
Fire Alarm Control Panel
FACP Main Circuit Board
Form-C Alarm contact programmed to
activate on General Alarm.
Form-C Trouble contact which will
automatically activate on any Trouble
condition.
Form-C relay contact programmed to
activate on Supervisory condition.
Notes:
1. Connection between the FACP and the
transmitter are supervised by the transmitter.
2. This FACP/Transmitter arrangement can be
employed for NFPA 72 Proprietary
Protective Signaling System.
Figure C.4 Proprietary Protective Signaling System
PDRP-2001 Series PN 53043:A 5/08/2007
121
NFPA Standard-Specific Requirements
Central Station/Remote Station Transmitter: Connection to FACP Dry
C.2 Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts
The dry contacts of the PDRP-2001/E programmable relays can be used to trip a UL-864 Listed
Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.
Typical Central Station/Remote Station Transmitter Module
Trouble*
Superv.
Alarm
Typical Input Zone Triggers
*Note: The Trouble Relay is a
fail-safe relay. With power
applied to the FACP and no
troubles in the panel, the wiring
should be connected to the NO
and C contacts as indicated in the
illustration.
rp2002drysmit.cdr
Fire Alarm Control Panel
Figure C.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
122
PDRP-2001 Series PN 53043:A 5/08/2007
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts
APPENDIX D
FACP with Keltron
FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron Reveiver/
Transmitter.
CAUTION! For reasons of wiring diagram clarity, terminal designations of Keltron modules are
not shown in actual order. Follow Keltron manual and module markings for exact terminal
locations to prevent severe module damage!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
*Note: For more information,
refer to Keltron manual.
Sprinkler Supervisory Signal
Alarm/Trouble Signal
4XTM Module
Note: Cut TBL jumper on 4XTM module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in
their actual positions in order to
clarify wiring connections)
PDRP-2001 Series PN 53043:A 5/08/2007
123
Testing & Maintenance
APPENDIX E
Testing
Testing & Maintenance
E.1 Testing
E.1.1 Inspection
Once installation has been completed, a careful visual inspection should be made before applying
power to the system. Check the actual wiring hookup with the wiring diagrams. Insure that no
pieces of wire have fallen into the circuitry. Check for missing or damaged parts.
E.1.2 Alarm Test
An initial alarm test should be conducted following installation to determine that all parts of the
system are functioning properly. The panels should remain powered for 24 to 36 hours prior to
connecting the releasing solenoids. This precaution will avoid false activation of the suppression
system in case of faulty or improperly placed detectors.
To perform an alarm test on the control panel, proceed with the following steps:
1. Disconnect AC power and battery power
2. Disconnect the installed solenoid valve circuit leads and connect spare solenoid valves or
connect an End-of-Line device to serve as a dummy load
3. Reconnect AC and battery power
4. Initiate a first zone alarm condition by introducing smoke into one of the Zone 1 detectors.
This should cause the first zone alarm condition.
The red Fire Alarm indicator will illuminate
The LCD display will indicate an alarm condition for zone 1
The control panel piezo will sound
The Alarm relay will energize
The devices connected to the Indicating Circuit(s) programmed to activate on Zone 1
alarm will turn on
5. Repeat step 4 for each input zone
6. When testing has been completed, remove AC and battery power, reconnect the solenoid
valve circuits removed in step 2, reconnect AC and battery power and ensure that the control
panel is in normal standby condition
5.4.3 Detector Testing
Detectors must be tested after installation and following maintenance.
Important: Before testing, notify the proper authorities that maintenance is being performed and
the system will be temporarily out of service. Disable the zone or system undergoing maintenance
to prevent any unwanted alarms. Disconnect the installed solenoid valve circuit leads and connect
spare solenoid valves or connect an End-of-Line device to serve as a dummy load to prevent
unwanted water release.
Ensure proper wiring and power is applied. After power-up, allow 80 seconds for the detectors to
stabilize before testing. Refer to System Sensor’s i3 Installation and Maintenance Instructions
document I56-1800-00 for device specifications and testing procedures.
