Embedded Power for Business-Critical Continuity Rev. 2.16.09_165 LPT40-M Series of 3 LPT40-M Series 40 Watts Total Power: Input Voltage: # of Outputs: 40 - 55 Watts 85 - 264 VAC 120 - 300VDC Triple Special Features • • • • • • • • • • • Universal input 3” x 5” footprint Less than 1U high Remote sense on main output Built-in EMI filter Low output ripple Adjustable 5V output Overvoltage protection Overload protection 110 KHz switching frequency LPX40 enclosure kit available Electrical Specifications Input Input range: Frequency: Inrush current: Input current: Efficiency: EMI: Safety ground leakage current: 5-264 VAC 8 120-300 VDC 47-440 Hz < 18A peak @ 115 VAC; < 36A peak @ 230 VAC, cold start @ 25 °C 1A max. (RMS) @ 115VAC 70% typical at full load (60% for LPT41) FCC Class A conducted; CISPR 22 Class A conducted EN55022 Class A conducted; VDE 0878 PT3 Class A conducted < 75 µA @ 50/60 Hz, 264 VAC input Output Safety • • • • VDE UL CSA CE 0750/EN60601-1 (IEC601) 113769 UL2601 E182560 CSA 22.2 No.601.1 LR109492 Mark (LVD) Maximum Power: 40W for convection; 55W with 30CFM forced air Cross regulation: Adjustment range: Hold-up time: Overload protection: 2% on output 1; ±5% on outputs 2, 3 ± -5, +10% minimum 20ms @ 40W load, 115 VAC nominal line Short circuit protection on all outputs. Case overload protected @ 110% to 145% above peak rating 5.7 to 6.7 VDC on the main output LPT41: 3.6 to 4.6VDC Compensates for 0.5 V lead drop min. Will operate without remote sense connected. Reverse connection protected. Overvoltage protection: Remote sense: Embedded Power for Business-Critical Continuity Rev. 2.16.09_165 LPT40-M Series of 3 Environmental Specifications Operating temperature: 0° to 50 °C ambient derate each output at 2.5% per degree from 50° to 70 °C, -20 °C start up. Electromagnetic susceptibility: Humidity: Designed to meet IEC 801, -2, -3, -4, -5, -6, Level 3 Vibration: Three orthogonal axes, sweep at 1 oct/min, 5 min. dwell at four major resonances 0.75G peak 5 Hz to 500 Hz, operational Storage temperature: -40° to 85 °C Temperature coefficient: ±.04% per °C MTBF demonstrated: > 550,000 hours at full load and 25 °C ambient conditions Operating; non-condensing 5% to 95% Ordering Information Output Minimum Maximum Load with Maximum Load with Peak Ripple P/P Regulation2 Voltage Load Convection cooling 30CFM Forced Air Load1 (PARD)3 +5V 0.4A 4A 5A 7A ±2% 50mV LPT42-M +12V 0.2A 2A 2.5A 4A ±5% 120mV -12V 0A 0.5A 0.7A 1A ±5% 120mV +5V 0.4A 4A 5A 7A ±2% 50mV LPT45-M +15V 0.2A 2A 2.5A 3A ±5% 150mV -15V 0A 0.5A 0.7A 1A ±5% 150mV 1.Peak current lasting < 30 seconds with a maximum 10% duty cycle. 2.At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3.Peak-to-peak with 20 MHz bandwidth and 10 µF in parallel with a 0.1 µF capacitor at rated line voltage and load ranges. 4.Minimum Loads are required. Model Number Power Derating Curve 55W 30 CFM Forced Air Cooling 40W 30W Output Power (Watts) 20W Natural Convection Cooling 27.5W 20W 10W 0W 0°C 10°C 20°C 30°C 40°C 50°C 60°C 70°C TA – Ambient Temperature – °C Embedded Power for Business-Critical Continuity Americas Mechanical Drawing 0.22" (5.6) 4.55" (115.6) SK201 3.00" (76.2) 2.55" (64.8) 3 SK 1 1 5810 Van Allen Way Carlsbad, CA 92008 USA Telephone:+1 760 930 4600 Facsimile: +1 760 930 0698 5.00" (127) M1 GND M2 _ + 1 2 3 4 5 6 N Rev. 2.16.09_165 LPT40-M Series of 3 Remote Sense Connector Voltage Adj. Pot SK 2 Europe (UK) Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone:+44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355 Asia (HK) L 0.15" (4) DIA (4 places) 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone:+852 2176 3333 Facsimile: +852 2176 3888 For global contact, visit: www.PowerConversion.com 1.14" (29) techsupport.embeddedpower @emerson.com While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 0.12" (3) Mating Connectors Pin Assignments Connector SK1-1 SK1-3 SK2-1 SK2- 2 SK2- 3 SK2-4 LPT42-M Line Neutral +12V +5V +5V Common LPT45-M Line Neutral +15V +5V +5V Common SK2-5 Common Common SK2-6 SK201-1 SK201-2 -12V +Sense -Sense -15V +Sense -Sense AC Input: Molex 09-50-8031 (USA) 09-91-0300 (UK) PINS: 08-58-0111 DC Molex 09-50-8061 (USA) Outputs: 09-91-0600 (UK) PINS: 08-58-0111 Remote Molex 22-01-2025 Sense: PINS: 08-52-0114 Emerson Network Power Connector Kit #70-841-006, includes all of the above 1. Specifications subject to change without notice. 2. All dimensions in inches (mm), tolerance is ±0.02” (±0.5mm) 3. Mounting holes M1 and M2 should be grounded for EMI purposes. 4. Mounting hole M1 is safety ground connection. 5. Specifications are for convection rating at factory settings at 115 VAC input, 25 °C unless otherwise stated. 6. Warranty: 2 year 7. Weight: 0.5lbs/0.23kg Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection EmersonNetworkPower.com Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.