EMERSON-NETWORKPOWER HPS3000

Embedded Power for
Business-Critical Continuity
Rev. 7.10.09_81
HPS3000 Series
of 7
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
Special Features
•3000 W output power
•40 W/cu-in
•Optional customer provided air
•1U x 3U form factor
•N+1 Redundant
•Hot-swap
•Internal OR-ing
•5 V housekeeping
•High efficiency 89% @ 200 Vac,
100% load
•Variable speed “smart fans”
•One year warranty
Compliance
• POE Isolation
• EMI Class B - EN55022, Level “A”
• EN61000 Immunity
Safety
• UL/cUL • CSA • China
• Nemko • CB Report
• CSA 22.2
60950
60950
CCC
TUV
60950
Electrical Specifications
Input
Input ra­nge (operating):
Frequency:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
43 to 63 Hz
Input fusing:
Inrush current:
Internal 25 A fuses
≤40 A peak
Both lines fused
Either hot or cold start
Power factor:
0.97 typical
Meets EN61000-3-2
Harmonics:
Meets IEC 1000-3-2
requirements
@ 50% load
Input current:
19 A max input current
Holdup time:
10 ms minimum
At full rated load
Leakage current:
1.4 mA
At 240 Vac
Power line transient:
MOV directly after the fuse
Input range (nominal):
Input through Card Edge Connection
on same end as DC output
Embedded Power for
Business-Critical Continuity
230V ac E ffic ienc y
230 Vac Efficiency
Rev. 7.10.09_81
HPS3000 Series
of 7
100.00
90.00
80.00
70.00
60.00
50.00
40.00
30.00
20.00
10.00
10
20
30
40
50
60
70
80
90
100
% o f T o tal Ou tp u t Po w e r
Output
Output rating
Set point
Total regulation range
Rated load
Minimum load
Output noise
Output voltage overshoot
Transient response
48 V @ 62.0 A
5 Vsb @ 3.0 A
48 V @ 29.4 A
5V @ 3 A
48 V
48 V ± 10%
5 Vsb ± 4%
3000 W maximum @ 200 Vac Input
1500 W maximum @ 110 Vac Input
180 - 264 Vac
48 V @ 0.0 A
5 Vsb @ 0.0 A
480 mV max P-P
100 mV max P-P
No loss of regulation
± 5% maximum
5% maximum deviation
Max units in parallel
Short circuit protection
Output isolation
Forced load sharing
Over current protection (OCP)
Up to 4
120% - 130% of rated output
Per POE specs
Within 10% of all shared outputs
120% to 130%
100% to 125%
Over voltage protection (OVP) 110% to 120%
110% to 125%
Over temperature protection 10 - 15 deg C above safe
operating area
90 - 140 Vac
Programmable ±10% through I2C serial bus
Line/load/transient when measured at output connection
No derating over operating temp range
48 V output
5 Vsb output
Measured with a 0.1µF Ceramic and 10 µF Tantalum capacitor on any
input
Nominal Voltage Setting
50% load step @ 1 A/us
Step load valid between 10% to 100% of output rating.
Total power in 1U 19” rack is 12 KW
Output to return
>2000 Vac
Digital sharing control
48 V output
5 Vsb output
48 V output
5 Vsb output
Both PFC and output converter monitored
5 Vsb will operate under overtemperature condition.
Built in hysteresis
Environmental Specifications
Vibration/Shock:
Non-operational 5G Sine sweep from 5 Hz to 500 Hz, dwelling at resonant frequencies for 1 hour each
Operating temperature:­­­
Storage Temperature:
Cooling
Operating Relative Humidity:
Storage Relative Humidity:
-10 ° to +40 °C
-40 ° to +85 °C
External fans with Fan Fail and Fan Speed control
5% to 95% non-condensing
5% to 95% non-condensing
Operating Altitude
Storage Altitude:
RoHS Compliant:
Up to 10,000 feet above sea level
Up to 30,000 feet above sea level
Yes
Embedded Power for
Business-Critical Continuity
Module Information
(All units in mm)
321.4 ± 1.2
Rev. 7.10.09_81
HPS3000 Series
of 7
11.9 ± 1
19
106.7 ± 0.8
Tyco Connector
PN: 2007209
or
FCI
10053363-400LF
327.6 ± 1.2
AIRFLOW DIRECTION
8 ± 0.5
40 ± 0.8
11.6 ± 0.5
Pin Assignments
Bottom
Top
Pin
Pin
1
2
3
4
5
6
AC LINE
AC LINE
n.c.