124
PDRP-2001 Series PN 53043:A 5/08/2007
Maintenance
Testing & Maintenance
Test i3 Series detectors as follows:
Test Switch
1. An opening for the recessed test switch is located on the detector housing.
2. Insert a small screwdriver or allen wrench (0.18” max.) into the test switch opening; push
and hold.
3. If the detector is within the listed sensitivity limits, the detector’s red LED should light
within five seconds.
Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke
through the detector until it alarms.
Note: For the above tests, the detector will reset only after the power source has been momentarily
interrupted.
If a detector fails any of the above test methods, its wiring should be checked and it should be
cleaned as outlined in the Maintenance section of the System Sensor Document. If the detector still
fails, it should be replaced.
Notify the proper authorities when the system is back in service.
E.2 Maintenance
A regular schedule of inspection, testing and maintenance is vital to ensure proper and reliable
operation of the control panel. The procedures should be performed as required by the local
authority having jurisdiction. Refer to NFPA documentation for further details.
PDRP-2001 Series PN 53043:A 5/08/2007
125
Compatible Devices
APPENDIX F
Compatible Two-Wire Smoke Detectors (UL Listed)
Compatible Devices
Compatible Two-Wire Smoke Detectors (UL Listed)
Detector
ID
Detector
Type
Base
Model
Base
ID
Standby
Current (uA)
System Sensor 2W-B
A
Photoelectric I3
N/A
N/A
120
System Sensor 2WT-B
A
Photoelectric I3
N/A
N/A
120
System Sensor 1100/D
A
Ionization
N/A
N/A
100
System Sensor 1151
A
Ion
B401 / B110LP /
B116LP
A
120
System Sensor 1400
A
Ion
N/A
N/A
100
Model
System Sensor 1451
A
Ion
B401B / B406B
A
120
System Sensor 1451DH
A
Ion
DH-400
A
120
System Sensor 1800
A
Ion
N/A
N/A
120
System Sensor 1851B
A
Ion
B101B / B107B
A
120
System Sensor 1851DH
A
Ion
DH1851DC
A
120
System Sensor 2151
A
Photo
B401 / B110LP /
B116LP
A
120
System Sensor 2300T
A
Photo / Therm.
N/A
N/A
120
System Sensor 2400
A
Photo
N/A
N/A
120
System Sensor 2400AIT
A
Photo / Iso. Therm. /
Horn
N/A
N/A
120
System Sensor 2400AT
A
Photo / Therm. / Horn
N/A
N/A
120
System Sensor 2400TH
A
Photo / Therm.
N/A
N/A
120
System Sensor 2451
A
Photo
B401B / B406B
DH-400
A
120
System Sensor 2451TH
A
Photo / Therm.
B401B / B406B
A
120
System Sensor 2800
A
Photo
N/A
N/A
120
System Sensor 2800TH
A
Photo / Therm.
N/A
N/A
120
System Sensor 2851B
A
Photo
B101B / B107B
A
120
System Sensor 2851BTH
A
Photo / Therm.
