SCHURTER 80200603PT

SUT 6.3x32 Pigtail
Non resettable fuses
www.schurter.com/pg01_2
Axial Lead Fuse, 6.3x32 mm, low resistance, up to 30 A
UL 248-14 · 250 V · Slow-Blow
Description
Applications
Standards
References
-Up to 30 A, low resistance
-Ceramic Tube
-Single-phase high current applications up to 30 A
-Industrial electronic
-UL 248-14
-CSA C22.2 no. 248.14
General Product Information
Packaging Details
Approvals
Weblinks
Approvals, RoHS, CHINA-RoHS, Distributor-Stock-Check, Accessories,
Product Change Notification (PCN)
-UL File Number: E184831
Technical Data
Rated Voltage
Rated Current
Breaking Capacity
Characteristic
Admissible Ambient Air Temp.
Climatic Category
Material: Tube
Material: Endcaps
Material: Axial Leads
Material: Filler
Unit Weight
Storage Conditions
Product Marking
250 V
12 - 30 A
500 A
Slow-Blow
-40 °C to 85 °C
40/085/21 acc. to IEC 60068-1
Ceramic
Nickel-Plated Brass
Tin-Plated Copper
Sand
3.9 g
0 °C to 60 °C, max. 70% r.h.
, Type, Current, Voltage, Approvals
Dimensions
Soldering Methods
Solderability
Resistance to Soldering Heat
Wave, Iron
235 °C / 2 sec acc. to IEC 60068-2-20,
Test Ta, method 1
260 °C / 5 sec acc. to IEC 60068-2-20,
Test Tb, method 1A
øA
ø 6.85 ±0.5
32 mm
32.8 ±1
40
40
In = 12 A: ØA = 0.8 mm In ≥ 15 A: ØA = 1.0 mm
Pre-Arcing Time
Rated Current In
12 A - 30 A
1.0 x In min.
1.35 x In max.
4h
60 min
2.0 x In min. 2.0 x In max.
5s
60 s
Fuses
SUT 6.3x32 Pigtail
Non resettable fuses
www.schurter.com/pg01_2
Variants
Rated Current [A]
Rated Voltage [VAC]
12
250
15
250
20
Breaking
Capacity
Voltage Drop
1.0 In typ.
[mV]
Cold Resistance typ.
[mΩ]
Order Number
1)
78
5.6
72
l
8020.0603.PT
1)
81
4.7
152
l
8020.0604.PT
250
1)
87
3.6
750
l
8020.0605.PT
25
250
1)
62
2.1
1010
l
8020.0606.PT
30
250
1)
64
1.8
2050
l
8020.0607.PT
Melting I²t 10.0
Intyp. [A²s]
1) 500 A @ 250 VAC, 10 kA @ 125 VAC
Packaging Unit Bulk (1000 pcs.)
Time-Current-Curves
100000
10000
1000
Time in Seconds
100
10
1
0.1
0.01
0.001
1
10
Multiple of Rated Current In
The
specifications, descriptions and illustrations indicated in this document are based on
Fuses
current information. All content is subject to modifications and amendments.