Description
The IF602VE can monitor and control up to 252 intelligent
analog addressable input/output points. The interactive
operator’s display uses LED prompting for ease of programming and user operation. The alphanumeric display
and keypad simplify field programming, or download programming from a Windows®-based application.
State-of-the-art, single-channel (25 watts) voice evacuation
is built into the IF602VE panel. It is expandable to 50 watts.
With zone splitting, up to 50 watts of audio power can be
divided into as many as eight speaker circuits (zones), and
full manual control with status indication is included via a
separate keypad.
With the IF602VE, up to five field-programmable messages
(up to 60 seconds total message duration) can be recorded
with an integral microphone or from an external audio
source. The panel provides full supervision in both active
alarm and standby conditions; the amplifier outputs, field
wiring, message generator, all tone generators, and the
microphone are all supervised.
The IF602VE’s housing was designed to be both aesthetically pleasing and functionally sound. The cabinet is
designed to fit between studs for semi-flush mounting. The
compact design and key-activated dead-front construction
enables secure routine maintenance of the system. Access
to system function keys is limited by a key switch. Multiple
levels of password protection prohibit unauthorized use.
The circuit boards are mounted on a removable chassis,
and are designed with pluggable terminal strips for ease of
installation and service.
g2497ph1.jpg
The IdentiFlex 602 with Voice Evacuation (IF602VE) is ideally suited for small- to medium-sized installations of commercial, institutional, and industrial life-safety applications.
The IF602VE offers all the features of today’s most
advanced life safety systems. The integration of analog
and addressable hardwired circuits allows system engineers to customize panels and maximize efficiency for a
given application.
Feature
IF602VE
• One or two Signaling Line Circuits (SLC), up to 252
points.
• Polarity-insensitive SLC circuit wiring.
• SmartStart™ self-programming logic.
• Downloadable or front-panel programmable.
• Password protected.
• Approved for Agent Releasing and Supervisory Service.
• Fully digital SLC protocol.
• SmartLink™ peer-to-peer networkable.
• 1000-event history log.
• Automatic drift compensation.
• Coded signaling capability.
• Adjustable sensor sensitivity and temperature settings.
• Supervisory service.
• Style 6 (Class A) or Style 4 (Class B) SLC.
• Four Style Y (Class B), or two Style Z (Class A)
notification appliance circuits (NACs).
• Semi-flush mounting (between 16" studs).
• 160-character display.
• UDACT compatible.
• Built-in strobe and horn synchronization.
SmartStart™ and SmartLink™ are trademarks of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft Corporation.
An ISO 9000-2000 Company
SIGNALING
FM
APPROVED
S521
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2497 Rev. A page 1 of 4
Operator’s Display
Features (Continued)
The IF602VE’s operator’s display is the source of all user
access to the system. The display provides all of the necessary keys and annunciation points to maintain and monitor the system. Alarm, supervisory, and trouble conditions
are all indicated on the operator’s display by dedicated
LEDs and an internal sounder. The Acknowledge, Reset,
and Signal Silence keys are located directly below the 4 x
40-character backlit alphanumeric display. All system functions and operational logic can be programmed directly
from the front panel in the field. The IF602VE display
includes four user-programmable function keys.
• 25 watt, 25 Vrms audio with integral microphone, digital
message generator.
• Expandable to 50 watts.
• Single Style Z (Class A) or Style Y (Class B) speaker
circuits.
• Up to eight Style Z (Class A) or Style Y (Class B)
speaker circuits with zone splitting.
• Control inputs can be independently field programmed.
• Three command input circuits activate on contact
closure.
• Full manual control of all audio zones provided by zone
page module with keypad, with zone splitting.
• FACP automatically directs the voice message to each
or all audio zones, with zone splitting.
• Live voice paging.
• Remote microphone support.
Analog Addressable Signaling Line Circuits
The IF602VE analog interface module provides Signaling
Line Circuits (SLC), loop circuits that can monitor and control up to 126 analog/addressable devices on each powerlimited loop, for a total of 252 analog points in a dual-loop
system. Loop wiring is not polarity sensitive.
Each SLC loop has a dedicated microprocessor that simultaneously communicates with connected field devices and
the main CPU.
The IF602VE uses the advanced XP95 fully digital communications protocol to improve the speed and accuracy of
event reporting. The communications protocol provides for
alarm verification per detector, detector adjustability and
compensation, adjustable analog heat detector range
(131°F to 194°F, 55°C to 90°C), circuit isolation, and priority interrupts. Priority interrupts allow contact-type devices
such as manual fire alarm stations to interrupt the polling
cycle and transmit their addresses at any time during a
polling sequence.
The fully digital protocol allows the IF602VE to operate on
most types of field wiring, greatly expanding its use in retrofit applications. Consult the factory for specific wiring
requirements.
IF602VE Power Supply
The IF602VE power supply is a fully regulated 8.0 Amp
supply that furnishes system operating and signaling
power. It is equipped with a battery charger which maintains the secondary power source. The power supply is
monitored by the main CPU, ensuring that adequate power
levels are available. The power supply design allows for
high efficiency while providing precise power output. The
battery charger maintains batteries up to 26 AH. The supply powers four on-board NACs (two Class A) with multiple
built-in synchronization protocols.
I/O Devices
Addressable control output devices are the interface
between analog circuits and building functions. The outputs
are controlled by Control By Event (CBE) software within
the IF602VE, and can be programmed to respond to any
event. The control devices can also be used as supervised
remote signaling circuits.
