ADVANTECH ADAM

ADAM-6052
ADAM-6060
ADAM-6060W
Specifications
8
Logic level 0: close to GND
Logic level 1: open
Logic level 0 : 0 ~ 3 VDC
Logic level 1 : 10 ~ 30 VDC
Digital Output





Channels
8
Digital Output
10 ~ 35 VDC (Source Type)
Current
1 A (per channel)
Supports 5 kHz Pulse Output
Supports Over Current Protection
Ordering Information
 ADAM-6052
ADAM-6060W
General
10/100 Base-T
Digital Input
 Wet Contact
6-ch Wireless Digital Input and 6-ch Relay Module
Specifications
General
 Channels
 Dry Contact
6-ch Digital Input and 6-ch Relay Module
ADAM-6060
ADAM-6052
 LAN
16-ch Source-type Isolated Digital I/O Module
16-ch Source-type Isolated DI/O Module
 LAN
ADAM-6060: 10/100 Base-T
ADAM-6060W: IEEE802.11b WLAN
Digital Input
 Channels
 Dry Contact
 Wet Contact
6
Logic level 0: close to GND
Logic level 1: open
Logic level 0 ~ 3 VDC
Logic level 1: 10 ~ 30 VDC
Relay Output (Form A)
 Channels
 Contact Rating (Resistive)  Breakdown Voltage
 Relay On Time
 Relay Off Time
 Total Switching Time
 Insulation Resistance
 Maximum Switching
Rate (at rated load)
 Supports Pulse Output
6
AC: 120 V @ 0.5 A
DC: 30 V @ 1 A
500 VAC (50/60 Hz)
7 ms
3 ms
10 ms
1 GΩ min. at 500 VDC
20 operations/minute
Ordering Information
 ADAM-6060
 ADAM-6060W
Common Specifications
Digital Output
General
Protection
 Power Consumption
 Watchdog




2 W @ 24 VDC
System (1.6 second) and Communication
(programmable)
Unregulated 10 ~ 30 VDC
Power Input
Supports Peer-to-Peer
Supports GCL (ADAM-6052 and ADAM-6060)
Supports Modbus/TCP, TCP/IP, UDP and HTTP Protocol
Digital Input
 Supports 3 kHz Counter Input (32-bit + 1-bit overflow)
 Supports 3 kHz Frequency Input
 Supports Inverted DI Status
6-ch DI and 6-ch Relay Module
6-ch Wireless DI and 6-ch Relay Module
 Supports High-to-Low and Low-to-High Delay Output
 Power Reversal Protection
 Isolation Protection
2000 VDC
Environment
 Operating Temperature ADAM-6052 and ADAM-6060: -10 ~ 70° C
ADAM-6060W: -10 ~ 60° C
 Storage Temperature
-20 ~ 80° C
 Humidity
ADAM-6052 and ADAM-6060:
Operating: 20 ~ 95% RH (non-condensing)
Storage: 0 ~ 95% RH (non-condensing)
ADAM-6060W: 5 ~ 95% RH (noncondensing)
Online Download www.advantech.com/products