DF-52202 • D-110 July 13, 2004 FCPS-2404 24 Volt, 4 Amp NAC Power Expander www.firelite.com Section: Power Supplies/Accessories GENERAL The Fire•Lite FCPS-2404 is a compact, cost-effective, NAC power expander. Its filtered 24 VDC output can provide up to 4.0 amps of current to drive one Style Y (Class B) NAC (Notification Appliance Circuit). The FACP's (Fire Alarm Control Panel) NAC is connected to the power expander's input circuit. When the control input circuit activates due to reverse polarity of the FACP's NAC, the power expander will activate its NAC circuit. The FCPS-2404 is compatible with 12 VDC and 24 VDC control panels. California State Fire Marshal 7315-0075:197 MEA 141-01-E S2424 FEATURES • 4 amps total of continuous current available. • One 24 VDC Style Y (Class B) NAC. • One optically-isolated input/control circuit, compatible with 12 VDC and 24 VDC control panel. • External Strobe Synchronization could be added with UL listed synch module, which can be housed in the FCPS2404. • Can be wired daisy-chain style. • Self-contained in compact, lockable cabinet (15" [381 mm] H x 14.5" [368 mm] W x 3.050" [775 mm] D). • Output is filtered and completely power limited. • Integrated supervised battery charger for lead acid or gel type batteries. • Uses only 7 AH (Amp Hour) batteries — can be accomodated in the power supply cabinet. • NAC supervised by host FACP. • Earth fault detection by host FACP. • Fixed terminal blocks for field wiring capable of accepting 12 – 22 AWG wire. • AC fail Form-C relay contacts (fail-safe). • Battery/Charger trouble Form-C relay contacts (fail safe). • Optional hardware kit #90273 to be used when installing addressable or synchronization modules. LED INDICATORS • AC power on (green) LED. • Battery/Charger trouble (yellow) LED. SPECIFICATIONS Primary (AC) Power – TB1 • 120 VAC 50/60 Hz, 1.45 amps maximum. • Wire size: minimum #14 AWG (2 mm²) with 600V insulation. Control Input Circuit – TB3, Terminals 1 (+) & 2 (–) alarm polarity • Trigger Input Voltage: 9 to 32 VDC. • Input Current Draw in Alarm Polarity: 16 - 32 volts, 10 mA maximum. 9 -16 volts, 4 mA maximum. FCPS-2404 Important: Do not use shielded wire for Control Input Circuit. NAC Output Circuit – TB3, Terminals 3 (+) & 4 (–) alarm polarity • Voltage Rating: 24 VDC. • Current: 4 amps maximum total continuous current. • Style Y (Class B) – requires End-of-Line Resistor from circuit connected to input. • Refer to Fire•Lite Device Compatibility Document for listed compatible devices. Important: Do not use shielded wire for NAC Output Circuit. AC Fail Relay Contact Rating – TB6 • Fail-safe relay (normally energized, transfers with loss of power). • 1 amp @ 30 VDC. Fire•Lite® Alarms is a Honeywell company. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. DF-52202 • 07/13/04 — Page 1 of 3 Battery/ChargerTrouble Contact Rating – TB5 • Fail-safe relay (normally energized, transfers with loss of power). • 1 amp @ 30 VDC. Secondary Power (Battery) Charging Circuit • Maximum Battery Capacity: use only 7.0 AH batteries. • FCPS-2404 draws maximum standby current of 40 mA from batteries (includes End-of-Line Relay currrent if installed). Auxiliary Power Connector – P3 • Used for powering modules inside cabinet, such as control modules. • Voltage Rating: 24 VDC. • Current: 30 mA maximum. • Supports lead acid and gel type batteries only. • Float Charge Voltage: 27.6 VDC. • Maximum Charge Current: 750 mA. FCPS-2404 BOARD LAYOUT NAC Output - supervised (alarm polarity shown) Battery/Charger Trouble Relay Contacts NAC Input from FACP - supervised (alarm polarity shown) Note: No T-tapping addtional notification appliances Important: Do not use shielded wire for Control Input or NAC Output Circtuits AC Fail Report Jumper AC Fail Relays Contacts P3 Internal 24 VDC Power (nonsupervised) TB1 AC Power Connector (supervised) P2 Battery Connector (supervised) 2404bord.wmf F2 Fuse 8 amp for Battery Page 2 of 3 — DF-52202 • 07/13/04 F1 Fuse 1 amp for Charger CONTROLLING FCPS-2404 WITH CONTROL MODULE AND INTERNAL POWER Polarized Bell SLC Out to next addressable device Strobe Horn SLC In from FACP or previous addressable device - + + 24 VDC Control Module or Sync Module + 24 VDC FCPS-2404 Control Module mounting (if Sync Module used above) or second Control Module 2404app.wmf PRODUCT LINE INFORMATION FCPS-2404 NAC power expander (120 VAC). Includes main printed circuit board, transformers, red enclosure, and installation instructions. CMF-300 Intelligent addressable control module. MDL Sync module for use with SpectrAlert Series, red. MDLW Sync module for use with SpectrAlert Series, white. BAT-1270 Battery, 12 volt, 7.0 AH (two required). 90273 Hardware kit to be used when installing addressable or synch modules. FCPS-24RB Replacement motherboard. DF-52202 • 07/13/04 — Page 3 of 3