GAMEWELL-FCI 72224

Reflective Beam
Features
• Models for ranges of:
Smoke Detector
15 to 160 ft. (4.572 to 48.768 m)
160 to 330 ft. (48.768 to 100 m)
• Easy alignment.
• Calibrated obscuration test filters
included.
Description
g2154phl.jpg
Gamewell’s reflective beam smoke
detectors (72223-160 or 72223-330)
are a single infrared transceiver
and a reflective prism. The signal
generated in the transmitter
element and reflected by the prism
back to the receiver element is
analyzed for the presence of smoke.
The internal microprocessor determines an alarm condition when a
predetermined level is reached. The
system is designed to be mounted so that the beam will project between 1
foot (0.305 m) and 2 feet (0.61 m) below and parallel to the ceiling. Lateral
detection may be up to 30 feet (9.144 m) to either side of the beam, providing a maximum total area coverage of up to 19,800 square feet (60' x 330' or
18.288 m x 100 m).
• Selectable alarm thresholds: 25%, 35%,
50%.
• Microprocessor controlled.
• Low current draw.
• Selectable automatic reset.
• Automatic gain control.
• 12 VDC or 24 VDC operation.
• Status LEDs.
• Separate trouble contacts.
Engineer’s Specifications
The projected beam type smoke detector shall be a four-wire 12/24 VDC
device to be used with UL-Listed, separately supplied, four-wire control
panels only. Unit shall be Listed to UL 268 and shall consist of an integrated transmitter and receiver. The detector shall operate between a range
of 15 to 330 ft. (4.572 to 100 m). The temperature range of the beam shall
be –22°F to 131°F (–30°C to 55°C). The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration
from dirt accumulation on lenses. The unit shall include a wall-mounting
bracket. Testing shall be carried out using a calibrated test filter. The
projected beam type smoke detector shall be Gamewell model 72223-160
(160 ft./18.288 m) or 72223-330 (330 ft./100 m).
Smoke Detector Spacing
On smooth ceilings, up to 60 ft. (18.288 m) between projected beams and not
more than one-half that spacing between a projected beam and a sidewall.
Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72 for further information.
Reflective Beam CS-2154 06/23/04
Page1 of 2
Listings
Listings and approvals below apply to the
Reflective Beam Smoke Detectors. In
some cases, certain modules may not be
listed by certain approval agencies, or
listing may be in process. Consult factory
for latest listing status.
• UL Listed:
Specifications
Operational Specifications
Primary input power
10 to 30 VDC maximum.
Fault condition (trouble).
Standby
90% or more obscuration.
0.004 A maximum.
Automatic gain control limit.
Alarm current
0.014 A maximum.
Improper initial alignment.
Integral alignment aid: prism targeting mode.
Relay contacts
0.5 A at 30 VAC/VDC.
Alarm indicator: red LED.
Reset time
Trouble indicator: green LED.
5 seconds maximum.
Standby current
Ordering Information
0.040 A.
72223-160
Reflective beam smoke detector, 160 ft. (48.768 m) (50R).
72223-330
Reflective beam smoke detector, 330 ft. (100 m) (100R).
72224
Replacement prism.
Start-up time
10 seconds.
Optical wavelength
880 nm.
Temperature rating
—22°F to 131°F (—30°C to 55°C).
Relative humidity
10 to 93% RH non-condensing.
Dimensions
8.25" H x 4.5" W x 4.75" D (cm: 21.0 H
x 11.43 W x 12.065 D).
Finish
Gray/black.
Weight
1.5 lbs. (0.68 kg).
Range
15 ft. to 330 ft. (m: 5 to 100).
The Gamewell Company
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell.
Page 2 of 2
Reflective Beam CS-2154 06/23/04