ETC WM2-96AV53D

Energy Management
Modular Power Analyzers
Type WM2-96
• Class 1 (current/voltage)
• Modular power analyzer
• Front size: 96x96 mm
• 3-dgt/6-dgt µP-based indicator
• Manual or automatic scrolling of system and
single phase: kW, kVAr, PF, kWh, kVArh, A, VL-L avg,
VL1-N, VL2-N, VL3-N.
• TRMS measurement of distorted waves (voltage/current)
• All configuration functions selectable by
built-in key-pad
• Password protection of programming parameters
• Degree of protection (front): IP 65
• Optional pulse output (according to DIN43864)
• Optional serial RS 422 /485 port
• MODBUS, JBUS protocol.
Product Description
Ordering Key WM2-96 AV53D XXX
gle phase measurements and
indications. The housing is
easy to mount on a panel
and ensures a degree of protection (front) of IP 65.
Model
Range code
System
Power supply
1st output
2nd output
Range code
System
Power supply
1st output (pulse)
AV5:
3:
A:
XX:
O1:
µP-based modular power
analyzer with a built-in configuration key-pad. The power, power factor, current and
voltage are system and sin-
Type Selection
AV7:
1)
2)
3)
250/433 VAC - 5 AAC
(max. 300 V (L-N)/
520 V (L-L) - 6 A)
400/690 VAC - 5 AAC
(max. 480 V (L-N)/
830 V (L-L) - 6 A) 1)
One phase,
three-phase system,
3 or 4 wires, balanced load;
three phase system,
3 or 4 wires, unbalanced load
On request
Warning: this power supply cannot be used if the
RS485 module is needed
Compatible with any kind of output
B:
C:
D:
L:
H:
24 VAC, -15% +10%,
50/60 Hz 1) 2)
48 VAC, -15%+10%,
50/60 Hz 1) 2)
115 VAC, -15%
+10%, 50/60 Hz 1) 2)
230 VAC, -15%
+10%, 50/60 Hz
(standard) 2)
18 to 60 VDC/AC 3)
90 to 260 VDC/AC 3)
No output (standard)
Single open collector
output (30V/100mADC) 1)
O2:
Dual open collector output,
the second one is the copy
of the first one, like “O1” 1)
R1:
Single relay output,
(AC1-8AAC, 250VAC) 1)
R2:
Dual relay output,
the second one is the copy
of the first one, like “R1” 1)
2nd output
X:
S:
No output (standard)
Serial port, RS 485
multidrop bidirectional 1)
Input Specifications
Accuracy (48 to 62 Hz)
Voltage/current
(@ 25°C ± 5°C, R.H. ≤ 60%)
Active power
(@ 25°C ± 5°C, R.H. ≤ 60%)
Reactive power
(@ 25°C ± 5°C, R.H. ≤ 60%)
Power factor (PF)
(@ 25°C ± 5°C, R.H. ≤ 60%)
Energy
(@ 25°C ± 5°C, R.H. ≤ 60%)
Additional errors
Humidity
Power supply
Magnetic field
Un: 250V (AV5), 400V (AV7)
In: 5A
Rated input
Current
±0.5% f.s. (0 to 1.2 In,
0.5 to 1.2 Un)
±1% f.s. (PF ≥ 0.7 L/C,
0 to 1.2 In, 0.5 to 1.2 Un)
±1% f.s. (PF ≥ 0.7 L/C,
0 to 1 In, 0 to 1 Un)
±1% f.s., PF ≥ 0.7 L/C,
(0.6 to 1.2 In, 1 to 1.2 Un)
±1% RDG (kWh), ±2% RDG
(kvarh), (PF ≥ 0.7L/C, 0 to
1.2 In, 0.5 to 1.2 Un)
Voltage
Insulation
Temperature drift
Display
2 inputs (one/three-phase
balanced load)
6 inputs (one/three-phase
unbalanced load)
2 inputs (one/three-phase
balanced load)
4 inputs (one/three-phase
unbalanced load)
among the voltage and the
current inputs: 2000Vrms;
among the current inputs:
2000 Vrms
±250 ppm/°C
Backlighted LCD, h 13mm,
3-dgt (instantaneous meas.)
6-dgt (energies)
< 0.3% f.s., 60% to 90% R.H.
±0.5% rdg, -15 +10% p.s.
< 0.1% f.s. @ 400 A/m
Specifications are subject to change without notice
WM2-96DS0303
1
WM2-96
Input Specifications (cont.)