B101B / B107B
A
120
System Sensor 2851DH
A
Photo
DH2851DC
A
120
System Sensor 2100/D/S
A
Photoelectric
N/A
N/A
120
System Sensor 2100T/D/S
A
Photoelectric
N/A
N/A
120
System Sensor DH100P
A
Photoelectric
N/A
N/A
100
System Sensor DH100LP
A
Photoelectric
N/A
N/A
120
System Sensor 2WTA-B
A
Photoelectric
N/A
N/A
100
System Sensor 2WTAR-B
A
Photoelectric
N/A
N/A
100
126
PDRP-2001 Series PN 53043:A 5/08/2007
Maximum Number of Detectors per Zone
Compatible Devices
Maximum Number of Detectors per Zone
When using two-wire smoke detectors containing supplementary relays or indicators, the operation
of more than one detector per zone cannot be ensured
Base
Model
Model Number
PDRP-2001 Series PN 53043:A 5/08/2007
Number of
Devices
2W-B
N/A
16
2WT-B
N/A
16
1100/D
N/A
1151
B401/B110LP/
B116LP
20
1400
N/A
1451
B401B / B406B
1451DH
DH-400
1800
N/A
N/A
1851B
B101B
N/A
1851B
B107B
N/A
1851DH
DH1851DC
16
2100/D/S
N/A
16
16/16/1
20
16/ 1
16
2100T/D/S
N/A
2151
B401/B110LP/
B116LP
16
2300T
N/A
16
2400
N/A
16
2400AIT
N/A
1
2400AT
N/A
1
2400TH
N/A
16
2451
B401B / B406B
2451
DH-400
2451TH
B401B / B406B
16/1
2800
N/A
N/A
2800TH
N/A
N/A
2851B
B101B
N/A
2851B
B107B
N/A
2851BTH
B101B
N/A
2851BTH
B107B
N/A
2851DH
DH2851DC
16
DH100P
N/A
16
DH100LP
N/A
16
2WTA-B
N/A
20
2WTA-RB
N/A
1
16/16/1
16/1
16
127
Compatible Devices
Four-Wire Smoke Detectors/Devices (UL Listed)
Four-Wire Smoke Detectors/Devices (UL Listed)
Smoke Detector/Base
Detector Type
Max Standby
Current (mA)
Alarm
Current (mA)
System Sensor B112LP
System Sensor B114LP
System Sensor B404B
System Sensor DH100ACDC
System Sensor DH100ACDCLP
System Sensor DH100ACDCLWP
Base
Base
Base
Photoelectric
Photoelectric
Photoelectric
Ionization Duct
0.12
*
*
0.15
0.15
0.15
25
36
*
*
0.70
0.70
0.70
95
Photoelectric Duct
25
95
Ionization
Ionization
Ionization
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric w/135° Thermal
Photoelectric w/135° Thermal
Supervisory Relay
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
0.05
0.10
0.10
0.50
0.50
0.05
0.50
0.50
0.05
15
50
41
39
60/70
60/70
50
60/70
60/70
50
45
0.12
0.12
0.12
0.12
0.10
50
77
58
77
41
Photoelectric
0.10
41
Photoelectric
Photoelectric
Loop Test/Maintence Mod.
Photoelectric I3
0.10
0.10
30
.05
39
39
50
23
Photoelectric I3 w/Therm
.05
23
System Sensor 4WTA-B (12/24 Volt)
I3 Photo w/ Therm/Sounder
.05
35
System Sensor 4WTR-B (12/24 Volt)
I3 Photo w/ Therm/Relay
.05
35
System Sensor 4WTAR-B (12/24 Volt)
I3 Photo w/ Therm/
Sounder/Relay
.05
50
System Sensor 4WITAR-B (12/24 Volt)
I3 Photo w/ IsolatedTherm/
Sounder/Relay
.05
50
System Sensor 2W-MOD2
I3 Loop Test/Maintence
Mod.
.05
*
System Sensor RRS-MOD
I3 Reversing Relay/Sync
Module
Projected Beam
.05
*
10
28.4
Projected Beam
17
38.5
System Sensor DH400ACDCI1
System Sensor DH400ACDCP1
System Sensor 1112/24/D
System Sensor 1424
System Sensor 1451 (w/B402B Base)
System Sensor 2112/24ATR
System Sensor 2112/24AITR
System Sensor 2112/24/D
System Sensor 2112/24R
System Sensor 2112/24TR
System Sensor 2112/24T/D
System Sensor 2112/24TSRB
System Sensor 2312/24TB
System Sensor 2412 (12 volt)
System Sensor 2412AT (12 volt)
System Sensor 2412TH (12 volt)
System Sensor 24241
System Sensor 2424TH1
System Sensor 2451
System Sensor 2451TH (with/B402B Base)
System Sensor 2W-MOD
System Sensor 4W-B (12/24 Volt)
System Sensor4WT-B (12/24 Volt)
System Sensor 64241
System Sensor Beam 1224(S)
* Contact manufacturer for current draws
128
PDRP-2001 Series PN 53043:A 5/08/2007
Notification Appliances (UL Listed)
Compatible Devices
Notification Appliances (UL Listed)
Control panels with Notification circuits supplied by Special Purpose (FWR, Filtered) power must
use appliances listed in this table.
