SCHURTER MADM

MADM
Non resettable fuses
www.schurter.com/pg01_2
Special Fuse, 14.3 x 51 mm, 500 VAC, 250 VDC
DTCN · 500 VAC · 250 VDC
Description
References
Standards
Weblinks
-High Breaking Capacity
General Product Information
-NF C 63-210 / NF C 63-211
-DTCN: T/5920 DA
Approvals, RoHS, CHINA-RoHS, e-Store, Distributor-Stock-Check,
Accessories, Product Change Notification (PCN)
Technical Data
Rated Voltage
Rated Current
Breaking Capacity
Admissible Ambient Air Temp.
Climatic Category
Material: Tube
Unit Weight
Storage Conditions
Product Marking
500 VAC, 250 VDC
1 - 25 A
100 kA
-40 °C to 85 °C
40/085/21 acc. to IEC 60068-1
Ceramic
25 g
0 °C to 60 °C, max. 70% r.h.
Type, Current, Voltage
Dimensions
51 mm
ø5
+0.3
ø 14.3 ±0.1
R=
ø 15.3 +0.1
5
5
5.2
120˚
13
+0.2
8.5 +0
6.5 ±0.5
+1.6
51+1.0
Pre-Arcing Time
Rated Current In
1 A - 25 A
4.0 x In min. 6.3 x In max. 8.0 x In min.
60 s
60 s
500 ms
10.0 x In min.
12.5 x In max.
25.0 x In max.
50.0 x In max.
200 ms
500 ms
40 ms
9 ms
Fuses
MADM
Non resettable fuses
www.schurter.com/pg01_2
Variants
Rated Current [A]
Rated Voltage [VAC]
Rated Voltage [VDC]
Breaking
Capacity
Voltage Drop
1.0 In typ.
[mV]
Order Number
1
500
250
1)
110
l
7020.9110
1.6
500
250
1)
80
l
7020.9120
2.5
500
250
1)
70
l
7020.9130
5
500
250
1)
75
l
7020.9140
8
500
250
1)
70
l
7020.9150
12.5
500
250
1)
70
l
7020.9160
20
500
250
1)
75
l
7020.9170
1) 100 kA @ 500 VAC , p.f. ≥ 0.15 / 10 kA @ 50 VDC , L/R < 10 ms
Packaging Unit Small Box Pack (10 pcs.)
Time-Current-Curves
100000
10000
1000
Time in Seconds
100
10
1
0.1
12.5 A In max. 0.5 s
25.0 A In max. 0.04 s
50.0 A In max. 0.009 s
0.01
0.001
1
10
Multiple of Rated Current In
The
specifications, descriptions and illustrations indicated in this document are based on
Fuses
current information. All content is subject to modifications and amendments.