Decimal point position
Max. and min. indication
Voltage
Current (CT ratio = 1)
PF
Power (CT ratio = 1)
Active energy
Reactive energy
Sampling rate
Measurements
System variables
Total energies
Partial energies
Single phase variables
Measurement method
Instantaneous measurements:
Automatic selection according to the current transformer ratio of the CT being
connected (max. indication single phase):
CT ratio ≤ 5 : 11.11 (25.00A)
CT ratio ≤50.0: 111.1 (250.0A)
CT ratio ≤ 500.0 : 1111 (2500A)
CT ratio ≤ 999.9 : 11110 (6000A)
Energy measurements:
max. resolution:1 Wh/1 VArh
min. resolution: 1 kWh/1 kVArh
Max. 600
min. 0
Max. 6.00
min. 0.00
Max. 1.00
min. 0.00
Max. 5.40
min. 0.00
Max. 999999 min. –199999
Max. 999999 min. 0
3 times / second
Coupling type: Direct
Crest factor: ≥ 3
Ranges (impedances)
Frequency range
Over-load protection
Continuous: voltage/current
For 1 s
Voltage:
Current:
Keyboard
kW, kVAr, PF, VL-L, A,
kWh, kvarh
kWh, kvarh
(the meters are reset
automatically when the
values reach 14999*CT ratio)
kW, kVAr, PF, VL-N, A
TRMS measurement of a distorted voltage/current wave
250 V/433 V (≥400kΩ)
5 AAC (≤ 0.3 VA / ≤ 0.1Ω)
400V/690V (≥650kΩ)
48 to 62 Hz
Un: 250V (AV5), 400V (AV7)
In: 5A
1.2 Un /In
2 Un
20 In
4 keys:
”∆∇”:
- to enter programming
phase and password confirmation;
- for value programming
and basic measurement
scrolling.
“L”:
- for confirmation of new
programmed values and
going ahead to the next
programming step,
- single phase measurement scrolling.
“R”:
- for the reset of the partial
counted active and/or
reactive energy.
Output Specifications
Pulse output (on request)
Number of outputs
Static type
(according to DIN 43864)
Relay type
Pulse duration
Insulation
Serial port (on request)
Type
Connections
Addresses
2
Protocol
1, independent
From 0.1 to 999.9 programmable pulses for kWh,
KVArh, open collector (NPN
transistor)
VON 1.2 VDC/ max. 100 mA
VOFF 30 VDC max.
1 x SPDT
AC 1 - 8A, 250VAC
DC 12 - 5A,24VDC
AC 15 - 2.5A, 250VAC
DC 13 - 2.5A, 24VDC
200 ms (ON), ≥ 200 ms (OFF)
By means of optocouplers,
4000 Vrms output to
measuring input,
4000 Vrms output to
supply input.
Data (bidirectional)
Dynamic (reading only)
Static (writing only)
Data format
RS422/RS485;
Multidrop bidirectional (static
and dynamic variables)
4 wires, max. distance
1200m, termination directly
on the module
1 to 255, selectable
by key-pad
Baud-rate
Insulation
MODBUS/JBUS
System variables:
P, Q, PF, VL-L,
energies,
Single phase variables:
PL1, QL1, PFL1, VL1-N, AL1,
PL2, QL2, PFL2, VL2-N, AL2,
PL3, QL3, PFL3, VL3-N, AL3
All programming data, reset
of energy:
- partial kWh
- partial kVArh
- total kWh
- total kVArh
Stored energy (EEPROM)
≤ 999999 kWh
≤ 999999 kVArh
1-start bit, 8-data bit, no
parity/even parity, 1 stop bit
1200, 2400, 4800 and 9600
selectable bauds
By means of optocouplers,
4000 Vrms output to
measuring inputs
4000 Vrms output to
supply input
Specifications are subject to change without notice
WM2-96DS0303
WM2-96
Software Functions
Password
1st level
2nd level
Measurement scrolling
System:
Numeric code of max. 3 digits; 2 protection levels of
the programming data
Password “0”, no protection
Password from 1 to 255, all
data are protected
Active power (kW),
reactive power (kVAr),
power factor (cos ϕ),
current (A),
average phase-phase voltage (V)
total and partial active energy (kWh),
total and partial reactive
energy (kVArh)
Partial energy meters:
the counters of kWh and
kVArh are automatically
reset when the energy
reaches the value
(14999*CT).
Single phase:
Transformer ratio
Programmable ratio
Digital Filter
Filter operating range
Filtering coefficient
Filter action
Example: the CT is a
100A/5A so the ratio is 20,
consequently the maximum
counted energy is 299980
kWh or kVArh.
Active power (kW),
reactive power (kVAr),
power factor (cos ϕ),
current (A),
phase-neutral voltage (V)
For CT up to 5000 A
0.1 to 999.9
0 to 100% of the
input electrical scale
1 to 64
On the display and on the
variable being transmitted
by the serial communication
port.
