MTU 1750

A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
1750-XC6DT2
1750 ekW 60 Hz Standby
/ / 1600 ekW / 60 Hz / Prime
480 - 4160V
System Ratings
Standby
Voltage (L-L) Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V**
3
0.8
60
1750
2187.5
2631
600V**
3
0.8
60
1750
2187.5
2105
4160V
3
0.8
60
1750
2187.5
304
4700
743RSL4052
130°C/27°C
4 BAR WYE 3600
744RSS4292
125°C/40°C
4 LEAD WYE
4000
743FSM4370
130°C/27°C
6 LEAD WYE 480V
3
0.8
60
1600
2000
2406
600V
3
0.8
60
1600
2000
1925
4160V
3
0.8
60
1600
2000
278
4700
743RSL4052
105°C/40°C
4 BAR WYE 3600
744RSS4292
105°C/40°C
4 LEAD WYE
4000
743FSM4370
105°C/40°C
6 LEAD WYE Prime
Voltage (L-L) Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
2
/ // /
1750-XC6DT2
Facts
// // // // // // // // // // EPA Tier 2 Certified
Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
UL2200, CSA Listing Offered
Accepts Rated Load in One Step Per NFPA 110, Level 1
All engine-generator sets are prototype and factory tested
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
Custom Design for Any Application
12V4000 G83 Diesel Engine
- 57.2 Liter Displacement
- Common Rail Injection
- 4-Cycle
// // // // Complete Range of Accessories
Permanent Magnet Generator (PMG)
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
Digital Control Panel(s)
- UL Recognized,
, NFPA 110
- Complete System Metering
- LCD Display
Cooling System
- Integral Set-Mounted
- Engine Driven Fan
STANDARD EQUIPMENT
// Engine
Air Cleaners
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Inter Cooler Water Pump
Thermostats
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electric Isochronous
Base - Structural Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
to 10 seconds
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±.25% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible
3
/ // /
1750-XC6DT2
Application data
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Max Power: Prime: bhp (kWm)
Regulation
Frequency
Air Cleaner
// At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
68.7 (260)
42.3 (160)
10.6 (40)
154 (583)
// Electrical
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
Fuel Consumption
MTU Detroit Diesel
12V4000 G83
(T1238A36)
4-Cycle
12-V
3,491 (57.2)
6.69 (17)
8.27 (21)
16.5:1
1,800
ADEC
2,561 (1,910)
2,328 (1,736)
±.25%
60 Hz
Dry
Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
After Cooler Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
// // 24
2,600
// STANDBY
123 (466)
93 (352)
65 (246)
PRIME
111 (420)
85 (322)
60 (227)
Cooling - Radiator System
STANDBY
Ambient Capacity of Radiator: °F (°C)
104 (40)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H20 (kPa) 0.5 (0.12)
Water Pump Capacity: gpm (lit/min)
295 (1,117)
After Cooler Pump
Capacity: gpm (lit/min)
154 (583)
Heat Rejection to Coolant: BTUM (kW) 41,401 (728)
Heat Rejection to After Cooler: BTUM (kW) 31,279 (550)
Heat Radiated to Ambient: BTUM (kW)
8,955 (157)
PRIME
104 (40)
0.5 (0.12)
295 (1,117)
154 (583)
37,875 (666)
27,525 (484)
8,254 (145.1)
Air Requirements
Aspirating: *SCFM (m3/min)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
STANDBY
5,085 (144)
PRIME
4,873 (138)
60,120 (1,702) 60,120 (1,702)
20,196 (575) 18,616 (530)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
// Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
// 1” NPT
3/4” NPT
3 (1)
Diesel #2
190 (720)
Exhaust System
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m3/min)
Maximum Allowable
Back Pressure: in. H20 (kPa)
STANDBY
869 (465)
PRIME
815 (435)
12,925 (366) 12,078 (342)
34.1 (8.5)
34.1 (8.5)
4
/ // /
1750-XC6DT2
Weights and dimensions
Drawing above for illustration purposes only, based on standard open power 480 volt generator. Lengths may vary with other voltages. Do not use for installation design.
SystemDimensions (L x W x H)
OPU
242.88 x 89 x 114.25 in (6,170 x 2,260 x 2,900 mm)
Weight (less tank)
31,992 lb (14,511 kg)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Sound data
Unit Type
OPU w/Critical Grade Muffler (dBA)
Standby Full Load
103.5
Standby No Load
96
Prime Full Load
102
Prime No Load
96
Emissions data
NOx + NMHC
C/F
CO
C/F
Rating Definitions and conditions
PM
C/F
All units are in g/hp-hr and are EPA D2 cycle values.
Emission levels of the engine may vary as a function of ambient temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation,
etc. The data provided are laboratory results from one engine
representing this rating. The data was obtained under controlled environmental conditions with calibrated instrumentation
traceable to the United States National Bureau of Standards
and in compliance with US EPA regulations found within 40 CFR
Part 89. The weighted cycle value from each engine is guaranteed to be below the US EPA Standards at the US EPA defined
conditions.
// // // // Materials and specifications subject to change without notice.
Ambient capability factor at 984 ft (300 m). Consult your
local MTU Onsite Energy Power Generation Distributor for
other altitudes.
Standby ratings apply to installations served by a reliable
utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with
ISO-3046/1, BS 5514, AS 2789, and DIN 6271.
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO-8528/1, overload power in accordance
with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For
limited running time and base load ratings, consult the
factory.
Deration Factor:
Altitude: 2% per 1,640 ft (500 m) above 3,281 ft
(1,000 m)* at 77°F (25°C).
Temperature: 1% per 9°F (5°C) over 113°F (45°C) at
328 ft (100 m).
*Contact factory for deration above 6,562 ft (2,000 m).
// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone + 49 7541 90 7060 /
Fax +49 7541 90 7084 / [email protected] // Asia / Australia / Pacific / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore /
Phone + 65 6861 5922 / Fax + 65 6861 3615 / [email protected] // USA / Canada / Mexico / MTU Onsite Energy / 100 Power Drive / Mankato, Minnesota
56001 / USA / Phone + 1 507 625 7973 / Fax + 1 507 625 2968 / [email protected] // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich /
Germany / Phone + 49 89 203042 800 / Fax +49 89 203042 900 / [email protected] //www.mtu-online.com
© MTU Onsite Energy. Subject to alteration due to technological advances. 2009-05
Measurements for sound data are taken at 23 ft (7 m).