GAMEWELL-FCI AMM-2F

Velociti® Series
AMM-2F
Addressable
Monitor Module
Description
The Gamewell-FCI Velociti® Series, addressable monitor
module AMM-2F is a single Style B, Class B initiating
device circuit (IDC) with a 47KW end-of-line resistor. This
module provides an address for any device or group of
devices connected to this circuit on the signaling line
circuit (SLC) of the Gamewell-FCI addressable series fire
alarm control panel. Any initiating device with normally
open (N.O.) dry contacts may be made addressable
when connected to the AMM-2F module.
The Velociti® Series use a communication protocol that
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate
in a grouped fashion. If one of the devices in the group
has a status change, the panel’s microprocessor stops
the group poll and concentrates on the single device.
The net effect is response speed up to five times greater
than earlier designs.
The AMM-2F module can be programmed to provide a
wide variety of input functions to the Gamewell-FCI addressable series fire alarm control panels. It can be identified as a manual station, heat detector, plenum detector, waterflow switch, tamper switch, N.O. contact, smoke
detector, projected beam smoke detector, sub loop,
remote zone, etc. It can also serve as a remote system
silence, system reset, system acknowledge or drill
switch. It is even possible to customize its device type to
meet specific job requirements.
The initiating device circuit of the AMM-2F can support a
maximum line resistance of up to 40 ohms allowing the
use of linear heat detection devices. The compact size
facilitates the installation of the module inside manual
stations, or mounting boxes of various types of alarm
initiating devices.
AMM-2F
Features
• Compact size allows easy installation
• Class B, Style B, initiating circuit
• 40 Ohm line resistance for each initiating device
circuit
• Connects to any normally open dry contact device
• Bicolor LEDs flash green whenever the module
is addressed, and light steady red on alarm*
*Note: Only the red LED is operative in panels that do not
operate in Velociti® mode.
Specifications
Supervisory current:
Alarm current:
Operating temperature:
Relative humidity:
End-of-line Resistance:
Dimensions:
.000375 amps.
.00060 amps.
32˚ to 120˚ F (0˚ to 49˚ C)
10 to 93% (non-condensing)
47K ohms
1.3” L x 2.5” W x 0.5” D
(3.3 x 6.4 x 1.3 cm)
Ordering Information
An ISO 9001-2000 Company
Model
Description
AMM-2F
Addressable monitor module, single circuit,
Style B, Class B
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 Gamewell-FCI. All rights reserved.
www.gamewell-fci.com
9020-0626 Rev. C1 page 1 of 1