•
•
Refer to manufacturer’s installation instructions for more information.
Contact manufacturer for current draws or additional options
System Sensor - 24VDC
MODEL NUMBER & NOMENCLATURE (System Sensor)
CH12/24 Electronic Chime/Sounder
CH2415, CH241575, CH2475, CH24110 SpectrAlert Chime with Strobe
MA-12/24D Electronic Sounder
MA12/24EH Multi Alert Horn with Mechanical Tone
MAEH24LO, MAEH24LOC, MAEH24LOLA, MAEH24M, MAEH24MC, MAEH2415ADA,
MAEH2475ADA, MAEH241575ADA, MAEH24110ADA, MAEH2415ADAS, MAEH241575ADAS
Multi Alert Horn with Mechanical Tone/Strobe
MASS24D, MASS24LO, MASS24M Electronic Sounder/Strobe
MASS24LOC, MASS24MC Electronic Ceiling Sounder/Strobe
MASS24LOLA Electronic Sounder/Strobe with Fuego lens
MASS2415ADA, MASS2475ADA, MASS24110ADA, MASS241575ADA Sounder/Signaling Strobe
MASS2415ADAS, MASS241575ADAS Sounder/Signaling Strobe w/ Synch. Ckt.
MDL / MDLW Sync Modules for use with SpectraAlert series
P2415, P241575, P2430, P2475, P24110 SpectrAlert Horn/Strobe
PA400R Sounder
PC24115, PC24177 SpectrAlert Ceiling Mount Horn/Strobe
PS24LO Add-on Strobe
RP2415ADA, RP241575ADA, RP2475ADA, RP24110ADA Retrofit Strobe Plate
S2415, S241575, S2430, S2475, S24110 SpectrAlert Strobe
SC24115, SC24177 SpectrAlert Ceiling Mount Strobe
SP100W24LOC, SP100W24MC Ceiling Speaker/Strobe, 8"" round grille
SP101R24LO, SP101R24M Speaker/Strobe, 5"" square grille
SP2C24115, SP2C24177 SpectrAlert Ceiling Mount Speaker Strobe
SP2R2415, SP2R2430, SP2R2415/75, SP2R2475, SP2R24110 SpectrAlert Speaker Strobe
S1224MC, P1224MC, SP1224MC SpectrAlert Strobe
SS24, SS24LO, SS24M, Strobe
SSM24-6, SSM24-8, SSM24-10 Alarm Bell
SS24LOC, SS24LOBC(beige), SS24MC Ceiling Strobe
SS2415ADA, SS2475ADA, SS24110ADA, SS241575ADA Signaling Strobe
SS2415ADAS, SS241575ADAS Signaling Strobe with Synch. Circuit
V4R2415ADA, V4R2475ADA, V4R24110ADA, V4R241575ADA Speaker/Signaling Strobe
SPH-15R, SC2415, SC241575, SC2430, SC2475, SC2495, PC2415, PC242575, PC2430, PC2475,
PC2495, SP2C2415, SP2C242575, SP2C495
CH, CHS, HR, P2R, P2RH, P4R, P4RH, PC2R, PC2RH, PC4R, PC4RH, SCR, SCRH, SR, SRH
PDRP-2001 Series PN 53043:A 5/08/2007
129
Compatible Devices
Releasing Applications
Releasing Applications
Manufacturer
Model
Rated Current
DC Milliamps
Rated Voltage
DC Volts
Asco
HV2740607
375
24
Asco
HV2838521
375
24
Versa
CGS-4232-NB3-S2
438
24
Snap-Tite
2823A-2NB-A4F6
458
24
Snap-Tite
2823A-2NB-A4F5
917
12
Kidde-Fenwal
890181
2000
24
Viking
11591
417
24
Viking
11595
417
24
Barnbrook Systems
EA45
200
24
Honeywell/
Skinner
701X7028
917
24
TLX
PA0036-A
600
24
Door Holders (UL Listed)
MANUFACTURER
MODEL
Current
(mA)
TYPE
Edwards
DH150A
Floor Mount
96
Edwards
DH154A
Flush Mount
96
Edwards
DH158A
Surface Mount
96
Rixon Firemark
FM-980
Floor Mount, single
68
Rixon Firemark
FM-996
Surface Wiring
68
Rixon Firemark
FM-998
Concealed Wiring
68
Relays (UL Listed)
MANUFACTURER
System Sensor
130
MODEL
A77-716B
Current
(mA)
20
PDRP-2001 Series PN 53043:A 5/08/2007
Index
Numerics
2nd-Shot Water Switch 52
4XTM 120
A
ANN-BUS
wiring distance 30
AC Loss Delay 65, 67
AC power 20
AC power rating 13
AC power requirements 99
accessories 16
ACK
see also Acknowledge 12
Acknowledge 12
