MADM Non resettable fuses www.schurter.com/pg01_2 Special Fuse, 14.3 x 51 mm, 500 VAC, 250 VDC DTCN · 500 VAC · 250 VDC Description References Standards Weblinks -High Breaking Capacity General Product Information -NF C 63-210 / NF C 63-211 -DTCN: T/5920 DA Approvals, RoHS, CHINA-RoHS, e-Store, Distributor-Stock-Check, Accessories, Product Change Notification (PCN) Technical Data Rated Voltage Rated Current Breaking Capacity Admissible Ambient Air Temp. Climatic Category Material: Tube Unit Weight Storage Conditions Product Marking 500 VAC, 250 VDC 1 - 25 A 100 kA -40 °C to 85 °C 40/085/21 acc. to IEC 60068-1 Ceramic 25 g 0 °C to 60 °C, max. 70% r.h. Type, Current, Voltage Dimensions 51 mm ø5 +0.3 ø 14.3 ±0.1 R= ø 15.3 +0.1 5 5 5.2 120˚ 13 +0.2 8.5 +0 6.5 ±0.5 +1.6 51+1.0 Pre-Arcing Time Rated Current In 1 A - 25 A 4.0 x In min. 6.3 x In max. 8.0 x In min. 60 s 60 s 500 ms 10.0 x In min. 12.5 x In max. 25.0 x In max. 50.0 x In max. 200 ms 500 ms 40 ms 9 ms Fuses MADM Non resettable fuses www.schurter.com/pg01_2 Variants Rated Current [A] Rated Voltage [VAC] Rated Voltage [VDC] Breaking Capacity Voltage Drop 1.0 In typ. [mV] Order Number 1 500 250 1) 110 l 7020.9110 1.6 500 250 1) 80 l 7020.9120 2.5 500 250 1) 70 l 7020.9130 5 500 250 1) 75 l 7020.9140 8 500 250 1) 70 l 7020.9150 12.5 500 250 1) 70 l 7020.9160 20 500 250 1) 75 l 7020.9170 1) 100 kA @ 500 VAC , p.f. ≥ 0.15 / 10 kA @ 50 VDC , L/R < 10 ms Packaging Unit Small Box Pack (10 pcs.) Time-Current-Curves 100000 10000 1000 Time in Seconds 100 10 1 0.1 12.5 A In max. 0.5 s 25.0 A In max. 0.04 s 50.0 A In max. 0.009 s 0.01 0.001 1 10 Multiple of Rated Current In The specifications, descriptions and illustrations indicated in this document are based on Fuses current information. All content is subject to modifications and amendments.