Supply Specifications
AC voltage
230 VAC (standard),
-15%+10% 50/60 Hz
24 VAC, 48 VAC, 115 VAC
(on request),
-15%+10% 50/60 Hz
18 to 60VDC/AC
Power consumption
90 to 260VDC/AC
≤ 30VA / 12W (90 to 260V)
≤ 20VA / 12W (18 to 60V)
General Specifications
Operating temperature
Storage temperature
Insulation reference voltage
Insulation
Dielectric strength
Noise rejection
CMRR
EMC
0° to +50°C (32° to 122°F)
(R.H. < 90% non-condensing)
-10° to +60°C (14° to 140°F)
(R.H. < 90% non-condensing)
300 Vrms to ground
4000 Vrms between all inputs/
outputs to ground
4000 Vrms for 1 minute
100 dB, 48 to 62 Hz
EN 50081-2, EN 50082-2
Specifications are subject to change without notice
WM2-96DS0303
Safety standards
Other standards
Approvals
IEC 61010-1, EN 61010-1
Pulse output: DIN43864
CE
UL, CSA
Connector
Screw-type,
max. 2.5 mm2 wires x 2
Housing
Dimensions
Material
Degree of protection
Weight
96 x 96 x 140 mm
ABS,
self-extinguishing: UL 94 V-0
Front: IP65
Approx. 500 g
(packing included)
3
WM2-96
Mode of Operation
Accuracy class of the instrument as a relation of PI/Pn and cos ϕ (power factor)
Active Power
PI / Pn
Reactive Power
QI / Qn
2%
2%
1%
1%
5%
Test conditions:
V = 0.8 to 1.2 Un,
I = 0.1 to 1.2 In,
f = 48 to 62 Hz
Test conditions:
V = 0.8 to 1.2 Un,
I = 0.1 to 1.2 In,
f = 48 to 62 Hz
Input
Star
voltage
Delta
voltage
Current
Example 1:
Model AV5.3 (3-wire system).
Example 2:
Model AV5.3 (4-wire system).
AV5
Un: 250 V
Un: 430 V
In: 5 A
UI = 400 V (delta voltage)
II = 265 A (single phase cur-
UI = 230 V
II = 110 A (CT=300A)
rent)
PI/QI (installation power)
One phase system:
PI = UI · II · cos ϕ
QI = UI · II · sin ϕ
Three phase, 3-wire system:
PI = √3 · UI · II · cos ϕ
QI = √3 · UI · II · sin ϕ
Three phase, 4-wire system:
PI = 3 · UI · II · cos ϕ
QI = 3 · UI · II · sin ϕ
where:
UI = the real star voltage of
the electrical system being
measured.
I = the maximum phase current of the electrical system
being measured.
Cos ϕ = the average cos ϕ of
the electrical system being
measured.
4
Pn /Qn (rated power of the
instrument):
One phase system:
Cos ϕ = 0.85 (system power
factor) (CT=300A)
Un = 430 V
In = 5 A
CT (ratio) = 300
5 = 60
Pn = Qn = Un · In · CT(ratio)
Three phase, 3-wire system:
Pn = Qn = √3 · Un · In · CT(ratio)
Three phase, 4-wire system:
Pn = Qn = 3 · Un · In · CT(ratio)
where:
Un = the rated input voltage
of WM2-96.
In = the rated input current of
WM2-96.
CT (ratio) = the value of the
current transformer ratio.
PI = √3 · UI · II · cos ϕ
= √3 · 400 · 265 · 0.85
= 155.87 kW
Pn = √3 · Un · In · CT (ratio)
= √3 · 430 · 5 · 60
= 233.17 kW
PI 155.87
=
= 0.698
Pn 223.17
Cos ϕ = 0.85 (sin ϕ = 0.52)
Un = 250 V
In = 5 A
A
CT (ratio) = 300
5 A = 60
Qn = 3 · UI · II · sin ϕ
= 3 · 230 · 110 · 0.52
= 39.46 kvar
Qn = 3 · Un · In · CT (ratio)
= 3 · 250 · 5 · 60
= 225 kvar
39.46
PI
=
= 0.175
Pn
225
In both examples the accuracy of the measurement is
1% f.s. when considering the
changing of the measured
voltage from 0.9 Un to 1 Un
and the measured current
from 0.1 In to 0.9 In with a
cos ϕ of 0.85 (sin ϕ 0.52).
Specifications are subject to change without notice
WM2-96DS0303
WM2-96
Mode of Operation (cont.)