Acknowledge/Step 14, 85
Adjective
list 54
multiple entries 56
Alarm 88
alarm
piezo pulse rate 15
alarm relay 11, 24
contact rating 13
Alarm Silence 12, 14, 85
ANN-BUS 98
auto-configure 73
aux. power 33
device addressing 33
wiring configuration 32
wiring distance chart 31
ANN-BUS Devices 30
ANN-BUS devices 11
ANN-BUS modules 72
ANN-BUS wiring 30
ANN-I/O
LED zone assignments 75
ANN-LED 43, 45
ANN-LED Annunciator Module 41
ANN-S/PG module 97
auto-configure
ANN-BUS 73
Autosilence
NAC 60
Autosilence Timer 91
auxiliary power 24
Auxiliary Trouble Input 13
B
backbox
dimensions 15
mounting 17
Banner 64
setting 67
battery 15, 20
precautions 20
rating 13
battery box 16
battery calculations 102
PDRP-2001 Series PN 53043:A
5/08/07
buttons
see also control buttons 12
C
cabinet
mounting 17
cabinet dimensions 18
cabinet mounting 19
CAC-5X 21
California 62
charger capacity 13
Charger Disable 64
charger disable 70
circuits 11
Class A 16, 21, 27
Class A Converter Module 16
installation 26
Class B 11, 13, 21
clear programming 80
Clock Format 69
Coded Operation 90
Coding
NAC 61
combination circuit 22
combination waterflow/supervisory 22
requirements 22
wiring 22
compatibility
see also device compatibility 11
configuration
programming 50
Control Buttons 85
control buttons 12
controls 14
cross input zones 63, 94
Cross-Zone 62
cross-zoning 63
current
nonresettable power 24
resettable power 24
total output 23
current requirements for system 100, 101
D
Date setting 69
Daylight Savings 96
Daylight Savings Time 70
Description
detector label 55
description 11
Detector
adding description 53
enable/disable 51
detector functions 90
device compatibility 11
dimensions
backbox 15
Disable Release 46, 52
Disable/Enable 89
131
Index
DP-51050LED Dress Panel 16
dress panel 12, 16
Drill 12, 14, 85
E
earth ground 20
edit
detector screens 51
Enable/Disable 82
zone 51
End-of-Line resistor
IDC 13, 21, 22
NAC 13, 23
Enter key 48
Erase History 78
exiting
programming 47, 48
Read Status 47, 48
F
FACP configuration 50
fail-safe
trouble relay 24
features 11
Form-C
see also relay 11
freeze 21, 89
freeze signal
see also smoke detector monitoring 11
H
History 78, 97
erase 78
Maintenance Level 82
view events 78
history log 11
I
I3 detectors 21
IDC 11, 13, 21
alarm current 13
compatibility 21
End-of_Line resistor 22
End-of-Line resistor 13, 21
maximum loop resistance 13, 21
short circuit current 13
standby current 13
wiring 21
Indicator
AC Power 12, 15
Alarm Silence 12, 15
discharge 12, 15
Fire Alarm 12, 15
Supervisory 12, 15
System Trouble 15
Trouble 12
indicator
AC Power 86
Alarm Silenced 86
discharge 86
Fire Alarm 86
132
Supervisory 86
Trouble 86
Indicators 15
indicators 12, 14
Initiating Device Circuit 11, 13, 21
Class A 27
In-Line resistor
IDC combination circuit 22
input zone types 52
Input Zones 50, 93
installation 17
4XTM 29
class A converter module 26
option modules 26
transmitter module 28
J
J4 and J5
option module connectors 28
JP30 jumper
placement supervision 28
K
Key Panel 14
function keys 14
service/program keys 14
L
lamp test 14
LCD display 11, 14
LED annunciator module 16
LED driver module 16, 39
connections 40
specifications 39
