Flex GF506D, Pre-action / Deluge Control Panel

Flex GF506D
Pre-action / Deluge Control Panel
Description
General
The Flex GF506D is a six-zone FACP used for single and
dual hazard deluge and pre-action applications. The Flex
GF506D provides reliable fire detection. It also offers signaling and protection for commercial, industrial, and institutional buildings that require water-based releasing. The
Flex GF506D is compatible with System Sensor’s i3 detectors.
The i3 detectors are conventional smoke detectors that
transmit a maintenance trouble signal to the FACP that
indicates the need for cleaning. It also transmits a supervisory ‘freeze’ signal when the ambient temperature falls
below the detector rating of approximately 45°F (7.22°C).
In addition, the Flex GF506D control panel is compatible
with the following conventional input devices:
• two-wire and four-wire smoke detectors
• pull stations
• waterflow devices and tamper switches
• other normally-open contact devices
For a complete listing of compatible devices, refer to the
Gamewell-FCI Device Compatibility Document,
P/N: 52195.
There are four outputs that are programmable as NACs
(Notification Appliance Circuits) or releasing circuits. Three
programmable Form-C relays (factory programmed for
Alarm, Trouble, and Supervisory), and the 24 VDC special
application resettable and non-resettable power outputs
are included on the main circuit board. The Flex GF506D
supervises all wiring, AC voltage, battery charger, and
battery level.
The activation of a compatible smoke detector or any normally open fire alarm initiating device will do the following:
• turn on audible and visual signaling devices
• light an indicator
• display alarm information on the panel’s LCD
• sound the piezo sounder at the FACP
• activate the FACP alarm relay
• operate an optional module used to notify a remote
station or initiate an auxiliary control function
Flex GF506D
Features
•
•
•
•
•
•
•
Listed to UL Standard 864, 9th Edition.
IBC Seismic Certified.
Designed for sprinkler standards NFPA 13, 15 and 16.
Dual hazard operation.
Adjustable waterflow discharge timer and two soak timers.
Cross-zone (double-interlock) capability.
Six programmable Style B (Class B) IDCs (Initiating
Device Circuit) with optional Class A wiring.
• System Sensor i3 series detectors compatible.
• Four programmable Style Y (Class B) output circuits (special application power) with Class A Style Z option.
• Strobe Synchronization:
-Gentex
- Cooper-Wheelock
- System Sensor
- Faraday
- Amseco
•
•
•
•
•
Three programmable Form-C relays.
7.0 amps total 24 VDC output current.
Resettable and non-resettable output power.
Built-in Programmer.
ANN-BUS for connection to optional
(up to 8 total of any of the following):
-GFANN-80 Remote LCD Annunciator
-GFANN-RLY Relay Module
-GFANN-LED Annunciator Module
• 80-character LCD display (backlit).
• Real-time clock/calendar w/daylight savings time control.
SIGNALING
FM
i 3™ is a trademark of Honeywell International Inc.
®
UL is a registered trademark of Underwriter’s Laboratories Inc.
Reference Certificate
of Compliance
7165-1703:0171 VMA-45894-02C
(Revision 1)
APPROVED
S624
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60466 Rev. D page 1 of 4
©2013 by Honeywell International Inc. All rights reserved.
Features (Continued)
Features (Continued)
•
•
•
•
•
AC Power – TB1
The AC Power -TB1 for each panel is listed below:
• GF506D:
120 VAC, 50/60 Hz, 2.3 amps
• Wire size: minimum #14 AWG (2.0 mm2) with 600V
insulation.
• Supervised, non power-limited
•
•
•
•
•
•
•
•
•
History Log with 256 event storage.
Piezo sounder for alarm, trouble and supervisory.
24 volt DC operation.
Low AC voltage sense.
