GAMEWELL-FCI PK-CD

411UDAC
Features
Digital Alarm Communicator Transmitter
Description
411udac.tif
The Gamewell 411UDAC is a
compact multifaceted, stand-alone
Fire Alarm Communicator designed
for a variety of fire and non-fire
applications. It provides four
channels (inputs) that accept
waterflow devices, two- and fourwire smoke detectors, pull stations,
and other normally-open contact
devices. The 411UDAC is a costeffective solution for applications
that require an existing (or new)
Fire Alarm Control or Security
Panel to transmit system status to
an off-site monitoring facility for
Central or Remote Station compliance. Due to its extremely flexible
programming options, the 411UDAC is ideal for use as a stand-alone unit to
monitor: sprinkler systems for waterflow and supervisory conditions;
processes (i.e., water level, gas detection, loss of air flow); and normallyopen contact devices. With fifteen selectable transmission formats, including Ademco Contact ID, compatibility with virtually all Digital Alarm
Communicator Receivers (DACR) is ensured. Programming can be accomplished on-site with a hand-held programmer (PRO-411), or remotely
utilizing an optional PK-CD upload/download software package. The PK-CD
upload/download software also permits system interrogation and revision
from a remote site.
Two modular phone connections are provided on the 411UDAC, accessible
by simply opening the door. They provide connections for two separate
telephone lines using standard RJ31X jacks. Both telephone lines are
constantly supervised for proper voltage and current. If one phone line goes
into fault, and the remaining a operational, a report is sent to the central or
remote station via the operable phone line.
Communication Formats
• 1.0 Amp notification appliance power.
• Coded (temporal) notification appliance
(bell, signal) circuit.
• 12 VDC operation.
• Capable of 60 hours standby.
• Seven individual LEDs; six visible through
door: AC Power, system trouble, system
alarm, supervisory, communication fail,
battery trouble, and Earth fault ( not visible
with door closed).
• Dual telephone lines: Dual telephone line
voltage detect, and alternating phone lines
24-hour test messages ( programmable).
• Industry-first, UL recognized, “dialer
runaway” prevention feature.
• New long-distance Carrier Access Code
(CAC) compliant, accepting 20-digit central
station and service terminal telephone
numbers.
Features continued on page 2.
Listings and approvals below apply to
the basic 411UDAC. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be in
process. Consult factory for latest listing
status.
• UL Listed: file S624.
• MEA approved: file 328-94-E Vol. VI.
• NFPA 72 National Fire Alarm Code.
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK.
• FCC Registration: OAAUSA-25431-AL-E.
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK.
• Ringer Equivalance: 0.5 B.
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK.
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK.
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK.
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK.
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK.
09/01/06
• One Style Y (Class B) Notification Appliance
(bell) Circuit (NAC).
• CSFM approved: file 7300-0075:174.
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK.
CS-2509
• Inputs may be individually programmed
for stand-alone applications, or when
monitoring a host control panel, for:
Two- and four-wire smoke detectors (Inputs
1 and 3), pull station, normally-open
contacts, host panel trouble (slave mode),
supervisory, supervisory (autoresettable),
waterflow (silenceable and non-silenceable),
process monitoring, and process monitoring
(autoresettable).
Listings
Phone Line Connections
411UDAC
• Four supervised monitoring channels
(inputs): three fixed Style B ( Class B) and
one Style A (Class A) or style B ( Class B).
Page 1 of 4
Features continued...
• Fully programmed transmittal codes for fire
and non-fire (e.g., process monitoring)
applications.
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK.
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK.
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK.
• Industry-first, user-selectable restoral
methods.
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK.
• Capable of transmitting the following
DACT information, in addition to vital
system status of the host control panel:
DACT troubles, telephone line 1 and 2
voltage fault, primary or secondary Central
Station communication fault, system offnormal, 24-hour normal test and 24-hour
abnormal test.
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK.
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK.
E: Contact ID, DTMF, 1400/2300 ACK.
F: Future use.
