SCHURTER 5145

5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
IEC Appliance Inlet C14 with Filter, Circuit Breaker TA45
Standard- or Medical-Filter
C14
70° C
Description
Characteristics
-Panel Mount:
Screw-on mounting from front side
-3 Functions:
Appliance Inlet Protection class I, circuit breaker type TA45 2pole, Line filter in standard and medical version
-Quick connect terminals 6.3 x 0.8 mm
-Alternative: version without line filter 6145 -We recommend for new applications the new type DF12 -All single elements are already wired
Unwired versions available on request
-Line switch non-illuminated or illuminated
Thermal overload protection
Optional with undervoltage- or remote trip release
-Qualified for use in equipment according IEC/EN 60950
References
General Product Information
Approvals
Weblinks
-VDE License Number: 117118
-UL License Number: E72928
Approvals, RoHS, CHINA-RoHS, Mating Connectors, e-Store,
Distributor-Stock-Check, Accessories
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 15 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-10 °C to 55 °C
10/055/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class 1 acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet/-Outlet
Circuit Breakers
Line Switch
Line Filter
MTBF
EMC Products
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
conditions) pin-temperature 70 °C, 10 A,
Protection Class 1
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or nonilluminated. Optional with undervoltageor remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In ≥ 3A/240VAC : 300A
Rocker switch 2-pole non-illuminated or
illuminated acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601‑1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 100'000 h acc. to MIL-HB-217 F
5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
Dimensions
67.5 mm
Detail A
2
0
36
29 +0.2
1
43
6.3x0.8mm
ø6
3.25
A
0
6.3x0.8mm
50.7
M3/ø 3.6
13.5
67.5*
* --- Version TA45 with undervoltage release
Technical Data of Filter-Components
Rated Current
[A]
Filter-Type
Capacitance
CX [nF]
Capacitance
CY [nF]
R [MΩ]
2 x 11
47
2.2
-
1
Standard Version
2
Standard Version
2x4
47
2.2
-
3
Standard Version
2 x 2.5
47
2.2
-
4
Standard Version
2 x 1.6
47
2.2
-
6
Standard Version
2 x 0.7
47
2.2
-
8
Standard Version
2 x 0.6
47
2.2
-
10
Standard Version
2 x 0.4
47
2.2
-
15
Standard Version
2 x 0.1
47
2.2
-
1
Medical Version (M5)
2 x 11
47
-
1
2
Medical Version (M5)
2x4
47
-
1
6
Medical Version (M5)
2 x 0.7
47
-
1
8
Medical Version (M5)
2 x 0.6
47
-
1
10
Medical Version (M5)
2 x 0.4
47
-
1
15
Medical Version (M5)
2 x 0.1
47
-
1
Diagrams
Standard version
Medical version
1) Line
2) Load
1) Line
2) Load
Inductances
L [mH]
EMC Products
80 ±0.1
72
+0.1
0
80
91.5
R 3-0.5
5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
Attenuation Loss
Standard version
- - - - differential mode _____ common mode
1A
2A
3A
4A
6A
8A
10 A
15A
1A
2A
3A
4A
6A
8A
10 A
15A
Medical version (M5)
EMC Products
5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
EMC Products
5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
Packaging unit 20 Pcs Accessories
Description
Assorted Covers
Rear Cover
0859.0074
Mating Outlets/Connectors
Category / Description
Appliance Outlet Overview complete
IEC Appliance Outlet F, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
4787
IEC Appliance Outlet F, Snap-in Mounting, Front Side, Solder or Quick-connect Terminal
4788
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal
5091
IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder or Quick-connect Terminal
5092
Appliance Outlet further types to 5145
Connector Overview complete
IEC Connector C15, Rewireable, Straight
0101
IEC Connector C15A, Rewireable, Straight
0102
IEC Connector C15A, Rewireable, Straight
0102-G
IEC Connector C15A, Rewireable, Angled
0112
IEC Connector C13, Rewireable, Angled
4012
Connector further types to 5145
...
Power Cord Overview complete
Power Cord with IEC Connector C13, Angled
0311
Power Cord with IEC Connector C13, Angled
3011
Power Cord with IEC Connector C13, Angled
3012
Power Cord with IEC Connector C13, Angled
3013
Power Cord with IEC Connector C13
3020
Power Cord further types to 5145
...
EMC Products
5145
Power Entry Modules with Line Filter
www.schurter.com/pg06
Technical data (continued)
Circuit breaker
Tripping characteristics
In < 3 A
Tripping characteristics
In * 3…) 15 A
[ min ] [ sec ]
10’000
[ min ] [ sec ]
10’000
Type
TA45
Rated current
In < 3 A
60
2000
30
20
10
Ambient temp.
TA45
Rated current
I n ≥ 3... ≤ 15 A
1-pole protected
2’000
30
2-pole protected
1000
Type
60
1-pole protected
20
+23 °C
10
500
5
2-pole protected
1’000
+23 °C
Ambient temp.
500
5
200
200
100
1
100
1
50
20
20
10
10
5
5
2
2
1
1
0,5
0,5
Tripping time
Tripping time
50
0,3
0,2
0,1
1,05 1,32
2
3
Multiple of rated current
4
5
8
10
0,3
0,2
0,1
1,05 1,32
[ x In ]
2
Multiple of rated current
Effect of ambient temperature 1)
The unit is calibrated for an ambient temperature of +23 °C. To
determine the rated current for a lower or higher ambient temperature, use a correction factor from the table below.
* Ambient temperature [°C] Correction factor
–10
0,89
– 5
0,91
0
0,92
+23
1,00
+30
1,03
+40
1,08
+55
1,16
3
4
5
8
10
[ x In ]
* Temperature must be measured at the rear of the breaker next to
the terminals after equipment operating temperature has been
reached.
1)
Example
Rated current at +23 °C
Ambient temperature
Correction factor
Chosen rated current at
+ 40 °C ambient temperature
6,0 A
+40 °C
1,08
6 A x 1,08 = 6,5 A
Order code (Order example)
Type
Order code TA45
(2-pole rocker-switch without
accessories)
5145. A B T W F 1 5 0 C 0
see table 1
. 0 0 1
Wiring
0 Without
1 With
Type of line filter
1 Standard
3 Medical
Rated current of line filter
1
1 (A)
5
6 (A)
2
2 (A)
6
8 (A)
3
3 (A)
7
10 (A)
4
4 (A)
8
15 (A)
Please note that Schurter will establish an internal part number for logistical use in additional to the order code. The format of this internal part
number is, for example 5145.0031.001
The
specifications,
descriptions and illustrations indicated in this document are based on
EMC