wiring LEDs 41
LED option module
LED zone assignments 75
M
Main 10
maintenance 21
piezo pulse rate 15
Maintenance Alert 90
Maintenance Program Level 2 47, 81
maintenance signal
see also smoke detector monitoring 11
Manual programming 46
Map 53
March Time 62
Master Program Level 1 47, 49
Mode key 48
Mounting
main circuit board 17
mounting
cabinet 17
municipal box 29
municipal box transmitter
see also 4XTM 16
N
NAC 11, 13
Auto Silence 60
PDRP-2001 Series PN 53043:A
5/08/07
Index
coded 90
current 23
End-of-Line resistor 13, 23
maximum current 13
programmable 12
synchronized 62
wiring 23
NFPA 72 Auxiliary Fire Alarm System 116, 119
NFPA 72 Central Station Service (Protected Premises
Unit) or Remote Station Service 116
NFPA 72 Proprietary Fire Alarm System 116
NFPA 72 Proprietary Protective Signaling Systems 121
NFPA 72 Remote Station Protective Signaling System
120
NFPA Standard 116
nonpower-limited wiring 25
nonresettable power 11, 14, 24
current 24
maximum current 14
Normal 86
normal display 46
Notification Appliance Circuit 11, 13, 23
Class A 27
Noun
list 55
multiple entries 56
Noun/Adjective 53, 55
O
Operating Instructions 85
Operation
alarm 88
disable/enable 89
normal 86
supervisory 89
trouble 87
waterflow 89
Option Modules 71
option modules 16
installation 26, 28
Output
coding 61
silence inhibit 60
silenceable 59
output circuit MAP 53
Output Circuits 57
output circuits 23
Output enable/disable 58
output types 58
outputs 12
P
Password 48
change 80
Maintenance Level 2 48, 81
Master Level 1 48
Piezo
see also sounder 15
piezo 15
PDRP-2001 Series PN 53043:A
5/08/07
alarm 15
maintenance 15
see also sounder 12
supervisory 15
trouble 15
polarity reversal circuit
see also transmitter module 29
power 13, 20, 24
primary 20
secondary
see also battery 20
power supply calculations 99
power-limited wiring 25
Power-up
first time 47
printer connection 38
printer module 16, 37
installation 37
specifications 37
printer options 38, 73
Program
clear 80
program keys
see also Key Panel 14
Programming 46
autoprogramming 46
exiting 47
Level 1 47
Level 2 47
manual 46
Master Level 1 49
Programming Levels 47
Programming Screens 47
R
Read Status 46, 92
ANN-BUS 98
Configuration 93
Cross Input Zones 94
exiting 47
history 97
Input Zones 93
input zones 93
NAC 94
Output Circuits 94
Print 97
relay 95
Real-Time Clock 90
Recall/Increment Function 56
Relay
Form-C 64
programming 64
relay 11, 24
contact rating 13, 24
relay module 16
Relays 64, 95
Release Circuit 58
Release Stage 91
133
Index
Release Stage NAC 59
releasing circuit 13
releasing solenoid 12
releasing solenoids 11
remote LCD annunciator
installation 34
programming 36, 76
specifications 34
wiring 35
remote station service 29
Remote Station Transmitter Connection to FACP Dry
Contacts 122
Reset 12, 14, 85
resettable power 11, 13, 24
current 24
maximum current 13
reverse polarity circuit
see also 4XTM 16
S
Silence Inhibit 60
Silence Inhibit Timer 91
Silenceable
Output 59
silenceable circuits
synchronized signals 59
soak timer 65, 66
Soak Timers 91
sounder 12, 15
sprinkler standards
NFPA 12
Steady 62
strobes 12, 62
maximum 62
Style B 13, 21
see also Class B 11
