Embedded Power for Business-Critical Continuity Rev. 1.08.09_149 LPS50-M Series of 3 LPS50-M Series 60 Watts Total Power: Input Voltage: # of Outputs: 55 - 60 Watts 90 - 264 VAC 127 - 300 VDC Single Special Features Electrical Specifications •Medical Safety Approvals •Universal input •Less than 1U high •2” x 4” footprint •Remote sense •Overload and short circuit protection •Adjustable output voltage •High efficiency •High MTBF •Built in EMI filter (CISPR 22 Class B) •LED power good indicator •Input power < 74 watts •Complies with EN61000 -3-2 •UL Class I approved •LPX50 enclosure kit available •Dual AC fuses Input Input range: 90 - 264 VAC (wide range) 127-300 Vdc Frequency: 47-440 Hz Inrush current: < 60 A peak @ 230 VAC, cold start @ 25°C Input power: < 74 Watts Efficiency: 80% - 85% typical at full load EMI/RFI: FCC Class B conducted; CISPR 22 Class B conducted; EN55022 Class B conducted, VDE0878PT3 Class B conducted Safety ground leakage current: 275uA @ 50/60 Hz; 264 VAC input Output Maximum power: 60W for convection (LPS52, 55 W) Adjustment range: ±20% minimum Hold-up time: 10/20 ms 115/230 VAC input line Overload protection: Short circuit protection on all outputs. Case overload protected @ 110-160% of normal rating Overvoltage protection: 30-50% above nominal output Safety • UL: • CSA: • VDE: • CE: UL 60601-1 CSA-C22.2 No. 601.1-M90 EN60601-1 LVD & EMC Remote sense: Compensatesd for 0.5 V lead drop max. Will operate without remote sense connected. Reverse connection protected. Embedded Power for Business-Critical Continuity Rev. 1.08.09_149 LPS50-M Series of 3 Environmental Specifications Operating temperature: 0° to 50 °C ambient derate each output as 2.5% per degree from 50° to 70 °C. -20 °C start up Storage temperature: Electromagnetic susceptibility: -40 °C to +85 °C Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3 Humidity: Operating; non-condensing 10% to 95% RH Vibration: IEC68-2-6 to the levels of IEC721-3-2 MTBF demonstrated: > 550,000 hours at full load and 25 °C ambient conditions Mechanical Drawing VR1 Output Voltage M2 Adjust pot M1 C4 ~ ~ R3 Q5 R3 A DB1 VR1 3 C C32 24 T1 D R1 4 SK2 1 C30 F1 L1 C22 A C5 1 3 6 B T2 SK1 T3.15A 2.5A 250VAC F2 C1 C18 C9 R TH 1 DIP Q6 J3 22 2005 I C17 3.75" [95.3] 4.00" [101.6] E F J1 J2 G H R26 T3.15A 2.5A 250VAC L3 C2 2.00" [50.8] CN1 1 C27 C TP1 GND TP2 J4 L2 D2 1.75" [44.5] + HTSK_SEC D J LED1 Mounting Hole Ø0.16"[4.0] 4 Places Max. Screw Head Diameter .22” (5.6) 0.16" [4.0] 0.197” (5.0) Minimum Standoff Height 1.30" [33.0] GRN/ YEL Embedded Power for Business-Critical Continuity Americas Ordering Information Model Number Output Voltage Minimum Maximum Load with Load Convection Cooling Peak Load1 Regulation2 Ripple P/P (PARD)3 LPS52-M 5V 0A 11 A 12 A ±2% 50 mV LPS53-M 12 V 0A 5A 5.4 A ±2% 120 mV LPS54-M 15 V 0A 4A 4.4 A ±2% 150 mV LPS55-M 24 V 0A 2.5 A 2.75 A ±2% 240 mV LPS58-M 48 V 0A 1.25 A 1.35 A ±2% 480 mV 1. Peak current lasting < 15 seconds with a maximum 10% duty cycle. 2. At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings. 3. Peak-to-peak with 20 MHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges. Pin Assignments Connector SK1-1 SK1-3 LPS52-M LPS53-M LPS54-M LPS55-M LPS58-M Line Neutral Line Neutral Line Neutral Line Neutral Line Neutral SK2-1 SK2-2 SK2-3 SK2-4 SK2-5 SK2-6 +5 V +5 V Common Common -Sense +Sense +12 V +12 V Common Common -Sense +Sense +15 V +15 V Common Common -Sense +Sense +24 V +24 V Common Common -Sense +Sense +48 V +48 V Common Common -Sense +Sense Rev. 1.08.09_149 LPS50-M Series of 3 5810 Van Allen Way Carlsbad, CA 92008 USA Telephone:+1 760 930 4600 Facsimile: +1 760 930 0698 Europe (UK) Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone:+44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355 Asia (HK) 14/F, Lu Plaza 2 Wing Yip Street Kwun Tong, Kowloon Hong Kong Telephone:+852 2176 3333 Facsimile: +852 2176 3888 For global contact, visit: www.PowerConversion.com techsupport.embeddedpower @emerson.com While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Emerson Network Power. The global leader in enabling business-critical continuity. Mating Connectors AC Input: Molex 09-50-8031 (USA) 09-91-0300 (UK) PINS: 08-52-0113 DC Outputs: Molex 09-50-8061 (USA) 09-91-0600 (UK) PINS: 08-52-0113 AC Power Connectivity DC Power Embedded Computing Embedded Power Emerson Network Power Connector Kit #70-841-006, includes all of the above Monitoring Notes: 1. Specifications subject to change without notice. Outside Plant 2. All dimensions in inches (mm), tolerance is ±0.02” (±0.5mm) 3. Mounting holes M1 and M2 should be grounded for EMI purposes. Precision Cooling Racks & Integrated Cabinets 4. Mounting hole M1 is safety ground connection. Services 5. Specifications are for convection rating at factory settings at 115 VAC input, 25 °C unless otherwise stated. 6. Warranty: 2 year 7. Weight: 0.41lbs/0.18kg Power Switching & Controls Surge Protection EmersonNetworkPower.com Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.