9021-60721

GFANN-80
80-Character LCD
Description
The GFANN-80 annunciator is a compact, backlit 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system Status
indicators for AC power, Alarm, Trouble, Supervisory, and
Alarm Silenced conditions. The GFANN-80 and the FACP
communicate over a two-wire serial interface employing
the ANN-BUS communication format. Connected devices
are powered, via two additional wires, by either the host
FACP or a remote UL-Listed, filtered power supply. You
can order the GFANN-80 annunciator in red or white, (P/N:
GFANN-80-W).
The GFANN-80 displays English-language text of system
point information including, device type, zone, independent
point alarm, trouble or supervisory status, as well as any
custom alpha labels programmed into the control panel. It
includes control switches for the remote control of critical
systems functions. (A keyswitch prevents unauthorized
operation of the control switches).
To obtain the number of GFANN-80 devices that support
the ANN-BUS, refer to the host FACP manual.
GFANN-80
Features
•
•
•
•
The ANN-BUS
POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY
When the maximum number of ANN-BUS devices exceed
the ANN-BUS power requirements, use an auxiliary power
supply to power the ANN-BUS. See the FACP manual for
more information.
•
•
•
ANN-BUS DEVICE ADDRESSING
Each ANN-BUS device requires a unique address (ID
Number) to communicate with the FACP. A maximum of 8
devices can be connected to the FACP ANN-BUS communication circuit. See the FACP manual for more information.
•
•
•
•
•
WIRE REQUIREMENTS: COMMUNICATIONS
CIRCUIT
The ANN-80 connects to the FACP ANN-BUS communications circuit. To determine the type of wire and the maximum wiring distance that can be used with FACP ANNBUS accessory modules, it is necessary to calculate the
total worst case current draw for all modules on a single 4conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each
module.
Listed under UL Standard 864, 9th Edition
Offers backlit 80-character LCD display (20 characters x 4 lines)
Mimics all display information from the host panel
Includes control switches for System Acknowledge, Signal Silence,
Drill, and Reset
- Control switches can be independently enabled or disabled at the
FACP
Keyswitch enables/disables control switches and mechanically locks
annunciator enclosure
- Keyswitch can be enabled or disabled at the FACP
Enclosure supervised for tamper
Has system status LEDs for AC Power, Alarm, Trouble, Supervisory,
and Alarm Silence
Allows the local sounder to be enabled or disabled at the FACP
GFANN-80 connects to the ANN-BUS terminal on the FACP and
requires minimal panel programming
Displays device type identifiers, individual point alarm, trouble,
supervisory, zone, and custom alpha labels
Provides a time-and date display field
Installs surface mount directly to the wall or to a single, double, or 4"
square electrical box
An ISO 9001-2000 Company
SIGNALING
FM
APPROVED
S2424
MEA
Approved
442-06-E 7165-1703:0166
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60721 Rev. B page 1 of 2
©2012 by Honeywell International Inc. All rights reserved.
WIRE REQUIREMENTS:
COMMUNICATIONS CIRCUIT (Continued)
Features (Continued)
Note: For total worst case current draw on a single ANNBUS refer to appropriate FACP manual.
After calculating the total worst case current draw, the following table specifies the maximum distance the modules
can be located from the FACP on a single wire run. The
table ensures 6.0 volts of line drop maximum. In general,
the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*).
Maximum length can never be more than 6,000 feet (1,800
m), regardless of gauge used. See table below.
Wire Requirements: Power Circuit
• 14 to 18 AWG (0.75 - 2.08 mm2) wire for 24 VDC power
circuit is acceptable. Power wire distance limitation is
set by 1.2 volt maximum line drop form source to end of
circuit.
• All connections are power-limited and supervised.
• A maximum of eight ANN-80 modules may be connected to this circuit.
• Semi-flush mount to single, double, or 4" square electrical box. Use ANN-SB80KIT for angled view mounting.
• Can be remotely located up to 6,000 feet (1,800 m)
from the panel.
• Backlight turns off during AC loss to conserve battery
power but will turn back on if an alarm condition occurs
• May be powered by 24 VDC from the host FACP or by
remote power supply (requires 24 VDC).
Controls and Indicators
The following list the controls and indicators.
• AC Power
• Alarm
• Trouble
• Supervisory
• Alarm Silenced
Total Farthest Distance
Current Draw
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
0.200
0.300
0.400
0.500
0.600
0.700
0.800
0.900
1.000 (max.)
1,852 ft.
926 ft.
617 ft.
463 ft.
370 ft.
309 ft.
265 ft.
231 ft.
206 ft.
185 ft.
4,688 ft.
2,344 ft.
1,563 ft.
1,172 ft.
938 ft.
781 ft.
670 ft.
586 ft.
521 ft.
469 ft.
*6,000 ft.
3,731 ft.
2,488 ft.
1,866 ft.
1,493 ft.
1,244 ft.
1,066 ft.
933 ft.
829 ft.
746 ft.
*6,000 ft.
5,906 ft.
3,937 ft.
2,953 ft.
2,362 ft.
1,969 ft.
1,687 ft.
1,476 ft.
1,312 ft.
1,181 ft.
Table 1: Communication Pair Wiring Distance: FACP to Last ANn-BUS Module
Figure 1 illustrates the wiring between the FACP and the ANNBUS devices.
Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption:
@24 VDC nominal (filtered and
non-resettable): 40 mA maximum
Ambient Temperature:
32° F to 120° F (0° C to 49° C)
Relative Humidity:
93% ± 2% RH (non-condensing)
at 32° C ± 2° C (90° F ± 3° F)
5.375” H x 6.875” W x 1.375” D
(13.65 H x 17.46 W x 3.49 D cm)
For use indoors in a dry location
All connections are power-limited
and supervised.
Ordering Information
Figure 1 Wiring Configuration
Part Number
GFANN-80
GFANN-80-W
ANN-SB80KIT-R
ANN-SB80KIT-W
Description
Red, 80 character LCD Annunciator
White, 80 character LCD Annunciator
Red surface mount backbox with angled
wedge
White surface mount backbox with angled
wedge
GAMEWELL-FCI