Programming
An optional digital programming unit with a keypad, model PRO–411, is
available programming the 411UDAC. It is also used for troubleshooting
and accessing the various modes of operation. Off-site programming can
be accomplished with the optional PK-CD programming software. The PKCD enables a user to program the 411UDAC offsite via the public switched
telephone network using any personal computer with Windows® 3.1 or
higher or Windows® 95 and a 1200-baud Hayes® compatible modem.
Housing
• Includes 15 popular communication formats,
including the widely used Ademco Contact
ID format, ensuring compatibility with
virtually all DACRs.
• Local piezo sounder with separate and
distinct sounds for various conditions.
• Acknowledge/System Silence and Reset
switches.
• Alarm Verification.
The cabinet is red and measures 14.5" (36.83 cm) high x 12.5" (31.75 cm)
wide and 2.875" (7.303 cm) deep. It provides space for up to two 7 A.H.
batteries (order batteries separately). An optional dress panel, DP-2, which
mounts inside the cabinet, is available. The dress panel restricts access to
the system wiring but allows access to the membrane switch panel.
Transformer Assembly
One transformer is shipped in the same carton as the cabinet and main
circuit board but not mounted in the cabinet. The transformer should be
installed before the cabinet is mounted to the wall.
Auxiliary Relay
• Signal silence inhibit.
• Autosilence.
• Trouble reminder (with 24-hour resound).
• Real-time clock.
• Optional two Form-C relays (411 RK),
fully programmable to activate for the
following conditions: Fire alarm, process
monitoring (autoresettable), host control
panel trouble, total communication trouble,
fire supervisory (latching and autoresettable),
DACT trouble (factory default for relay) and
process monitoring.
• Optional PK-CD Remote Upload/Download Kit.
Two optional Form-C relays (411RK) are available for installation on the
411UDAC main circuit board. The relays are programmable for activation
on fire alarm, host panel trouble, fire supervisory, process monitoring, total
communications failure, and DACT trouble. Relay contact rating: 2.0
amps @ 30 VDC (resistive).
• Optional DP-2 Dress Panel.
Specifications
AC Power (TB3): 120 VAC, 60 Hz, 0.3 amps.
Wire size: minimum 14 AWG (2.00 mm²) with
600 V insulation.
Battery (lead-acid only) (J3): maximum
charging circuit: normal flat charge 13.7 V
@ 0.6 amps.
Maximum charger capacity: 14 AH battery.
Channels/Inputs (TB2 terminals 1 through 10):
• Programmable channels 1 through 4.
• Power-limited circuitry.
• Fully supervised (monitored for opens, shorts,
and earth faults).
• Normal operating voltage: 12.0 VDC (ripple
100 mV maximum).
Page 2 of 4
411UDAC
CS-2509
09/01/06
Specifications continued on page 3.
Specifications continued...
• End-of-line resistor: 2.2K ohms, 1/2 watt
(P/N 27070, UL listed).
Ordering Information
411UDAC
Four-channel, dual-line, stand-alone or slave Fire Alarm
Communicator. Includes housing, operating and programming instructions. Use PRO-411 (below) hand-held DACT
programmer for local programming; or PK-411UD (below)
Windows®-based programming software for remote programming and real-time diagnostics.
DP-2
Front dress panel.
PRO-411
Optional hand-held DACT programmer which can be used to
troubleshoot and program the 411UDAC, as well as access
the various modes of operation.
PK-CD
Remote upload/download programming software kit. The
PK-CD enables a user to program the 411UDAC off-site via
the public switched telephone network using any personal
computer with Windows® 3.1 or greater or Windows® 95
and a 1200-baud Hayes®-compatible modem.
Operation for each channel:
• Channel/Input1, Style B (Class B) two-wire
smoke detector input and Channel/Input 3,
Style B (Class B) or Style D (Class A) twowire smoke detector or waterflow input.
• Channel/Input 2 and Channel/Input 4 Style
B (Class B) contact closure input.
• Refer to Device Compatibility Document for
listed compatible devices.
Notification Appliance Circuit
(TB4 Terminals 1[+] and 2 [—]:
• Style Y (Class B) circuit.
• Power-limited and supervised (monitored for
opens, shorts, and earth fault).
• Operating voltage nominal 13.8 VDC.
• Current for all external devices: 1.0 amp.