AC NEUTRAL
AC NEUTRAL
n.c.
64
63
62
61
60
59
AC LINE
AC LINE
n.c.
AC NEUTRAL
AC NEUTRAL
n.c.
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
n.c.
n.c.
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
n.c.
V_STBY
STBY_RTN_SENSE
PRESENT#
DCOK/PWOK#
SDA
HVCC
PSON#
#ALERT
ISHARE
58
57
56
55
54
53
52
51
50
49
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
n.c.
n.c.
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc out
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
+48 Vdc RTN
n.c.
SYS_GND
STBY_SENSE
ACOK#
SMBUS_ALERT_OUT
SCL
A2
PSKILL
A1
A0
Embedded Power for
Business-Critical Continuity
Rev. 7.10.09_81
HPS3000 Series
4 of 7
Timing Diagram
AC On
AC Input
AC On
T PWOK_Off_
T Vout_Holdup
Main Vout
T PWOK_Off_
T AC_On_Delay
T PWOK_Off_
T PWOK_On
T PWOK_Off_
T PWOK_Off
PWOK
T PWOK_Delay
T PWOK_On
T PWOK_On
T PSON_PWOK
T sb_On
5 vsb Vout
T PSON_On_Delay
T SB_Vout
PS_ON
T ACOK_Delay
AC_OK
AC Input
ON / OFF Cycle
PSON
ON / OFF
Cycle
Embedded Power for
Business-Critical Continuity
Rev. 7.10.09_81
HPS3000 Series
5 of 7
Timing Signal Definitions
Turn ON/OFF Timing
Item
Tvout_rise
Tsb_on_delay
Description
48 V Output rise time
Delay from AC being applied to 5 Vsb being within regulation.
Tac_on_delay
Delay from AC being applied to all output voltages being within
regulation.
Tvout_holdup
Time all output voltages, including 5 Vsb, stay within regulation
after loss of AC.
Delay from loss of AC to de-assertion of PWOK
10
msec
5
msec
Delay from PSON# active to output voltages within regulation
limits.
Delay from PSON# de-active to PWOK being de-asserted.
Delay from loss of AC input to de-assertion of ACOK#.
5
Tpwok_holdup
Tpson_on_delay
Tpson_pwok
Tacok_delay
Tpwok_on
Tpwok_off
Tpwok_low
Tsb_vout
Min
5
Max
300
1500
Units
msec
msec
2000
msec
400
msec
50
msec
msec
10
Delay from output voltages within regulation limits to PWOK
asserted at turn on.
Delay from PWOK de-asserted to 48 V dropping out of regulation
limits.
Duration of PWOK being in the de-asserted state during an off/on
cycle using AC or the PSON# signal.
100
1000
msec
1
1000
msec
Delay from 5 Vsb being in regulation to 48 V being in
regulation at AC turn on.
50
100
msec
2000
msec
Signals and Controls - All Models
PSON #
The PSON# signal is required to remotely turn on/off the power supply. PSON# is an active low signal
that turns on the 48 V power rail. When this signal is not pulled low by the system, or left open, the
48 V output turns off. The 5 Vsb output remains on. This signal is pulled to a standby voltage by a
pull-up resistor internal to the power supply. The power supply fan(s) shall operate at the lowest speed.
PSON# Signal Characteristic
Signal Type
PSON# = Low
Accepts an open collector/drain input from
the system. Pulled-up to the 5 Vsb located in
power supply.
ON
PSON# = Open
OFF
MIN
Logic level low (power supply ON)
Logic level high (power supply OFF)
Source current, Vpson = low
Power up delay: Tpson_on_delay
MAX
0V
0.8 V
2.0 V
4.80 V
--
4 mA
5 msec
400 msec
Embedded Power for
Business-Critical Continuity
Rev. 7.10.09_81
HPS3000 Series
6 of 7
PWOK# (Power Good)
PWOK# is a power good signal and will be pulled LOW by the power supply to indicate that both the
outputs are above the regulation limits of the power supply. When any output voltage falls below
regulation limits or when AC power has been removed for a time sufficiently long so that power supply
operation is no longer guaranteed, PWOK will be de-asserted to a HIGH state. The start of the PWOK#
delay time shall be inhibited as long as the 48 V output is in current limit or the 5 Vsb output is below
the regulation limit.
