9020-0556 - Gamewell

AM-50 Series
AM-50 Series Amplifiers
Description
The Gamewell-FCI, AM-50 Series amplifiers are a 50 watt,
digital, switching power amplifier. The following lists the 2
types of AM-50 Series amplifiers that may be ordered.
• The AM-50-25 amplifier produces 25 VRMS audio output.
• The AM-50-70 amplifier produces 70.7VRMS audio output.
The amplifiers are components of the following E3 Series®
Systems.
• E3 Series Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Voice Evacuation System
AM-50-25
WARNING: AM-50 Series Amplifiers Node Restriction:
The INI-VGX can support up to 4 AM-50 Series amplifiers
with the same output voltage. However, you cannot wire an
AM-50-25 amplifier and an AM-50-70 amplifier to the same
INI-VGX Voice Gateway Node.
Each AM-50 Series amplifier provides 2 speaker circuits
that can be wired Style Y (Class “B”) or Style Z (Class “A”).
The terminal connections can accommodate up to 12
AWG, twisted-pair, shielded wire. Both speaker circuits produce a combined total of 50 watts of power. The 50 watts
of power can be divided between the 2 integral Class A/B
speaker circuits. The 2 speaker circuits may be individually
activated and supervised by an INI-VGX Transponder
Voice Gateway.
The AM-50 Series amplifier can be programmed to broadcast 16 messages generated from its local INI-VGX Voice
Gateway. In addition, the AM-50 Series amplifiers produce
superior clarity for intelligible LIVE voice paging.
When the selected System Sensor, SpectrAlert® Advance
Series speakers are used with the Manufacturer’s 520 Hz
audiophile, the E3 Series® System is compliant with UL
Standard 464 Low Frequency requirements.
For additional information, refer to the SpectrAlert Advance
Series Data Sheet, P/N:9021-60346.
Installation
As many as four AM-50 Series amplifiers can be installed
in the following cabinets when supervised and controlled
by an INI-VGX Voice Gateway.
• Cabinet B, INX CAB-B
• Cabinet C, INX-CAB-C
• Cabinet D, INX-CAB-D
AM-50-70
Features
• Listed under UL® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass
Notification.
• Complies with UL Standard 464 for 520 Hz Low
Frequency.
• Provides digital, switching amplifier technology.
• Produces 50 watts of digital power.
• Includes 2 speaker circuits, wired Style Y (Class B)
or Style Z (Class A).
• Up to 4 AM-50 Series amplifiers with the same output voltage can be controlled by the INI-VGX voice
gateway.
SIGNALING
FM
MEA
City of
Chicago
Approved City of
Class 1 DENVER
FDNY:
S1869 3017416 COA #6077 7165-1703:0125 Class 2 Approved
High Rise
®
®
E3 Series and SpectrAlert are registered trademarks of Honeywell International Inc.
®
UL is a registered trademark of Underwriters Laboratories, Inc.
Approved
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0556 Rev. K1 page 1 of 2
©2015 Honeywell International Inc. All rights reserved.
Description (Continued)
Ordering Information
The AM-50 Series amplifiers can be installed using the
AM-50 Extender Plate whenever the E3 Series control
panel is used in conjunction with the Autonomous Control
Unit of the E3 Series Combined Fire and Mass Notification
System.
• Cabinet C, E3 INCC-CAB-C
For additional information, refer to the E3 Series Combined
Fire and Mass Notification Data Sheet, P/N:9021-60758
Part Number Description
1100-0456
AM-50-70
AM-50-25, INX 25VRMS audio output, 50
watt amplifier
INX 70.7VRMS audio output, 50 watt
amplifier
Specifications
AM-50-25 Amplifier
Operating Voltage:
Operating Current:
Alarm Current:
Audio Output:
AM-50-70 Amplifier
Operating Voltage:
Operating Current:
Alarm Current:
Audio Output:
AM-50 Series Amplifiers
Relative Humidity:
Operating Temperature:
Dimensions:
27.3 to 20.4 VDC
0.086 amp normal standby
2.206 amp max. alarm @ 50
Watt
50 watts max. @ 25 VRMS
27.3 to 20.4 VDC
0.049 amp normal standby
2.30 amp max. alarm @ 50
watt
50 watts max. @ 70.7 VRMS
0 to 93% max., (non-condensing) at 90° F (32° C)
32° to 120° F (0° to 49° C)
7 1/2” W x 3 1/2” H x 1 1/4” D
(19 W x 9 H x 3 D cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118