The IF602VE, with Gamewell-FCI’s complete line of 600
Series devices, provides a foundation for system design.
The IF602VE’s RS-232 output expands system monitoring
and control capabilities.
Remote Display and Control
Add serial annunciators to display system activity and control. Serial annunciator drivers are available in 16-point
increments and are an ideal interface to graphic annunciators. Switches can be used for Acknowledge, Reset, Signal
Silence, Drill, etc., to customize the remote status control
network.
An alphanumeric display can also be used for remote status and control. The alphanumeric display is designed to
communicate over the serial communications network.
The IF602VE can communicate locally or remotely with a
printer to document system activity.
See the RAN/SAN data sheet (CS-2025) for complete
annunicator details.
Applications
The IF602VE Analog Addressable Control Panel is
designed for new or retrofit small- to mid-sized projects that
require state-of-the-art life-safety systems. The embedded
CPU offers users unrivaled reliability without sacrificing
flexibility or value.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2497 Rev. A page 2 of 4
With compatible analog sensors and addressable input and
control interface devices, and its remote status and control
capabilities, the IF602VE provides system engineers with
all the tools necessary to design effective system solutions
for any application.
The IF602VE can also control bulk fire-suppressant materials releasing. The IF602VE is capable of releasing the following NFPA types of suppressant: 13 Sprinkler, 15 Water
Spray, 11 Low-Expansion Foam, 16 Water Foam, 17 Dry
Chemical, and 2001 Clean Agent.
Architectural/Engineering Specifications
The control panel furnished and installed shall be capable
of supporting 252 addressable devices and two analog
loops. The panel shall utilize a fully digital Signaling Line
Circuit (SLC) protocol. The panel shall contain four onboard Notification Appliance Circuits (NACs) that support
multiple synchronization protocols. The panel shall utilize a
160-character Liquid Crystal Display (LCD) and a 1,000event history log. The panel shall be a Gamewell-FCI
IF602VE.
Specifications
Common Control:
Standby Current:
Alarm Current:
Input Power:
0.125A
0.171A plus signaling circuit power,
plus 0.002A for master box, or plus
0.022A for reverse-polarity.
120 VAC, 3.0A; or 240 VAC, 1.5A
Auxiliary Output:
S+/S–, A+/A–:
Common Relays:
2.0A maximum
1.0A @ 30 VDC or 0.5A VAC @ 250
Notification Appliance Circuits:
Circuits:
Four Class B, two Class A.
Output:
3.0A maximum@24 VDC per circuit.
Maximum 8.0A total for all circuits.
Analog SLC:
126
252
Standby Current:
0.045A
0.055A
Alarm Current:
0.045A
0.055A
Panel Dimensions:
VE Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
Battery Storage Dimensions
(without zone splitter):
VE Cabinet:
8.0" H x 22.0" W x 5.5" D
(20.32 H x 55.88 W x 13.97 D cm)
Relative Humidity: 93% non-condensing
Temperature
Rating:
32°F – 120°F (0°C – 49°C)
Ordering Information
Model
IF602VE-126
Description
IF602 analog addressable system, consisting of the following:
• IF602 common control.
• 8.0 amp main power supply.
• One (1) analog circuit module
(126 analog addressable points).
• Basic audio subsystem with one 25W
amplifier and microphone.
Cabinet:
30.0" H x 22.0" W x 5.5" D
(72.2 H x 55.88 W x 13.97 D cm)
IF602VE-252 IF602 analog addressable system, consisting of the following:
• IF602 common control.
• 8.0 amp main power supply.
• Two (2) analog circuits module
(252 analog/addressable points).
• Basic audio subsystem with one 25W
amplifier and microphone.
Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
IF602VE-126Z IF602 analog addressable system, consisting of the following:
• IF602 common control.
• 8.0 amp main power supply.
• One (1) analog circuit module
(126 analog addressable points).
• Basic audio subsystem with 8-zone
integrated audio circuit splitter.
• One 25W amplifier and microphone.
Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
IF602VE-252Z • IF602 analog addressable system,
consisting of the following:
• IF602 common control.
• 8.0 amp main power supply.
• Two (2) analog circuits module
(252 analog addressable points).
• Basic audio subsystem with one 25W
amplifier and microphone.
Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
52286
IdentiFlex 602VE and Audio Subsystem
Installation/Operating Manual
30177
CTM-602, city-tie/remote signaling
module, for 602 Series panels.
31078
ISO-232, RS-232 serial-port isolator
module, for 602 Series panels.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2497 Rev. A page 3 of 4
Ordering Information (Continued)
Model
Description
31079
CLA-602, Class “A” adapter module for
SLC, 602 Series panels.
Audio Subsystem:
ACC-AAM25
FC-XRM70
FC-RM
FC-LPS
ACC-EPM
BAT-1270
BAT-12120
BAT-12180
Optional 25 watt, 25 VRMS Audio Amplifier
Module with single Class A or Class B
speaker circuit.
Optional 70.7 VRMS Converter Module
(one required per amplifier).
Optional Remote Microphone, includes
backbox (only one FC-RM per system).
Optional Local Playback Speaker (not for
use with zone-splitting systems).
Optional External Page Microphone for
zone-splitting systems.
Battery, 12 volt, 7.0 AH (two required).
Battery, 12 volt, 12.0 AH (two required).
Battery, 12 volt, 18.0 AH (two required).
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2497 Rev. A page 4 of 4