Waveform of the signals that can be measured
Figure H
Sine wave, indented
Fundamental content
10...100%
Harmonic content
0...90%
Frequency spectrum 3rd to 16th harmonic
Required result: additional error < 1%
Figure G
Sine wave, undistorted
Fundamental content
100%
Harmonic content
0%
1.1107 | A |
Arms =
Figure I
Sine wave, distorted
Fundamental content
70...90%
Harmonic content
10...30%
Frequency spectrum 3rd to 15th harmonic
Required result: additional error < 0.5%
Wiring Diagrams
Single phase input connections
Fig. 2
Fig. 1
I
1
3
5
L1
L2
L3
2
4
6
8
L1
7
N
L2
9
10
L3
I
U
1
3
5
L1
L2
L3
2
4
6
8
L1
7
N
10
L3
L2
9
U
L1
L1
N
N
CT connection
Direct connection
Three phase 3-wire input connections - Balanced loads
Fig. 4
Fig. 3
CT connection (3-wire system)
Direct connection (3-wire system)
Specifications are subject to change without notice
WM2-96DS0303
5
WM2-96
Wiring Diagrams (cont.)
Three phase, 4-wire input connections - Balanced loads
Fig. 6
Fig. 5
Direct connection (4-wire system)
CT connection (4-wire system)
Three-phase, 3-wire input connections Unbalanced load
Three-phase, 3-wire input ARON connections Unbalanced load
Fig. 7
Fig. 8
CT connection (3-wire system)
CT connection (3-wire system)
Three phase, 4-wire input connections - Unbalanced load
Fig. 9
Direct connection (4-wire system)
6
Fig. 10
CT connection (4-wire system)
Specifications are subject to change without notice
WM2-96DS0303
WM2-96
Front Panel Description
- To enter into the programming procedure and select
programming functions together with the ”L” key.
“L”:
To scroll all the single phase variable of each basic
measurement
“R”:
To reset the partial counted energies (kWh, kVArh).
2
2. Display
Instantaneous measurements:
- 3-digit (maximum read-out 999)
Energies:
- 6-digit (maximum read-out 999999).
1
Alphanumeric indication by means of LCD display for:
- Displaying the configuration parameters
- All the measured variables.
1. Key-pad
Set-up and programming procedures are easily controlled
by the 4 pushbuttons.
▲ and ▼
- To scroll all the basic measurements (system variables)
- To increase or decrease programming values
Sequence of the variables on the display
SYSTEM
VARIABLE
V
L1 - L2 - L3
(average)
PHASE 1
SINGLE PHASE VARIABLES
PHASE 3
PHASE 2
V L1
(V L1-N )
L
V L2
(V L2-N )
L
L
V L3
(V L3-N )
L
I L1 L2 L3
I
L
L1
I
L
L2
L
I
L
cosϕ
L3
L
cosϕ
L1 L2 L3
cosϕ
L
L1
L
cosϕ
L2
L3
L
kW
L1 L2 L3
kW
L
L1
kW L2
L
L
kW L3
L
kVAr
L1 L2 L3
L
kVAr
L1
L
kVAr
L2
L
kVAr
L3
L
kWh
total
kWh
L
partial
L
kVARh
total
kVARh
L
partial
L
Specifications are subject to change without notice
WM2-96DS0303
7
WM2-96
The available modules
Type
N. of
channels
WM2-96 base + AV5.3 input
WM2-96 base + AV7.3 input
24VAC power supply
48VAC power supply
115VAC power supply
230VAC power supply
18-60VAC/DC power supply
90-260VAC/DC power supply
RS485 port
Relay output
Relay output
Open collector output
Open collector output
Ordering code
AB1012
AB1013
AP1025
AP1024
AP1023
AP1022
AP1021
AP1020
AR1034
AO1058
AO1035
AO1059
AO1036
1
1
2
1
2
Note
Neither UL nor CSA approved
Neither UL nor CSA approved
Neither UL nor CSA approved
Neither UL nor CSA approved
The second output can be used as redoundant output
The second output can be used as redoundant output
The possible module combinations
Slot
Basic unit
RS485 port
Single relay output (pulse)
Single open collector output (pulse)
B
Out 1
D
Out 2
Slot
Basic unit
RS485 port
Dual relay output (pulse)
Dual open collector output (pulse)
B
Out 1
D
Out 2
Dimensions
8
Specifications are subject to change without notice
WM2-96DS0303
WM2-96
Terminal boards
Digital output modules
AO1058
Single relay output
AO1035
Dual relay output
AO1059
Single open collector
output
AO1036
Dual open collector
output
Other input/output modules
AR1034
RS485 port
Power supply modules
AP1025
24VAC power supply
AP1022
230VAC power supply
Specifications are subject to change without notice
AP1024
48VAC power supply
AP1021
18-60VAC/DC power supply
WM2-96DS0303
AP1023
115VAC power supply
AP1020
90-260 VAC/DC power supply