SCHURTER 5150

5150
Power Entry Modules with Line Filter
www.schurter.com/pg06
IEC Appliance Inlet C14 with High Frequency Filter, X2Y Technology, ECO design, Front- or Rear Side
Mounting
Screw-on or rivet mounting
from front or rear side
Standard- or Medical-Filter
Screw-on mounting from rear side
(integrated thread)
C14
70° C
Description
-Panel Mount:
Screw-on version from front or rear side
-2 Functions:
Appliance Inlet, High frequency line filter as standard, industrial and
medical version, Protection class I
-Quick connect terminals 6.3 x 0.8 mm
Approvals
Characteristics
-Very compact filter for frequencies up to 1 GHz
Patented X2Y Technologie for broadband high frequency filtering
-Double shielding for best filter performance
One single filter design for the given current range
-Designed for standard, industrial and medical applications
Suitable for assembly in metal plated plastic housings
-For use in equipment acc. IEC 60950/60601
Other versions on request
-VDE License Number: 40023426
-UL License Number: E72928
-Solder terminals
References
General Product Information
Weblinks
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
10 A @ Ta 40 °C / 250 VAC; 50 Hz
15 A @ Ta 40 °C / 250 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 43/80 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 85 °C
25/085/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Themoplast / steel tin-plated, black /
metallic, UL 94V-0
Appliance-Inlet/-Outlet
Line Filter
MTBF
EMC Products
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
Standard, medical and industrial version, IEC 60939, IEC 60601‑1, UL
1283, UL 544, CSA C22.2 no. 8
Technical details
> 3'300'000 h acc. to MIL-HB-217 F
5150
Power Entry Modules with Line Filter
www.schurter.com/pg06
Dimensions
54.5 mm
Front or rear side mounting for screws with nuts or blind rivets (panel cutout for frontside mounting)
54.5
40
39.5
3
12
29 ±0.1
max.R3
8.5
4.4
24.6
12
21.5 ±0.1
48.6
40 ±0.10
3.6
M3
Rear side mounting with pre-formed, threaded holes for M3 screws (panel cutout for rear side mounting)
54.5
40
39.5
3
30.5 ±0.1
12
max.R3
8.5
4.4
24.6
12
40 ±0.10
M3
3.6
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Capacitance
CY [nF]
R [MΩ]
10
Standard Version
1.25
2.5
-
10
Standard Version with Bleed Resistor
1.25
2.5
1
10
Industrial Version
2.35
4.7
-
10
Medical Version (M80)
0.225
0.45
1
Diagrams
Standard and industrial version
1)
Medical M80 and standard version
with bleed resistor
2)
1)
1) Line
2) Load
Capacitance
CX [nF]
2)
1) Line
2) Load
EMC Products
22.5 ±0.1
48.6
5150
Power Entry Modules with Line Filter
www.schurter.com/pg06
Attenuation Loss
- - - - differential mode _____ common mode
Standard version
CISPR 17 Test Method
Alternate Test Method
same attenuation loss with bleed resistor
Medical version (M80)
CISPR 17 Test Method
Alternate Test Method
Industrial Version
CISPR 17 Test Method
Alternate Test Method
Comment about alternate test method
see table of variants
Variants
Rated Current
IEC [A]
Rated Current
UL [A]
Filter-Type
Panel mounting
Mounting side
10
10
Order Number
15
Standard Version
Screw-on/Rivet
Front-/Rear-Side
5150.0011.0
15
Standard Version
Screw
Rear-Side
5150.0011.1
10
15
Standard Version with Bleed Resistor
Screw-on/Rivet
Front-/Rear-Side
5150.0021.0
10
15
Standard Version with Bleed Resistor
Screw
Rear-Side
5150.0021.1
10
15
Industrial Version
Screw-on/Rivet
Front-/Rear-Side
5150.0041.0
10
15
Industrial Version
Screw
Rear-Side
5150.0041.1
10
15
Medical Version (M80)
Screw-on/Rivet
Front-/Rear-Side
5150.0031.0
10
15
Medical Version (M80)
Screw
Rear-Side
5150.0031.1
The Alternate Test Method allows the measurement in the GHz frequency range whereas the CISPR 17 method does not cover
frequencies above 30MHz. The insertion loss is measured in a throughput method (common mode) and a cross coupled method
(differential mode). The differential mode measurement of the alternate test method is not directly comparable to the conventional
measurement acc. CISPR 17.
Further information on the X2Y filter technology and on the alternate insertion loss measurement method can be found under www.
schurter.com/info_emc
Packaging unit 10 Pcs EMC Products
5150
Power Entry Modules with Line Filter
www.schurter.com/pg06
Accessories
Description
Assorted Covers
Rear Cover
0859.0048
Cord retaining kits
Cord retaining strain relief
Flat head, E
4700.0005
Flat head, G
4700.0007
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
5092
Appliance Outlet further types to 5150
Connector Overview complete
IEC Connector C15, Rewireable, Straight
0101
IEC Connector C15A, Rewireable, Straight
0102
IEC Connector C15A, Rewireable, Straight
0102-G
IEC Connector C15A, Rewireable, Angled
0112
IEC Connector C13, Rewireable, Angled
4012
Connector further types to 5150
...
Power Cord Overview complete
Power Cord with IEC Connector C13, Angled
0311
Power Cord with IEC Connector C13, Angled
3011
Power Cord with IEC Connector C13, Angled
3012
Power Cord with IEC Connector C13, Angled
3013
Power Cord with IEC Connector C13
3020
Power Cord further types to 5150
...
The
specifications,
descriptions and illustrations indicated in this document are based on
EMC