Style D 16, 21, 27
Style Y 13
see also Class B 11
Style Z 16, 27
subscreen 47
supervision
transmitter option module placement 28
Supervisory 11, 89
supervisory
piezo pulse rate 15
supervisory relay 24
contact rating 13
Synchronization 62
synchronization 62
Synchronized 62
synchronized 62
synchronized signals 62
and silenceable circuits 59
system current calculations 100
System Settings 95
System Setup 64
134
T
Temporal 62
Time setting 69
Time-Date
Maintenance Level 84
Time-Date setting 64, 68
Timers 64, 96
timers 65
Transmitter Module 16
transmitter module 29
installation 28, 29
operation 29
specifications 29
transmitter option module
placement supervision 28
trim ring 16
Trouble 87
trouble
piezo pulse rate 15
Trouble Input
Auxiliary 13
trouble relay 11, 24
contact rating 13
fail-safe 24
Trouble Reminder 64, 70, 91
Type
zone 51
type
zone 51
types
outputs 58
U
UL
wiring requirements 25
V
View Events 78
W
Walktest 79, 91
audible 79
Maintenance Level 83
operation 91
silent 79
Waterflow Delay timer 65, 66
Waterflow DelayTimer 91
waterflow/supervisory circuit 22
wiring
ANN-BUS 30
class A converter module 27
Class A IDC 27
Class A NAC 27
combination waterflow/supervisory 22
IDC 21
NAC 23
nonpower-limited 25
power-limited 25
UL requirements 25
PDRP-2001 Series PN 53043:A
5/08/07
Index
Z
Zone
type 51
Zone Setup
Maintenance Level 82
zone type
inputs 52
PDRP-2001 Series PN 53043:A
5/08/07
135
Notes
136
PDRP-2001 Series PN 53043:A 5/08/2007
Notes
PDRP-2001 Series PN 53043:A 5/08/2007
137
Notes
138
PDRP-2001 Series PN 53043:A 5/08/2007
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen
(18) months from the date of manufacture, under normal use and
service. Products are date stamped at time of manufacture. The sole
and exclusive obligation of Honeywell International Inc. is to repair
or replace, at its option, free of charge for parts and labor, any part
that is defective in materials or workmanship under normal use and
service. All returns for credit are subject to inspection and testing at
the factory before actual determination is made to allow credit.
Honeywell International Inc. does not warrant products not
manufactured by it, but assigns to the purchaser any warranty
extended by the manufacturer of such products. This warranty is void
if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell
International Inc. in writing, or is serviced by anyone other than
Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our
Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products.
Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended. Buyer
acknowledges that Honeywell International Inc., is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS
BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF
THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS.
FURTHERMORE,
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL
OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by Honeywell International Inc. No increase or
alteration, written or verbal, of the obligation of this warranty is
authorized.
Warn-HL-05-2007.fm
3825 Ohio Avenue
St. Charles, IL 60174-5465
1-800-SENSOR2
Fax: (630) 377-6495