Outputs Programmable for the following:
- Releasing circuits or NACs
NACs programmable for the following:
- Silence Inhibit
- Auto-Silence
- Strobe Synchronization
- Selective Silence (horn-strobe mute)
- Temporal or Steady Signal
- Silenceable or Non-silenceable
- Release Stage Sounder
Disable/Enable control per input zone and output zone.
Extensive transient protection.
Automatic battery charger with charger supervision.
Optional Dress Panel DP-51050 (red).
Optional Trim Ring TR-CE (red) for semi-flush
mounting the cabinet.
Optional CAC-5X Class A Converter Module for
Outputs and IDCs.
Optional 4XTMF Municipal Box Transmitter Module.
Optional Digital Alarm Communicators (411, 411UD,
411UDAC).
Programming and Software
The programming software offers the following features:
• Custom English labels (per point) may be manually
entered or selected from an internal library file.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming
at the front panel.
• Program Check automatically catches common errors
not linked to any zone or input point.
User Interface
The user interface features are listed below:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight
savings adjustments.
• ANN-Bus for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
The panel provides the following LED Indicators:
• Fire Alarm (red)
• AC Power (green)
• Supervisory (yellow)
• Alarm Silenced (yellow)
• Trouble (yellow)
• Discharge (red)
Control Buttons
• Acknowledge
• Alarm Silence
• System Reset (lamp test)
• Drill
Battery (sealed lead acid only) – J12:
The Battery (for sealed lead acid only) - J12 specifications
are listed below.
• Maximum Charging Circuit - Normal Flat Charge:
- 27.6 VDC @ 1.4 amp. Supervised, non power-limited.
• Maximum Charger Capacity:
- 26 Amp Hour battery (two 18 Amp Hour batteries can
be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or
BB-55).
• Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 and TB6
The Initiating Device Circuits for TB4 and TB6
specifications are listed below.
• Alarm Zones 1 - 5 on TB4
• Alarm Zone 6 on TB6
• Supervised and power-limited circuitry
• Style B (Class B) wiring with Style D (Class A) option
• Normal Operating
Nominal 20 VDC
Voltage:
• Alarm Current:
15 mA minimum
• Short Circuit Current: 40 mA max
• Maximum Loop
100 Ohms
Resistance:
• End-of-Line Resistor:
4.7KOhms, 1/2 watt
(PN 71252)
• Standby Current:
4 mA
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
Notification Appliance and Releasing Circuit(s) TB5 and TB7
The notification appliance and releasing circuits for TB5
and TB7 specifications are listed below.
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional
converter module
• Strobe synchronization
• Special Application power
• Supervised and power-limited circuitry
• Normal Operating
Voltage:
Nominal 24 VDC
• Maximum Signaling
7.0 amps (3.0 amps
Current:
maximum per NAC)
• End-of-Line Resistor:
4.7KOhms, 1/2 watt
(PN71252)
• Max. Wiring Voltage
2 VDC
Drop:
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60466 Rev. D page 2 of 4
www.gamewell-fci.com
Features (Continued)
Product Line Information
Form-C Relays - Programmable - TB8
Product
Description
The Form-C Relays for TB8 specifications are listed below.
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe
Trouble Relay)
• Relay 3 (factory default programmed as Supervisory
Relay).
• Relay Contact Ratings:
- 2 amps @ 30 VDC (resistive)
- 2 amps @ 30 VAC (resistive)
GF506D
Auxiliary Trouble Input – J6
4XTMF
Six-zone, 24 volt Pre-action Deluge Control Panel (includes backbox, power supply, technical manual, and a frame &
post operating instruction sheet) for single and dual hazard deluge and preaction applications.
Class A Converter Module can be used
to convert the Style B (Class B) Initiating
Device Circuits to Style D (Class A) and
Style Y (Class B) Output Circuits to Style
Z (Class A).
Transmitter Module provides a supervised output for the local energy municipal box transmitter and the alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED.
LCD Annunciator is a remote LCD
annunciator that mimics the information
displayed on the FACP LCD display. The
recommended wire type is unshielded.