PSON# Signal Characteristic
Signal Type
PWOK = High
Open collector/drain output from power
supply. Pullup to 5 Vsb external to the power
supply.
ON
PWOK = LOW
OFF
Logic level low voltage, Isink=4mA
Logic level high voltage, Isource=200µA
MIN
MAX
0V
0.8 V
2.0 V
4.80 V
Sink current, PWOK = low
4 mA
Source current, PWOK = high
2 mA
PWOK delay: Tpwok on
100 msec
1000 msec
PWOK rise and fall time
100 µsec
Power down delay: Tpwok off
1 msec
1000 msec
Power Supply Present Indicator (PRESENT#)
The PRESENT# signal is primarily used to provide a mechanism by which the host system can sense the
number of power supplies physically present (operational or not). This pin is connected to ground in the
power supply.
AC INPUT Present Indicator (ACOK#)
The AC OK# signal is used to indicate presence of AC input to the power supply. This signal shall be
connected to 5 Vsb through a resistor on the host system side. A logic “Low” level on this signal shall
indicate AC input to the power supply is present. A Logic “High” on this signal shall indicate a loss of AC
input to the power supply.
Signal Type
PRESENT# = Low
Table 12
ACOK# Signal Characteristics
Pull-up to 5 Vsb through a resistor in the host
system.
Present
PRESENT# = High
Not present
MIN
MAX
Logic level low voltage, Ising=4mA
0V
0.8 V
Logic level high voltage, Isink=50µA
2.0 V
4.80 V
Sink current, PRESENT# = Low
4 mA
Source current, PRESENT# = High
50 µA
Embedded Power for
Business-Critical Continuity
Americas
LED INDICATORS
There will be a green POWER LED (PWR) to indicate that AC is applied to the
PSU and standby voltage is available when blinking. This same LED should go
solid when the 48 V output is enabled and operational.
Rev. 7.10.09_81
HPS3000 Series
of 7
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone:+1 760 930 4600
Facsimile: +1 760 930 0698
Europe (UK)
There will be an Amber Power Supply Fail LED (FAIL) to indicate that the power Waterfront Business Park
supply has failed and a replacement of the unit is necessary. Faults including
Merry Hill, Dudley
UVP, OVP, OTP, or Fan Fail when PSON# is asserted “Logic Low” shall cause the West Midlands, DY5 1LX
Kingdom
amber LED to turn on. The LED can be turned off by recycling PSON# signal or United
Telephone:+44 (0) 1384 842 211
by an AC power interruption more than 1 second. The LED shall be off when
Facsimile: +44 (0) 1384 843 355
PSON# is not asserted “Logic Low”. Refer to table 13 for conditions of the
LED’s:
Asia (HK)
Table 13
LED Indicators
Power LED
(GREEN)
OFF
Power Supply Condition
No AC power to PSU
AC present / Standby Output On
Fail LED
(AMBER)
OFF
Blinking
OFF
Power supply 48 V output ON and OK
ON
OFF
Power supply failure (includes
overvoltage, overtemperature)
Current limit
OFF
ON
ON
Blinking
MTBF
The power supply has a minimum MTBF of 300K hours using the Bell core 332,
issue 6 specification @ 25 °C and 40 °C, ambient, at full load. With the power
supply installed in a system in a 25 °C ambient environment and
operating at full load, capacitor life shall be 10 years, minimum for ALL
electrolytic capacitors contained within this power supply. The power supply
shall demonstrate a MTBF level of > 500,000 hours.
Quality Assurance
Full QAV testing shall be conducted in accordance with Emerson Network
Power Standards with reports available upon request.
Warranty
Emerson Network Power shall warrant the power supply to be free of defects
in materials and workmanship for a minimum period of one year from the date
of shipment, when operated within specifications. The warranty shall be fully
transferable to the end owner of the equipment powered by the supply.
Ordering Information
Model Number
Main Output
HPS3000-9
48 Vdc
Main Output
Current
62.0 A
Standby Output
Standby Current
5.0 V
3.0 A
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone:+852 2176 3333
Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com
techsupport.embeddedpower@
emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and service marks of Emerson Electric Co.
©2009 Emerson Electric Co.