EMERSON-NETWORKPOWER LPS52-M

Embedded Power for
Business-Critical Continuity
Rev. 1.08.09_149
LPS50-M Series
of 3
LPS50-M Series
60 Watts
Total Power:
Input Voltage:
# of Outputs:
55 - 60 Watts
90 - 264 VAC
127 - 300 VDC
Single
Special Features
Electrical Specifications
•Medical Safety Approvals
•Universal input
•Less than 1U high
•2” x 4” footprint
•Remote sense
•Overload and short circuit
protection
•Adjustable output voltage
•High efficiency
•High MTBF
•Built in EMI filter
(CISPR 22 Class B)
•LED power good indicator
•Input power < 74 watts
•Complies with EN61000 -3-2
•UL Class I approved
•LPX50 enclosure kit available
•Dual AC fuses
Input
Input ra­nge:
90 - 264 VAC (wide range) 127-300 Vdc
Frequency:
47-440 Hz
Inrush current:
< 60 A peak @ 230 VAC, cold start @ 25°C
Input power:
< 74 Watts
Efficiency:
80% - 85% typical at full load
EMI/RFI:
FCC Class B conducted; CISPR 22 Class B conducted; EN55022 Class B
conducted, VDE0878PT3 Class B conducted
Safety ground leakage
current:
275uA @ 50/60 Hz; 264 VAC input
Output
Maximum power:
60W for convection (LPS52, 55 W)
Adjustment range:
±20% minimum
Hold-up time:
10/20 ms 115/230 VAC input line
Overload protection:
Short circuit protection on all outputs. Case overload protected @
110-160% of normal rating
Overvoltage protection: 30-50% above nominal output
Safety
• UL:
• CSA:
• VDE:
• CE:
UL 60601-1
CSA-C22.2 No. 601.1-M90
EN60601-1
LVD & EMC
Remote sense:
Compensatesd for 0.5 V lead drop max. Will operate without remote sense
connected. Reverse connection protected.
Embedded Power for
Business-Critical Continuity
Rev. 1.08.09_149
LPS50-M Series
of 3
Environmental Specifications
Operating temperature:
0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C.
-20 °C start up
Storage temperature:
Electromagnetic susceptibility:
-40 °C to +85 °C
Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3
Humidity:
Operating; non-condensing 10% to 95% RH
Vibration:
IEC68-2-6 to the levels of IEC721-3-2
MTBF demonstrated:
> 550,000 hours at full load and 25 °C ambient conditions
Mechanical Drawing
VR1
Output Voltage
M2
Adjust pot
M1
C4
~
~
R3
Q5
R3
A
DB1
VR1
3
C
C32
24
T1
D
R1
4
SK2
1
C30
F1
L1
C22
A
C5
1
3
6
B T2
SK1
T3.15A 2.5A
250VAC
F2
C1
C18 C9
R
TH
1
DIP
Q6
J3
22
2005
I
C17
3.75"
[95.3]
4.00"
[101.6]
E
F
J1
J2
G
H
R26
T3.15A
2.5A
250VAC
L3
C2
2.00"
[50.8]
CN1
1
C27
C
TP1
GND
TP2
J4
L2
D2
1.75"
[44.5]
+
HTSK_SEC
D
J
LED1
Mounting Hole
Ø0.16"[4.0] 4 Places
Max. Screw Head
Diameter .22” (5.6)
0.16"
[4.0]
0.197” (5.0) Minimum Standoff Height
1.30"
[33.0]
GRN/
YEL
Embedded Power for
Business-Critical Continuity
­Americas
Ordering Information
Model
Number
Output
Voltage
Minimum Maximum Load with
Load
Convection Cooling
Peak
Load1
Regulation2
Ripple P/P
(PARD)3
LPS52-M
5V
0A
11 A
12 A
±2%
50 mV
LPS53-M
12 V
0A
5A
5.4 A
±2%
120 mV
LPS54-M
15 V
0A
4A
4.4 A
±2%
150 mV
LPS55-M
24 V
0A
2.5 A
2.75 A
±2%
240 mV
LPS58-M
48 V
0A
1.25 A
1.35 A
±2%
480 mV
1. Peak current lasting < 15 seconds with a maximum 10% duty cycle.
2­. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3­. Peak-to-peak with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and
load ranges.
Pin Assignments
Connector
SK1-1
SK1-3
LPS52-M
LPS53-M
LPS54-M
LPS55-M
LPS58-M
Line
Neutral
Line
Neutral
Line
Neutral
Line
Neutral
Line
Neutral
SK2-1
SK2-2
SK2-3
SK2-4
SK2-5
SK2-6
+5 V
+5 V
Common
Common
-Sense
+Sense
+12 V
+12 V
Common
Common
-Sense
+Sense
+15 V
+15 V
Common
Common
-Sense
+Sense
+24 V
+24 V
Common
Common
-Sense
+Sense
+48 V
+48 V
Common
Common
-Sense
+Sense
Rev. 1.08.09_149
LPS50-M Series
of 3
5810 Van Allen Way
Carlsbad, CA 92008
USA
Telephone:+1 760 930 4600
Facsimile: +1 760 930 0698
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
Telephone:+44 (0) 1384 842 211
Facsimile: +44 (0) 1384 843 355
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
Telephone:+852 2176 3333
Facsimile: +852 2176 3888
For global contact, visit:
www.PowerConversion.com
techsupport.embeddedpower
@emerson.com
While every precaution has been taken to ensure
accuracy and completeness in this literature, Emerson
Network Power assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
Emerson Network Power.
The global leader in enabling
business-critical continuity.
Mating­ Connectors
AC Input:
Molex 09-50-8031 (USA)
09-91-0300 (UK)
PINS: 08-52-0113
DC Outputs: Molex 09-50-8061 (USA)
09-91-0600 (UK)
PINS: 08-52-0113
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Emerson Network Power Connector Kit #70-841-006, includes all of the above
Monitoring
Notes:
1. Specifications subject to change without notice.
Outside Plant
­2. All dimensions in inches (mm), tolerance is ±0.02”­­ (±0.5mm)
3. Mounting holes M1 and M2 should be grounded for EMI purposes.
Precision Cooling
Racks & Integrated Cabinets
4. Mounting hole M1 is safety ground connection.
Services
5. Specifications are for convection rating at factory settings at 115 VAC input, 25 °C unless otherwise
stated.
6. Warranty: 2 year
7. Weight: 0.41lbs/0.18kg
Power Switching & Controls
Surge Protection
EmersonNetworkPower.com
Emerson Network Power and the Emerson
Network Power logo are trademarks and
service marks of Emerson Electric Co. ©2008 Emerson Electric Co.