LABORATORY DLM 600 Series 6 0 0 W A T T S P R O G R A M M A B L E D C S U P P LY Features • • • • • • • High power density High efficiency Remote voltage sense & remote operation Master/slave paralleling, active current sharing Low output noise CE mark, UL listing mark and C-UL listing mark Ethernet/LAN Interface Option Specifications OPERATING INPUT Input voltage 90-132 / 180-264VAC,auto-ranging, 2 Wires + ground Frequency 47-63Hz Current 11A max. at 115VAC, 6A max. at 230VAC Efficiency 84% typical at maximum power 82% typical for DLM 5-7 and DLM 8-75 Parallel/Series operation Up to 4 unit of the same model can be connected in parallel, with active current sharing control. Series operation, multiple units of same model can be connected in series, limited by 300Vpk between either output terminal and chassis Remote sense The maximum allowed load line drop with remote sensing is 1V total for DLM 5-75 & DLM 8-75 model, 2V total for all other model Remote programming Voltage , current (0-100%) and OVP (5-110%) of full scale can be programmed by selectable 0-5VDC, 0-10VDC, or 0-5KΩ OUTPUT Voltage adjustment Zero to rated output Current adjustment Zero to rated output Ripple & Noise See table Line regulation Voltage: 0.005% of Vmax + 2mV Current: 0.01% of Imax + 2mA Load regulation Voltage: 0.005% of Vmax + 2mV Current: 0.02% of Imax + 5mA Remote monitoring Voltage or current can be Monitored with userselectable ranges, scaled to 0-5VDC or 0-10VDC Transient response 500s to steady-state output voltage (within 0.1% of Vmax) for 50-100% or 100-50% load change Displays and indicators Two 3.5 digital LED displays indicate voltage, current and, over-voltage output set point, fault, external off, remote and output on Stability +/-0.05% of maximum voltage or current over 8 hours after 30 minute warm-up time at fixed line, load and temperature Software LabVIEW® driver for M9G/M85 (Contact Powerbox) Regulatory compliance CE mark, UL listing mark and C-UL listing mark Temperature coefficient 0.02%/°C of maximum output voltage 0.03%/°C of maximum output current ENVIRONMENTAL Operating temperature 0°C to 50° Storage temperature -40°C to 65°C Cooling Internal variable speed fan with over-temperature protection. MECHANICAL Case Enclosed Dimensions 1RU 44(H) x 216 (W) x 432mm(D) Weight 4.4Kg Connectors Input: IEC320 Output: Bus bar with 10-32 screws for 5-60VDC models; terminal blocks with 6-32 screws for 80-300V models Your dependable power partner – www.powerbox.com.au 481 LABORATORY DLM 600 Series 6 0 0 W A T T S P R O G R A M M A B L E D C S U P P LY Selection Table MODEL NUMBER DLM 5-75 DLM 8-75 DLM10-60 DLM 20-30 DLM 40-15 DLM 60-10 DLM 80-7.5 DLM 150-4 DLM 300-2 OUTPUT RATING LINE REGULATION LOAD REGULATION VOLTAGE (VDC) CURRENT (ADC) POWER (WATTS) VOLTAGE (0.01%OF VMAX +2MV) CURRENT (0.02%OF IMAX +2MA) VOLTAGE (0.01%OF VMAX +2MV) CURRENT (0.05%OF IMAX +5MA) 0-5 0-8 0-10 0-20 0-40 0-60 0-80 0-150 0-300 0-75 0-75 0-60 0-30 0-15 0-10 0-7.5 0-4 0-2 375 600 600 600 600 600 600 600 600 2.4mV 2.4mV 2.5mV 3mV 4mV 5mV 6mV 9.5mV 17mV 9.5mA 9.5mA 8mA 5mA 3.5mA 3mA 2.8mA 2.2mA 2.1mA 2.4mV 2.4mV 2.5mV 3mV 4mV 5mV 6mV 9.5mV 17mV 20mA 20mA 17mA 11mA 8mA 7mA 6.5mA 5.8mA 5.4mA PROGRAMMING ACCURACY MODEL NUMBER ETHERNET (M130/M131) GPIB (M9G/M85) VOLTAGE (0.1% OF VMAX) CURRENT (0.25% OF IMAX) OVP (0.5% OF 1.1 X VMAX) VOLTAGE (0.2% OF VMAX) CURRENT (0.5% OF IMAX) OVP (1.0% OF 1.1 X VMAX) VOLTAGE (0.5% OF VMAX +1 CURRENT (1.0% OF IMAX +1 8mV 188mA 44mV 16mV 375mA 55mV 35mV 850mA DLM 8-75 8mV 188mA 44mV 16mV 375mA 88mV 50mV 850mA DLM10-60 10mV 150mA 55mV 20mV 300mA 110mV 60mV 700mA DLM 20-30 20mV 75mA 110mV 40mV 150mA 220mV 200mV 400mA DLM 40-15 40mV 38mA 220mV 80mV 75mA 440mV 300mV 160mA DLM 60-10 60mV 25mA 330mV 120mV 50mA 660mV 400mV 110mA DLM 80-7.5 80mV 19mA 440mV 160mV 38mA 880mV 500mV 85mA DLM 150-4 150mV 10mA 825mV 300mV 20mA 1.65V 850mV 50mA DLM 300-2 300mV 5mA 1.65V 600mV 10mA 3.3V 2.5V 30mA DLM 5-75 MODEL NUMBER RIPPLE AND NOISE, VOLTAGE MODE TEMPERATURE OVP STABILITY COEFFICIENT ADJUSTME CURRENT NTRANGE VOLTAGE CURRENT VOLTAGE (5% - 110% (0.05% OF (0.05% OF (0.02%/°C (0.03%/°C VMAX) IMAX) OF VMAX ) OF IMAX) OF VMAX) MAXIMUM TOTAL REMOTE SENSE DROP RIPPLE (RMS)* NOISE (P-P)* DLM 5-75 5mV 30mV 0.25-.5.5V 2.5mV 37.5mA 1mV/°C 22.5mA/°C 1V DLM 8-75 5mV 30mV 0.4-8.8V 4mV 37.5mA 1.6mV/°C 22.5mA/°C 1V DLM10-60 5mV 30mV 0.5-11V 5mV 30mA 2mV/°C 18mA/°C 2V DLM 20-30 2.5mV 15mV 1-22V 10mV 15mA 4mV/°C 9mA/°C 2V DLM 40-15 2.5mV 15mV 2-44V 20mV 7.5mA 8mV/°C 4.5mA/°C 2V DLM 60-10 2.5mV 20mV 3-66V 30mV 5mA 12mV/°C 3mA/°C 2V DLM 80-7.5 4mV 20mV 4-88V 40mV 3.75mA 16mV/°C 2.25mA/°C 2V DLM 150-4 7mV 40mV 7.5-165V 75mV 2mA 30mV/°C 1.2mA/°C 2V DLM 300-2 10mV 60mV 15-330V 150mV 1mA 60mV/°C 0.6mA/°C 2V *RMS noise typical from 20Hz to 20MHz 482 DISPLAY ACCURACY LABORATORY DLM 600 Series 6 0 0 W A T T S P R O G R A M M A B L E D C S U P P LY REMOTE INTERFACE OPTIONS PARALLEL CABLE M9G IEEE-488.2 and RS 232 Interfaces DLMP1 Disconnect & Polarity reversal relays(10V to 300V models only, This option requires at least one of the following operations: M9G, M85, M130 or M131) RACK-MOUNT KIT M6 M13 Locking Shafts M51A Optically Isolated Analog Programming and Monitoring M85 Multi-channel Slave Interface M130 Ethernet/LAN and RS232C Interfaces (16 bit) M131 Multi-channel Slave Interface (16 bit)(M130 Master ONLY) DLMRX Paralleling Cable; One cable per slave unit Rack-mount Kit for single DLM with filter panel and for two units mounted side by side Technical Illustrations Your dependable power partner – www.powerbox.com.au 483