Annunciator Module provides three
LEDs for each zone: Alarm, Trouble and
Supervisory. Ships with enclosure (red
and black enclosures available; refer to
P/N: DF-60241).
Relay Module, which can be mounted
inside or outside the cabinet, provides 10
programmable Form-C relays.
Dress panel (red) is available as an
option. The dress panel restricts access
to the system wiring while allowing
access to the membrane switch panel.
Trim-ring (red) is available as an option.
The trim-ring allows semi-flushing
mounting of the cabinet.
Battery box, holds up to two (2) 18 Amp
Hour batteries.
Battery box, houses two (2) 55 Amp
Hour batteries, red.
Refer to P/N: DF-52397.
UL-Listed compatible event printer. Dotmatrix, tractor-fed paper, 120 VAC.
Programming cable.
Use this cable to update the FACPs
Flash firmware. (Also it requires an
RS485 to RS232 converter).
The Auxiliary Trouble Input is an open collector circuit
which can be used to monitor external devices for trouble
conditions. It can be connected to the trouble bus of a
peripheral, such as a power supply, which is compatible
with open collector circuits.
CAC-5X
GFANN-80
Special Application Resettable Power - TB9
The Special Application Resettable Power - TB9
specifications are listed below.
• Operating Voltage:
Nominal 24 VDC
• Maximum Available
500 mA - appropriate for
Current:
powering 4-wire smoke
detectors (see note 1).
• Power-limited Circuitry
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
GFANN-LED
GFANN-RLY
DP-51050
NOTE 1: Total current for resettable power, non-resettable
power and Output Circuits must not exceed 7.0 amps.
TR-CE
Special Application Resettable or Non-resettable
Power - TB9
BB-17F
The Special Application Resettable or Non-resettable
Power - TB9 specifications are listed below.
• Operating Voltage:
Nominal 24 VDC
• Maximum Available
500 mA (see Note 1)
Current:
• Power-limited circuitry
• Jumper selectable by JP31 for resettable or non-resettable power.
For a list of compatible devices, refer to the Gamewell-FCI
Device Compatibility Document, P/N: 52195.
PRN-6
PRT/PK-Cable
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
9021-60466 Rev. D page 3 of 4
System Specifications
System Specifications (Continued)
System Capacity:
Temperature and Humidity Ranges
Annunciators ............8
Electrical Specifications
Flex GF506D
(FLPS-7 Power Supply): 120 VAC, 50/60 Hz, 2.3 amps
Wire size:
minimum 14 AWG (2.0 mm²)
with 600 V insulation,
supervised, non power-limited
This system meets NFPA requirements for operation at 0°
–49°C/32° – 120°F and at a relative humidity 93% ± 2%
RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and
the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is
recommended that this system and its peripherals be
installed in an environment with a normal room temperature of 15° – 27°C/60° – 80°F.
Cabinet Specifications
Door
Dimensions:
Backbox:
Dimensions:
Trim Ring (TR- CE):
Dimensions:
NFPA Standards
19.26" H x 16.82" W x 0.72"
(48.92 H x 42.73 W x 1.82 D cm)
19.00" H x 16.65" W x 5.25" D
(48.26 H x 42.29 W x 13.34 D cm)
22.00" high x 19.65" wide
(55.88 H x 49.91 W cm)
Shipping Specifications
Dimensions:
- Height 20.00" (50.80cm)
- Width 22.50" (57.15cm)
- Depth 8.50" (21.59cm)
The GF506D complies with the following NFPA 72 Fire
Alarm Systems requirements:
- NFPA 13 Installation of Sprinkler Systems
- NFPA 15 Water Spray Fixed Systems
- NFPA 16 Deluge Foam-Water Sprinkler and FoamWater Spray Systems
- NFPA 72 National Fire Alarm Code for Local Fire
Alarm Systems and Remote Station Fire Alarm
Systems (requires an optional Remote Station Output
Module)