Optional dry auxiliary Form-C relays, with contacts rated
for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC
(resistive). Optional use requires two relays.
• End-of-line resistor: 2.2K ohms, 1/2 watt
(P/N 27070).
MCBL-7
DACT phone cord, seven feet long (two required).
BAT-1270
Battery, 12-volt, 7.0 AH (one required for 24-hour systems;
two [wired in parallel] required for 60-hour systems).
17062
Gamewell key.
Two Optional Form-C Relays
(TB1 Terminals 1 through 6):
Operating voltage: nominal 12 VDC.
Contact rating: 2.0 amps @ 30 VDC
(resistive), or 0.5 amps @ 30 VAC.
17066
Gamewell lock.
411RK
• Refer to Device Compatibility Document for
listed compatible devices.
12 VDC Resettable Power (TB4 Terminals
3[+] and 4 [—]:
• Operating voltage: nominal 12 volts.
• Up to 200 mA available to power four-wire
smoke detectors.
• Power-limited and supervised circuitry.
• Recommended maximum standby current: 50
mA.
Note: For power supply and battery
calculations, refer to the 411UDAC manual.
OPERATING POWER:
Primary Power Source (AC):
AC power connections are made inside the
411UDAC cabinet. The primary power source
is 120 VAC, 60 Hz, 0.3 amps.
Secondary Power Source (Batteries):
One 12-volt battery can provide power for up
to 7 AH applications. Two 12-volt, 7 AH
batteries (in parallel) can provide power for
up to 14 AH applications (60-hour standby).
The battery charger is current-limited and
capable of recharging sealed lead-acid-type
batteries. The charger shuts off when the
system is in alarm. Refer to the battery
calculations table in the 411UDAC manual to
determine the correct battery rating.
411UDAC
CS-2509
09/01/06
Page 3 of 4
Compatible UL-Listed Recievers
The chart below shows UL-listed receivers compatible with the 411UDAC:
Format # (addresses 16 & 42)
Ademco
685
(1)
Silent
Knight
9000
ITI
CS4000
(3)
FBI
CP220FB
Osborne
Hoffman
Models
1&2
0
4+1 Ademco Express
4
4
1
4+2 Ademco Express
4
4
4 (8)
2
3+1/Standard/1800/2300
4
4 (2)
4
4 (4)
4
3
3+1/Expanded/1800/2300
4
4 (2)
4
4 (4)
4
3+1/Standard/1900/1400
4
4 (2)
5
3+1/Expanded/1900/1400
4
4 (2)
6
4+1/Standard/1800/2300
4
4 (2)
7
4+1/Expanded/1800/2300
4
8
4+1/Standard/1900/1400
9
Radionics
6000/6500
(5)
Sescoa
3000R
(7)
SurGuard
MLR-2
(9)
4
4
4
4
4
4
4
4
4 (4)
4
4
4
4 (4)
4
4
4
4 (4)
4
4 (2)
4 (4)
4
4
4
4
4 (2)
4 (4)
4
4
4
4+1/Expanded/1900/1400
4
4 (2)
4 (4)
4
4
4
A
4+2/Standard/1800/2300
4
4 (2)
4 (4)
4
4
4
B
4+2/Expanded/1800/2300
4
4 (2)
4 (4)
4
4
4
C
4+2/Standard/1900/1400
4
4 (2)
4 (4)
4
4
4
D
4+2/Expanded/1900/1400
4
4 (2)
4 (4)
4
4
4
E
Ademco Contact ID
4
4
4
4
4
4 (5,6)
4 (5)
4 (5)
4
4
51735rec.tbl
KEY:
(1) With 685-8 Line Card with Rev 4.4d software.
(2) With 9002 Line Card Rev 9035 software or 9032 Line Card
with 9326A software.
(3) Rev. 4.0 software.
(4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a
memory card with Rev 3.8 software.
(5) Model 6500 with Rev 600 software.
(6) Model 6000 with Rev 204 software.
(7) With Rev B control card at Rev 1.4 software and Rev C line
card at Rev 1.5 software.
(8) Model 2 only.
(9) Version 1.62 software.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 4 of 4
411UDAC CS-2509