GAMEWELL-FCI 302-AW-135

302 Series
Features
Rate-Anticipation Heat Detectors
• Eliminates false alarms. The 302 Series do
not respond to momentary temperature
fluctuations below the selected temperature.
Description
The Thermotech 302 Series rateanticipation heat detectors operate
within a conrolled range of two to
three degrees of their set points,
regardless of the speed or rate of
temperature rise. These detectors
are available in either 135° F or 194°
F ratings.
The 302 Series are normally-open
devices designed especially for fire
detection and alarm systems.
• Universal application. The 302 Series can be
used in all areas for any type of occupancy.
• Self-restoring.
• Hermetically sealed, shock resistant,
corrosion resistant, and tamper-proff.
6935pho1.jpg
Principles of
Operation
The 302 Series rate-anticipation
heat detectors respond and
activate the fire alarm immediately whenever the ambient temperature
reaches the preset temperature setting. Under rapid heat rise conditions,
the rate-anticipation feature enables the detector to respond one to three
degrees ahead of the setting. At the same time, however, it does not respond
to momentary temperature flucuations below the selected protection level,
thus eliminating false alarms. When temperature drops back down below
the protection level, the detector automatically resets itself.
Application Information
09/01/06
Listings
Listings and approvals below apply to the
302 Series M Rate-Anticipation Heat
Detectors. In some cases, certain modules
may not be listed by certain approval
agencies, or listing may be in process.
Consult factory for latest listing status.
• UL Listed: file S539 & E35018A.
• CSFM approved: file 7270-0021:001.
302 Series detectors have a smooth-ceiling UL rating of 50' x 50' (15.24 x
15.24 meters) and are the only type of heat detectors having such a rating
on both fixed temperature and rate anticipation.
302 Series CS-2519
• Immediate response. The 302 Series
activates whenever ambient air temperature
reaches a detector's setting,eliminating the
thermal time lag inherent in conventional
heat detectors.
Page 1 of 2
• FM approved: file
Product Line Information
302-135: 135°F Interior Vertical Mounting, FM and UL (See Note 1).
302-194: 194°F Interior Vertical Mounting, FM and UL (See Note 1).
302-AW-135:135°F All-Weather Vertical Mounting, FM and UL (See Note 2).
302-AW-194: 194°F All-Weather Vertical Mounting, FM and UL (See Note 2).
302-ET-135:135°F All-Weather Vertical Mounting, FM and UL (See Note 3).
302-ET-194: 194°F All-Weather Vertical Mounting, FM and UL (See Note 3).
302-EPM-135: 135°F Explosion-Proof Mounting, UL (See Note 4).
302-EPM-194: 194°F Explosion Proof Mounting, UL (See Note 4).
AP-P: Decorative white plastic adaptor plate for mounting 302 and 302-AM to 4"
outlet box.
Specifications
Dimensions
Total overall length: 4-1/8"
Base diameter: 2"
Electrical Ratings
Voltage
6-125 VAC
6-25 VDC
125 VDC
Current
5 amps
1 amp
0.5 amp
Note 1: For interior mounting in any atmosphere that is compatible with terminal screw type connections. UL rating 50' x 50' (15.24 x 15.24 meters).
Note 2: Humitically sealed for moisture-proof or dust-proof installations. Requires
no special backbox when the all-weather leads are properly spliced to 'THW' or
equivalent type wire.
Note 3: Humitically sealed for moisture-proof or dust-proof installations. Requires
no special backbox. Has plastic hexagonal wrench grip bushing with 1/2" (1.27 cm)
conduit threads for attachment to threaded hub cover, or any special outlet box.
Note 4: Explosion-proof for installation in hazardous locations. Has hexagonal
wrench grip bushing with 1/2" (1.27 cm) conduit threads for attachment to threaded
hub cover of Series JL fixture fitting as manufactured by Killark Electric Co., or
equal.
Cut-Away View
FINE SILVER
CONTACT POINTS
EXPANSION STRUTS
HIGH EXPANSION
SENSING SHELL 0.040
ANODIZED ALUMINUM
HEAT ANTICIPATION
CONTROL SLEEVE
SETTING SCREW
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
DEVCON
HERMETIC SEAL
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 2 of 2
302 Series CS-2519
09/01/06